Powered by Safety 01.4IB Powell GIS (Gas Insulated Switchgear)

Similar documents
SM-1700 Secondary Shunt Trip Coil Assembly. Powered by Safety

IB PowlVac ITE-HK Remote Racking Device

Gas Insulated Metal-clad Switchgear, HMGS!

Type 2 Arc Resistant WL Low Voltage Metal-Enclosed Switchgear

PIX-H Metal-clad switchgear up to 17.5kV

ZX1.5-R. Gas-insulated medium voltage for railway application DISTRIBUTION SOLUTIONS. Gas-insulated medium voltage for railway application ZX1.

B kv T&D GAS INSULATED SWITCHGEAR

NXPLUS C Single busbar. Maintenance-free for lifetime

Instruction manual. Type 3AH35-MA vacuum circuit breaker magnetic-actuator operator module.

Powered by Safety 01.4IB.77000B PowlVac-ND Vacuum Circuit Breaker

GE Consumer & Industrial Power Protection. New. SecoGear kV Metal-clad Switchgear. GE imagination at work

CPG.1 Gas insulated, single busbar cubicle range Up to 27 kv / 2000 A / 31.5 ka Up to 38 kv / 2000 A / 31.5 ka IEEE Standards

ZX2.2 Gas-insulated medium voltage switchgear

ZX2 Gas-insulated medium voltage switchgear

GE Industrial Solutions. User/Installation Manual for 4.76kV -15kV SecoBloc

KYN28A-12 (GZS1) A.C METALCLAD REMOVABLE SWITCHGEAR FOR INDOOR USE CHINATCS

TECHNICAL SPECIFICATION OF 11KV SF6 / VCB METAL ENCLOSED, INDOOR (PANEL TYPE) / OUTDOOR RING MAIN UNIT (RMU). (IEC standard equipment)

SF 6 Gas Insulated Switchgear Type SDH314 / SDHa314 for 72.5 to 145 kv

PATENT PENDING. Phone: (877) Operation and Service Manual

GHA. Gas-Insulated Switchgear. Gas-Insulated Switchgear. Switchgear extension and replacement of a panel

11kV Compact Switchgear. tec - range. Minimum to Zero SF6 Insulation Gas. Outec Controls

Cable arrangement 15 Preparation for cable installation. 15 Installation of the cables 16 Finishing of the cable installation. 17 Examples.

SF 6 Gas Insulated Switchgear Type SDH714 for 72.5 to 145 kv

Vacuum Circuit Breaker (Vehicle)

Medium Voltage Metal-Enclosed Switches

CPG.0 Single busbar gas-insulated cubicles

Metal Clad Air Insulated Switchgear

EISHO TEK. Vacuum Circuit Breaker

Instruction for Installation and Operation

IB PowlVac CDR Vacuum Circuit Breaker. 5kV & 15kV 1200A, 2000A, & 3000A. Powered by Safety

Instruction manual. Type 3AH35-MA vacuum circuit breaker magnetic-actuator operator module.

Vacuum Circuit Breakers (Vehicle)

SF6 GAS INSULATED METAL ENCLOSED SWITCHGEAR (GIS)

AIR INSULATED EXTENDABLE SWITCHGEAR UP TO 12KV GUIDE

UniGear. Technical Guide

General. Main electric circuits Fuses compartment Operating mechanisms Cables connection compartment

B kv Gas-insulated Substations

CGMCOSMOS. Reliable innovation. Personal solutions. Fully gas insulated modular and compact (RMU)system.

CR193 Vacuum Limitamp* Contactors

IB-20206A Low Voltage Metal-Enclosed Switchgear. Equipped with Siemens WL Circuit Breakers. Powered by Safety

BHARAT HEAVY ELECTRICALS LIMITED, JHANSI

University of Houston Master Construction Specifications Insert Project Name

Medium Voltage Metal-Enclosed Switches

with Vacuum Circuit Breaker HAF

Air-insulated switchgear UniGear type ZS1

Type SIMOPRIME A4, up to 24 kv, Air-Insulated Medium-Voltage Switchgear

Metal-Enclosed Switches. Medium Voltage. Medium Voltage Metal-Enclosed Switches Contents

Switchgear Type SIMOSEC, up to 24 kv, Air-Insulated, Extendable

M-RING 24. SF6 Insulated Ring Main Unit Metal-Enclosed (LSC2A)

Unified requirements for systems with voltages above 1 kv up to 15 kv

Catalog HA Edition up to 24 kv, Air-Insulated, Extendable. Medium-Voltage Switchgear. siemens.com/simosec

1. Safety practices General Introduction Standards...3

THP145 HYBRID GAS INSULATED SWITCHGEAR (HGIS) Energy, Fast! tgood.com

36kV Gas Insulated Medium Voltage Switchgear

SYSclad switchboard equipped with draw out type vacuum circuit breaker closed dooroperationoperation. SYSclad 12 17,5kV A.

AIR INSULATED METAL ENCLOSED SWITCHGEAR AND CONTROLGEAR

Switchgear Type SIMOSEC, up to 24 kv, Air-Insulated, Extendable

Vacuum Circuit Breakers (Vehicle) Type HKR 7.5kV to 15kV. Instructions Installation Operation Maintenance SGIM-9928C

Installation Instructions For Motor Control Center (MCC) Units

ZF SERIES HV GAS INSULATED SWITCHGEAR (GIS) tgood.com. Energy. Fast.

All rights reserved. Neither this catalogue nor any part of it may be copied using any method or for any purposes. Most studies are legally protected.

ME Switchgear with Vacuum Circuit Breaker and Auto-jet II Switch with Ground Position

abb SafeLink SF 6 Insulated Ring Main Unit Installation and Operating Instructions Switchgear Division Auckland, New Zealand SLMIO ver 2.

Gas-Insulated Switchgear. Type 8VN1 blue GIS up to 145 kv, 40 ka, 3150 A

Powered by Safety Powell GIS Type G81 Switchgear

Submersible Vacuum Fault Interrupters

Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers

8DJ. Maintenance-free for lifetime

Pretest Module 29 High Voltage Unit 1

MV Air Insulated Switchgear TAP17. Technical Data TGOOD

SIEMENS. XJ-L Busway Systems. Storage, Installation and Maintenance Instructions for... Piece No. 32-J Rev 3

SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Brochure

SUBSTATION VACUUM CIRCUIT BREAKER (38KV)

UBC Technical Guidelines Section Edition Commissioning of Electrical Systems Page 1 of 5

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV)

SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV)

Fixed-Mounted Circuit-Breaker Switchgear Type 8DA and 8DB up to 40.5 kv, Gas-Insulated

Instruction and Installation Guide

Circuit-Breaker Switchgear Type SIMOPRIME, up to 17.5 kv, Air-Insulated Medium-Voltage Switchgear.

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE

Test Cabinet (Inspection Box) Instructions. for Testing Accessories on Manually and Electrically Operated EntelliGuard G Low Voltage Circuit Breakers

Vacuum Circuit Breakers (Vehicle)

A. Submit manufacturer's literature and technical data before starting work.

Air Insulated Switchgear NXAirS, 40.5kV Answers for infrastructure and cities.

