Grounding and Wiring of Protection and Control Equipment

Similar documents
EMC INSTALLATION INFORMATION

Construction and Wiring Guidelines for Ergon Energy Substation Panels

EMC Compatible enclosure assembly

WIRING THE HEATER POWER SUPPLY

FITTING THE RELAY SWITCH BOARD FITTING THE INPUT SELECTOR SWITCH

o o Parker Automation

SECTION 15. GROUNDING AND BONDING

Installation Guide. Auxiliary Pressure Control Manifold on 6890 GC Accessory G1570A

QUASAR ELECTRONICS KIT No ELECTRONIC CAR IGNITION

SLOVAK UNIVERSITY OF TECHNOLOGY Faculty of Material Science and Technology in Trnava ELECTRICAL ENGINEERING AND ELECTRONICS.

IBER DISTRIBUTION FRAME (FDF) FOR EXCHANGE SIZE 900MM x 2200MM x 300 MM

Product Brochure. Generator Circuit-Breaker HVR-EBCB For hydro or pump storage power plant

Compliance with CE Marking and UL Standard

Recommended Practices for Installation for EC Directive 2014/30/EU Relating to EMC

GHA. Gas-Insulated Switchgear. Gas-Insulated Switchgear. Switchgear extension and replacement of a panel

LINE CONDITIONERS USER'S GUIDE

Cable arrangement 15 Preparation for cable installation. 15 Installation of the cables 16 Finishing of the cable installation. 17 Examples.

UNIVERSITY OF CAMBRIDGE INTERNATIONAL EXAMINATIONS International General Certificate of Secondary Education

MPA Chassis for Multi-Probe Magnetic Transducers

PIX. Operation - Replacement of Fuses Replacement of Voltage Transformers Technical manual. Medium Voltage Distribution

Toothed belt axis ELGC-TB-KF. Operating instruction [ ]

A Practical Guide to Free Energy Devices

CHAPTER 13 MAGNETIC EFFECTS OF ELECTRIC CURRENT

OPERATING INSTRUCTION

EULR Fan. Fläkt Woods 8192 GB Specifications are subject to alteration without notice

ABB Switzerland Ltd Phone Surge arresters Telefax:

3M Cold Shrink QT-III Silicone Rubber Three-Core Termination Kits

Application Note EMC - Checklist

MEDIUM VOLTAGE PRODUCTS. Fault Current Limiters I S. -limiter and FC-Protector The worldʼs fastest switching devices

3M Cold Shrink QT-III Silicone Rubber 3/C Cabinet Mount Termination Kit

Safety Sensor CSS 180 Product Information

TECHNICAL GUIDE FOR PROXIMITY SENSORS DEFINITIONS YAMATAKE PROXIMITY SENSOR CATEGORIES

Copyright 2012 DelSolar Co. Ltd MQWRD installation manual-iec Ver. 1.4

Installation Instructions (Translation) Marking. Description. Danger, warning and note symbols. Technical data. ANTARES ExtSet.

QUASAR ELECTRONICS KIT No WINDSCREEN WIPER CONTROLLER

Safe, fast HV circuit breaker testing with DualGround technology

HIGH VOLTAGE MODULE TEST SYSTEM

CLP POWER HONG KONG LIMITED. SUPPLY RULES March 2001

QUASAR KIT No THYRISTOR - TRIAC TESTER

3M Cold Shrink Silicone Rubber Termination QT-III 7600-S-3G Series Three-Core Outdoor Termination

INSTRUCTION MANUAL MANOSTAR TRANSMITTER EMT1. RoHS READ THE INSTRUCTION MANUAL BEFORE USING. No. TR-EMT1-E08

Installation Instructions

Product brochure. Gas-insulated switchgear ELK-04 C, 145 kv Modular and reliable

Welcome to the ABB Industrial Drives, ACS800 planning the installation training module. If you need help navigating this module, click the Help

Braking Module / braking resistor SINAMICS. SINAMICS G130 Braking Module / braking resistor. Safety information 1. General. Mechanical installation

Displacement Sensor. Model 8739, 8740, 8741

Installation, Operation and Maintenance Instructions

Raritan PX. Power Cord Installation Guide. Safety Guidelines. Safety Instructions

LCD Annunciator Installation Instructions

Differential Pressure Sensors

Preparing the Site. Information About the Site Requirements CHAPTER

Kinetix 350 Single-axis EtherNet/IP Servo Drives

INSTALLATION MANUAL.

