A. This Section includes Low Voltage Switchgear Work, as indicated on the drawings, and as specified herein.

A. Submit manufacturer's literature and technical data before starting work.

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

A. Work Included: Provide low voltage switchboard work as shown, scheduled, indicated, and as specified.

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

University of Houston Master Construction Specifications Insert Project Name

Section SWITCHBOARDS. Introduction. Part 1 - General. Related Work

SECTION MOTOR CONTROL

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5

2018 Consultant s Handbook Division 26 Electrical 2413 Switchboards

Quik-Spec Coordination Panelboard Specifications

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE

Design Standard. Purpose: Design Standard:

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV)

SECTION PANELBOARDS

SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV)

SUBSTATION VACUUM CIRCUIT BREAKER (38KV)

BUSWAY Low Voltage (Pow-R-Flex)

IN2 Enclosed Switches and Circuit Breakers

1. Division 26 Section "Elevator Shunt-Trip Fused Disconnect Switches".

QMB Panel boards Switchboards. 200,000A. short circuit rating. www. ElectricalPartManuals. com

1. The term "withstand" means "the unit will remain in place without separation of any parts from the device when subjected to the seismic forces.

University of Houston Master Construction Specifications Insert Project Name

A. This Section includes ac, enclosed controllers rated 600 V and less, of the following types:

A. Provide a complete system of overcurrent protective devises as indicated on the drawings, and as specified herein.

WARREN COUNTY, N.Y. M/E REFERENCE

SECTION LOW VOLTAGE SWITCHBOARDS - SPECTRA. A. The requirements of the Contract, Division 1, and Division 16 apply to work in this Section.

QMB Fusible Panelboards

Applications. Trim are flat gauge steel per code. Standard painted finish ANSI 61 gray. Directory card with plastic cover on front of trim

CONTROLLIX CORPORATION CONTROLLIX.COM LOW VOLTAGE AUTOMATIC SWITCH CAPACITOR BANK SPECIFICATIONS

DIVISION 26 ELECTRICAL SECTION CIRCUIT BREAKERS

CITY OF LOMPOC UTILITIES DEPARTMENT ELECTRICAL DIVISION SPECIFICATION NO. ELE-112 SUBSTATION CLASS VACUUM CIRCUIT BREAKERS OCTOBER 2008

Defender Mini Online Emergency Central Lighting Inverter (CLI) Technical Specifications

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION

9. Non-Residential Services (Commercial, Industrial, and Agricultural)

Model ESV Uninterruptible Power System 1.5 KVA/KW KVA/KW Single Phase

Fortress 1 Outdoor Emergency Central Lighting Inverter (CLI) Technical Specifications

SECTION LOW VOLTAGE SWITCHBOARDS - Spectra Bolt-On

SECTION SWITCHGEAR. A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section.

Cobra 3 Stand-By Emergency Central Lighting Inverter (CLI) Technical Specifications

SECTION ENCLOSED CONTROLLERS

Horizontal Circuit Switchers

SECTION ELECTRIC DISTRIBUTION

Horizontal Circuit Switchers

University of Houston Master Construction Specifications Insert Project Name SECTION ELECTRONIC VARIABLE SPEED DRIVES PART 1 - GENERAL

GE 8000-Line Motor Control Centers

SECTION DISTRIBUTION AND GROUNDING

Detail Bill of Material Page 1 of 1 Project Name: Amphi School - MVS Replacement Negotiation No: TU700213X7K2 General Order

DISCONNECT SWITCH REQUIREMENTS FOR DISTRIBUTED GENERATION CUSTOMERS

Power Lynx 3 Uninterruptible Power System (UPS) Technical Specifications

SWITCHGEAR DIVISION PRODUCT PROFILES

10 Commercial, Industrial, Agricultural Services

SECTION LOW VOLTAGE DISTRIBUTION EQUIPMENT

C. System Design and Performance Requirements

A system fault contribution of 750 mva shall be used when determining the required interrupting rating for unit substation equipment.

