GDB..3..1A GLB..3..1A

Similar documents
Air damper actuators

Air damper actuators

Use. Functions. OpenAir TM. Rotary version, modulating, with spring return, AC 24 V

Actuators for Fire and Smoke Protection Dampers

Actuators for Fire Protection Dampers

Actuators for Fire and Smoke Protection Dampers

Actuators for Fire and Smoke Protection Dampers

OpenAir Electronic Damper Actuators GLB Series Enhanced Non-spring Return Rotary

MF /MS Series

DuraDrive MF /MS Series Non-spring Return Rotary Electronic Damper Actuators 24 Vac Three-position/Modulating

OpenAir Electric Damper Actuator GDE/GLB Series Non-spring Return Rotary 24 Vac 3-position Control

Technical Instructions Document No EA GQD May 6, OpenAir GQD Series. Spring Return, 20 lb-in (2 Nm), Rotary Electronic Damper Actuators

Technical Instructions Document No P25 EA GMA January 19, OpenAir. GMA Series Spring Return Rotary Electronic Damper Actuators

OpenAir Electric Damper Actuators GBB/GIB Series NSR Rotary 24 Vac - Modulating Control

Technical Instructions Document No P25 EA GMA May 19, OpenAir. GMA Series, Spring Return, 62 lb-in, Rotary, Electronic Damper Actuators

OpenAir Electric Damper Actuator GDE/GLB Series Non-spring Return, 24 Vac Floating Control, Rotary

OpenAir Electric Damper Actuators GDE/GLB Series Non-spring Return Rotary 24 Vac - Modulating Control 0 to 10 Vdc

Electromotoric Actuators

OpenAir Electric Damper Actuators GDE/GLB Series Non-spring Return Rotary 24 Vac - Modulating Control 0 to 10 Vdc

OpenAir Electric Damper Actuators GDE/GLB Series Non-spring Return Rotary 24 Vac - Modulating Control 0 to 10 Vdc

OpenAir Electric Damper Actuator GDE/GLB Series Non-spring Return, 24 Vac Floating Control, Rotary

OpenAir GBB/GIB Series Electronic Damper Actuators Non-Spring Return, 24 Vac, Modulating Control

OpenAir GBB/GIB Series Electronic Damper Actuators Non-Spring Return, 24 Vac, Modulating Control

Rotary actuators for ball valves

Electromotoric Actuators

OpenAir GCA Series Spring Return 142 lb-in Electronic Damper Actuators

Commercial Actuator Selection Chart Non-Spring Return

OpenAir. Technical Instructions. GCA Series Spring Return 160 lb-in Electronic Damper Actuators. Document No P25 EA GCA-1.

Actuators for small valves

Electromotoric Actuators

Actuators for air dampers and control valves of oil burners

Electromotoric Actuators

Actuators for air dampers and control valves of oil burners

Actuators for air dampers and control valves of oil burners

DC-132 Non Spring Return Electronic Actuator Series

Temperature Controller (Heat Pumps)

Electromotoric actuators

SAV Electronic Valve Actuator

SAX Electronic Valve Actuator

2-position electric actuators with Ball valves VBZ ½...11/4

Dodge Engineering & Controls, Inc. Toll Free (877) Fax: (978) EN44 and EN88 Non-Spring Return Electronic Actuators

Dodge Engineering & Controls, Inc. Toll Free (877) Fax: (978) ES142 Spring Return Electronic Actuators

Differential Pressure Sensors

SQL35.00 SQL85.00 SQK angle of rotation

Electromotoric Actuators

Flowrite 599 Series SAX Electronic Valve Actuator Non-spring Return, 24 Vac, 3-Position Control

Electromotoric Actuators

Modulating control valve PN16 with magnetic actuator

Differential Pressure Sensors

Differential Pressure Sensors for air and non-corrosive gases, with calibration certificate