1. What type of material can be induced to become a temporary magnet? A) diamagnetic B) ferromagnetic C) monomagnetic D) paramagnetic

Transmission Line Arrester TLA

DUAL 60V 20A POWER FLEX POWER SUPPLY INSTRUCTION MANUAL

Installation Instructions. Y-Series Brushless Servo Motor

MODEL 8682 SUREFLOW ADAPTIVE OFFSET CONTROLLER

Installation Instructions

Chapter 22: Electric motors and electromagnetic induction

TIDALFLUX 2300 F Quick Start

1ZSE EN, REV. 4. Wall bushings type GSA-AA Technical guide

VW Embedment Strain Gauge

Magnetism and Electricity ASSIGNMENT EDULABZ. the mere presence of magnet, is called...

ALL POSITION VARIABLE SPEED TRAVEL CARRIAGE

Transformer bushings, type GOA 250. Installation and maintenance guide

MULTICHANNEL ULTRASONIC FLOW METER AFLOWT UF

MSD Stacker-4 (4-Channel), PN 7010 Stacker-8 (8-Channel), PN 7020

Product Information. Neutral Wall Bushing GOFL

Load Cell for Manually Operated Presses Model 8451

All rights reserved. Neither this catalogue nor any part of it may be copied using any method or for any purposes. Most studies are legally protected.

Operating Manual (Edition 04/2004) sinamics. Braking Module / Braking Resistor SINAMICS G130

3M Cold Shrink Silicone Rubber Outdoor Termination Kit QT-III 7600-S-3W Series

Product brochure. Gas-insulated switchgear ELK-04 C, 145 kv Modular and reliable

P200 P/I Transducer. Installation, Operation, and Maintenance Instructions INTRODUCTION

KD1E Range Potential Indicators

SUSPENSION 04 CLAMPS

CLASSIFIED 5 MAGNETISM ELECTROMAGNETIC INDUCTION GENERATOR MOTOR - TRANSFORMER. Mr. Hussam Samir

Warranty Information Operators Manual Installation Instructions. Sudenga

Air-insulated switchgear UniGear type ZS1

DSL-220 MkIII Single Pass Opacity Monitor Measures 0-100% Opacity

INSTALLATION INSTRUCTIONS

INSTALLATION MANUAL. Instructions, precautions, suggestions for installing and servicing resin transformers in full compliance with safety rules

SINAMICS. SINAMICS G130 Braking Module / braking resistor. Safety information 1. General. Mechanical installation. Connection 4

PART 10 ELECTRICAL INSTALLATIONS

Electrohydraulics Basic Level Textbook TP 601

Single Point Overfill Prevention Control Monitor Model: ST-15C Series Technical Manual

User s Manual. ACH550-CC/CD Packaged Drive with Classic Bypass Supplement for ACH550-UH HVAC User s Manual

Installing the Flame Ionization Detector EPC Flow Control Manifold

CFW PowerCable Redefining EMC. TN-S - the induction-free, low-radiation installation cable

Chapter 14:08 Factories and Works (Electrical) Regulations, Chapter 14:08 Factories and Works (Electrical) Regulations, 1976

WORLDWIDE GUARDWIRE ACCESSORIES INSTALLATION MANUAL PROVEN PERIMETER PROTECTION

POWERHEAT TYPE AHT TERMINATION INSTRUCTIONS. Ref TK/AHT Issue C Date 16 August 1999

standards based cylinder DNCI Operating instructions e [ ]

Current accuracy class. Sensor principles

web:

DURESCA Busbar system. For indoor and outdoor applications, type DE / type DG DURESCA

1MRB Uen Edition September Multifunction Relay Types MCX 912 and MCX 913. Operating Instructions. Home

B kv Gas-insulated Substations

Operating Instructions CYR52

Transcription:

Grounding and Wiring of Protection and Control Equipment 1MRB520197-Ten Edition February 2002 p Technical Document

1997 ABB Switzerland Ltd Baden/Switzerland 2nd Edition All rights with respect to this document, including applications for patent and registration of other industrial property rights, are reserved. Unauthorised use, in particular reproduction or making available to third parties without our explicit consent in writing, is prohibited. This document has been carefully prepared and reviewed. Should in spite of this an error be found, you are requested to inform us at your earliest convenience. The use is only allowed for the purpose laid down in the contract.

