Surepowr Series 100 Installation Manual

Similar documents
SUREPOWR TM SERIES -SURE 49 FIELD INSTALLATION INSTRUCTIONS

SUREPOWR TM SERIES -SURE 24/25 FIELD INSTALLATION INSTRUCTIONS

Surepowr Series Sure 150

Milwaukee's Electric Actuator Installation, Operation & Maintenance Manual

Quarter Master Series 94 Actuator

12 Series Linear Actuators. Operation & Maintenance Manual, Analog Positioner Installation

Installation Instructions

Electric Actuator Installation, Operation & Maintenance Manual

ANDCO Eagle Actuator Instruction Manual

VA-908x Series Electric Rotary Actuators for Two-Position and Modulating Service

Radius, LLC Electric quarter turn actuator EW series Installation, Maintenance and Operating Manual

Electric Actuator Installation, Operation & Maintenance Manual

Installation & Operation Manual

AE Installation Operation & Maintenance Instructions

Installation & Operation Manual

Series 10 Actuator. Installation, Operation and Maintenance Manual

Installation & Operation Manual

Installation, Maintenance and Operation Manual

SERIES 73 ELECTRIC ACTUATOR OPERATION AND MAINTENANCE MANUAL. The High Performance Company

Installation and Operating Manual

Installation & Operation Manual

Installation, Operation and Maintenance Manual

Installation & Operation Manual

Quarter Master Chief Series 92 Actuator

HQ Series ¼ Turn Electric Actuator

Safe & Secure Series Electric Actuator with Internal Battery Back-up Installation, Operation & Maintenance Manual

LCR Series REVERSING ELECTRIC ACTUATORS. Installation, Maintenance and Operating Instructions

ECON ELECTRIC ACTUATOR Fig ELA60 Ex

OIL FIELD ELECTRIC ACTUATOR INSTRUCTION MANUAL SPECIAL APPLICATIONS ACTUATORS Q 6.0.1

IMO-517 (7027) ISSUE 3/97 ERA12, 25, 50, 83, 125, 167, 208 AND 250 ELECTRIC ACTUATORS INSTALLATION, MAINTENANCE AND OPERATING INSTRUCTIONS

Installation & Operation Manual

Your Global Flow Control Partner. Series 70 24V On/Off Electric Actuator Operation and Maintenance Manual

Technical Specification. RCS Electric Actuators with a ProfiBus Field Control and Communication Module

Series 70 24V On/Off Electric Actuator Operation and Maintenance Manual

OPEN/CLOSE SERVICE ELECTRIC ACTUATORS OPERATION AND MAINTENANCE MANUAL COMMERCIAL AND INDUSTRIAL VALVES AND AUTOMATION

Installation & Operation Manual

OPERATION INSTRUCTONS MODEL SG 05.1 SG Quarter-Turn Actuators

Electric Modulating Actuator Installation, Operation & Maintenance Manual

12 Series Linear Electric Actuator Installation, Operation & Maintenance Manual

NOAH ACTUATOR NA-SERIES MANUAL EMICO EUNHA MACHINERY INDUSTRIAL CO.,LTD.

Reproduction or other use of this Manual, without the express written consent of Vulcan, is prohibited.

Current consumption Auxiliary switch. Angle of rotation 90 (internal electrical stops) Running time

HQ Series ¼ Turn Electric Actuator

ROM Series. Keeping the World Flowing. Installation Manual. Valve Actuators

Small Motorized Actuator

I-BFV.KIT Butterfly Valve Gear Operator Replacement

VALVCON. QX-Series ELECTRIC ACTUATORS. Installation, Maintenance and Operating Instructions

ELECTRIC ACTUATOR HVAC/BAC ELECTRIC IOM. E024, EO25, E026, EO29 & E030 Installation Operation and Maintenance Instructions TABLE OF CONTENTS

HQ-006 ¼ Turn Actuator

ICI Indelac Controls, Inc. Installation, Operation & Maintenance Manual For Electric Spring Return Actuator

K10 Intrinsically Safe Electro-Pneumatic Positioner Operating Manual

Installation & Operation Manual

MAx-305 & MAx-318 Series MAx-405 Through MAx-419 Series Two-Position Actuators

Series 72 Electri-SAFE On/Off Operation Including CLC Option Installation, Operation and Maintenance Instructions

SPECIFICATIONS ATTENTION OPERATION DESCRIPTION

CENTURA CE Series. Installation, Operation SR and Limit Maintenance Switch Method Instructions