Minimum 18 in-lb Torque

Modulating control valves with magnetic actuators, PN 16

Electromotoric actuators

Differential Pressure Sensors

Actuators for heating, ventilation, air-conditioning 2. LM-4 -CD. Product Information Damper actuators. i

Overview of types. Technical data. Safety notes

Power consumption In operation At rest For wire sizing

Power consumption Wire/transformer sizing. Motor. Spring return. Motor. Spring return. EMC Low voltage directive

LKS 160 FOR AIR DAMPERS ON MULTI-STAGE AND MODULATING BURNERS

Electric actuators for small valves

Electrical data Nominal voltage AC/DC 24V Nominal voltage frequency 50/60Hz

AKM 105, 115: Rotary actuator for ball valve

Electrical data Nominal voltage AC 24 V, 50/60 Hz DC 24 V. Power consumption In operation At rest For wire sizing

Mounting and operating instructions EB 5801 EN. Electric Actuators Type 5801 (Rotary Actuator) Type 5802 (Linear Actuator)

See «Overview of types»

Technical data. Safety notes. Power consumption In operation At rest For wire sizing. 1.5 nominal torque 0.2 W 4 VA Auxiliary switch

DA-053 Series. Overview. Applications. Features & Benefits. Datasheet. 53lb-in (6 Nm), Non-Spring Return Damper Actuators

Technical data. Safety notes. Power consumption In operation At rest For wire sizing. 1 nominal torque 0.2 W 2 VA Auxiliary switch

Electro-hydraulic actuators for valves

Versatile and Powerful

Electrical data Nominal voltage AC 24 V, 50/60 Hz DC 24 V

LMX120-SR. Proportional Control, Non-Spring Return, Direct Coupled,100 to 240 VAC, for 2 to 10 VDC and 4 to 20 ma

Differential Temperature Controller

NFB24, NFB24-S, NFX24, NFX24-S On/Off, Spring Return, 24 V

Actuators for Air and Gas Dampers

FSAF24(-S) US, FSAF120(-S) US

Actuators for Air and Gas Dampers

SmartX MF and MS

2. A E LM Form-fit versions Linear adapter ZH-LM

Electrical data Nominal voltage AC V / DC V Nominal voltage frequency

Polygyr -Compact Exhaust Air Temperature Controller

See «Overview of types» 90 s / 60 mm 150 s / 100 mm Manual triggering of the adaption by pressing the «Adaption» button or with the PC-Tool

MX4X-6XXX Series MX4X-7XXX Series. Selection Guide. Applications. DuraDrive Series Actuators and Accessories

GMX On/Off-Floating Point Control, Non-Spring Return, Direct Coupled, 100 to 240 VAC

Modulating control valve with magnetic actuator PN16

SQN9... Damper Actuators. Building Technologies HVAC Products. SQN9..., front (covers removed) SQN9..., rear (covers fitted)

For air dampers and control valves of oil or gas burners

Electrical Actuators

Power consumption In operation At rest For wire sizing. Actuating force Inhibiting force. Position accuracy ±5% Direction of stroke Motor

Mount directly to 1.05 jackshafts. (new ZG-120 bracket shown) EFB24-S N4, EFX24-S N4(H) EFB24-S, EFX24-S (p. 21)

Power consumption In operation At rest For wire sizing. Functional data Torque Motor Spring return. Rated impulse voltage Control pollution degree 3

Differential pressure sensor

Minimum 18 in-lb Torque. Applications. TF Series At A Glance. TF Series Spring Return Direct Coupled Actuator. For damper areas up to 4.

Power consumption In operation At rest For wire sizing

Current consumption Auxiliary switch. Angle of rotation 90 (internal electrical stops) Running time

Technical Instructions. SQV Series Electromotive Valve Actuators. Document No

Electromotoric Actuators. for zone valves VVI46.., VXI46.., VVS46.. and VXS46..