Publication No.: PSG

Quick Start Guide TS 910 & TS 920

MEDIUM VOLTAGE AIR INSULATED ARC-RESISTANT LOAD BREAK AND DISCONNECT SWITCHES

MEDIUM VOLTAGE CE-B METAL CLAD SWITCHBOARDS. CE-B-C-en-REV

PowlVac Type PV STD/CDR Vacuum Circuit Breaker

MESG 12 / 17.5 / 24 / 36 KV

Typical Specification

VOLUME: IIIC SCHEDULE IIIC/4 11 KV AND 3.3 KV SWITCHGEARS

5kV to 38kV, 630 Amp to 4000 Amp Indoor or Outdoor Application

Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kv, Gas-Insulated

Instruction Booklet for the Installation, Operation and Maintenance of Type 5-15 kv VCP-WG Vacuum Circuit Breaker 4000A MiniMod

Fixed-Mounted Circuit-Breaker Switchgear Type NXPLUS C up to 24 kv, SF 6 -Insulated. Medium-Voltage Switchgear Catalog HA 35.

Switchgear Type 8DJH for Secondary Distribution Systems up to 24 kv, Gas-Insulated

Benefits, typical uses

SecoVac * Ground & Test Device

Quick Start Guide TS 910

Transcription:

Powered by Safety Powell GIS (Gas Insulated Switchgear) G81-36kV / 1250A, 2000A, 2500A, & 3150A / 40kA G82-38kV / 1200A, 2000A, 2500A / 40kA

Powell GIS 38kV Gas Insulated Switchgear Contact Information Powell Electrical Systems, Inc. powellind.com info@powellind.com Service Division PO Box 12818 Houston, Texas 77217-2818 Tel: 713.944.6900 Fax: 713.948.4569 Powered by Safety

Signal Words As stated in ANSI Z535.4-2007, the signal word is a word that calls attention to the safety sign and designates a degree or level of hazard seriousness. The signal words for product safety signs are Danger, Warning, Caution and Notice. These words are defined as:! DANGER DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury.! WARNING WARNING indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. Qualified Person For the purposes of this manual, a qualified person, as stated in NFPA 70E, is one who has skills and knowledge related to the construction and operation of the electrical equipment and installations and has received safety training to recognize and avoid the hazards involved. In addition to the above qualifications, one must also be: 1. trained and authorized to energize, deenergize, clear, ground, and tag circuits and equipment in accordance with established safety practices. 2. trained in the proper care and use of personal protective equipment (PPE) such as rubber gloves, hard hat, safety glasses or face shields, flash clothing, etc., in accordance with established safety practices. 3. trained in rendering first aid if necessary.! CAUTION CAUTION, used with the safety alert symbol, indicates a hazardous situation which, if not avoided, could result in minor or moderate injury. CAUTION CAUTION, used without the safety alert symbol, is used to address practices not related to personal injury. NOTICE NOTICE is used to address practices not related to personal injury. Powered by Safety

Powell GIS 38kV Gas Insulated Switchgear This page left blank intentionally. Powered by Safety

Contents Ch 1 General Information...1 A. Scope...2 B. Purpose...2 C. Instruction Bulletins Available Electronically...2 Ch 2 Safety...3 A. Safe Work Condition...3 B. Safety Guidelines...3 C. General...4 D. Specific...4 E. X-Rays...5 F. Safety Labels...5 Ch 3 General Powell GIS...6 A. Description...6 1) Safety and Maintenance... 6 2) Four Completely Segregated Areas... 6 Ch 4 General Specification...7 A. Applied Standard...7 B. Service Condition...7 C. Structure...7 1) General... 7 2) Circuit Breaker... 7 3) 3-Position Switch... 7 4) Bus... 7 5) Current Transformer... 8 6) Potential Transformer... 8 7) Lightning Arrester... 8 8) Painting... 8 Ch 5 Technical Specification...9 A. Ratings...9 B. 3-Position Switch... 10 Powered by Safety i

Powell GIS 38kV Gas Insulated Switchgear Contents Ch 6 Structure...11 A. General... 11 B. Circuit Breaker... 11 C. Mechanisms... 12 1) Circuit Breaker Mechanism...12 2) 3-Position Switch Mechanism...12 D. Bus Compartment... 13 E. Cable Compartment... 13 Ch 7 Operation...14 A. Construction of each Feeder... 14 B. Operation Circuit Breaker... 16 C. Operation of 3-Position Switch... 19 1) Electric Operation...20 2) Manual Operation...20 Ch 8 Components...22 A. Circuit Breaker (HHF)... 22 B. Vacuum Interrupter Construction... 22 C. 3-Position Switch (3PS)... 23 D. Bus Bar Connector (Single Phase)... 23 E. 3-Position Switch Bushing (Connects Bus Bar Compartment and Circuit Breaker Compartment)... 23 F. Cable Socket... 23 G. Rupture Disc... 24 Ch 9 Assembly & Carry...25 Ch 10 Installation...26 A. Installation... 26 B. Erection of Powell GIS... 27 1) End Panel...27 2) Next Panel...27 3) Installation of End Panel...32 4) Connecting Primary and Secondary Cables...32 5) Pressure Relief Arc Gas Ducts...32 6) Special Accessories for G81 & G82 Installation...32 C. Extension of Panels on Site... 33 D. HV Cable Connection... 35 E. Final Equipment Check... 35 F. Insulation Gas... 35 ii Powered by Safety

Contents Ch 11 Maintenance & Test Procedure...36 A. Maintenance... 36 1) Safety...36 2) Maintenance Terms...36 3) Check of Insulation Gas...36 4) Instruction for Lubrication Use...36 B. Test Procedure... 37 1) Visual Check...37 2) Functional Test...37 3) Cleaning...37 4) Check the Control Circuit Wiring...37 5) SF₆ Gas Leakage Test...37 6) Control Circuit Wiring Test...38 7) Timing...38 8) 3-Position Switch (disconnector or earth) Operating Test...38 9) Manual Close/Open Test...38 10) Potential Transformer Test...38 Ch 12 Others...39 A. Post Processing of Bolt and Torque Valve... 39 B. Processing of Contact Surface... 39 1) Cleaning...39 C. Gas Monitoring System (HMD3)... 39 1) Channel Scan...39 2) Automatic Scan Mode...39 3) Manual Scan Mode...40 4) Change the Parameter...40 Powered by Safety iii