GROUNDING AND WIRING 1MRB520197-Ten ABB Switzerland Ltd Contents 1. GENERAL... 2 2. CUBICLE... 3 2.1. Mechanical design... 3 2.2. Grounding system... 3 2.2.1. Grounding a single cubicle... 3 2.2.2. Grounding system for adjacent cubicles... 4 2.2.3. Grounding system for equipment... 5 3. OPEN EQUIPMENT RACKS... 6 4. SCS CONSOLE... 7 5. GROUNDING STRIPS (braided copper) AND THEIR INSTALLATION... 8 6. WIRING... 9 6.1. External wiring... 9 6.2. Internal wiring... 9 6.3. Communication cables... 10 7. SCREENING... 12 7.1. Cable shields... 12 7.2. Grounding the ends of cable shields... 12 7.3. Grounding the shields of interface cables... 13 1

ABB Switzerland Ltd GROUNDING AND WIRING 1MRB520197-Ten 1. GENERAL Switching operations in HV installations generate transient overvoltages in measurement and control cables. Electrostatic or magnetic RF fields either of a latent nature or caused by various operations are also induced in the devices themselves or in the cables connected to them. Interference of this kind can impair the operation of electronic equipment. On the other hand, electronic equipment itself can transmit electromagnetic waves that interfere with other electronic equipment. To keep this interference within acceptable limits, the grounding, wiring and screening of the equipment must fulfil certain minimum standards. For these precautions to have the desired effect, the station ground must be of good quality. 2

2. CUBICLE GROUNDING AND WIRING 1MRB520197-Ten ABB Switzerland Ltd 2.1. Mechanical design The cubicle must be designed and fitted out such that the impedance for RF interference of the ground path from the electronic device to the cubicle ground terminal is as low as possible. Metal accessories such as side plates, blanking plates etc., must be effectively connected surface-to-surface to the grounded frame to ensure a low-impedance path to ground for RF interference. The contact surfaces must not only conduct well, they must also be non-corroding. If the above conditions are not fulfilled, there is a possibility of the cubicle or parts of it forming a resonant circuit at certain frequencies that would amplify the transmission of interference by the devices installed and also reduce their immunity to induced interference. 2.2. Grounding system 2.2.1. Grounding a single cubicle Movable parts of the cubicle such as doors (front and back) or hinged equipment frames must be effectively grounded to the frame by three braided copper strips (see Fig. 1). Door or hinged equipment frame Rack Device Cubicle ground rail close to floor Station ground rail Braided copper strip, width 20 mm, cross-section 16 mm 2 Grounding strip terminal (sleeve) or conducting connection Fig. 1 Cubicle grounding system 3

ABB Switzerland Ltd GROUNDING AND WIRING 1MRB520197-Ten The metal parts of the cubicle housing and the ground rail are interconnected electrically conducting and corrosion proof. The contact surfaces shall be as large as possible. For metallic connections please observe the voltage difference of both materials according to the electrochemical code. The greater the voltage difference, the greater the danger of electrochemical corrosion. The cubicle ground rail must be effectively connected to the station ground rail by a grounding strip (braided copper, see Section 5.). Where the two ground rails are more than 5 m apart, two grounding strips must be run parallel and as close as possible to each other. 2.2.2. Grounding system for adjacent cubicles Where cubicles are placed next to each other ( 1 m apart), the requirements of Fig. 2 must be observed in addition to those of Fig. 1. Cubicle Cubicle ground rail Station ground rail Fig. 2 Cubicle grounding system in the case of several cubicles next to each other The cubicle ground rails are linked together and each one individually connected to the station ground rail. If the cubicles are further than 1 m apart, they do not have to be interconnected. In the case of cubicles with several compartments, the ground rails of the compartments are linked together and each one is connected to the station ground rail. 4

GROUNDING AND WIRING 1MRB520197-Ten ABB Switzerland Ltd 2.2.3. Grounding system for equipment Grounding strips may be attached to the left (as in Fig. 1) or to the right of racks and devices (see Fig. 3a). Take care that the grounding strip is always as short as possible. Note the admissible and inadmissible arrangements illustrated in Fig. 3. Grounding strip Device a) Admissible b) Inadmissible Fig. 3 Grounding system for two devices installed next to each other If the devices or electrical equipment racks have a tight, extensive corrosion proof and electrically conducting connection to the cubicle metal, there is no need for grounding straps, even if ground connection screws and labels are attached to the device. 5

ABB Switzerland Ltd GROUNDING AND WIRING 1MRB520197-Ten 3. OPEN EQUIPMENT RACKS The surface of open equipment rack frames must be electrically conducting and non-corroding and must be effectively connected to the station ground rail (see Fig. 4). 19" rack with modules Mounting plate Electrically conducting junction on both sides Interface module Device Open equipment rack Cover plate Station ground rail Fig. 4 Grounding system for open equipment racks (front view) Metal interface modules not having their own grounding strips, mounting plates and all kinds of cover plates must have an electrically conducting connection to the equipment rack, i.e. neither contact surface may be painted and yet must be noncorroding (e.g. galvanised). Devices and 19" racks must be grounded as shown in Fig. 1. Always take care to keep the grounding strips as short as possible. As stipulated in Section 2.2.1, a second grounding strip must be run parallel and as close as possible to the first, if the station ground rail is more than 5 m away. 6