ZG-JSL, ZG-JSLA Jackshaft Retrofit Linkage For AF, NF, LF, NMX and AMX Series Actuators

Modulating control valves with magnetic actuator PN 16

Power consuption Motor (Motion) Power consuption Standby (end position) Auxiliary switch Contact load Switching point

Transcription:

4 624 OpenAir Air damper actuators Rotary version, three-position control, AC 24 V or AC 230 V GDB31A GLB31A Electric motor-driven actuators for three-position control, 5 / 10 Nm nominal torque, AC 24 V or AC 230 V operating voltage, mechanically adjustable working range between 090, pre-wired with connecting cables of 09 m Type-specific variations with adjustable auxiliary switches for supplementary functions or with potentiometer for position indication Use In ventilating and air conditioning plants to actuate air dampers with nominal torque of 5 Nm for damper areas of approx up to 08 m 2 and 10 Nm for damper areas of approx up to 15 m 2 ideal for modulating three-position controllers or ON/OFF controls (eg, outside air dampers, flue gas dampers, etc) Type summary Operating voltage Torque Standard version AC 24 V With 2 auxiliary switches With positioner Standard application AC 230 V With 2 auxiliary switches With positioner 5 Nm GDB1311A GDB1361A GDB1321A GDB3311A GDB3361A GDB3321A 10 Nm GLB1311A GLB1361A GLB1321A GLB3311A GLB3361A GLB3321A Ordering Delivery Connecting cables You cannot later install auxiliary switches and positioners For this reason, order the type that includes the desired options Individual parts such as position indicator and other mounting materials for the actuator are delivered separately and require additional mounting The actuator comes with 09 m long pre-wired connecting cables Siemens Building Technologies HK2N4624en / 032000 Landis & Staefa Division 1/10

Accessories, spare parts The following accessories are available for function upgrades of the actuators, see data sheet N4698: Rotary/linear set with lever ASK715 Rotary/linear set with lever and mounting plate ASK716 Centering insert, D-profile dia 12 x 9 mm ASK784 Centering insert, round ½" ASK785 Centering insert, square profile 8 mm ASK786 Centering insert, square profile 10 mm ASK787 Spare parts and ordering information as per data sheet N4698 Equipment combinations These actuators can be connected to all control devices with a three-position output supplying a switching voltage of AC 24 V or AC 230 V Functions Basic functions Rotational movement Three-position control Position indication Manual adjustment Mechanical limitation of rotational angle The actuator's rotational movement (clockwise or counterclockwise) depends on the electrical control As soon as the operating voltage AC 24 V or AC 230 V is applied, the actuator starts to turn The connected damper can be operated as follows via the respective actuator control: Example: clockwise direction damper opens (0 90 ) damper closes (90 0 ) With no power applied, the damper remains in the respective position The position indicator inserted in the housing coupling bushing indicates the rotational angle position of the air damper When no voltage is supplied, you can disengage the gear train and manually adjust the actuator or the air damper by means of the red slider The rotational angle can be limited stepless between 0 and 90 Type-specific functions Adjustable auxiliary switches Electrical position indication Auxiliary switches provide supplementary functions The switching points for auxiliary switches A and B (one changeover switch each) can be set independently in increments of 5 within the 0 90 rotational angle Refer to "Technical design", "Commissioning notes" and "Diagrams" The integrated potentiometer can be connected to voltage as a positioner; refer to "Technical data" The voltage applied is proportional to the actuator's rotational angle HK2N4624en / 032000 Siemens Building Technologies 2/10 Landis & Staefa Division