Powell GIS 38kV Gas Insulated Switchgear Figures Figure 1 Drawing of G81...11 Figure 2 Circuit Breaker Mechanism...12 Figure 3 3-Position Switch Mechanism...12 Figure 4 G81 Single Bus System...14 Figure 5 G82 Transfer Bus System...15 Figure 6 Circuit Breaker Schematic...16 Figure 7 Flowchart for Circuit Breakers...17 Figure 8 Available position for 3-Position Switch and Circuit Breaker...18 Figure 9 3-Position Switch Schematic...19 Figure 10 Operation Device & Switch Position...21 Figure 11 Circuit Breaker and Mechanism...22 Figure 12 Vacuum Interrupter for HVS-03644...22 Figure 13 Structure of 3-Position Switch...23 Figure 14 Structure of Bus bar Connector...23 Figure 15 Structure of 3PS Bushing...23 Figure 16 Structure of Cable Socket...23 Figure 17 Rupture Disc...24 Figure 18 Equipment Lifting...25 Figure 19 Installation...26 Figure 20 End Panel Installation...27 Figure 21 Bolting of Guide Pin...28 Figure 22 Installing Bolts and Guide Pins...29 Figure 23 Connecting to Bus Bar Socket...29 Figure 24 Panel and Bus Bar Connection...30 Figure 25 Figure of Installation Site...31 Figure 26 Bus Bar Closing Caps...32 Figure 27 Future of Extension Site...34 Figure 28 Connection of the HV Cable Plug...35 Figure 29 Lubrication of Circuit Breaker Mechanism...36 Figure 30 Lubrication of 3-Position Switch Mechanism...37 Figure 31 HMD3...41 Figure 32 Wiring Connection Diagram...42 iv Powered by Safety

Tables Table A Cubicle Type Gas Insulated Switchgear Ratings...9 Table B 3-Position Switch...10 Table C Installation Steps...26 Table D Erection of Powell GIS Steps...27 Table E Next Panel Installation...27 Table F Installation of End Plate Steps...32 Table G Special Accessory for G81 & G82 Installation...32 Table H Extension of Panels on Site Steps...33 Table I Maintenance Terms...36 Table J Inspection...36 Table K Timing...38 Table L Insulation Resistance...38 Table M Class 8.8 or 9.8 Bolt and Nut...39 Table N Class 10.9 Bolt and Nut...39 Table O Change the Parameter...40 Powered by Safety v

Powell GIS 38kV Gas Insulated Switchgear This page left blank intentionally. vi Powered by Safety

Ch 1 General Information! WARNING The equipment described in this document may contain high voltages and currents which can cause death or serious injury. The equipment is designed for use, installation, and maintenance by knowledgeable users of such equipment having experience and training in the field of high voltage electricity. This document and all other documentation shall be fully read, understood, and all warnings and cautions shall be abided by. If there are any discrepancies or questions, the user shall contact Powell immediately at 1.800.480.7273.! WARNING Prior to adjustments, servicing, maintenance, or any act requiring the operator to make physical contact with the equipment, the power source must be disconnected and the equipment grounded. Failure to do so may result in death or serious injury. NOTICE The information in this instruction bulletin is not intended to explain all details or variations of the Powell equipment, nor to provide for every possible contingency or hazard to be met in connection with installation, testing, operation, and maintenance of the equipment. For additional information and instructions for particular problems, which are not presented sufficiently for the user s purposes, contact Powell at 1.800.480.7273. NOTICE Powell reserves the right to discontinue and to change specifications at any time without incurring any obligation to incorporate new features in products previously sold. General Information Powered by Safety 1

Powell GIS 38kV Gas Insulated Switchgear A. Scope The information in this instruction bulletin covers the technical data in respect to the 36kV/38kV, 40kA SF₆ Powell GIS (Gas Insulated Switchgear). B. Purpose The information in this instruction bulletin is intended to provide information required to properly operate and maintain the Gas Insulated Switchgear described in Ch 1 General Information, A. Scope. This instruction bulletin provides: 1. Safety guidelines 2. General descriptions of the operation and maintenance of the gas insulated switchgear 3. Instructions for installation and placing the switchgear into service 4. Instructions for part replacement 5. Information for ordering renewal parts 6. Procedure for critical adjustments 7. Illustrations, photographs, and description of the switchgear The illustrations contained in this document may not represent the exact construction details of each particular type of gas insulated switchgear. The illustrations in this document are provided as general information to aid in showing component locations only.! WARNING Be sure to follow the appropriate safety precaution while handling any of the equipment. Failure to do so may result in serious injury or death. To the extent required, the products described herein meet the applicable ANSI, IEEE, NEMA, and IEC Standards; however, no such assurance is given with respect to local codes and ordinances which may vary greatly. C. Instruction Bulletins Available Electronically NOTICE Changes to the instruction bulletin may be implemented at any time and without notice. Go to powellind.com to ensure use of the current instruction bulletin for the Powell equipment. For more information visit powellind.com. To contact the Powell Service Division call 1.800.480.7273 or 713.944.6900, or email info@powellservice.com. For specific questions or comments pertaining to this instruction bulletin email documents@powellind.com with the IB number in the subject line. All illustrations and photos are shown using deenergized equipment. 2 Powered by Safety General Information

Ch 2 Safety A. Safe Work Condition The information in Section A is quoted from NFPA 70E 2012 - Article 120, 120.1 Establishing an Electrically Safe Work Condition. 120.1 Process of Achieving an Electrically Safe Work Condition 1. Determine all possible sources of electrical supply to the specific equipment. Check applicable up-to-date drawings, diagrams, and identification tags. 2. After properly interrupting the load current, OPEN the disconnecting device(s) for each source. 3. Wherever possible, visually verify that all blades of the disconnecting devices are fully OPEN or that drawout type circuit breakers are withdrawn to the fully disconnected position. 4. Apply lockout/tagout devices in accordance with a documented and established policy. 5. Use an adequately rated voltage detector to test each phase conductor or circuit part to verify they are deenergized. Test each phase conductor or circuit part both phase-to-phase, and phase-to-ground. Before and after each test, determine that the voltage detector is operating satisfactorily. Informational Note: See ANSI/ISA-61010-1 (82.02.01)/UL 61010-1, Safety Requirements for Electrical Equipment for Measurement, Control, and Laboratory Use - Part 1: General Requirements, for rating and design requirements for voltage measurement and test instruments intended for use on electrical systems 1000 V and below. 6. Where the possibility of induced voltages or stored electrical energy exists, ground the phase conductors or circuit parts before touching them. Where it could be reasonably anticipated that the conductors or circuit parts being deenergized could contact other exposed energized conductors or circuit parts, apply ground connecting devices rated for the available fault duty. B. Safety Guidelines Study this instruction bulletin and all other associated documentation before uncrating the switchgear. Each user has the responsibility to instruct and supervise all personnel associated with usage, installation, operation, and maintenance of this equipment on all safety procedures. Furthermore, each user has the responsibility of establishing a safety program for each type of equipment encountered. The switchgear described in this instruction bulletin are operated by a high-energy, high-speed mechanism that is interlocked to provide specific operating sequences. It is mandatory that the following rules be observed to ensure the safety of personnel associated with usage, installation, operation, and maintenance of these circuit breakers. The safety rules in this instruction bulletin are not intended to be a complete safety program. The rules are intended to cover only some of the important aspects of personnel safety related to gas insulated switchgear. Safety Powered by Safety 3