McCANNA Actuation Systems B

Instruction Manual for Barber-Colman Series EA Electric High Torque Actuators

SERIES 70 TUNNEL DAMPER MODEL ELECTRIC ACTUATOR OPERATION AND MAINTENANCE MANUAL

Val-Matic Air / Oil Hydraulic Panel Pump Control System. Operation, Maintenance and Installation Manual

SB 2000 PUSH TO SEARCH NEXT STAG E. Aerotech, Inc. FORM: QM 1320

V Series 115 VAC AND 230 VAC STANDARD ELECTRIC ACTUATORS. Installation, Maintenance and Operating Instructions

FRACTIONAL HORSEPOWER MOTORS & ACCESSORIES

1980 Rotating Cam Limit Switches. Ordering Guide & Technical Information

ELECTRIC ACTUATOR 94OE IOM. E024, EO25, E026, EO29 & E030 Installation Operation and Maintenance Instructions TABLE OF CONTENTS

ROM Series. Established Leaders in Flow Control. Installation Manual. Valve Actuators

V Series. 115 VAC AND 230 VAC STANDARD ELECTRIC ACTUATORS With Isolated Control/Position Feedback Board Installed (Option U )

USER INSTRUCTIONS. Limitorque LY Series: LY 1001, LY 2001 and LY Installation Operation Maintenance. Experience In Motion

1.0 Features and Description

Valtek Position Pac GENERAL INFORMATION INSTALLATION INSTRUCTIONS OPERATION. Valtek Linear Actuators

2.11. Limit Switches. Contents Description. Special Purpose Limit Switches. Special Purpose Limit Switches

VALVCON V-Series ELECTRIC ACTUATORS 115 VAC AND 230 VAC With Iso/Readback Board Installed (Option U )

Electric Actuator Instructions

1980 Rotating Cam Limit Switches. Ordering Guide & Technical Information

Installation Instructions

aero 2 -IOM aero 2 ACTUATOR - INSTALLATION, OPERATION & MAINTENANCE MANUAL

Installation Instructions

SERIES 90/91 R PNEUMATIC ACTUATOR OPERATION AND MAINTENANCE MANUAL. The High Performance Company

VA-9070 Series Electric Rotary Actuators for Two-Position and Modulating Service

VALVCON I-SERIES I6600 OPTION DN DEVICENET PROTOCOL

RE Generation II Troubleshooting Guide Section I Preliminary Information and Evaluation

RCS Actuators. Versatile Automation Solutions. RCS Actuators

Quarter Master Series 94 Actuator

Current consumption Auxiliary switch. Angle of rotation 90 (internal electrical stops) Running time

Operation & Instructions Manual SA 3 - SA 100 SAR 3 - SAR 100

IOM FOR DYNATORQUE D-LOCK LOCKING DEVICE (DL TYPE)

Installation & Operation Manual

MODULATING SERVICE ELECTRIC ACTUATORS OPERATION AND MAINTENANCE MANUAL COMMERCIAL AND INDUSTRIAL VALVES AND AUTOMATION

I. Safety Requirement WARNING. ATV/UTV Winch

VALVCON V-Series ELECTRIC ACTUATORS 115 VAC AND 230 VAC. Installation, Maintenance and Operating Instructions

INSTALLATION INSTRUCTIONS AND OPERATION MANUAL

Installation & Operation Manual

MOTORTRONICS Solid State AC Motor Control

CB-005N Circuit Board

M9216 Series Electric Spring Return Actuators

Type Installation, Operation and Maintenance Instructions. Ordering Information. Contents CA20 -

Powers TM Controls EA 338 Electronic Actuator

WARRANTY INFORMATION...

Direct-Coupled ControlSet Actuators (120/180/320 in-lbs.) Installation Guide 2-7/16"

Electric Actuators Maximum in-lbs

Transcription:

