BCP-8S BCP-8X 35F 13PSI AND BCP-8S <AB> DE GH JK HI LO -- OFF. Part Number /0408 STEAM SEQUENCING CONTROL SYS AUX OUT

Similar documents
ESV. Electronic Steam Valve Control Modulates One or Two Actuators. Installation and Operation Manual ESV. Control Module

INSTALLATION AND OPERATION INSTRUCTIONS. Variable Speed Pump Control

INSTALLATION/OPERATING INSTRUCTIONS TSC

INSTALLATION/OPERATING INSTRUCTIONS MCP

SRC. An Outdoor Reset Control for Sub-Atmosphere Steam Systems OUTDOOR TEMPERATURE

INSTALLATION AND OPERATION INSTRUCTIONS ZCP. with Domestic Hot Water (DHW) Priority

INSTALLATION/OPERATING INSTRUCTIONS VSP. A Variable Speed Pump Control

CURTIS TOLEDO. AF Series Compressors VS models with VFD WARNING

Modulating Furnace Information. Warning on Meter Setting - Read First!

Flight Systems. Replacement for KASSEC DESCRIPTION

TC62D Installation Instructions

EXPERT 2V4SA. Temperature Controller. User s manual CLEAN MODE COMPENSATION HUMIDITY OUTSIDE TEMPERATURE

BAPI-Stat 4 Room Humidity Sensor (BA/ B4 -H200 Series)

UL/NEMA Type 1 & Type 12 FRENIC-HVAC Combination VFD

! WARNING To avoid risk of electrical shock, personal injury or death; disconnect power to oven before servicing, unless testing requires power.

ICL Three Pump Controller

Combined Ventilation Controller RVWS-T-224HA

Installation Instructions & Users Manual

MANUAL TROUBLESHOOTING. ECM Motor. ECM / ECM-DX Series. v100 Issue Date: 08/15/ Price Industries Limited. All rights reserved.

Inlet Controller TC5-ITA USER'S MANUAL. M rev. 02 K rev. 00

Cascade CD101 Auto-Start Controller. Installation and Operations Manual Sections 40 & 75

MATRIX LLC LEVEL CONTROL PANEL

Application Engineering

Model H30 Operation Manual

GSC300. Auto Start Engine Controller. Installation and User Manual for the GSC300 Auto Start Engine Controller. Full Version

LK Control v.3 & LK Control v.3 - RA

Installation and Maintenance Instructions. World Leader in Modular Torque Limiters. PTM-4 Load Monitor

PF3100 TROUBLESHOOTING SOLUTIONS TO COMMON PROBLEMS. v1.1 Revised Nov 29, 2016

Installation, Operation, and Maintenance Manual CEMLINE CORPORATION

! WARNING To avoid risk of electrical shock, personal injury or death; disconnect power to oven before servicing, unless testing requires power.

S4562C 1085 COMBI BOARD APPLICATION. Contents PRODUCT HANDBOOK. General

Factory Packaged Controls. OE (AAON Part No. V12090) MODGAS-X Controller Field Technical Guide

Model No. DFC-X Support DIRECT FIRED DIGITAL TEMPERATURE CONTROL INSTALLATION, OPERATION, AND MAINTENANCE MANUAL

CO 2 Room Sensor in the BAPI-Stat 3 Enclosure with Common Ground Configuration

TIMER INTERFACE USER MANUAL

Q&A FOR Webinar on Electrical Basics & Boiler Wiring

Motorized Tempering Valves with Transformers for

DIESEL Engine Fire Pump Controllers Features

SERIES VAC Microprocessor Based Direct Spark Ignition Control FEATURES DESCRIPTION APPLICATIONS THE TOTAL SOLUTION FOR GAS IGNITION CONTROL

VC-4820 Programmable DC-DC Converter with Battery Charger function USER'S MANUAL

Application Engineering

IMC SOLAR EAGLE 2 DIFFERENTIAL TEMPERATURE CONTROLLERS

MAGPOWR Spyder-Plus-S1 Tension Control

INSTALLATION MANUAL ACL 5500 COMBUSTION SAFETY CONTROLLER

SMT-150 Installer Manual

DFC-1 STANDARD TEMPERATURE CONTROL. DFC-2 TEMPERATURE CONTROL w/ INTEGRAL 40 F-90 F SELECTOR DFTD TEMPERATURE SELECTION DIAL DFTS TEMPERATURE SENSOR

MicroTech II Applied Rooftop Unit Controller

BAPI-Stat Quantum Temperature Sensor with Display and Slider Setpoint

OPERATING MANUAL Digital Diesel Control Remote control panel for WhisperPower generator sets

Induction Power Supplies

INSTALLATION INSTRUCTION

BAPI-Stat Quantum Temperature Sensor with Display, Button Setpoint, Fan or System Mode Control

Application Guide Paragon TM Control Module (PCM) Slide Valve and Protection Control 10/25/2016 Rev 1. Carlyle Controller Part No.

32XR. 3 Phase Duplex Pump Control Panel (Level Transmitter Based) Quick Start Guide

BAPI-Com, Two Wire Multifunction Sensor with Setpoint Slider (BA/BS4SCOM) Temperature/Humidity Sensor

Designed for ease of integration with automation systems

SB 2000 PUSH TO SEARCH NEXT STAG E. Aerotech, Inc. FORM: QM 1320

FVC2100/2200 TEK-AIR TECHNICAL PRODUCT DATA SHEET FUME HOOD FACE VELOCITY MONITOR AND CONTROLLER. Application. General Description

MODEL 520 REMOTE START ENGINE MANAGEMENT SYSTEM

Product Manual (Revision A, 8/2015) Original Instructions. ProAct II Digital Speed Control System. Technical Supplement

Power Flame Incorporated

HGM1780. Automatic Genset Controller USER MANUAL. Smartgen Technology

Vission 20/20 micro-controller. Operation and service manual

GENSET CONTROL MODULE LEVEL 1 A121CM / A241CM. Special logic to re-establish cranking following a false start.