PDI PowerWave 2 Bus System

A. This section includes unit capacitors for power factor correction.

Solar Power Switchgear & Energy Storage Renewable Energy Systems

Fortress 3 Harsh. Harsh Environment. Emergency Central Lighting Inverter (CLI) Technical Specifications

Electrical Switchgear Replacement Montgomery County Community College

DRAFT. Western Michigan University Campus Facilities

Bussmann series Quik-Spec Coordination Panelboard

SECTION MOTORS AND VARIABLE FREQUENCY DRIVES

FIXED POWER FACTOR CORRECTION EQUIPMENT 5KV CLASS MEDIUM VOLTAGE SECTION Z

SECTION 16426B. RELATED SECTIONS Section 16671A Transient Voltage Surge Suppression Section Microprocessor-Based Metering Equipment

A. This section includes enclosed dry type transformers for lighting and power loads, with primaries and secondaries rated 600 volts and less.

WARREN COUNTY, N.Y. M/E REFERENCE A. Submit manufacturer's product data on all motors and adjustable speed drives.

Busway Construction. Bus Bars

BGE STRATEGIC CUSTOMER ENGINEERING

ME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position

16.13 Unit Substation to 15kV Construction Standards Page 1 of 7

UNIFIED FACILITIES GUIDE SPECIFICATIONS

Introduction. Features. Intelligent Technologies Motor Control Center Structures

A. Products shall be designed, manufactured, tested, and installed in compliance with the following standards:

East Central College

Design Build Deliver. Metal Enclosed Switchgear, 5-35kV 1200 A Maximum Loadbreak, 4000 A Maximum Non-Loadbreak

Low Voltage Switchgear Type WL Low Voltage Metal-Enclosed Switchgear

POWER-ZONE 4 Low Voltage Metal-Enclosed Drawout Switchgear with MASTERPACT NW Low Voltage Power Circuit Breakers

Switchgear Skid, C1192

EMERGENCY GENERATOR SET

SECTION MOTOR CONTROLLERS

Three-Phase Pole Mounted Recloser

Specification Guide. for RMAX. Direct Replacement. AC Low Voltage. Power Circuit Breakers

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation

Metering and Service Installation:

Special Specification 6058 Battery Back-Up System for Signal Cabinets

Fused Coordination Panelboard

Dual ground lug - one lug for earth ground, one lug for utility ground.

GE Energy. GE Panelboards. The right panelboard for any application. imagination at work

Quik-Spec Electrical Gear

Specification Pad-Mounted Capacitor Bank with Dual Fusing Integral Load-Interrupter on Line-Side Fuse Mountings

UNIFIED FACILITIES GUIDE SPECIFICATIONS

AMENDMENT ELECTRIC SERVICE MANUAL 2014

UNDERGROUND SERVICES - SECONDARY

Design Standard. Capacitor Bank. Detailed specifications follow. PART 1 - GENERAL

7. SERVICES OVER 600 VOLTS

A. Three-phase, oil filled self-cooled, padmounted transformers are installed outdoors on pads in the EWEB distribution system.

Outdoor Power Transmission & Distribution

SECTION LOW VOLTAGE MOTOR CONTROL CENTERS LINE WITH POWER MANAGEMENT. A. Low Voltage Motor Control Center with Power Management

MECHANICAL AND ELECTRICAL COORDINATION SECTION MECHANICAL AND ELECTRICAL COORDINATION PART 1 - GENERAL

Transcription:

Specification Number: 26 24 13.20 Product Name: GROUP MOUNTED MAIN FUSIBLE SWITCH, GROUP MOUNTED BRANCH FUSIBLE SWITCH (LONG) SECTION 26 24 13.20 SWITCHBOARDS (Long) Main Disconnect Group Mounted Fusible Switch Distribution Disconnects Group Mounted Fusible Switches PART 1 GENERAL 1.01 SECTION INCLUDES A. Main Switchboard - Furnish and install the Service Entrance switchboard(s) as herein specified and shown on the associated electrical drawings. B. Distribution Switchboard - Furnish and install the Distribution Switchboard(s) as herein specified and shown on the associated electrical drawings 1.02 REFERENCES The switchboard(s) and overcurrent protection devices referenced herein are designed and manufactured according to the following appropriate specifications. A. ANSI/NFPA 70 - National Electrical Code (NEC). B. ANSI/IEEE C12.16 - Solid State Electricity Metering. C. ANSI C57.13 - Instrument Transformers. D. NEMA KS 1 - Enclosed Switches. E. NEMA PB 2 - Deadfront Distribution Switchboards, File E8681 F. NEMA PB 2.1 - Proper Handling, Installation, Operation and Maintenance of Deadfront Switchboards Rated 600 Volts or Less. G. NEMA PB 2.2 - Application Guide for Ground Fault Protective Devices for Equipment. H. UL 50 - Cabinets and Boxes. I. UL 98 - Enclosed and Dead Front Switches. J. UL 891 - Dead-Front Switchboards. K. Federal Specification W-C-870 - Fuseholders (For plug and enclosed cartridge fuses). L. Federal Specification W-S-865 - Enclosed Knife Switch. 1.03 SUBMITTALS A. Shop Drawings shall indicate front and side enclosure elevations with overall dimensions shown; conduit entrance locations and requirements; nameplate legends; one-line diagrams; equipment schedule; and switchboard instrument details. 1.04 QUALIFICATIONS A. To be considered for approval, a manufacturer shall have specialized in the manufacturing and assembly of switchboards for at least fifty (50) years. B. Furnish products listed by Underwriters Laboratories Incorporated and in accordance with standards listed in Article 1.03 - References. C. The manufacturing facility shall be registered by Underwriters Laboratories Inc. to the International Organization for Standardization ISO 9002 Series Standards for quality. 1.05 DELIVERY, STORAGE, AND HANDLING A. Deliver, store, protect, and handle products in conformance with manufacturer's recommended practices as outlined in applicable Installation and Maintenance Manuals. B. Each switchboard section shall be delivered in individual shipping splits for ease of handling. They shall be individually wrapped for protection and mounted on shipping skids. C. Inspect and report concealed damage to carrier within their required time period. D. Store in a clean, dry space. Maintain factory protection and/or provide an additional heavy canvas or heavy plastic cover to protect structure from dirt, water, construction debris, and traffic. Where applicable, provide adequate heating within enclosures to prevent condensation.

E. Handle in accordance with NEMA PB 2.1 and manufacturer's written instructions. Lift only by lifting means provided for this express purpose. Handle carefully to avoid damage to switchboard internal components, enclosure, and finish. 1.06 ENVIRONMENTAL REQUIREMENTS A. Conform to NEMA PB 2 service conditions during and after installation of switchboards. 1.07 MAINTENANCE MATERIALS A. Provide one (1) set of installation and maintenance instructions with each switchboard. Instructions are to be easily identified and affixed within the incoming or main section of the line-up. 1.08 WARRANTY A. Manufacturer shall warrant equipment to be free from defects in materials and workmanship for the lesser of one (1) year from date of installation or eighteen (18) months from date of purchase. PART 2 PRODUCTS 2.01 MANUFACTURERS A. Shall be Square D Company. B. Substitutions must be submitted in writing three (3) weeks prior to original bid date with supporting documentation demonstrating that the alternate manufacturer conforms to all aspects of the specifications herein. 2.02 SWITCHBOARD - GENERAL A. Utility Metering Compartment: The utility current transformer compartment shall comply with the local utility construction specifications. B. Short Circuit Current Rating: Switchboards shall be rated with a minimum short circuit current rating of [ ] rms symmetrical amperes at [ ] VAC maximum. C. Future Provisions: All unused spaces provided, unless otherwise specified, shall be fully equipped for future devices, including all appropriate connectors and mounting hardware. D. Enclosure: Type [1 - General Purpose.][1 - With Drip Hood.][3R - Rain tight.] 1. Sections shall be aligned front and rear. 2. Removable steel base channels (1.5 inch floor sills) shall be bolted to the frame to rigidly support the entire shipping section for moving on rollers and floor mounting. 3. The switchboard enclosure shall be painted on all exterior surfaces. The paint finish shall be a medium gray, ANSI #49, applied by the electro-deposition process over an iron phosphate pre-treatment. 4. All front covers shall be screw removable with a single tool and all doors shall be hinged with removable hinge pins. 5. Top and bottom conduit areas shall be clearly indicated on shop drawings. E. Nameplates: Provide 1 inch high x 3 inches engraved laminated (Gravoply) nameplates for each device. Furnish black letters on a white background for all voltages. F. Bus Composition: Shall be [plated copper] [plated aluminum]. Plating shall be applied continuously to all bus work. The switchboard bussing shall be of sufficient cross-sectional area to meet UL Standard 891 temperature rise requirements. The phase [and neutral] through-bus shall have an ampacity as shown in the plans. For 4-wire systems, the neutral shall be of equivalent ampacity as the phase bus bar. Tapered bus is not acceptable. Full provisions for the addition of future sections shall be provided. Bussing shall include all necessary hardware to accommodate splicing for future additions. G. Ground Bus: Sized per NFPA70 and UL 891 Tables 25.1 and 25.2 and shall extend the entire length of the switchboard. Provisions for the addition of future sections shall be provided. 2.02A SWITCHBOARD - INCOMING MAIN SECTION DEVICES A. Fusible Switch 1. Single main group mounted 400A through 800 A (QMB) a. Fusible main switch shall be group mounted plug-on with mechanical restraint. No additional hardware shall be required to mount the fusible switch into the switchboard. b. Switch shall have dual cover interlocks designed to prevent the opening of the cover when the switch is ON. The cover interlock shall prevent the switch from being