GROUNDING AND WIRING 1MRB520197-Ten ABB Switzerland Ltd 4. SCS CONSOLE Basically, an SCS console is mechanically the same as a cubicle (see Section 2.1). The console housing must be electrically connected to the station ground rail by a braided copper strip (see Section 5) as shown in Fig. 5 (insertion from below). Console Braided copper strip Station ground rail Fig. 5 Grounding system for an SCS console The grounding strip is bolted to the inside of the console housing immediately adjacent to the inlet gland (electrically conducting surface-to-surface, see Fig. 6). As stipulated in Section 2.2.1, a second grounding strip must be run parallel and as close as possible to the first, if the station ground rail is more than 5 m away. All the devices installed in the console must be connected by grounding strips to the console housing. Always take care that the grounding strip is as short as possible. 7

ABB Switzerland Ltd GROUNDING AND WIRING 1MRB520197-Ten 5. GROUNDING STRIPS (braided copper) AND THEIR INSTALLATION High frequency currents are produced by interference in the ground connections and because of skin effect at these frequencies, only the surface region of the grounding strips is of consequence. The grounding strips must therefore be of (preferably tinned) braided copper and not round copper conductors, as the crosssection of round copper would have to be too large. Data of braided copper strip: Width 20 mm, Cross-section 16 mm 2 (protection ground) Proper terminations must be fitted to both ends (press/pinch fit and tinned) with a hole for bolting them firmly to the items to be connected. The surfaces to which the grounding strips are bolted must be electrically conducting and non-corroding. Braided copper strip Press/pinch fit cable terminal Terminal bolt Contact surface Fig. 6 Ground strip and termination If the contact surface is aluminium, a cupal (copper plated aluminium) washer must be inserted between the grounding strip and the aluminium to prevent electrochemical corrosion (the voltage difference of Cu Al amounts to approximately 2 V). 8

6. WIRING GROUNDING AND WIRING 1MRB520197-Ten ABB Switzerland Ltd 6.1. External wiring The external wiring includes all the connections from the primary plant to the cubicle or open equipment rack terminals or directly to the device terminals. This cables are preferably run in metal ducts that are connected to the station ground at several places. The external wiring is of the following types: instrument transformer leads auxiliary supply cables binary inputs and outputs. Since experience has shown that the main source of interference is the c.t. and v.t. leads, these should be run in different cable ducts separately from the other cables. C.t. and v.t. leads and leads conducting binary signals are recommended to be shielded (see Section 7.). 6.2. Internal wiring The internal wiring includes all the connections from the cubicle or equipment rack terminals to the device terminals. In the case of open equipment racks, these connections should be kept as short as possible. As mentioned in Section 6.1. above, it is an advantage for the c.t. and v.t. leads to be run separately from the other cables, i.e. they should not be run in the same cable duct or in the same cable loom. Mutual coupling can be avoided by crossing cables of different types perpendicularly and not running them parallel (see Fig. 7). 9

ABB Switzerland Ltd GROUNDING AND WIRING 1MRB520197-Ten Device C.t/v.t. leads Binary inputs and outputs Auxiliary supply Terminals Fig. 7 Example of crossing c.t./v.t. leads and supply/ signal cables perpendicularly 6.3. Communication cables No precautions have to be taken in the case of optical fibre cables. Conventional copper communication cables must be screened (see Section 7.). The cable shield must be effectively connected to ground in the cubicles at both ends immediately adjacent to the cable inlet (see Section 7.2.). With the cable shields grounded at both ends, any potential differences between the cubicles will cause balancing currents to flow in the shields that can induce interference in the cables. This can interfere with the function of a device at cable lengths of 10 m and more. A possible solution is to run the cables along ground rails of the meshed ground system of the station building and grounding the shields at intervals of 5 to 10 m. For this purpose, a suitable length of insulation is stripped from the shield and the exposed shield connected by a cable cleat to a grounded metal surface (Fig. 9). Both the cleat and the contact surface must be electrically conducting and non-corroding. 10