General Description. Product Specification. Document Digital Temperature Interlock

Installation. Part A, Section 3. This section covers the following unit configurations. Voltage 1, 2, 3. Vista Standard (V) A3EN-04-[3V-A-AAXV]-11

Product Manual. Part Number: MVP-193 Mefi-6 ECU Revision: 1.0

Inlet Controller SB3500 USER'S MANUAL

Installation Manual. Mixing Box Control Systems Installation, Operation, and Maintenance Manual. 605 Shiloh Road Plano, Texas

P445 Series Electronic Lube Oil Control

FM200 FLOW/NO-FLOW MONITOR INSTALLATION AND TECHNICAL MANUAL 120 VAC MODEL 6/1/2017

SYMBOL LEGEND DANGER WARNING NOTE THIS INDICATES DANGER TO THE LIFE AND HEALTH OF THE USER IS APPROPRIATE PRECAUTIONS ARE NOT TAKEN

MC200CAB/4 Integral Version

MicroTech II Applied Rooftop Unit Controller

HP21 SERVICE SUPPLEMENT UNIT INFORMATION. TSC6 Two-Speed Control

ITCEMS950 Idle Timer Controller - Engine Monitor Shutdown Isuzu NPR 6.0L Gasoline Engine

BAPI-Stat 3 Room Sensor

ACCESSORY KIT INSTALLATION INSTRUCTIONS Low Ambient Accessory For Air Cooled Split System Air Conditioners HB 180/240, HF -15,-20 Models Only

TG350 User Manual. Manual Revision: Min. FW Revision: Date Released: 09/01/ DYNAGEN Technologies Inc

ANALOG CONTROL PANEL

BCS Modutrol Motor M7484A

Dycon D2430 EN54-4 Fire Alarm Power Supply Series

Installation. Part A, Section 3. This section covers the following unit configurations. 3400V 3500V. Voltage 4. Pump Piston (E, F, G)

Setup and Programming Manual

MiG2 TIME SWITCHES. 1, 2 & 4 Channel, 365 Day, Energy Saving Time Switches

AUTOFLAME Combustion Managment System

- Wiring Brochure Universal Reset Module 422e

OpenEVSE - 40A Charging Station

- Wiring Brochure Universal Reset Module 422

POWERLINE 2000 Energy Management System TM

CONTENTS ESC CONTENTS... 1 FEATURES... 2 LAYOUT... 3 DISPLAYS... 4 CONNECTIONS... 5 MENU... 6 MESSAGES... 7 SYSTEM OPERATION... 8

GLM SERIES CONTROL Users Manual Rev:

Observe all necessary safety precautions when controlling the soft starter remotely. Alert personnel that machinery may start without warning.

COMMERCIAL CONCENTRATED ENERGY ELECTRIC BOILER 22.5 KW TO 180 KW

PowerView PV380-R2 Mechanical Configuration

Fan Coil Thermostat. Specification & Installation instructions TFC54F3X1. Technical Data

HGM1780 AUTOMATIC GENERATOR MODULE CONTENT 1. SUMMARY PERFORMANCE AND CHARACTERISTICS SPECIFICATION OPERATION...

HGM6320T AUTOMATIC GENERATOR CONTROLLER USER MANUAL

BAPI-Com, Two Wire Multifunction Sensor BA/BS4SCOM Temperature/Humidity Sensor Installation and Operating Instructions

Application. Tek-Air Systems, Inc. 41 Eagle Road Danbury, CT (203) FAX: (203) SALES FAX: (203)

Transcription:

BCP-8S AND BCP-8X BCP-8S STEAM SEQUENCING CONTROL Stage A Stage B Stage C Stage D Stage E Stage F Stage G Stage H C SYS AUX OUT COMB. AIR US 13PSI 35F <AB> DE GH JK HI LO -- OFF STAGE MENU OUTPUT RATING: 2A, 120VAC. MAXIMUM 15A TOTAL FOR ALL CIRCUITS INPUT RATINGS: 120VAC 60Hz, 12VA MAX ENCLOSED ENERGY MANAGEMENT EQUIPMENT LISTED 99RA PWR L N 1 2 CAUTION: Risk of Electric Shock. Use Copper Conductors Only. PROGRAM Stage A Stage B Stage C Stage D Stage E Stage F Stage G Stage H SYS AUX COMB. System Auxiliary Outdoor Auxiliary Auxiliary OUT AIR 4-20mA + - Input1 Temp Input2 Input3 PROVE SHUTDOWN /TSTAT /SETBACK 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 RUN DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS SENSORS MUST BE GOLD SERIES RS485 Part Number 550-100-069/0408

3 4 5 PID Operation................... 5 OSS Operation................... 5 6 Selecting the System Features........... 6 7 Mounting the Enclosure............... 7 Install the Sensors.................. 8 System Pressure Sensor Installation....... 8 Outdoor Sensor Installation............ 8 Wiring........................ 9 Wiring the Power (Terminals 1, 2)......... 9 Wiring the Inputs................... 9 System Pressure Sensor Wiring (Terminals 25, 26) 9 Outdoor Sensor Wiring (Terminals 29, 30)..... 9 Wiring the Shutdown (Terminals 35, 36)...... 9 Wiring the T-STAT (Terminals 35, 36)....... 10 Wiring the Setback (Terminals 35, 36).......10 Wiring the Prove (Terminals 37, 38)........10 Wiring the Outputs..................10 Wiring the System Output (Terminals 19, 20)... 10 Wiring the Comb. Air Damper (Terminals 23, 24). 10 Wiring the Stages (Terminals 3 to 17)....... 11 Connecting to the BCP-8X Panels and 420MOD Interface...................... 11 Selecting the BCP-8X Panel Letter........ 11 12 14 Program Change Settings.............14 Startup Sequence.................14 Control Mode...................14 Sensor Type....................14 Display Standard..................14 Setting the EMS Set Points (Available in 420MOD only) 14 Combustion Air Damper Output..........15 External Input Mode................15 Burner Type....................15 Total Boilers....................15 Staging.......................15 Sequence.....................16 Control Logic....................16 Sensor Fault....................16 Setting the Control to Factory Defaults.......16 Operating Settings..................17 Program Change Settings.............17 Season.......................17 Set Point (Not Adjustable in EMS Mode).....17 Outdoor Cutoff Temperature............17 System Settings...................17 Program Change Settings.............18 Stage Settings....................18 Reaction Time...................18 Purge Delay....................18 Minimum Runtime.................18 Standby Delay...................18 Last Stage Hold..................19 Lead Settings....................19 Lead Boiler.....................20 Rotate Mode....................20 Setback Schedule..................20 Setback......................20 Day/Night Schedules...............21 Set Present Time.................21 Combustion Air Damper Operation.........21 Run-On......................21 System Exercise..................21 Maintenance.....................21 System & Outdoor Sensor Trim.......... 22 History........................22....................22 Display.......................22 Pressure Transducer Default Settings and Ranges24 25 26 Program Change Settings.............26 Season.......................26 Set Point (Not Adjustable in EMS Mode).....27 Outdoor Cutoff Temperature............27 Setback......................27 Day/Night Schedules...............27 2 2