Powell GIS 38kV Gas Insulated Switchgear C. General 1. Only supervised and qualified personnel trained in the usage, installation, operation, and maintenance of gas insulated switchgear shall be allowed to work on this equipment. It is mandatory that this instruction bulletin, any supplements, and service advisories be studied, understood, and followed. 2. Maintenance programs must be consistent with both customer experience and manufacturer s recommendations, including service advisories and instruction bulletin(s). A well planned and executed routine maintenance program is essential for circuit breaker s reliability and safety. 3. Service conditions and circuit breaker applications shall also be considered in the development of safety programs. Variables include ambient temperature; humidity; actual continuous current; thermal cycling; number of operations; interrupting duty; and any adverse local conditions including excessive dust, ash, corrosive atmosphere, vermin and insect infestations. D. Specific 1. Do not work on an energized circuit breaker. 2. Do not work on a circuit breaker with the control circuit energized. 3. Extreme care must be exercised to keep all personnel, tools, and other objects clear of mechanisms which are to be operated, discharged, or released. These circuit breakers utilize stored energy mechanisms. These mechanisms must be serviced only by skilled and knowledgeable personnel capable of releasing each spring load in a controlled manner. Detailed information regarding these mechanisms is found in this instruction bulletin. 4. Do not attempt to close the circuit breaker manually on an energized circuit. 5. Do not use an open circuit breaker as the sole means of isolating a high voltage circuit. For complete isolation, the circuit breaker shall be in the open position and disconnector open, and circuit earthed. 6. All components shall be disconnected by means of a visible break and securely grounded for safety of personnel performing maintenance operations on the circuit breakers. 7. Interlocks are provided to ensure the proper operating sequences of the circuit breakers and for the safety of the user. If for any reason an interlock does not function as described, do not make any adjustments, modification, or deform the parts. Do not force the parts into position. Contact Powell for instructions. 4 Powered by Safety Safety

E. X-Rays When high voltage is applied across the contacts of a vacuum interrupter, there is the possibility of generation of X-rays. The intensity of the X-radiation is dependent on the peak voltage and the contact gap. At the normal operating voltage for this type of equipment, the radiation levels are negligible. At the voltages specified for testing, test personnel shall be in front of the circuit breaker such that the two layers of steel used in the frame and front cover construction are between the test personnel and the vacuum interrupters, and that the test personnel be no closer than one meter (3 ) from the front of the circuit breaker. The circuit breaker shall be either fully open, or fully closed when making high potential tests. Do not test with contacts partially open. F. Safety Labels The equipment described in this document has DANGER, WARNING, CAUTION, and instruction labels attached to various locations. All equipment DANGER, WARNING, CAUTION, and instruction labels shall be observed when the circuit breaker is handled, operated, or maintained. NOTICE Warning and Caution labels are located in various places in and on the switchgear and on the circuit breaker removable element. Always observe these warnings and caution labels. Do NOT remove or deface any of these warning/caution labels. Safety Powered by Safety 5

Powell GIS 38kV Gas Insulated Switchgear Ch 3 General Powell GIS A. Description Powell s cubical type gas-insulated switchgear is an integrated assembly of a vacuum circuit breaker, the 3-position switch/disconnector, bus connecting system and control devices coordinated electrically and mechanically for a medium voltage power system. 1) Safety and Maintenance The 3-position switch is interlocked with circuit breaker mechanically Circuit breaker function accompanied by earthing function in combination with the 3-position switch Operating mechanism is accessed from outside of enclosure 2) Four Completely Segregated Areas Bus compartment(s) Circuit breaker compartment Cable compartment Low voltage compartment 6 Powered by Safety General PGIS

Ch 4 General Specification A. Applied Standard 1. Powell GIS if manufactured in accordance with the IEC standards. IEC 62271-100: High-Voltage alternating current circuit breakers IEC 62271-200: AC Metal-Enclosed Switchgear and control gear for rated voltages above 1kV and up to and including 52kV. IEC 62271-102: High-Voltage alternating current disconnector and earthing. IEC 60376: Specification of technical grade sulfur hexafluoride (SF₆) for use in electrical equipment. IEC 60480: Diagnosis guide of SF₆ gas for electric device. B. Service Condition 1. Location: Indoor 2. Ambient Temperature: -5 ~ +40 C 3. Altitude: Not exceeding 1,000m above sea level 4. Atmospheric Condition: Not notably polluted C. Structure 1) General The gas tank has been designed for its entire life. It is made of stainless-steel (SUS 304L), contains a 3-position switch/disconnector switch, bus bar and vacuum interrupter. 2) Circuit Breaker The circuit breaker is rated up to 36kV/38kV, 40kA. The circuit breaker consists of a vacuum interrupter, insulator frame and operating mechanism. The circuit breaker poles are installed horizontally in the circuit breaker compartment. The vacuum interrupter is supported by the insulator frame located in the circuit breaker compartment. The circuit breaker is operated by a stored energy mechanism normally charged by a small universal motor, but it can be also charged by a manual handle for emergency manual to close and open. The circuit breaker has three independent vacuum interrupters. 3) 3-Position Switch The 3-positon switch is rated up to 36kV/38kV, 40kA and is a motor operating rod-type switch. Live switch components (bus bar, insulated spindle with moving contact) are in the gas compartment and the operating mechanism components (drive motor, position indicator and emergency manual operation) outside of the gas compartment. 4) Bus Single and double bus system Transfer Bus System The tank is permanently sealed. No maintenance or refilling of the tank required. In the event of an internal arc, each tank has a rupture disc which direct gases to an arc duct assembly. General Specifications Powered by Safety 7

Powell GIS 38kV Gas Insulated Switchgear 5) Current Transformer The current transformer is an individual cast-resin insulated product available to be installed inside a SF₆ gas compartment. 6) Potential Transformer The potential transformer is a plug-in and epoxy molding type. 7) Lightning Arrester The lightning arrester is a plug-in type. 8) Painting The gas tanks are stainless steel and do not require painting. All other external metal surfaces are cleaned, rust proofed and painted in accordance with Powell s paint thickness. 8 Powered by Safety General Specifications

Ch 5 Technical Specification A. Ratings Table A Cubicle Type Gas Insulated Switchgear Ratings Switchgear Type HMGS-G81 HMGS-G82 Rated Voltage (kv) 36 [40.5] 1 38 Power Frequency Withstand Voltage (kv) 70 [95] 1 80 Lightning Impulse Withstand Voltage (kv) 170 [190] 1 150 [200] 1 Rated Frequency (Hz) 50 / 60 50 / 60 Normal Current (Amperes) Main Bus 3150 2500 Feeder 1250 / 2000 / 2500 / 3150 1200 / 2000 / 2500 Rated Short Time Withstand Current, 3s (ka) 40 40 Rated Peak Withstand Current (ka, peak) 104 104 Rated Short Circuit Breaking Current (ka) 40 40 Rated Short Circuit Making Current (ka) 104 104 Rated Operating Sequence O-0.3s-CO--15s-CO O-0.3s-CO--15s-CO Closing Time (ms) 70 70 Opening Time (ms) 50 40 Breaking Time (cycle) 5 3 Auxiliary Voltage (V) DC110 / 125 2 DC110 / 125 2 Insulation Gas SF 6 SF 6 Rated Pressure at 20 C (bar) 0.3 [0.4] 1 0.4 Minimum Operating Pressure at 20 C 0.2 [0.3] 1 0.3 Arc Classification (62271-200) B FLR, 40kA / 1s B FLR, 40kA / 1s Bus Bar System Single / Double Single / Double / Transfer Size (mm) 3 Notes: Width (W) 1250A 600 [800] 4 800 2000A 800 800 Depth (D) [optional extra depth] 1760 [1960] 5 1960 Height (H) 2400 2400 1 The value in [ ] is for the system according to the GOST 1516.3, GB 3906 or relevant standard on request. 2 The auxiliary voltage can be changed on request. 3 The size of actual panel can be different according to the rating, quantity and arrangement of components. 4 Width of the panel in [ ] is when voltage transformer is installed. 5 Depth of the panel can increase according to the numbers and size of components in low voltage compartment. Technical Specification Powered by Safety 9