Technical design Motor technology Adjustable auxiliary switches (typespecific) A reversible synchronous motor enables accurate speed control The magnetic coupling serves as a torque limitation on overload to protect both actuator and dampers The illustration below shows the adjustable switching values for auxiliary switches A and B in relation to the rotational angle Actuator scale: Clockwise Setting increments: 5 Switching hysteresis: 3 Adjustment range for switches A and B Actuator scale: Counterclockwise -2,5 0 10 20 30 70 80 90 92,5 A B 0 10 20 30 70 80 90 92,5 90 80 70 60 20 10 0-2,5 4634D04 A B 10 20 80 70 60 50 Aux Switch Adjustment 4634Z13 Note The setting shafts for the auxiliary switches turn together with the actuator The scales are valid only for the zero position of the actuator on clockwise movement Mechanical design Basic components Housing Gear train Slider for manual adjustment Coupling bushing Shaft insert for GLB 1 (10 Nm) Mounting bracket Electrical connection A robust, light-weight plastic housing and a gear train plate made from steel guarantee an extended actuator life even under severe environmental conditions Maintenance-free and noise-free gear train with stall and overload protection for the life of the actuator The red slider on the side serves for manually releasing and adjusting the gear train The coupling bushing is made from hardened sintered steel to attach the actuator on the damper shaft for differing shaft diameters and cross sections (square, round) The shaft insert is also made from hardened sintered steel and has the following purposes: ensuring a friction-locked connection between a damper shaft with a small diameter (8 10 mm) and the coupling bushing reducing the vertical movement of the actuator by applying eccentric movement A metal strip with bolt serves to prevent the actuator from twisting All actuators are equipped with pre-wired 09 m long connecting cables Type-specific elements Auxiliary switch Potentiometer for position indication For supplementary functions, the auxiliary switches A and B can be adjusted on the actuator front (top right) A potentiometer has been integrated as a positioner for the electrical position indication of the damper position Siemens Building Technologies HK2N4624en / 032000 Landis & Staefa Division 3/10

Setting and operating elements Refer to "Technical design" and "Commissioning notes" in this data sheet 1 12 11 2 90 A B 10 20 10 8,9 45 90 80 70 60 50 Aux Switch Adjustment 7 6 3 4 5 13 4624Z01 1 Base plate and housing 2 Rotational angle scales 0 90 / 90 0 3 Connecting cable for power and positioning signal 4 Connecting cable for auxiliary switches or potentiometer 5 Slider to disengage the gear train 6 Coupling bushing 7 Shaft insert for GLB 1 for shaft diameters 8 10 mm) 8,9 Setting shafts for auxiliary switches A and B 10 Position indicator 11 Adjustment lever with shaft fastening screw 12 Adjusting screw for rotational angle limitation 13 Mounting bracket Engineering notes STOP Intended use The basic system data for the control systems in use contain all engineering information; refer to this data prior to mounting, wiring, and commissioning the actuator and carefully read all safety information Use these actuators in a system only for applications as described in the basic system documentation of the applied control systems Additionally, include all actuator-specific features and conditions as described in the brief description on the title page of this data sheet (bold print) and in the chapters "Use", "Engineering notes", and "Technical data" The sections flagged with a warning symbol as illustrated in the left margin contain safety-related requirements and restrictions; it is important that you adhere to them to prevent physical injuries or equipment damages AC 24 V supply AC 230 V supply Auxiliary switches A, B Operate the actuators only on safety extra-low voltage (SELV) or protection by extralow voltage (PELV) as per HD 384 The actuators are double-insulated and do not provide a connection for the protective ground Apply only mains voltage or only safety extra-low voltage to the switching outputs of auxiliary switches A and B Mixed operation is not permissible However, operation using various phases is permissible HK2N4624en / 032000 Siemens Building Technologies 4/10 Landis & Staefa Division