LEDs indicate associated relay s status Program Switch to restrict access to function changes. This Switch is covered with Enclosure Wiring Cover. Button function is presented on bottom row of the display. BCP-8S STEAM SEQUENCING CONTROL Stage A Stage B Stage C Stage D Stage E Stage F Stage G Stage H C SYS AUX OUT COMB. AIR US 13PSI 35F <AB> CD EF GH HI LO -- OFF BOILER MENU OUTPUT RATING: 2A, 120VAC. MAXIMUM 15A TOTAL FOR ALL CIRCUITS INPUT RATINGS: 120VAC 60Hz, 12VA MAX ENCLOSED ENERGY MANAGEMENT EQUIPMENT LISTED 99RA PWR L N 1 2 CAUTION: Risk of Electric Shock. Use Copper Conductors Only. PROGRAM Stage A Stage B Stage C Stage D Stage E Stage F Stage G Stage H SYS AUX COMB. System Auxiliary Outdoor Auxiliary Auxiliary OUT AIR 4-20mA + - Input1 Temp Input2 Input3 PROVE SHUTDOWN /TSTAT /SETBACK 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 RUN DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS SENSORS MUST BE GOLD SERIES RS485 Output Relays to manage the stages. System Output controls system components. Comb. Air relay is controlled when configured. When connecting Pressure Sensors, Polarity is observed. However, when connecting Temperature Sensors, no Polarity is observed. Prove terminals must be connected for BCP-8S to operate stages. Connect to Extension panels to add additional stages or connect to 420MOD Interface for external set point. 3

The BCP-8S is the perfect control whenever multiple boilers are required for steam heating applications. The BCP-8S controls the stages to maintain a precise system set point. The BCP-8S s control PID algorithm allows it to look at the rate of change in the system. If the system oscillation is minimal, the BCP- 8S will make slow and gradual output adjustments. If the load is changing quickly, the BCP-8S can be set to OSS sequencing where it will react based on load changes. set point. The BCP-8S s alphanumeric digital display names each system parameter in simple English and shows its precise value. The easy to commands. Rotating the lead stage on a call for output promotes even wear on each boiler. The BCP-8S has three modes of rotation: Manual, FOFO (First-On/First-Off), or Time. The Time option rotates the lead stage every selected period, from every hour to every 41 days. in standby mode will remove it from the rotation sequence. In this mode, the boiler will be used as a backup in large demand periods These outputs work with the control logic to operate system and a combustion air damper relays. In addition, a System PROVE input one of the same boiler. That will be repeated for each of the lag boilers. that the operation of the higher stages turn off the lower operating stages. This can be achieved by selecting 'Single' from the Startup Staging menu. As a stand-alone, the BCP-8S is designed to control eight stages. However, it has the capability of expanding its control to two BCP-8X extension panels each with eight stages. Thus, the BCP-8S can control a total of up to 24 stages. Regardless of the type of applications, Setback is an energy saving feature. The BCP-8S offers a built-in day/night schedule for the setback period. On the other hand, if external scheduling is to be used, the Setback can be activated using an external signal by shorting the SETBACK input terminals. 4

The BCP-8S has multiple operating modes that satisfy most steam systems. It can sequence stages to achieve an adjustable Set Point. Moreover, when used with the 420MOD Interface (389-900-226) it can accept a 4-20mA signal as a set point. The 420MOD must be purchased separately. This gives the BCP-8S the capability of being controlled remotely. heat, by either closing the TSTAT input or opening the SHUTDOWN input, and when the outdoor temperature is below the Outdoor Cutoff, the BCP-8S After the elapse of the purge period, the BCP-8S will start calculating the Reaction Period. If after a full Reaction Time the control logic foresees additional stages are When the BCP-8S PID logic foresees that the system will overshoot, regardless of the current system and target values, it will make sure from short cycling. setting, as a mean to calculate the number of stages the BCP-8S shall have on at any point. For every Throttle Range below the set point 55 Psi -1 ---- None A None 50 Psi 0 ---- None ---- A 45 Psi 1 A A B A 41-44 Psi 1 ---- A ---- A + B 40 Psi 2 B A + B C A + B 35 Psi 3 C A + B +C D A + B +C 30 Psi 4 D A + B +C + D E A + B +C + D 25 Psi 5 E A + B +C + D + E F A + B +C + D + E 20 Psi 6 F A + B +C + D + E + F ---- A + B +C + D + E + F 15 Psi 7 ---- A + B +C + D + E + F ---- A + B +C + D + E + F 5

features available in the control and give more comfortable heat when needed. The program should consist of the following: The BCP-8S has been designed with Steam heating as the primary purpose. With this in mind, many of the BCP-8S features can be (389-900-226). The BCP-8S can receive an external Set Point as a 4-20mA signal from an EMS system using the 420MOD Interface. is slow and requires a long period to achieve or measure the results. However, OSS can be used for applications where the load changes frequently and the sequencing must match the load and its immediate change. Extension Panels, each with eight stages. PROVE input to check the status on the Combustion rotation: Manual, First-On-First-Off, or Timed Rotation. This option automatically rotates boilers every selected period from one hour to every 41(999 hours) days. Two Setback modes are available for the BCP-8S: The Day/Night Scheduling provides an adjustable time-based schedule for the Setback. 6

Each of the BCP-8S and BCP-8X consists of three primary enclosure components. enclosed with the Enclosure Wiring Cover for security. The wiring terminals are of the plug-in type to ease installation and removal. components mount on the base. The bottom section of the Enclosure Base contains the wiring chamber with knockouts on the bottom to ease installation. seals the wires from the external environment. It has two screws to hold it to the base and a hole to secure a lock on the wiring enclosure. A plastic web that separates the wiring chamber into high and low volt sections has been provided. 8S or the BCP-8X. operating temperature is from 20 to 120 F. removing the two bottom screws. mounting holes on the back of the enclosure. should not exceed ¼" Enclosure Display Module Enclosure Wiring Cover Enclosure Base Hole for optional Padlock (not supplied) Mounting Base Display Mounting Screws Wiring Cover Mounting Screws 7

before any takeoffs. on the transducer are not used. class 2 voltage. If the System Sensor cannot sense the correct system pressure being supplied to the building, the BCP-8S will not provide comfortable heat levels. Be sure that it is located on the main supply header before any takeoffs. separately). should never be in direct sunlight. other possible heat sources. hold the conduit and enclosure base together. Screw the cover to the base. the sensor and wall except from the bottom. (#18/2). Do not ground the shield at the sensor but at the control using the terminal marked with an O. Seal around sensor and wall Mounting screws location Outdoor Sensor Outdoor drip-hole Outdoor Sensor snap-in location Shield not connected Conduit Outdoor Label on back of Sensor 8