Powell GIS 38kV Gas Insulated Switchgear B. 3-Position Switch Type Rated Voltage Frequency Rated Current Power Frequency withstand Voltage Lightning impulse withstand voltage (1.2/50) Short-time withstand current frequency Disconnector class of mechanical endurance Operation method Control Voltage Control Voltage change range Table B 3-Position Switch 3PS 36(38)kV 50/60Hz 1200A/1250A/2000A/2500A/3150A Phase to earth and between phases Across the isolating distance Phase to earth and between phases Across the isolating distance 40kA Peak withstand current Duration of shortcircuit M1 Motor & Handle DC110 / 125VDC 85 ~ 110% 70(80)kV 80(88)kV 170kV 195kV 104kA 3s 10 Powered by Safety Technical Specification

Ch 6 Structure Figure 1 Drawing of G81 A. General i Powell GIS is a metal enclosure 3-phase conductor that is symmetrically arranged with a compact structure. a f B. Circuit Breaker The circuit breaker compartment contains a vacuum interrupter assembly that is connected to a mechanism for open and close operation. The 3-position switch can connect and disconnect the main bus. The switch can also ground the circuit breaker and connected line or load terminals. b d e g h k c f i j l a. Main Bus b. 3-Position Switch Mechanism c. 3-Position Switch d. Main 3-Pole Bushing (Contact Conductor) e. Vacuum Interrupter f. Rupture Disc g. Vacuum Interrupter Housing h. Circuit Breaker Mechanism i. Arc Gas Duct j. Current Transformer (Block Type) k. Cable Socket (Structure) l. Instrument Compartment Structure Powered by Safety 11

Powell GIS 38kV Gas Insulated Switchgear C. Mechanisms 1) Circuit Breaker Mechanism Motor : ~ 125 VDC, for close spring charging Auxiliary switch : 5 Poles or 10 poles Close coil : 86 Ohm Trip coil : 86 Ohm for 5 cycles or (42 Ohm for 3 cycles) 2) 3-Position Switch Mechanism Figure 3 Motor : ~125 VDC Auxiliary switch (DS,Open,ES) : Up-to 10 Poles Motor & hand operation 3-Position Switch Mechanism a Figure 2 Circuit Breaker Mechanism b c d b f h k m a c d e g i j l n e f g h a. Close/Open Indicator b. Breaker Shaft c. Dash Pot d. Operating Counter e. Opening Button f. Closing Mechanism g. Open Solenoid h. Close Spring i. Closing Button j. Manual Charging Operating Hole k. Trip Spring l. Closing Solenoid m. Spring Charge Indicator n. Motor o. Auxiliary Switch o a. Indicator b. Handle Insert Hole c. Motor d. Interlock Rod e. Limit Switch for Motor Control f. Auxiliary Switch g. Drive Gear h. Clutch for Motor Control 12 Powered by Safety Structure

D. Bus Compartment Bus bar compartment contains a main bus bar, feeder bus bar including the 3-position switch (3PS), filled with SF₆ gas with safety rupture discs activated by overpressure. E. Cable Compartment Cable compartments contain the incoming or outgoing cable supports and earthing bus. The cable compartment is sealed by metal walls. Under the Arc Fault condition, the rupture disc may rupture and should be checked visually by opening the arc gas duct panel. Structure Powered by Safety 13

Powell GIS 38kV Gas Insulated Switchgear Ch 7 Operation A. Construction of each Feeder Figure 4 G81 Single Bus System Circuit Diagram for Typical Unit Arc Way Outgoing Feeder Incoming Feeder Bus - VT Bus - Coupler Arc Way 3PS 3PS 3PS 3PS CB 1250A CB 2500A PF VT CB CT CT VT CT SA VD ZCT 250 600 800 800 800 250 CB Panel/Outgoing Feeder a b c d g e f h i j k a. Main Bus b. 3-Position Switch c. 3-Position Switch Mechanism d. Bushing e. Vacuum Interrupter f. Rupture Disc g. Circuit Breaker Mechanism h. Current Transformer (Block Type) i. Inner Cone Socket j. Surge Arrestor k. Zero Sequence Current Transformer Note: 1. Width of panel can be increasing according to the specification or quantity of current transformers. 2. An arc way is needed at each side of the end panel 14 Powered by Safety Operation

Figure 5 G82 Transfer Bus System Circuit Diagram for Typical Unit Arc Way Incoming Feeder Outgoing Feeder Bus PT Bus-Coupler Arc Way 3PS DS 3PS DS 3PS 3PS 3PS CB 3PS CB PF PT PF PT CB CT CT CT 250 800 800 800 800 250 CB Panel/Outgoing Feeder with Plug-in Circuit l a b c d f e g h i j k l a. Main Bus b. 3-Position Switch c. 3-Position Switch Mechanism d. Bushing e. Vacuum Interrupter f. Circuit Breaker Mechanism g. Rupture Disc h. 3-Position Switch i. 3-Position Switch Mechanism j. Current Transformer k. Inner Cone Socket l. Arc Gas Duct Note: 1. An arc way is needed at each side of the end panel Operation Powered by Safety 15

Powell GIS 38kV Gas Insulated Switchgear B. Operation Circuit Breaker Figure 6 Circuit Breaker Schematic P Close Command Open Command 1 6 4 S21 S22 21 22 A1 M A2 21 22 13 S3 14 61 ASO 62 1 K1 5 A1 Y9 A2 6 K1 4 8 K1 7 R S3 11 12 63 ASO 64 A1 Y1 A2 2 7 5 N S21 & S22 S3 ASO K1 M Y1 Y9 : Limit Switch for Driving Springs : Limit Switch Close : Auxiliary Switch : Anti Pumping Relay : Motor for Spring Charging : Trip Coil : Closing Coil 16 Powered by Safety Operation

Figure 7 Flowchart for Circuit Breakers Motor Motion Closing Spring Charging Limit Switch S3 Close Limit Switch S21, S22 Open CB Closing Signal Input Motor Stop Energizing Trip Coil CB Close CB Close by Manual (by button) Charging Closing Spring by Handle Release Closing Spring Limit Switch S21, S22 Close CB Open Signal (Protection Relay CS S/W) Energizing Trip Coil CB Open CB Open by Manual (by button) Electric Operation Manual Operation Operation Powered by Safety 17

Powell GIS 38kV Gas Insulated Switchgear Figure 8 Available position for 3-Position Switch and Circuit Breaker DISCONNECT / OPEN CONNECT / CLOSE READY FOR EARTHING CABLE SIDE EARTHING 3PS 3PS 3PS CB CB CB 3PS CB 18 Powered by Safety Operation