Potentiometer for positioner Consider the potentiometer's electric data (max load and sliding contact current) Caution, maintenance Electric parallel connection of actuators Note Required actuator type Do not open the actuator! The unit is maintenance-free Any repair work must be conducted by the manufacturer only Electric connection in parallel of the GDB 1 actuators with GLB 1 is permissible only if the operating voltage is within the required tolerance Remember to include voltage drops at the feed lines A relay must be used for electric connection in parallel when the actuators are operated with SQE1, SQR 1, GBB 1 or GIB 1 Do not mechanically couple the actuators Selection of the actuator depends on several torque factors After obtaining the damper torque rating (Nm/m 2 ) from the manufacturer and determining the damper area, calculate the total torque required to move the damper as follows: Total Torque = Torque Rating Damper Area Determine your type of actuator from the below table: If Total torque [ Nm] SF 1 5 Nm 10 Nm 20 Nm 35 Nm then use type GDB 1 (5 Nm) GLB 1 (10 Nm) GBB 1 (20 Nm) GIB 1 (35 Nm) 1 Safety factor SF: When calculating the number of actuators, non-definable variables such as slight misalignment, damper age, etc must be included as a safety factor We recommend a safety factor of 080 (or 80% of the torque characteristic) Sizing transformers for AC 24 V (SELV) Wiring and commissioning Use safety insulating transformers with double insulation as per EN 61 558; the transformers must be made for 100% runtime Observe all local safety rules and regulations pertaining to sizing and protection of transformers Determine the transformer s power consumption by adding up the power consumption in VA for all actuators used Refer to "Commissioning notes" and "Diagrams" in this data sheet as well as to the HVAC job drawings Mounting notes Mounting instructions Mounting position Mounting bracket Shaft insert for GLB 1 (10 Nm) All information and steps to properly prepare and mount the actuator are listed in the Mounting Instruction guide supplied with the actuator Both position indicator and mounting bracket are delivered separately Choose the actuator's mounting position so that you can easily access the cables as well as the setting shafts on the actuator front Refer to "Dimensions" When you mount the actuator directly on the damper shaft, use the mounting bracket The pivot must have sufficient working depth in the base plate and sufficient play toward the shaft center, especially for smaller shaft diameters that cause greater eccentric movement To ensure a friction-locked connection at a shaft diameter of 8 10 mm, install the supplied shaft insert between the damper shaft and the coupling bushing as per the mounting instructions Siemens Building Technologies HK2N4624en / 032000 Landis & Staefa Division 5/10

Damper shafts Manual adjustment Mechanical limitation of rotational angle Using the linear mounting set Information on minimum length and diameter for the damper shaft is available in "Technical data" Disconnect the voltage supply before manually adjusting the actuator via the red slider Where required, you can set the rotational angle range by positioning the adjusting screw accordingly The mounting set as described in "Type summary" for changing the rotational movement to a linear stroke is mounted separately Commissioning notes References Ambient conditions Mechanical check Electrical check Switches A and B: Factory setting Note For commissioning, the following reference documentation must exist: This data sheet N4624 Mounting instructions 4 319 2883 0 (M4634) Job diagram Check to ensure that all permissible values as contained in the "Technical data" have been observed Check for proper mounting and to ensure that all mechanical settings correspond to the plant-specific requirements Additionally, ensure that the dampers are shut tight when in the closed position Check the direction of rotation Use the red slider (while no voltage is supplied) to manually adjust the dampers or the actuator Fasten the actuator securely to avoid twisting and blocking of the actuator Check to ensure that the cables are connected in accordance with the plant wiring diagram (see "Diagrams") The operating voltage AC 24 V or AC 230 V (SELV/PELV) must be within the tolerance values Functional check: Control signal AC 24 V between wires 1-6 : actuator turns clockwise between wires 1-7 : actuator turns counterclockwise Control signal AC 230 V between wires 4-6 : actuator turns clockwise between wires 4-7 : actuator turns counterclockwise The actuator remains in its current position if no control signal is applied Measure the potentiometer s change of resistance while the actuator turns from 090 While the actuator reaches the respective switching positions the auxiliary switch contacts "A" and "B" must change The auxiliary switches have the following factory settings: Switch A: switching point at 5 Switch B: switching point at 85 The settings for A and B can be set to the desired values using the setting shafts; refer to "Technical design" In order to ensure an exact switching position for switches A and B, refer to "Adjustable auxiliary switches" under the "Technical design" heading The angle values are valid only for the "0 " actuator position (clockwise direction) HK2N4624en / 032000 Siemens Building Technologies 6/10 Landis & Staefa Division