Shutdown Dry Contact Outdoor Sensor Sensor Shiled Line Neutral L. N. PWR L N 1 2 120VAC Power Source System Auxiliary 4-20mA + - Input1 25 26 27 28 located on the common header. Contact the factory for pressure sensor options. 2-conductor cable (Belden #8760 or equivalent). 25 (+) and connect the Black wire to terminal 26 (-). BLACK RED Transducer 4-20mA 8S will disable all boilers when the outdoor temperature is above the adjustable Outdoor Cutoff temperature. This feature will automatically be activated when an outdoor sensor is connected. marked OUTDOOR TEMP - 29, 30. 30 with one of the sensor wires. xiliary Outdoor put1 Temp Auxiliary Input2 Aux Inp 7 28 29 30 31 32 33 Startup menu on page 1. another controller (i.e. EMS input), or a switch. SHUTDOWN terminals. SHUTDOWN- 35,36. Auxiliary Input2 Auxiliary SHUTDOWN /TSTAT Input3 /SETBACK 3132 3334 3536 3 P 9

Prove Dry Contact Setback Dry Contact T-Stat Dry Contact EMS input or thermostat). It will only be available when Tstat is selected as the External Input Mode option from the Startup menu on page 1. TSTAT terminals. TSTAT- 35,36. menu on page 1. input or external time clock). No Day/Night scheduling options will be available with this feature. SETBACK terminals. SETBACK- 35,36. used to check on the Combustion Air Damper by connecting it to the end switch of the damper. In this case, the Comb. Air Output option must be activated from the Startup Menu on page 1. All stage outputs will be off. replaced by a Prove signal. PROVE - 37, 38. No voltage can be placed across the PROVE terminals y Auxiliary Input3 SHUTDOWN /TSTAT /SETBACK PROVE 2 33 34 35 36 37 38 y Auxiliary Input3 SHUTDOWN /TSTAT /SETBACK PROVE 2 33 34 35 36 37 38 TSTAT ETBACK PROVE 5 36 37 38 controls as required by local codes. No boiler stage will start unless Prove terminals are shorted. DO NOT remove the PROVE jumper supplied unless replacing it with a Prove signal. PROVE input is shorted. AUX COMB. S OUT AIR 0 21 22 23 24 The BCP-8S can control the Combustion Air Damper when the Comb. Air Output option is activated in the Startup Menu (See page 1 ). In this scenario, the PROVE input will be used to check on the Combustion Air Damper status. boiler stages. relay is a Normally Open (N.O.) dry contact. It does not source any power. L N Comb. Air Damper 10

Output A followed by the higher stage of the same boiler and wire it to Stage B. Stage A Stage B Stage C Stage D Stag 3 4 5 6 7 8 9 10 11 Lo Hi Lo Hi Unit1 Stages Unit2 Stages (389-900-226) using the provided 6-pin phone cable. to the second extension or the420mod Interface (389-900-226). be to use the 420MOD Interface (389-900-226) to provide a 4-20mA set point signal to the BCP-8S. communication problem. Extension B requires the Switch to be set to "B" will operate stages "Q" through "X". Connecting BCP-8 to Two Extension Panels and 420MOD Interface using RS485 Ext A Ext B BCP-8 BCP-8X A BCP-8W HYDRONIC SEQUENCING CONTROL BCP-8X SEQUENCING CONTROL EXTENSION Stage A Stage B Stage C Stage D Stage E Stage F Stage G Stage H SYSTEM DHW PUMP COMB. AIR SYS=144F OD=35F <AB > DE GH JK HI LO -- OFF STAGE MENU I Q J R K S L T M U N V Comm O W P X Power OUTPUT RATINGS: 120VAC, 6A RESISTIVE 1A PILOT DUTY, 15A TOTAL FOR ALL CIRCUITS INPUT RATINGS: 115VAC 60Hz, 12VA MAX INPUT RATINGS: 115VAC 60Hz, 12VA MAX ENCLOSED ENERGY MANAGEMENT EQUIPMENT C LISTED 99RA US PWR L N 1 2 DO NOT APPLY ANY VOLTAGE TO INPUT TERMINALS CAUTION: Risk of Electric Shock. SENSORS MUST BE GOLD SERIES Use Copper Conductors Only. PROGRAM RUN DHW COMB. SHUTDOWN RS485 Stage A Stage B Stage C Stage D Stage E Stage F Stage G Stage H SYSTEM PRESS OUTDOOR RETURN PUMP DHW /TSTAT AIR TEMP PROVE + - TEMP TEMP /SETBACK 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 PWR L N 1 2 CAUTION: Risk of Electric Shock. Use Copper Conductors Only. Ext A I Q J R K S L T M U N V O W P X 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 Ext B EXTENSION MODULE RS-485 6 Pin Phone Cable (provided with Extension) BCP-8X B BCP-8X SEQUENCING CONTROL EXTENSION 420MOD EMS Interface I Q J R K S L T M U N V Comm O W P X Power OUTPUT RATINGS: 120VAC, 6A RESISTIVE 1A PILOT DUTY, 15A TOTAL FOR ALL CIRCUITS INPUT RATINGS: 115VAC 60Hz, 12VA MAX 4-20 ma EMS 4-20mA INPUT RS485 + Signal GND EXTENSION 1 2 3 CONNECTORS PWR CAUTION: Risk of Electric Shock. Use Copper Conductors Only. I Q J R K S L T M U N V O W P X Ext A Ext B EXTENSION MODULE L N RS-485 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 4-20mA (+) EMS Signal (-) 6 Pin Phone Cable (provided with 420MOD EMS Interface) 11