C. Operation of 3-Position Switch Figure 9 3-Position Switch Schematic 13 13 13 13 23 23 23 23 E1CX D1OX E1OX D1CX E1CX D1OX E1OX D1CX 14 14 14 14 24 24 24 24 3PS1 XA1 025 23 25 9 XA1 11 + + 023 024 M - CH - 10 12 24 33 33 33 33 E1CX D1OX E1OX D1CX 34 34 34 34 D1CX : Disconnector Close Command Contact D1OX : Disconnector Open Command Contact E1CX : Earthed Close Command Contact E1OX : Earthed Open Command Contact M CH : Motor : Motor Clutch Operation Powered by Safety 19

Powell GIS 38kV Gas Insulated Switchgear 1) Electric Operation Refer to Figure 9 during electric operation. A clutched motor is used for the electrical operation of the 3-Position disconnector. The motor can be operated forward or reversed direction and the motor clutch makes the operation of the motor stop to prohibit over operating of the disconnector as follows: a. Disconnector : Off On When the command contact D1CX is closed, the motor is rotated clockwise so that the position of the disconnector is connected. b. Disconnector : On Off If the command contact D1OX is closed, the motor is rotated counterclockwise so that the position of this disconnector is disconnected. c. Earthing : Off On If the command contact E1CX is closed, the motor is rotated counterclockwise so that the position of this disconnector is placed earth. d. Earthing : On Off When command contact E1OX is closed, the motor is rotated clockwise so that the position of this disconnector is placed disconnected. 2) Manual Operation Refer to Figure 10 during manual operation. Carefully follow the instructions on the face of the selector switch mechanism. The 3-position switch can only be operated when the circuit breaker is in the open position. If the circuit breaker is closed, the 3-position switch cannot be operated mechanically as the circuit breaker interlock prohibits insertion of the manual handle into the access port. The circuit breaker can only be operated when the 3-position switch is fully in the connected, disconnected, or earthed position. The manual handle can not be removed until switching operation has been completed. The 3-position switch contains a moving contact that moves in a longitudinal direction by an internal trapezoid threaded screw among fixed and earthing contacts. The alternating movement provides for the switching of the disconnecting switch contact, open position or switching of the earthing contact of the 3-position switch. As the switch is rotated clockwise from the OFF position, it is placed in the connected (service on) position. From the connected position, counter-clockwise rotation returns the switch to the open position. As the switch is rotated counterclockwise from the open position, the switch is now in the earthed position. From the earthed position, clockwise rotation returns the switch to the open position. 20 Powered by Safety Operation

Figure 10 Operation Device & Switch Position Connected Position! DANGER! CAUTION Disconnected Position DISCONNECTING OFF OFF ON ON EARTHING Earthed Position Operation Powered by Safety 21

Powell GIS 38kV Gas Insulated Switchgear Ch 8 Components B. Vacuum Interrupter Construction A. Circuit Breaker (HHF) Figure 12 Vacuum Interrupter for HVS-03644 Figure 11 Circuit Breaker and Mechanism a c d a b e b c a. Contact Spring b. Circuit Breaker Mechanism c. Pole with VI f a. Contact Tip b. Contact Base c. Bellows d. Fixed Stem e. Arc Chamber f. Movable Stem 22 Powered by Safety Operation

C. 3-Position Switch (3PS) Figure 13 Structure of 3-Position Switch E. 3-Position Switch Bushing (Connects Bus Bar Compartment and Circuit Breaker Compartment) Figure 15 Structure of 3PS Bushing a c a. Manual Handle Insert hole b. Operating Screw Rod c. 3PS Pole b D. Bus Bar Connector (Single Phase) F. Cable Socket Figure 14 Structure of Bus bar Connector Figure 16 Structure of Cable Socket a. Bus Bar Connector for 1250A b. Bus Bar Connector for 2500A Operation Powered by Safety 23

Powell GIS 38kV Gas Insulated Switchgear G. Rupture Disc Figure 17 Rupture Disc Normal Ruptured 24 Powered by Safety Operation

Ch 9 Assembly & Carry It is recommended that the equipment be moved by crane but if one is not available a forklift or hand push vehicle is sufficient. When using a crane to lift, make sure to keep the same angles of the chain on both sides of the equipment. Always keep the equipment in an upright, horizontal position during movement. Figure 18 Equipment Lifting Assembly & Carry Powered by Safety 25

Powell GIS 38kV Gas Insulated Switchgear Ch 10 Installation Figure 19 Installation A. Installation Step #1 Step #2 Step #3 Step #4 Step #5 Step #6 Step #7 Step #8 Step #9 Table C Installation Steps Bolt the individual base frames together. Set the distances according to the installation plan. Keep them in one plane. Position the whole base frame on the floor. Check distances to wall and to cable openings. In the case of concrete floor, drill holes for plugs. Place in the fastening bolts. (First do it in the two traverse corners, then in all other points). Continuously check the right position. Insert steel shims below the height adjusting points and insert adjusting screws. Adjust the whole base frame structure into horizontal plane by adjusting the base frame height adjusting screws. Check the position again. Fasten the base frame firmly to the floor. When reaching a final position and horizontal plane checking weld base frame height adjusting screws to prevent any change in settings. Earth the base frame connecting it properly to the local earthing system. (Optional) Insert auxiliary bolts into the base frame to avoid penetration of screed into the nuts. Complete the preparation of the floor. Fill the foundation by screening it carefully. The Surface of the base frame shall be +/-0.5 mm above the final floor level. 1...3 mm 2 3 7 6 1 4 5 Foundation 2 Foundation 1 No. Description 1 Base Frame 2 Bottom frame of the panel 3 Panel height adjusting screw 4 Shim 5 Base Frame fixing bolt 6 Panel fixing bolt 7 Base Frame height adjusting screw (option) 26 Powered by Safety Installation

B. Erection of Powell GIS 1) End Panel Table D Erection of Powell GIS Steps Step #1 Step #2 Step #3 Step #4 Step #5 Step #6 Figure 20 Grease the upper surface of base frame where the panel will be intended to slide. Put the end-panel to the base frame as close to the final position as possible Position the panel by slightly sliding it on the greased base frame Insert fixing bolts into the nuts Align and position the panel precisely. Fix height-adjusting screws by counter nuts. Fasten the panel firmly to the base frame after a final checking. End Panel Installation 2) Next Panel Step #1 Step #2 Step #3 Step #4 Step #5 Step #6 Step #7 Step #8 Step #9 Step #10 Step #11 Step #12 Table E Next Panel Installation Bolt the guide pins into the neighboring panel. Bolt the special connecting bolts into the neighboring panel. Grease the upper surface of the base frame where the next panel will be intended to slide. Put the next panel to the base frame near the neighboring panel leaving enough room to carry out preparatory work described in Steps #5 through #8. Remove the protective caps from the adjacent bus bar sockets of both panels. Carefully check the bus bar sockets, conductor and insulating parts of the bus bar connecting elements ( BB connector ). Clean all surfaces if necessary. Prepare connecting surfaces of conductor and insulating parts of the bus bar connecting elements applying grease. Insert conductor and insulating part of the bus bar connecting element into the bus bar socket of the neighboring panel. Slide the panel toward the neighboring panel and help to penetrate guiding pin into the next panel. Adjust the height of the next panel by height-adjusting screws if necessary. As soon as the next panel is close enough to neighboring panel, insert-connecting screws. From now approach the next panel by tightening these screws step by step evenly. Make a final check (and adjustment if necessary). The gap between main bus compartments shall be 10(+0/-1)mm. Fasten the next panel to the base frame. Connect the main earthing bar of the Two panels Step #13 Earthing Bar Connection Installation Powered by Safety 27