Surepowr Series 100 Installation Manual Safety First In the maintenance and operation of mechanical equipment, safety is the basic factor which must be considered at all times. Through the use of the proper clothes, tools and methods of handling, serious accidents causing injury to you or your fellow workers can be prevented. Throughout this manual are listed a number of safety precautions. Study them carefully and follow them; also insist that those working for you do the same. Remember, an accident is usually caused by someone s carelessness, neglect or oversight. To prevent ignition of hazardous atmospheres, do not remove actuator cover while circuits are live. Loaded spring inside actuator. Do not attempt to repair actuator below top gear plate, unless properly trained on repair methods. Installation Note: SurePowr actuators can be supplied for clockwise or counter-clockwise spring driven rotation (viewed from the top of the actuator). The spring drive rotation is noted on the actuator name tag and wiring diagram. Ensure that the actuator has been supplied with the proper spring drive operation for the application prior to installation on the driven device. 1. The actuator is shipped in the power off (fail) position. Ensure that the driven device is orientated to its fail position prior to installation of the actuator. 2. Care should be taken to maintain proper alignment between the actuator and the device shaft. If the actuator is not in the correct alignment with the device shaft, repeat the procedure in Step 1. 3. Mount the actuator to the device. Ensure the actuator is centered properly with the device shaft, and then tighten all bolts and nuts evenly.. Remove the cover bolts located around the actuator motor and control cover flange. 5. Terminate field wiring per the appropriate RCS wiring diagram, supplied with the actuator. Use a minimum of #18 AWG stranded wire. Note: Ensure the driven device is properly positioned in its full fail position. If it is not, use the adjustable end of travel stop on the Sure 100 (see figure ) to properly adjust the fail end of travel stop. Only the fail end of travel may be adjusted. Loosen the lock nut to free the adjusting screw, then use a wrench to turn the screw. The total adjustment available is +/- 5. Figure 1 Power circuits are live. Ensure proper precautions against contact to live circuits. Cover the terminal strip with electrical tape or insulating material to prevent contact with the terminals while working in the actuator. Switch adjustments for clockwise spring fail operation (viewed from the top of the actuator) a. Ensure actuator is de-energized and positioned in the clockwise (fail) position. Ensure the end of travel stop is properly adjusted. Rotate the screw clockwise to move the actuator output shaft in a counter-clockwise direction. Rotate the screw in a counter-clockwise direction to move the actuator output shaft in a clockwise direction. Loosen the setscrews on Cams 1 and 3. Rotate both counter-clockwise until they clear the switch arm rollers of Switches 1 and 3. b. Rotate Cam 1 clockwise until it comes in contact with Switch 1 s arm roller and the switch breaks. A light click can be heard. Tighten the set-screws on Cam 1. 1

c. Rotate Cam 3 clockwise until it comes in contact with Switch 3 s arm roller and the switch just breaks. A light click can be heard. d. Rotate Cam 3 slightly further in the clockwise direction. This ensures that Switch 3 will break just prior to the actuator reaching the full fail position. Tighten the setscrews on Cam 3. Energize the actuator. This will move the actuator to the opposite end of travel. Closely monitor the electrical stroke, as the travel limit switches are not yet properly adjusted. Ensure the actuator does not over-travel and damage the driven equipment. e. Upon reaching the opposite end of travel, Cam 2 should just engage the roller on Switch 2 so that the switch just breaks. This action will stop the actuator. Check that the actuator has properly positioned the driven equipment. f. If actuator travel is insufficient, rotate Cam 2 slightly clockwise until the cam just clears the roller of Switch 2. As soon as the cam clears the roller, the actuator will bump electrically towards the end of travel. Continue until the actuator reaches the full end of travel. g. If the actuator has over-traveled, rotate Cam 2 slightly counter-clockwise, then move the actuator towards the fail position electrically. Stop and electrically reverse the direction of travel. Move the actuator until Cam 2 operates Switch 2 and the actuator stops. Repeat this procedure until the actuator is properly positioned. h. Rotate Cam until it comes in contact with Switch s arm roller and the switch just breaks. A light click can be heard. Rotate the cam slightly counter-clockwise. This ensures that Switch will break just prior to the actuator reaching the extreme opposite end of travel. Tighten the setscrews on Cams 2 and. Switch adjustments for counter-clockwise spring fail operation (viewed from the top of the actuator) a. Ensure the actuator is de-energized and positioned in the counter-clockwise (fail) position. Ensure the end of travel stop is properly adjusted. Rotate the screw counterclockwise to move the actuator output shaft in a counter-clockwise direction. Rotate the screw in a clockwise direction to move the actuator output shaft in a clockwise direction. Loosen the setscrews on Cams 2 and. Rotate both clockwise until they clear the switch arm rollers of switches 2 and. 2 b. Rotate Cam 2 counter-clockwise until it comes in contact with Switch 2 s roller arm and the switch breaks. A light click can be heard. Tighten the setscrews on Cam 2. c. Rotate Cam counter-clockwise until it comes in contact with Switch s arm roller and the switch just breaks. A light click can be heard. Closely monitor the electrical stroke, as the travel limit switches are not yet properly adjusted. Ensure the actuator does not over-travel and damage driven equipment. d. Rotate Cam slightly further in the counterclockwise direction. This ensures that Switch will break just prior to the actuator reaching the full fail position. Tighten the setscrews on Cam. Energize the actuator. This will move the actuator to the opposite end of travel. e. Upon reaching the opposite end of travel, Cam 1 should just engage the roller on Switch 1 so that the switch just breaks. This action will stop the actuator. Check that the actuator has properly positioned the driven equipment. f. If actuator travel is insufficient, rotate Cam 1 slightly counter-clockwise until the cam just clears the roller of Switch 1. As soon as the cam clears the roller, the actuator will bump electrically towards the end of travel. Continue until the actuator reaches the full end of travel.if the actuator has over-traveled, rotate Cam 1 slightly counter-clockwise, then move the actuator towards the fail position electrically. Stop and electrically reverse the direction of travel. Move the actuator until Cam 1 operates switch 1 and the actuator stops. Repeat this procedure until the actuator is properly positioned. g. If the actuator has over-traveled, rotate Cam 1 slightly clockwise, then move the actuator towards the fail position electrically. Stop and electrically reverse the direction of travel. Move the actuator until Cam 1 operates switch 1 and the actuator stops. Repeat this procedure until the actuator is properly positioned. h. Rotate Cam 3 until it comes in contact with Switch 3 s arm roller and the switch just breaks. A light click can be heard. Rotate the cam slightly further in the clockwise direction. This ensures that Switch 3 will break just prior to the actuator reaching the extreme opposite end of travel. Tighten the setscrews on Cams 1 and 3.