8.5 psi 45 F TGT=9.0 psi ABC <DEF> ---- LO Boiler Menu ------ SETTINGS ------ Season Winter Set Point 9 psi EMS SetPoint 9 psi <System Settings> <Maintenance> <System Startup> ---- MAINTENANCE ---- Unit F Present Time12:30P <Sensor Trim> <Histories> <Configuration> BCP-8S V1.00 Pressure 30psi EMS 4-20mA, Shtdown 0psi - 30psi BACK NEXT ARE YOU SURE? No Yes the Menu button for over three seconds. settings the Program/Run Switch must be set to Program. --- SENSOR FAULT --- Stages On Stages Off --- CONTROL LOGIC--- PID OSS ------ SEQUENCE ------- Lo/Hi/Lo/Hi Lo/Lo/Hi/Hi ------ STAGING ------ Multiple Outputs Single Output -- CONTROL MODE --- Set Point EMS 4-20mA --- SENSOR TYPE --- Pressure 15psi Pressure 30psi Pressure 100psi Pressure 200psi Pressure 300psi Pressure 0.250MPa Pressure 0.600MPa Pressure 1.000MPa Pressure 1.600MPa Vacuum 3in/762mm -DISPLAY STANDARD - English Metric EMS 4mA SET POINT 0 psi EMS 20mA SET POINT 30 psi Sys=10 psi 10:00AM BACK NEXT --- SENSOR TRIM ---- Sys Trim +0.0 psi Outdoor Trim +0 F - BOILER AB MODE - Auto Standby Off On -- TOTAL BOILERS -- 8 --- BURNER TYPE ---- On/Off 2-Stage 3-Stage 4-Stage ----- BOILER AB ----- Mode Auto Runtime 58Hrs <Prev Boiler> <Next Boiler> -COMB. AIR OUTPUT- No Yes -- EXTERNAL INPUT - Shutdown Tstat Setback BOILER AB Runtime 58hrs BACK CLEAR OK 12

-- EMS SET POINT -- 8.0 psi BACK SAVE ----- SET POINT ----- 8.0 psi 8.5 psi 45 F TGT=9.0 psi ABC <EFG> ---- LO Boiler Menu ----- SETTINGS ------ Season Winter Set Point 9.0psi EMS Set Point 9.0psi <System Settings> <Maintenance> <System Startup> - SYSTEM SETTINGS - <Stage Settings> <Setback Schedule> Setback 0.0psi Run-On 2min Sys Exercise Off - SYSTEM EXERCISE - Off On ------- RUN-ON ------- 2min - OUTDOOR CUTOFF - 60 F ---- SEASON --- Winter Summer - STAGE SETTINGS - Reaction Time 1min Purge Delay 0.0min Min Runtime 2min Standby Delay 10min Lst Stge Hold 5.0psi Throttle 2.0psi <Lead Settings> SETBACK SCHEDULE Setback 0.0psi Present Time **:** Day Schdul 7:00Am Night Schdul 7:00Pm - NIGHT SCHEDULE -- 07:**Pm -- DAY SCHEDULE ---- 07:**Am - SET PRESENT TIME **:** ------ SETBACK ------- 0.0 psi -- REACTION TIME -- 2min --- PURGE DELAY ---- 0.0min - MINIMUM Runtime 2min -- STANDBY DELAY -- 10min LAST STAGE HOLD 0.0 psi - THROTTLE RANGE - 2.0 psi -- LEAD BOILER -- AB CD -- LEAD SETTINGS -- Lead Boiler AB Rotate Mode Time -- LEAD ROTATION -- Time Manual FOFO AUTO ROTATE PERIOD 24hrs 13

Can be accessed by holding down the Menu button for over three seconds. To be able to change the BCP-8S settings the Program/Run Switch must be set to Program. The switch is located under the Enclosure Wiring Cover for security. The Enclosure Wiring Cover can be securely closed using a padlock. A good practice after performing any Startup menu adjustments to match the new settings. PROGRAM ARE YOU SURE? Hold Button: MENU/<System Startup> No Yes described in this section. RUN Hold Button: MENU/<System Startup>/.../Control Mode in Set Point mode it will be used only as an Outdoor Cutoff point. That is, to turn the stages, system, and Comb. Air relays off. EMS/BMS system. This requires the use of the 420MOD Interface (389-900-226). Hold Button: MENU/<System Startup>/.../Sensor Type Hold Button: MENU/<System Startup>/.../Display Standard capability of displaying pressure and temperature information in either of the standards. Hold Button: MENU/<System Startup>/.../EMS 4mA Set Point/EMS 20mA Set Point accept the 4-20mA signal and transmit it to the BCP-8S. First, set the pressure reading at 4mA, then the set it at 20mA. 4mA and 20mA settings entered. 2-22mA range. The display will show the message "Shutdown by EMS" and all --- CONTROL MODE --- Set Point EMS 4-20mA --- SENSOR TYPE --- Pressure 15psi Pressure 30psi Pressure 100psi Pressure 200psi Pressure 300psi Pressure 0.250MPa Pressure 0.600MPa Pressure 1.000MPa Pressure 1.600MPa Vacuum 3in/762mm -DISPLAY STANDARD- English Metric EMS 4mA SET POINT 0psi EMS 20mA SET POINT 100psi 14

- COMB. AIR OUTPUT- No Hold Button: MENU/<System Startup>/.../Comb. Air Output Air Damper or not. Yes PROVE input to check on the status of the Combustion Air Damper. In a failure situation, the message "Wait for Comb. Prove" will display when there is a call for a boiler until Prove is shorted. Comb. Prove Failure PROVE input will be used to check System status instead of the Combustion Air Damper. PROVE input, leave the supplied jumper in place on terminals 37 and 38. Hold Button: MENU/<System Startup>/.../External Input terminals 35 and 36 to turn off all the relays including all boiler stages. 35 and 36 the capability of functioning as a heat-call. That is, when the terminals are shorted, the BCP-8S will sequence the stages to maintain the set point. However, when terminals are opened, all stages will turn off. weekends. when Shutdown or Tstat is selected as the External Input, or an external dry contact signal to switch to setback by selecting Setback from this menu. Hold Button: MENU/<System Startup>/.../Burner Type Hold Button: MENU/<System Startup>/.../Total Boilers number of outputs the BCP-8S is to control. additional units containing these stages will have CE operate. Hold Button: MENU/<System Startup>/.../Staging output stages. These boilers will need to select the Multiple Output option. That means -- EXTERNAL INPUT - Shutdown Tstat Setback --- BURNER TYPE ---- On/Off 2-Stage 3-Stage 4-Stage -- TOTAL BOILERS -- 8 ------ STAGING ------ Multiple Outputs Single Output 15