turned ON with the cover open. Interlock may be manually overridden for testing purposes. Switch cover shall include a means by which the cover can be padlocked in the closed position. The operating handle shall feature positive lock-off means by providing provisions for (3).375 in padlocks. c. Load side fusible switch connections shall be jaw type. 2.02B SWITCHBOARD - DISTRIBUTION SECTION DEVICES B. Branch Fusible Devices 1. Fusible switch a. Group mounted, [30 through 600 A, Type QMJ], [30 through 800 A, Type QMB]. b. Fusible switches shall be group mounted plug-on with mechanical restraint. No additional hardware shall be required to mount the fusible switch into the switchboard. c. Modular construction shall permit 30 through 800 A devices to be field installed by the Contractor due to a project change order or to accommodate future expansion. d. Line side fusible switch connections are to be jaw type construction. e. The operating mechanism shall be spring driven, with quick-make, quick-break action. Operating handles shall be flange mounted as an integral part in the operating mechanism. Switch contact shall be knife-blade and jaw construction. Switch shall include visible blades as a positive blade status indicator. f. Switches shall be secured to the bus with spring reinforced jaw assemblies. In the event of a short circuit condition, the increased magnetic flux shall cause the jaws to grip the bus more firmly. g. Fusible switch units shall be equipped with all required mounting brackets and guides. h. Switch shall have dual cover interlocks designed to prevent the opening of the cover when the switch is ON. The cover interlock shall prevent the switch from being turned ON with the cover open. Interlock may be manually overridden for testing purposes. Switch cover shall include a means by which the cover can be padlocked in the closed position. The operating handle shall feature positive lock-off means by providing provisions for (3).375 in padlocks. i. There shall be two forms of visible ON/OFF indication: j. A dual-color operating handle and a large steel ON/OFF nameplate with the O/I international markings. The universal nameplate shall be readable regardless of the switch orientation. Each nameplate shall furnish an easily removable circuit directory card. k. Fusible switches shall be UL Listed when equipped with field installable accessories: Compression lugs, copper mechanical lugs, and electrical interlocks. l. 30 through 100 A fusible switches shall have fuse pullers provided. The fuse puller design shall be of the type that the line side of the fuse is disconnected from the switch before the load side of the fuse is removed. m. Fuse clips shall be designed to accommodate Class (Select one) [H] [J] [R] [T] fuses for 30 through 600 A. Class L fuses shall be used on all devices above 600 A. 2.03 MIMIC BUS (OPTIONAL) (Select appropriate choice and delete any remaining choices) A. [Show the entire single line switchboard bus work, as depicted on the factory record drawing, on a photo engraved nameplate. The nameplate plate shall be at least.032 inch thick anodized aluminum and located at eye level on the front cover of the switchboard incoming service section.] B. [Show the entire single line switchboard bus work, as depicted on the factory record drawing, on an engraved laminated plastic (Gravoply) nameplate. The nameplate shall be at least.0625 inch thick and located at eye level on the front cover of the switchboard incoming service section.] 2.04 METERING (CUSTOMER) A. Manufacturers: 1. [Square D] Model [PM XXX].