6. Operate the actuator electrically several times to ensure proper operation and to verify that travel limits and stops are correctly set. 7. De-energize the actuator to verify proper spring failure operation. Ensure the driven device is properly positioned in the spring failure position. 8. If the actuator is supplied with an optional feed back potentiometer and/or position controller, verify proper calibration of input and output signals after making cam and stop bolt adjustments. 9. Replace the actuator cover and cover screws. 10. The actuator is now ready for electrical operation. Wiring Diagrams Spring Drive CW on Loss of Power Spring Drive CCW on Loss of Power FIELD WIRING TB 6 ACTUATOR WIRING +t HEATER (OPT.) FIELD WIRING TB 6 ACTUATOR WIRING +t HEATER (OPT.) L2 (NEUTRAL) 1 M1 THERMAL OVERLOAD AUTOMATIC RESET L2 (NEUTRAL) 1 M1 THERMAL OVERLOAD AUTOMATIC RESET A.C. LINE L1 CCW STOP CW SP-3 POSITION SNAP ACTION SWITCH BRIDGE MOTOR RECTIFIER BRAKE SWITCH 2 2 5 SWITCH 1 3 7 8 SWITCH 3 9 M2 M CAPACITOR M3 A.C. LINE L1 CCW STOP CW SP-3 POSITION SNAP ACTION SWITCH BRIDGE MOTOR RECTIFIER BRAKE SWITCH 2 2 5 SWITCH 1 3 7 8 SWITCH 3 9 M2 M CAPACITOR M3 10 11 12 SWITCH 10 11 12 SWITCH GREEN GROUNDING SCREW GREEN GROUNDING SCREW Figure 2 Power to terminals 1 and 2 will motor drive and hold actuator in CCW most position if the brake is energized at terminal 1 & when switch N.O. of SW2 closes. Power to terminals 1 and will brake hold actuator in whatever position it is in at the time. Power to 1 and 3 will motor drive and spring hold actuator in CW most position. Loss of power will spring drive and spring hold actuator in CW most position. Figure 3 Power to terminals 1 and 3 will motor drive and brake hold actuator in CW most position if the brake is energized at terminal 1 & 5 when switch N.O. of SW1 closes. Power to terminals 1 and 5 will brake hold actuator in whatever position it is in at the time. Power to terminal 1 & 2 will motor drive and spring hold actuator in CCW most position. Loss of power will spring drive and spring hold actuator in CCW most position. IMPORTANT Direction of rotation is based on viewing actuator from top. To operate multiple actuators in parallel from a single source requires isolating relays in the field wiring. 3