Powell GIS 38kV Gas Insulated Switchgear Figure 21 Bolting of Guide Pin b a c a. Guide Pin b. Guide Nut c. Connecting Piece 28 Powered by Safety Installation

Figure 22 Installing Bolts and Guide Pins Installing the guide pins Install the connecting bolts The connecting bolts of the BB compartment The connecting bolts of the CB compartment Figure 23 Connecting to Bus Bar Socket Epoxy Mold Connecting Conductor & Silicone Tube Installation Powered by Safety 29

Powell GIS 38kV Gas Insulated Switchgear Figure 24 Panel and Bus Bar Connection 30 Powered by Safety Installation

Figure 25 Figure of Installation Site Put the first panel Place new panel and install busbar connector Place in busbar closing caps and fix gas duct closing plate Connect all panels Installation Powered by Safety 31

Powell GIS 38kV Gas Insulated Switchgear 3) Installation of End Panel Table F Installation of End Plate Steps Step #1 Step #2 Step #3 Step #4 Place in and fix bus bar closing caps on the first and last panels Place in and fix arc gas duct closing plates on the first and last panels Place in and fix lateral side covers on the first and last Place in bus bar closing caps and fix arc gas duct closing plate 6) Special Accessories for G81 & G82 Installation Table G Special Accessory for G81 & G82 Installation No. Name Figure Quantity per Bus Compartment 1 Guide Pin 4 2 Guide Nut 4 Figure 26 Bus Bar Closing Caps 3 Connecting Piece 2 4 Connecting Bolt for BB Compartment 2 5 Connecting Bolt for CB Compartment 6 Insulation (Silicone) Tube 3 7 Connecting Conduct with Special Contact 3 8 Insulation Grease Silicone Grease 1 9 Conducting Grease B8 Grease 1 2 4) Connecting Primary and Secondary Cables Primary cables shall be connected to the switchgear before assembling the rear arc gas ducts. Connect secondary wiring system to the panels. 5) Pressure Relief Arc Gas Ducts After erecting all panels top pressure relief ducts, rear arc gas ducts and side arc gas ducts shall be assembled onto the panels and joining to each other according to the installation plan. 32 Powered by Safety Installation

C. Extension of Panels on Site Powell Powell GIS can be extended on site either on the left side or the right size after commissioning. The factory assembled and SF₆ gas filled panels don t need any gas handling on installation site. CAUTION If future extension is expected the necessary space requirement shall be considered in foundation layout. CAUTION Do not work on energized equipment. Working on energized equipment may cause personal injury or even death. Table H Extension of Panels on Site Steps Step #1 Step #2 Step #3 Step #4 Step #5 Step #6 Step #7 Step #8 Step #9 Step #10 Step #11 Step #12 Step #13 Step #14 Step #15 Step #16 Step #17 Step #18 Step #19 Step #20 Step #21 Step #22 Make the necessary measurements according to valid regulation in order to provide safe and effective work Remove the lateral side covers of the extended panel Remove the closing plate of arc gas duct Remove the closing caps of all bus bars Place new panel near to the existing panel series Place in all bus bar connection assemblies (contacts and insulator tubes) Place in arc gas duct connecting elements Insert positioning tools (pins) Move the new panel toward the existing panel series Check correct position by positioning tools Set correct panel height position by adjusting tools Repeat steps 10 and 11 as many times as it is necessary. When the new panel is in the correct position remove positioning tool and join the new panel to the existing panel series Fix new panel to the basement frame Fix arc gas duct connecting elements Connect earthing bar of the new panel to the earthing bar system of the existing panel series Place in and fix bus bar closing caps on the new panel Fix arc gas duct connecting elements Place in and fix arc gas duct closing panel on the new panel. Place in and fix end panel on the new panel Connect primary cables to the new panel Connect secondary wiring system to the new panel Make the necessary inspection, checking and other measures according to valid regulation in order to ensure suitable condition of the extended panel series Installation Powered by Safety 33

Powell GIS 38kV Gas Insulated Switchgear Figure 27 Future of Extension Site The existing panels Remove lateral side covers and closing caps Place new panel and install busbar connector Place in busbar closing caps and fix gas duct closing plate on the new panel Extenstion of panels 34 Powered by Safety Installation

D. HV Cable Connection Cables are connected to Powell GIS utilizing a plug in inner sealing cone assembly. 1. When connecting the HV cable, it is recommended to treat ending part with termination kit in accordance with cable plug manufacturer s recommendations. 2. Access the cable compartment, and then pull the cable plug up to the cable socket. 3. Fix the cable to the cable support by clamp. E. Final Equipment Check 1. Tightening between Powell GIS and foundation 2. Main bus cover compartment bolts 3. Earth bus bar bolts 4. Control cable bolts 5. Check Auxiliary Circuit and Control Circuit 6. Check Current Transformer Circuit 7. Aux Circuit and Control Circuit Check 8. Check CT Circuit by CT Circuit Drawing Figure 28 Connection of the HV Cable Plug F. Insulation Gas Check input pressure by pressure meter. Enclosure Surface M8 (15±3Nm) Installation Powered by Safety 35

Powell GIS 38kV Gas Insulated Switchgear Ch 11 Maintenance & Test Procedure A. Maintenance 1) Safety Extreme care must be exercised to keep all personnel, tools, and other objects clear of mechanisms which are to be operated, discharged, or released. These circuit breakers utilize stored energy mechanisms. These mechanisms must be serviced only by skilled and knowledgeable personnel capable of releasing each spring load in a controlled manner. 2) Maintenance Terms Maintenance Terms Every 4 years Every 12 years After CB mechanism operation is 2,000 times After 3PS mechanism operation is 1,000 times Table I Maintenance Terms Description - Check SF₆ gas pressure, if need refilling - Check SF₆ gas pressure - Grease driving device - Test solenoid coil - CB mechanism operating test and grease driving device - Test solenoid coil - 3PS mechanism operating test and grease driving device 4) Instruction for Lubrication Use Figure 29 In general, the operating mechanism requires only moderate lubrication at regular intervals and all excess must be removed with a clean cloth to prevent any accumulation of dust or dirt. Avoid any lubricant on insulation or other electrical parts. Lubricate the mechanism with Alvania #2 or equivalent. Moving parts should then be moved slightly to let the grease penetrate and become properly distributed. After lubrication, operate the breaker several times manually. The points to be lubricated is shown in Figure 29. Lubrication of Circuit Breaker Mechanism 3) Check of Insulation Gas Check of SF₆ Gas Range of gas sensor is in 1.2~1.5 bar (abs) Table J Inspection Description - Fill to recommended pressure range - Relieve pressure if above range Outer surface of spring guide Outer surface of shaft and pin Latch for closing/opening Cam for closing 36 Powered by Safety Maintenance & Test Procedure