------ SEQUENCE ------- Lo/Hi/Lo/Hi Hold Button: MENU/<System Startup>/.../Sequencing Hi/Hi. Then, the BCP-8S will sequence the lower stages of all Automatic boilers before sequencing the higher stages. Lo/Lo/Hi/Hi higher stage of the lag boiler. --- CONTROL PID LOGIC--- Hold Button: MENU/<System Startup>/.../Sequencing Boiler Min. Run Time. The PID relies on the rate of change in the system pressure. The PID logarithmic calculations foresee changes and sequence stages based on those OSS the set point. At one Throttling range below the Set Point, only one stage will be on. For each additional Throttling range below the Set Point, an additional stage will be activated. The last stage on will be allowed to exceed the Set Point by one full Throttling range before turning off that stage. This helps to prevent the last stage from short cycling. See Throttle Range. When PID is selected, the following are the settings that directly affect this mode of operation: Settings/System Settings/Stage Settings/Reaction Time Settings/System Settings/Stage Settings/Purge Delay Settings/System Settings/Stage Settings/Min Runtime Settings/System Settings/Stage Settings/Standby Delay Settings/System Settings/Stage Settings/Last Stage Hold Settings/System Settings/Stage Settings/Throttle --- SENSOR FAULT --- Stages On Hold Button: MENU/<System Startup>/.../Sensor Fault The Sensor Fault will determine the operating status of all output stages that are set to Auto or Standby when a sensor reads Short or Open. Stages Off the Shutdown was active, all stages will be Off on a sensor fault. To Reset the BCP-8S control to its original factory defaults, follow the following steps: TOTAL CLEAR STARTED Power down the control. Release buttons Hold down the two right most buttons while powering the control back up until the Total Clear Started screen appears. The Display will direct you to the Startup Please Wait and menu to program the control after the defaults are loaded. NOTE: After resetting the control to the original factory defaults, the user must go through all control settings. After performing a total reset, do not turn off power to the control until all Startup settings have been made. Otherwise, 16

Can be accessed by holding down the Menu button for over three seconds. To be able to change the BCP-8S settings the Program/Run Switch must be set to Program. The switch is located under the Enclosure Wiring Cover for security. The Enclosure Wiring Cover can be securely closed using a padlock. Button: MENU/Season Summer to show status. temperature falls to or below the Outdoor Cutoff setting. In addition, it will begin heating whenever the System pressure falls below the Set Point. The Message Display Summer to turn off all heating instead of turning off the control. This will preserve the battery life. PROGRAM RUN DO NOT turn power off to the BCP-8S when in off-season. If you do so, the battery will run down and have to be replaced. Instead, switch to Summer. ---- SEASON --- Winter Summer ----- SET POINT ----- 12.0psi Button: MENU/Set Point system pressure around the Set point. Stage Settings. Shutdown by EMS -- OUTDOOR CUTOFF - ºº ºº 60 F Button: MENU/Set Point/Outdoor Cutoff automatically appear after the pressure Set Point has been selected. boiler stages to hold the set point. temperature and the burner stages will be active to hold the set point. Hold Button: MENU/<System Settings> for enhanced comfort and better fuel savings. The BCP-8S behaves differently based on the selected Control Modes (see Startup Settings on page 14). - SYSTEM SETTINGS - <Stage Settings> <Setback Schedule> Setback 0.0Psi Run-On 2min System Exercise Off 17

To be able to change the BCP-8S settings the Program/Run Switch must be set to Program. The switch is located under the Enclosure Wiring Cover for security. The Enclosure Wiring Cover can be securely closed using a padlock. PROGRAM RUN Hold Button: MENU/<System Settings>/<Stage Settings> Hold Button: MENU/<System Settings>/<Stage Settings>/Reaction Time ). stage until the Reaction Time has elapsed. Then, it will recalculate if a stage is need. on a single stage and calculate how long it takes until the system begins to respond to that stage. That period should be set as the Reaction Time. -- STAGE SETTINGS -- Reaction Time 1min Purge Delay 0.0min Min Runtime 2min Standby Delay 10min Lst Stge Hld 5.0psi Throttle 2psi <Lead Settings> -- REACTION TIME -- 2min [ ] --- PURGE DELAY ---- 0.0min Hold Button: MENU/<System Settings>/<Stage Settings>/Purge Delay ). over. This allows the boiler to fully come on line and to begin producing output. through the entire Purge Delay period (see PID operation on page ). - MINIMUM Runtime - 2min Hold Button: MENU/<System Settings>/<Stage Settings>/Min Runtime [ ). ] Minimum Runtime to half the Reaction Time. Minimum Runtime. If boilers tend to short cycle, increase Minimum Runtime. -- STANDBY DELAY -- 10min Hold Button: MENU/<System Settings>/<Stage Settings>/Standby Delay [ ). ] The Standby Delay only applies to boilers in Standby Mode. will result in smoother set point operation in extreme conditions. However, longer Standby Delays may prevent a Standby boiler from starting if the other boilers can eventually meet the load, or if the load decreases. 18

- LAST STAGE HOLD 0 PSI Hold Button: MENU/<System Settings>/<Stage Settings>/Last Stge Hold ). turned off. until the system reaches 10 Psi. During that period, the display will show "Hold Until 10 Psi" then, the lead stage will turn off Hold Button: MENU/<System Settings>/<Stage Settings>/Throttle ). -- THROTTLE RANGE -- 2PSI will be turned on or off. Set Point. A second stage will be activated when the pressure falls to two full Throttling Ranges below the Set Point, and so on, with one extra stage being turned on for every throttling range below the Set Point the System pressure reaches. stages. 55 Psi -1 ---- None A None 50 Psi 0 ---- None ---- A 45 Psi 1 A A ---- A 41-44 Psi 1 ---- A ---- A 40 Psi 2 B A + B B A + B 35 Psi 3 C A + B +C C A + B +C 30 Psi 4 D A + B +C + D D A + B +C + D 25 Psi 5 E A + B +C + D + E E A + B +C + D + E 20 Psi 6 F A + B +C + D + E + F F A + B +C + D + E + F 15 Psi 7 ---- A + B +C + D + E + F ---- A + B +C + D + E + F Hold Button: MENU/<System Settings>/<Stage Settings>/<Lead Settings> the system. -- LEAD SETTINGS -- Lead Boiler AB Rotate Mode Time 19