NEMA, 6, 7 & 9 Dimensional Information 11.56 Dia. 2.3 Dia. 5.78 Indicator Cover 21.53 28.81 Cover removal 18.6 Two, 3/ N.P.T. Conduit Entrance 10.87 CCW spring drive adjustable end of travel stop. CW spring drive adjustable end of travel stop. Spring housing Figure Valve mounting surface Conduit Entry 5/16 18U x 0.63 DP. Typ. places located on a 2.756 D.B.C. 1.102 Dia. x 1.38 DP. 1.20.00 Dia. Conduit Entry Notes: 1. Direction of rotation is based on viewing actuator from top. 2. Actuator shown in power fail position. 3. Mounting geometry complies with ISO 5211 flange type F07 (except bolt thread). *. Two keys are recommended for driving device. 0.315 x 0.276 [8mm x 7mm] Key Typ. 2 places CCW Spring Return Figure 5 CW Spring Return

To prevent ignition of hazardous atmospheres, do not remove actuator cover while circuits are live. Operation Power On: The electric motor drives the gear train, which in turn winds the spring and turns the device. An internal limit switch de-energizes the motor and the brake, which holds the return spring and device in position. Power Off: When the current is interrupted by either a control signal or a power failure, the return spring drives the device to its original position. Note: It is recommended that the actuator be driven electrically in both directions for normal operation to prolong cycle life. Maintenance Gear train is permanently lubricated at the factory for the average life of the actuator. No further attention is required. Thermal Overload The internal thermal overload switch de-energizes the motor and prevents overheating of the motor windings due to excessive operation, stalling or high ambient temperatures. Duty Cycle The maximum duty-cycle to be expected without interruption by thermal cut-off at an ambient temperature of 65C is 25% (3 OFF times for every 1 ON time) for the 5 and 10 second design, and 50% (1 OFF time for every 1 ON time) for the 30 second design. Storage The Surepowr actuator must be stored in a clean, dry, temperature controlled building which is protected from the weather. Precautions shall be taken to prevent condensation inside or outside the actuator. If there is insufficient external temperature and humidity control, internal heaters must be installed and energized to protect the unit against condensation from extreme temperature variations. The actuators shall be stored off the floor on suitable pallets and must be covered with an unsealed dust protector allowing side and bottom ventilation. Isolation Relays To operate multiple actuators in parallel from a single signal requires isolating relays in the field wiring. Consult Factory. Troubleshooting (New Unit) Note: Most actuator problems occur due to incorrect cam/travel limit switch setting, or the use of an external travel stop on the device that the actuator is operating. Problem 1: Actuator is receiving electric power but the motor does not respond. 1a. Check actuator nameplate to insure correct model, voltage type and spring return direction. 1b. Check all wiring against installation wiring diagram. 1c. Actuator with clockwise fail position: Using a volt meter, check that power is available between terminals 1 and 2. Then check the voltage between terminal 1 (common) and the two legs of the motor and capacitor. The meter should indicate a value equal to or greater than the supply voltage indicated on the actuator nametag. Actuator with counter-clockwise fail position: Using a volt meter, check that power is available between terminals 1 and 3. Then check the voltage between terminal 1 (common) and the two legs of the motor and capacitor. The meter should indicate a value equal to or greater than the supply voltage indicated on the actuator nametag. If power is not present at the motor or capacitor leads: Cam adjustments are required Switch malfunction Improper wiring 5

Problem 2: Actuator is receiving electric power but the motor only hums. 2a. Perform steps 1a through 1c listed above. 2b. Check to insure the brake is completely disengaged when power is applied. Problem 3: Actuator runs but operation is erratic. 3a. Perform steps 1a through 1c listed above. 3b. Check ambient temperature. Standard Surepowr actuators have a maximum ambient operating temperature rating of 65 C. 3c. Check duty cycle (frequency of operation). See above for details. 3d. Ensure that actuator is not continuously stalled. Problem : Motor runs continuously in spring return direction after actuator output shaft has stopped. a. Adjust spring return side travel cam/switch so that the cam trips the switch before the shaft stops motion. Problem 5: Motor runs continuously but output shaft does not turn. 5a. Check for power to the bridge rectifier and clutch solenoid. Note: Standard Surepowr actuators are manufactured with thermal overload protectors in series with the motor common. Should any of the above problems cause the protector to open, it will automatically reset when the motor temperature is lowered to a safe level. Locating and Ordering Parts For ease and accuracy in identifying and ordering spare or replacement parts, submit the following information from unit nameplate. 1. Serial Number 2. Model Number 3. Voltage Industrial Products Group Dresser, Inc. 1620 Port Northwest Drive Houston, Texas 7701-265 USA Ph: 832.590.2306 Fax: 713.89.2879 Toll Free Phone: 800.95.9898 Email: rcs@dresser.com 2008 Dresser, Inc. RCS, and DRESSER are registered trademark(s) of Dresser, Inc. www.dresser.com Surepowr Series_100_im 7.08