Figure 30 Lubrication of 3-Position Switch Mechanism 3) Cleaning According to the result of the visual check cleaning may be necessary. Note: Only isolated, earthed and/or securely isolated parts of Powell GIS should be subjected to cleaning. Keep in mind all safety regulation of relevant standards. 4) Check the Control Circuit Wiring Shaft and saw-tooth of all gears Guide pin and Driving shaft B. Test Procedure 1) Visual Check a. General condition of cabinets and compartments b. All operating mechanisms (especially that of the circuit breaker, 3-position switch/disconnector switch, and mechanical interlocks. 2) Functional Test After performing the visual check, the circuit breaker or 3-position switch mechanical test should be performed on all related devices, including mechanical interlocks. During this test the device shall be operated with no (electrical) load. If the visual check raises doubts about the proper characteristics of a component, consult with Powell on what tests are to be performed. Check the connecting condition of wiring according to the drawing. 5) SF₆ Gas Leakage Test If pressure is below recommended level, perform this test to confirm that leakage of SF₆ gas sealed in the Powell GIS has not occurred. a. Leak Test Method i. Test all the compartments, o-ring and bolting connections for leaks using the SF₆ gas detector. ii. The SF₆ gas detector detects Freon gas. So, where a leak is detected smear the spot with soapy water to confirm the leakage. Wipe away the soapy water after confirmation. iii. Standard of judgment: No detection of gas leakages. Maintenance & Test Procedure Powered by Safety 37

Powell GIS 38kV Gas Insulated Switchgear 6) Control Circuit Wiring Test a. Test Method Confirm electrical operations with an approved drawing. Validate proper operation of all functional electrical components and interlocks. 7) Timing At normal control voltage, operate the test source to the close position to close the circuit breaker and record the closing time. The closing time from energizing the closing coil to vacuum interrupter contact touch should not exceed the values in Table K Timing. Again, at normal control voltage, operate the test source to the open position to open the circuit breaker and record the opening time. The opening time from energizing the shunt trip coil to vacuum interrupter contact part should not exceed the values in Table K Timing. 9) Manual Close/Open Test a. Test Method Repeat open & close operation by manual handle. Purpose of this test is checking DS and ES operation status. 10) Potential Transformer Test a. Test Method Use a 1000V megger for validating the main bus insulation. Use a 500V megger for validating control wire insulation. Table L Insulation Resistance Main circuit and earth Between main circuit terminal Above 500 MΩ (DC 1000V Megger) Control circuit and between control circuit and earth Above 2MΩ (DC 500V Megger) Table K Timing Closing Time Tripping Time 3 Cycle 80 ms <35 ms 5 Cycle 80 ms <50 ms 8) 3-Position Switch (disconnector or earth) Operating Test a. Test Method Purpose of this test is to check characteristics of ES and DS. Measuring open and close time b. Control Voltage: 80-110% c. Standard of judgement: Fully changes positions in 10 seconds 38 Powered by Safety Maintenance & Test Procedure

Ch 12 Others A. Post Processing of Bolt and Torque Valve If the torque value of the gas compartment is above 8.8 and uses a whisker coated bolt, install using Loctite 222 or an anti reveling device. For outside installation a normal bolt is used. Torque values are represented in Table M Class 8.8 or 9.8 Bolt and Nut and Table N Class 10.9 Bolt and Nut. Table M Class 8.8 or 9.8 Bolt and Nut Torque (Nm) Min Max M6 7 9 M8 18 22 M10 36 44 M12 63 77 M16 153 187 M20 297 363 Table N Class 10.9 Bolt and Nut Torque (Nm) Min Max M6 13 15 M8 32 40 M10 65 80 M12 90 110 M16 243 297 B. Processing of Contact Surface Before fixing bolt, following operations are required: 1) Cleaning a. Use liquid detergent to clean a foreign substance on the surface b. If the degree of pollution is high, use grinder to clean the foreign substance. C. Gas Monitoring System (HMD3) Do not connect anything to the terminal marked NC. 1) Channel Scan! CAUTION Channel Skip The selected channel is skipped when CHn is OFF. Then the skipped channel LED and the relay operations all become OFF status. 2) Automatic Scan Mode At the operating display, pressing the SET key for more than 1 second turns to the Auto Scan mode. While in the Auto Scan mode, it scans the channels that are Chn = ON and displays for approximately 2 seconds each. However, if a channel has a certain problem, the Auto scan is stopped and the problem status is displayed with the channel locked. Surface must be cleaned Exposed surface bus must be grinded (without rust resistant part) Spread rust resistant grease Others Powered by Safety 39

Powell GIS 38kV Gas Insulated Switchgear 3) Manual Scan Mode At the operating display, pressing the SET key turns to the Manual Scan mode. While in the manual scan mode, every time the SET is pressed once, the channels that has CHn=ON is scanned and displayed. * n = 1~3 (Channel Number) 4) Change the Parameter Table O Change the Parameter Parameter Name <--> Parameter Value Parameter Value Parameter Name <--> Changed Parameter Value When the parameter name and the parameter value Are displayed on the indicator panel in alternately Then only the parameter value is displayed, and at this time, by using keys to change the value, after which the SET key is pressed The changed parameter values are registered, and the parameter name and the parameter value are displayed alternate. 40 Powered by Safety Others

<< << Figure 31 HMD3 1 2 3 4 5 6 HDM3 P1 P2 123.4 bar < << P3 SET POWELL << << No. 1 2 3 4 5 6 Description OPERATING ZONE lamp of each P1, 2, & 3 (Green) LOW ZONE Lamp of each P1, 2, & 3 (Yellow) Low-Zone Lamp of each P1, 2, & 3 (Red) Channel indicating Lamp of each P1, 2, & 3 (Green) PV Indicator DOT Indicator << Direction setting shift key SET: SET KEY Setting level reduction key << Setting level increasing key Others Powered by Safety 41

Powell GIS 38kV Gas Insulated Switchgear Figure 32 Wiring Connection Diagram P1 L. LOW ZONE L. LOW ZONE P1 LOW ZONE COM COM NC P2 P2 P3 P3 LOW L. LOW ZONE ZONE P1 P2 P3 4-20 ma 4-20 ma 4-20 ma 11 12 13 14 15 16 17 18 19 20 LOW ZONE 1 2 3 4 5 6 7 8 9 10 + - * Caution: Do not connect anything to NC + - + - + - COM NC! Power 100 E ~ -240VDC/AC 50/60 Hz FG 42 Powered by Safety Others

Powell GIS (Gas Insulated Switchgear) G81-36kV / 1250A, 2000A, 2500A, & 3150A / 40kA G82-38kV / 1200A, 2000A, & 2500A / 40kA June 2015 Powell Electrical Systems, Inc. Service Division - Houston PO Box 12818 Houston, TX 77217 Powered by Safety 2006 Powell Industries, Inc. All rights reserved. Tel: 713.944.6900 Fax: 713.948.4569 powellind.com info@powellind.com