2. [Square D] Model [CM XXXX]. 3. [ ] Model [ ]. 4. Substitutions: substitutions shall be made only after proper verification B. The switchboard shall be metered using: (Select 1 or more) 1. [Square D Type PM 600] A, V, kw, kvar, kva, PF, F, kwh, kvarh, kvah, KYZ, RS-485 communications 2. [Square D Type PM 620] A, V, kw, kvar, kva, PF, F, kwh, kvarh, kvah, KYZ, RS-485 communications, THD, Demand, kwd, kvard, kvad, date/time stamping 3. [Square D Type PM 650] A, V, kw, kvar, kva, PF, F, kwh, kvarh, kvah, KYZ, RS-485 communications, THD, Demand, kwd, kvard, kvad, date/time stamping, predicted power demand, onboard alarms, min/max. readings, data log, event log 4. [Square D Type CM 2150] predicted power demand, onboard alarms, min/max. readings, data log, event log, and extend memory (100k) 5. [Square D Type CM 2250] memory (100k) and waveform capture 6. [Square D Type CM 2350] memory (100k), wave form capture, and disturbance monitoring 7. [Square D Type CM 2450] memory (100k), wave form capture, disturbance monitoring and programmable logic. 2.05 METERING TRANSFORMERS A. Manufacturer: Shall be Square D Company. B. Current Transformers: ANSI C57.13; 5 ampere secondary. C. Voltage Transformers: ANSI C57.13; 120 V single secondary, (Not required for type PM meters) 2.06 ACCESSORIES A. For switchboards installed outdoor only, provide thermostatically-controlled electric heaters in each section. [Provide terminals for separate source connection of heater power circuit. Voltage Rating: [120] [ ] V.] [Provide control power transformer with the total VA rating of the electric heaters in the switchboard.) 2.07 RELATED SECTIONS A. [Section 16290-3]- ELECTRICAL POWER MONITORING & COMMUNICATION B. [Section 16280-1] - TRANSIENT VOLTAGE SURGE SUPPRESSION DEVICES IN SWITCHBOARDS & SWITCHGEAR

C. [Section 16415-1] - AUTOMATIC TRANSFER SWITCHES IN LOW VOLTAGE EQUIPMENT PART 3 EXECUTION 3.01 INSPECTION A. Examine area to receive switchboard to provide adequate clearance for switchboard installation. B. Check that concrete pads are level and free of irregularities. C. Start work only after unsatisfactory conditions are corrected. 3.02 INSTALLATION A. Install switchboard in accordance with manufacturer's written guidelines, the NEC, and local codes. 3.03 FIELD QUALITY CONTROL A. Inspect completed installation for physical damage, proper alignment, anchorage, and grounding. B. Measure, using a Megger, the insulation resistance of each bus section phase-to-phase and phase-to-ground for one minute each, at minimum test voltage of 1000 VDC; minimum acceptable value for insulation resistance is 1 megohms. NOTE: Refer to manufacturer's literature for specific testing procedures. C. Check tightness of accessible bolted bus joints using calibrated torque wrench per manufacturer's recommended torque values. D. Physically test key interlock systems to check for proper functionality. E. Test ground fault systems by operating push-to-test button. 3.04 ADJUSTING A. Adjust all operating mechanisms for free mechanical movement per manufacturers specifications. B. Tighten bolted bus connections in accordance with manufacturer's instructions. C. Adjust circuit breaker trip and time delay settings to values [indicated.] [as instructed by the Architect/Engineer.] 3.05 CLEANING A. Touch up scratched or marred surfaces to match original finish. END OF SECTION