Hold Button: MENU/<System Settings>/<Stage Settings>/<Lead Setting>/Rotate Mode call for output. As more output is needed, additional Stages are added. 1 ), the display will Hold Button: MENU/<System Settings>/<Stage Settings>/<Lead Setting>/Rotate Mode (FOFO). The automatic rotation is recommended for most applications. if the Time was not set. However, if the Time was set, the rotation will always take place at 2:00AM. The following rotations will take place every 24 hours thereafter. moment the setting is changed. the stages starts, it will turn off A, B, Then C. Then stage D will be the new lead for the next load. -- LEAD BOILER -- AB CD EF -- LEAD ROTATION -- Time Manual FOFO If Time Rotation is selected AUTO ROTATE PERIOD 24hrs SETBACK SCHEDULE Setback 0psi Present Time **:** Day Schdule 7:00Am Night Schdul 7:00Pm Button: MENU/<System Settings>/<Stage Settings>/<Setback Schedule> Button: MENU/<System Settings>/<Setback Schedule>/Setback Button: MENU/<System Settings>/Setback load is required during the night or on the weekends when the building is not occupied, but heat is still required. ------ SETBACK ------- 0psi Setback to 5 Psi". 8S s Set Point for the reasons detailed below. dissipated. Therefore, the pressure in the header could be lower than that registered by the boiler sensors. The temperature limits set on the boilers must be higher than the BCP-8S Set Point. Read the section at left for details that will prevent erratic system operation. 20

to prevent the boilers internal limits being reached. In this situation, the boiler high limit should be set at approximately 12 Psi to prevent the difference in boiler pressure vs. header pressure causing erratic operation. Button: MENU/<System Settings>/<Setback Schedule>/Day Schedules and people are active. sleeping. This setting reduces the set point by the Setback setting. If the Day calculated pressure was 8 Psi and the Setback was 3 Psi, the Night Schedule will run at (8 Psi - Button: MENU/<System Settings>/<Setback Schedule>/Present Time Button: MENU/<Maintenance>/Present Time followed by the minutes. If hours are to be set to PM, scroll through the AM hours to reach the PM hours. -- DAY SCHEDULE ---- 07:**Am -- NIGHT SCHEDULE -- 10:**Pm - SET PRESENT TIME **:** Remember that the battery is used as a time backup. If no power is supplied to the BCP-8S, the battery will die in three months and time clock values will be lost. Thus, DO NOT power down the control during off-season. The BCP-8S controls multiple relays each controlling different types of equipment. In addition to the control of the boilers, it can control a combustion air damper. See Comb. Air Damper 1. Hold Button: MENU/<System Settings>/Run-On to dissipate the excess energy from the boilers. ------- RUN-ON ------- 2min [ ] Hold Button: MENU/<System Settings>/System Exercise used for seven days. Hold Button: MENU/<Maintenance> The Maintenance menu gives access to sensor trimming. In addition, you will have access to To be able to change the BCP-8S settings the Program/Run Switch must be set to Program. The switch is located under the Enclosure Wiring Cover for security. The Enclosure Wiring Cover can be securely closed using a padlock. - SYSTEM EXERCISE - Off On ---- MAINTENANCE ---- Standard English Present Time12:30P <Sensor Trim> <Histories> <Configuration> 21

Hold Button: MENU/<Maintenance>/Outdoor Trim require no calibration. However, sometimes it may be desirable to make small adjustments to the displayed value. --- SENSOR TRIM ---- System Trim +0.0psi Outdoor Trim +0 F Hold Button: MENU/<Histories> The BCP-8S provides users with a graphical history of the System and Outdoor values for the previous 24 hours. The values are sampled every 12 minutes. That is, readings of pressure and temperatures are recorded and stored every 12 minutes for the last 24 hours. and read the upper left temperature. you will be able to view the Outdoor Temperature History. Hold Button: 22 Sys=12psi 10:00AM BACK NEXT BCP-8S V1.00 Pressure 30psi EMS 4-20mA, Shtdown 0psi - 30psi BACK NEXT 8 X On/Off PID,Fault Stgs Off Comb. Air BACK NEXT The BCP-8S display layout provides a variety of information that gives an immediate picture of the operation status. The display shows four heating boilers at a time. The two middle buttons scrolls the screen to view additional boilers. Moreover, all the information is brightly displayed. It can be viewed in brightly or dimly lit rooms. background on the screen's bottom line. System Pressure Outdoor Temp when in menus or to change values of settings when in its 9.0PSI Message Display Line However, that will be replaced by a message indicating an important status. See Display Messages on next page. MENU button fast displays the User Menu. MENU button for more than 3 seconds displays the Installer Menu. BOILER button fast displays the Boiler Menu. BOILER button for more than 3 seconds displays the Display Contrast Menu. 58 F TGT = 13.0psi <AB> CD EF GH HI HI LO ---- BOILER MENU Units and their Status Button functions Button ------ CONTRAST ------- 18 The BCP-8S status gives immediate access to each Boiler status. The following list shows all possible boiler status:

number of control and extension stages. The BCP-8S normal display layout reserved the second line for message indications. The following is a list of the most common system pressure reaches 12 Psi. PROVE terminals are open before the SETBACK terminals are shorted. SETBACK terminals are have been opened recently. Button: BOILER/ Type from the Startup on page 1 ). menu and make all the settings. Continue until all boilers have been set. Previous Stage menu options will scroll through the BCP-8X stages as well. ----- BOILER AB ----- Mode Auto Runtime 58Hrs <Prev Boiler> <Next Boiler> -- BOILER AB MODE - Auto Button: BOILER/Mode Standby Off On - The BCP-8S will control the unit s operation to maintain the desired Set Point. Only units set to Auto can be lead unit. These units can only be activated when all units in Auto have been at HI for an adjustable Standby delay period. Standby units are generally used as a backup in extreme load conditions. Note that, a Standby unit cannot be a lead unit. Standby Delay is only available in PID mode. Any output unit not connected to a physical unit should be set to Off. The Off Mode can also be used to disable units that are being serviced. The On Mode should only be used when testing a unit. The On Mode overrides the PROVE and SHUTDOWN inputs. Once set to On the unit will immediately start all of its stages. 23

Outdoor Sensor Shutdown Dry Contact Sensor Shiled Prove Dry Contact Button: BOILER/Runtime together. BOILER AB Runtime 58hrs BACK CLEAR OK 0 15 5 0 5 0 0 3 1.5 0.25 3 0.5 0 30 8 0 10 0 0 6 3 0.5 6 1 0 100 30 0 30 0 0 20 10 1 20 2 0 200 60 0 60 0 0 40 20 2 40 4 0 300 80 0 90 0 0 60 30 3 60 6 0 0.25 0.1 0 0.1 0 0 0.05 0.025 0.002 0.05 0.005 0 0.6 0.2 0 0.2 0 0 0.12 0.06 0.006 0.12 0.012 0 1 0.3 0 0.3 0 0 0.2 0.1 0.01 0.2 0.02 0 1.6 0.5 0 0.5 0 0 0.32 0.16 0.015 0.32 0.03 0 30 10 0 10 0 0 6 3 0.5 6 1 0 760 250 250 0 0 150 80 10 150 30 BCP-8S STEAM SEQUENCING CONTROL Stage A Stage B Stage C Stage D Stage E Stage F Stage G Stage H SYS AUX OUT COMB. AIR 13PSI 35F <AB> CD EF GH HI LO -- OFF BOILER MENU OUTPUT RATING: 2A, 120VAC. MAXIMUM 15A TOTAL FOR ALL CIRCUITS INPUT RATINGS: 120VAC 60Hz, 12VA MAX ENCLOSED ENERGY MANAGEMENT EQUIPMENT LISTED 99RA DO NOT APPLY ANY VOLTAGE CAUTION: Risk of Electric Shock. TO INPUT TERMINALS PWR Use Copper Conductors Only. PROGRAM RUN SENSORS MUST BE GOLD SERIES L N Stage A Stage B Stage C Stage D Stage E Stage F Stage G Stage H SYS AUX COMB. System Auxiliary Outdoor Auxiliary Auxiliary OUT AIR 4-20mA + - Input1 Temp Input2 Input3 PROVE SHUTDOWN /TSTAT /SETBACK 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 RS485 L N Unit1 Lo Unit2 Lo Unit3 Lo Unit4 Lo L N Comb. Air Damper BLACK RED Transducer 4-20mA 24 Unit1 Hi Unit2 Hi Unit3 Hi Unit4 Hi