Technical data Power supply AC 24 V for GDB / GLB1311 GDB / GLB1321 GDB / GLB1361 AC 230 V supply for GDB / GLB3311 GDB / GLB3321 GDB / GLB3361 Mechanical data Operating voltage AC 24 V + 20 % Safety extra-low voltage (SELV) or Protection by extra-low voltage (PELV) as per HD 384 Requirements of external safety insulating transformer (100% ED) as per EN 61558 Supply line fuse max 10 A Frequency 50/60 Hz Power supply (with control signal) 83 ma Power supply (with control signal) 2 VA/1 W Operating voltage AC 230 V + 10 % Supply line fuse max 10 A Frequency 50/60 Hz Power supply (with control signal) 87 ma Power supply (with control signal) 2 VA/1 W Torque GDB31 Nominal torque 5 Nm Minimum holding torque (with/without operating voltage) > 5 Nm Maximum torque < 7 Nm Torque GLB31 Nominal torque 10 Nm Minimum holding torque (with/without operating voltage) > 10 Nm Maximum torque < 14 Nm Nominal rotational angle (with position indication) 90 Maximum rotational angle (mechanic limitation) 95 ± 2 Runtime for nom rotational angle 90, motor operation at 50/60 Hz 150 s / 125 s Rotational movement direction (defined by signal on wire 6 or 7) clockwise / counterclockwise Mechanical life 10 5 cycles Inputs Outputs Control signals AC 24 V Wires 1-6 Wires 1-7 Control signals AC 230 V Wires 4-6 Wires 4-7 clockwise counterclockwise clockwise counterclockwise Auxiliary switch for GDB / GLB1361 GDB / GLB3361 Number of changeover switches 2 Life: 6 A resistive, 2 A inductive 10 4 switchings 5 A resistive, 1 A inductive 5 x 10 4 switchings without load 10 6 switchings Switching voltage AC 24230 V Nominal current resistive/inductive 6 A / 2 A Insulation resistance between auxiliary switches and housing AC 4 kv Switching range of the auxiliary switches 5 85 Setting increments 5 Switching hysteresis 3 Factory changeover settings Switch A 5 Switch B 85 Positioner for GDB / GLB1321 GDB / GLB3321 Potentiometer Change of resistance (wires P1-P2) Load Maximum sliding contact current Insulation resistance between potentiometer and housing 01000 Ω < 1 W < 10 ma AC 500 V Wire connections Housing protection Cable lengths 09 m Supply AC 24 V (wires 1, 6, 7) / AC 230 V (wires 4, 6, 7) 3 x 075 mm 2 Auxiliary switches A and B (wires S1S6) 6 x 075 mm 2 Potentiometer (wires P1-P2) 3 x 075 mm 2 Degree of protection as per EN 60 529 IP 54 Protection class Insulation class AC 24 V AC 230 V Auxiliary switch III II II Siemens Building Technologies HK2N4624en / 032000 Landis & Staefa Division 7/10