GROUNDING AND WIRING 1MRB520197-Ten ABB Switzerland Ltd An alternative is to run a low-impedance ground connection parallel to the screened cables to bypass the balancing currents (Fig. 8). Screened signal cables E.g.consol Cubicle Bypass (braided copper parallel ground) Grounded cable shield Fig. 8 Low-impedance parallel ground connection Fig. 8 shows a parallel ground connection between an SCS console and a cubicle. The same arrangement applies in the case of two cubicles. The parallel ground is of braided copper (see Section 5.). It should be kept parallel to the signal cable. This reduces the PLC impedance of the connection between the container and the cubicle. In order to guarantee paralleling, the braided copper band and the signal line may be loosely strapped together at intervals. Cables conducting analogue (LF) signals must have twisted cores. Multi-core cables must have twisted pairs. 11

ABB Switzerland Ltd GROUNDING AND WIRING 1MRB520197-Ten 7. SCREENING 7.1. Cable shields The cable shields shall be braided and have a cover factor of at least 80 %. 7.2. Grounding the ends of cable shields The ground connection to a cable shield must extend around the entire circumference. Grounding a shield by soldering a wire to it achieves only an inadequate screening effect in industrial installations. Cable shields must be grounded at both ends. The best screening effect is achieved when the cable would enter the cubicle via a screwed cable gland. If a cable gland of this type is not provided, the cable must be grounded as shown in Fig. 9 and Fig. 10 on the inside of the cubicle immediately adjacent to the cable inlet. To ground the cable, remove a suitable length of the insulation and push the braiding of the shield back over the end of the insulation. Secure the end of the cable to the grounded surface by means of a metal cleat (Fig. 9). The cleat and the contact surface must be electrically conducting and non-corroding. Cable insulation Cleat Braided shield pushed back over end of insulation Cores Fig. 9 All-round grounding of the end of the cable shield The shield must be pushed back over the insulation to prevent it from fraying with time and the quality of the ground contact di 12

GROUNDING AND WIRING 1MRB520197-Ten ABB Switzerland Ltd minishing. It also reduces the risk of pinching the shield and the cores. Choose a cleat that holds the shield firmly but does not pinch the shield or the cores. The grounding system in the case of open equipment racks is executed as shown in Fig. 9 and Fig. 10. Bear mounting plate supporting device (or 19"-style rack) Open rack frame Screened cables Shields grounded as in Fig. 9 Station ground rail Fig. 10 Grounding cable shields in the case of an open equipment rack (rear view) The rear of the mounting plate must not be painted and the surface must be a good conductor and non-corroding. As explained in Section 5 and shown in Fig. 4, the mounting plate must be in good electrical contact with the frame of the open rack. The unscreened ends from the point of grounding to the device terminals must be kept as short as possible. Certain groups of cables must also be run separately as explained in Section 6.2. 7.3. Grounding the shields of interface cables Connector housings must be either of metal or metal-coated plastic and be equipped with an effective strain relief that is electrically connected to the housing. 13

ABB Switzerland Ltd GROUNDING AND WIRING 1MRB520197-Ten The insulation is stripped and the shield pushed back as described in Section 7.2. The cable strain relief must ground the shield around the entire circumference in the same way as the cleat in the preceding cases. The screws securing the connector in place after it has been inserted must be firmly tightened to establish a reliable ground connection. Many signal cables still ground the cable shield via a pin on the connector (mostly plastic connector housings). The screening effect achieved in such cases is inadequate in industrial installations. The same applies when the shield is grounded via a wire coming out of the connector housing and connected to an external ground terminal. 14

Notification Form for Errors in this Document Dear User, We are always endeavouring to improve the quality of out technical publications and would like to hear your suggestions and comments. Would you therefore please fill in this questionnaire and return it to the address given below. ABB Switzerland Ltd Utility Automation Technical Publications, Dept. UTASB-5 Römerstrasse 29 / Building 733/3 CH-5401 Baden Telefax +41 58 585 28 00 --------------------------------------------------------------------------------------------------------------- Concerns publication: 1MRB520197-Ten (Earthing and Wiring of Protection and Control Units) Have you discovered any mistakes in this publication? If so, please note here the pages, sections etc. Do you find the publication readily understandable and logically structured? Can you make any suggestions to improve it? Is the information sufficient for the purpose of the publication? If not, what is missing and where should it be included? Name Date Company Postal code Town Country

IMPORTANT NOTICE! Experience has shown that reliable operation of our products is assured, providing the information and recommendations contained in this technical document are adhered to. It is scarcely possible for this technical document to cover every eventuality that can occur when using technical devices and systems. We would therefore request the user to notify us directly or our agent of any unusual observations or of instances, in which this technical document provides no or insufficient information.

ABB Switzerland Ltd Utility Automation Brown Boveri Strasse 6 CH-5400 Baden / Switzerland Phone +41 58 585 77 44 Fax +41 58 585 55 77 E-mail substation.automation@ch.abb.com www.abb.com/substationautomation Printed in Switzerland (0203-0040-0)