When OPEN, Check the sensor is connected and the wires are continuous to the BCP-8S. Finally follow the procedure for Incorrect Temperature or Pressure Display. When SHORT Remove the wires from the sensor terminals. The display should change to read OPEN. If it does not, the BCP-8S may be damaged. -30 117720-20 82823-10 59076 Remove the wires from the sensor terminals. The display should change to read OPEN. If 0 10 42683 31215 it does not, the BCP-8S may be damaged. Take an ohm reading across the detached sensor 20 23089 wires. The ohm reading should correspond to the Temperature sensor Table. If it does not, the 25 19939 sensor may be damaged. 30 17264 35 14985 System Trim. If reading is SHORT, remove the wires from the sensor terminals. The display should change to read OPEN. If it does not, the BCP-8S may be damaged. 40 45 50 13040 11374 9944 55 8714 60 7653 70 5941 Check if the control has any of the following: - The BCP-8S will only sequence boilers their mode is set to Auto or Standby. Make sure non of the boilers have their Mode set to ON. 80 90 4649 3667 100 2914 110 2332 120 1879 Check if the control has any of the following: 130 1524 Setback value. - The BCP-8S will only control boilers their mode is set to Auto or Standby. Check if any boilers have their Mode set to Manual, Off, or Standby. - Increase the Minimum Runtime only if all boilers tend to short-cycle. - If the system is overshooting, increase the Reaction Time. This will allow the stages enough time to respond before bringing on another stage. However, if the system was oscillating, increase the Reaction Time and the Minimum Runtime. - If the application the system is used on requires fast response that the normal PID mode cannot provide, try using the OSS mode and adjust the Throttle Range according to the system requirements. 25

8.0 psi 45 F TGT=9.0 psi ABC <DEF > ---- LO Boiler Menu ---- SEASON --- Winter Summer ---- SETBACK ------- 2.0 psi ------ SETTINGS ------ Season Winter Set Point 9.0 psi EMS StPont 9.0 psi Outdoor Cutoff 70 F Setback 2.0psi DO NOT turn power off to the BCP-8S when in off-season or season is over. If you do so, the battery will run down and will have to be replaced. Instead, switch to Summer or Winter. ----- SET POINT ----- 9.0 psi -- EMS SET POINT -- 9.0 psi - OUTDOOR CUTOFF - 70 F -- DAY SCHEDULE ---- 07:**Am - NIGHT SCHEDULE -- 07:**Pm settings in addition to Startup and more advanced operation settings. The installer menu can be access by holding down the Menu button for three seconds or more. To be able to change the BCP-8S settings the Program/Run Switch must be set to Program. The switch is located under the Enclosure Wiring Cover for security. The Enclosure Wiring Cover can be securely closed using a padlock. Button: MENU/Winter PROGRAM RUN ---- SEASON --- Winter Summer Summer to show status. Cutoff setting. In addition, it will begin heating whenever the System pressure falls below the Set Point. The Message Display 26

Button: MENU/Set Point system pressure around the Set point. will be available as read only. ----- SET POINT ----- 10.0 psi - OUTDOOR CUTOFF - ºº ºº 70 F Button: MENU/Outdoor Cutoff BCP-8S will control and sequence the boiler stages to hold the set point. temperature and the burner stages will be active to hold the set point. Button: MENU/<System Settings>/<Setback Schedule>/Setback Button: MENU/<System Settings>/Setback load is required during the night or on the weekends when building is not occupied, but heat is still required. ---- SETBACK ------- 0.0 psi Setback to 5 Psi". Button: MENU/<System Settings>/<Setback Schedule>/Day Schedules and people are active. sleeping. This setting reduces the set point by the Setback setting. If the Day calculated pressure was 8 Psi and the Setback was 3 Psi, the Night Schedule will run at (8 Psi - -- DAY SCHEDULE ---- 07:**Am -- NIGHT SCHEDULE - 10:**Pm 27

............................................................................................. 20 F/-7 C to 120 F/49 C...... 11"W x 9" H x 3 ¾.............................................................Time ( 1 to 999 Hours (41 days)), Manual, First-On/First-Off.................... 10 N.O. S.P.S.T (8 Stages, 1 System, 1 Combustion Air)..................1 System (pressure), 1 Outdoor, Ext Shutdown, Ext Tstat, Ext Setback, Prove................................................ Auto, Standby, Off, On... 1 to 60 minutes................. 2 Amp inductive (Maximum of 1/4 HP)................................................................................................................ Fahrenheit or Celsius...................................... Graphical Alphanumeric (7 rows x 21 char. each).......................................... F........................... 20 F/-17 C to 100 F/38 C, ON and OFF.............................................................................. 1 to 10 minutes................................. 0 to 60 minutes... 0.0 to 10.0 minutes........................................................................................................................ 0 to 60 minutes.......................................... 1 Day and 1 Night (Setback) settings per day...0 F/0 C to 80 F/44 C................. Shutdown Input, Tstat Input, Setback Input and/or Prove Input. (Dry Contacts Only)...................................................... Winter and Summer....Toggle Switch A or B... 1 Power (Dual Color Green (A)/Red (B)), 1 Communication, 8 Stage Output relays (Dual Color Green (A)/Red (B))................................................... 8 N.O. S.P.S.T.................. 2 Amp inductive (Maximum of 1/4 HP)................................ 28 500 Blaine Street Michigan City, Indiana 46360 219-879-6561 http://www.weil-mclain.com Part Number 550-100-069/0408 HT #059079-00 A