Environmental conditions Operation IEC 721-3-3 Climatic conditions Class 3K5 Mounting location interior, weather-protected Temperature 3055 C Humidity (non-condensing) < 95% rh Transport IEC 721-3-2 Climatic conditions Class 2K2 Temperature 3060 C Humidity (non-condensing) < 95% rh Mechanical conditions Class 2M3 Standards Product safety Automatic electrical controls for EN 60 730-2-14 household and similar use (type 1) Electromagnetic compatibility Immunity EN 50 082-2 Emissions EN 50 081-1 Conformity Electromagnetic compatibility as per 89/336/EEC Low voltage directive 73/23/EEC Dimensions Actuator W x H x D see Dimensions Damper shaft Round Square Min length Max shaft hardness Shaft insert Used with GLB3 1 for shaft diameter 68 x 137 x 595 mm 816 mm 612 mm 20 mm < 300 HV 8 10 mm Weight Without packaging 048 kg Diagrams Internal diagram GDB/ GLB1311 GDB/ GLB1321 GDB/ GLB1361 GDB13 GLB13 AC 0 V 01000 Ω AC 24 V230 V / 6 (2) A 6 7 P1 P2 P3 S1 S4 (Y1) (Y2) (a) (b) (c) (Q11) (Q21) 100% A B M AC 24 V (SELV/PELV) 0% (G) (Q12) (Q14) (Q22) (Q24) 1 S2 S3 S5 S6 AC 24 V 4634G03 GDB/ GLB3311 GDB/ GLB3321 GDB/ GLB3361 GDB33 GLB33 AC 230 V 01000 Ω AC 24 V230 V / 6 (2) A 6 7 P1 P2 P3 S1 S4 (Y1) (Y2) (a) (b) (c) (Q11) (Q21) 100% A M B AC 230 V 0% (N) (Q12) (Q14) (Q22) (Q24) 4 S2 S3 S5 S6 4634G02 HK2N4624en / 032000 Siemens Building Technologies 8/10 Landis & Staefa Division

Cable labeling All wires are color-coded and labeled Connection Cable Designation Code No Color Abbreviation Actuator G 1 red RD System potential AC 24 V AC 24 V Y1 6 purple VT Control signal AC 24 V (0 V), clockwise Y2 7 orange OG Control signal AC 24 V (0 V), counterclockw Actuator N 4 blue BU Neutral conductor AC 230V Y1 6 black BK Control signal AC 230 V, clockwise Y2 7 white WH Control signal AC 230 V, counterclockwise Auxiliary Q11 S1 gray/red GY RD Switch A Input switches Q12 S2 gray/blue GY BU Switch A Normally closed contact Q14 S3 gray/pink GY PK Switch A Normally open contact Q21 S4 black/red BK RD Switch B Input Q22 S5 black/blue BK BU Switch B Normally closed contact Q24 S6 black/pink BK PK Switch B Normally open contact Positioner a P1 white/red WH RD Potentiometer 0100 % (P1-P2) b P2 white/blue WH BU Potentiometer pick-off c P3 white/pink WH PK Potentiometer 100 0 % (P3-P2) Connection diagram GDB/ GLB1311 GDB/ GLB1321 GDB/ GLB1361 SP (G) AC 24 V (SELV/PELV) (G0) (Y1) (Y2) N AC 24 V 6 7 P1 P2 P3 S1 S4 SN GDB13 GLB13 Y 1 S2 S3 S5 S6 4624A01 N Regulator or controller Y Actuator, three-position: GDB / GLB131, AC 24 V SP System potential AC 24 V SN System neutral GDB/ GLB3311 GDB/ GLB3321 GDB/ GLB3361 L (L) AC 230 V AC 230 V (N) (Y1) (Y2) N 6 7 P1 P2 P3 S1 S4 N GDB33 GLB33 Y 4 S2 S3 S5 S6 4624A02 N Y L N Regulator or controller Actuator, three-position: GDB / GLB331, AC 230 V Phase conductor AC 230 V Neutral conductor Siemens Building Technologies HK2N4624en / 032000 Landis & Staefa Division 9/10

Dimensions 428 1202 23 12 20 90 o 45 50 68 5 4 180 41 595 332 87 3 137 min 6 2 min100 x GLB1E GDB1E x = x = 10-16 mm 8-16 mm min 200 min 60 12 mm 15 mm 12 mm 15 mm 4634M01 Dimensions in mm 2000 Siemens Building Technologies Ltd HK2N4624en / 032000 Siemens Building Technologies 10/10 Landis & Staefa Division