COOPER POWER SERIES. Types D and DV recloser installation instructions. Reclosers MN280030EN

Similar documents
Effective November 2016 Supersedes September 1998 (S )

Type NR oil switch installation and operation instructions

Effective June 2016 New Issue

COOPER POWER. SERIES ELF Current-Limiting Dropout Fuse Installation Instructions. Fusing Equipment MN132028EN. Pull ring. Housing

COOPER POWER SERIES. KA1169R Closing Coil Transfer-Switch Accessory Operation. Reclosers MN280069EN

COOPER POWER SERIES. Current-Limiting Type NXC (C-Rated) Fuse Installation Instructions. Fusing Equipment MN132014EN

COOPER POWER SERIES. K-Limiter back-up current-limiting fuse installation instructions. Fusing Equipment MN132010EN

COOPER POWER SERIES. 600 A 15, 25, and 35 kv Class Cleer Loadbreak Bushing Insert Installation Instructions. Loadbreak/Deadbreak Connectors MN650016EN

COOPER POWER SERIES. QD5 Quik-Drive tap-changer reversing neutral stationary contact asssembly kit A26 installation instructions

COOPER POWER SERIES. Edison Modular Fuse (EMF) Installation Instructions. Fusing Equipment MN132031EN

COOPER POWER SERIES. 200 A loadbreak junction 15 and 25 kv class installation instructions. Loadbreak Connectors MN650015EN

COOPER POWER SERIES. Testing a motor capacitor on a voltage regulator procedure instructions. Voltage Regulators MN225064EN

COOPER POWER SERIES. S.T.A.R. type LVR faulted circuit indicator installation instructions. Fault Indicators MN320005EN

COOPER POWER SERIES. UltraSIL polymer-insulated D-73P disconnect switches installation instructions. Switches MN008004EN

COOPER POWER SERIES. High-voltage primary bushings installation instructions. OEM Equipment MN800008EN

Effective March 2015 Supersedes S August 2012

COOPER POWER. SERIES CMU Medium voltage power fuse installation instructions. Fusing Equipment MN132032EN

COOPER POWER SERIES. Types 4H single-phase and 6H three-phase vacuum interrupter conversion kits. Reclosers MN280014EN

COOPER POWER SERIES. HX-CB loadbreak fuse cutout installation instructions. Fusing Equipment MN132011EN

COOPER POWER SERIES. RTE EL-BAY-O-NET FUSE Re-Fusing Instructions. Fusing Equipment MN132024EN

COOPER POWER SERIES. Pad-mounted Switchgear MN285019EN. Effective March 2017 Supersedes February 2007 (S )

COOPER POWER SERIES. ELSG Full-Range Current-Limiting Fuse Re-Fusing Instructions. Fusing Equipment MN132017EN

COOPER POWER SERIES. 200 A Fused Loadbreak Elbow Connector Replacement Fuse Installation Instructions. Fusing Equipment MN132021EN

COOPER POWER SERIES. Screened Separable Connectors MN650023EN. Effective October 2016 Supersedes March 2012 (IS )

COOPER POWER SERIES. S.T.A.R. Hot line voltage indicator installation instructions. Fault Indicators MN320011EN. Indicator boot.

COOPER POWER SERIES. KA716L7001 adjustable control valve kit for Types L, E, 4E, V4E, and V4L reclosers installation and adjustment instructions

Effective November 2016 Supersedes February 2012 (S )

COOPER POWER SERIES. KA662R tank-lifting windlass assembly and installation instructions. Recloser Mountings MN280071EN

COOPER POWER SERIES. Screened Separable Connectors MN650024EN. Effective October 2016 Supersedes March 2012 (IS )

COOPER POWER SERIES. Dielectric grease application to recloser cable instructions. Reclosers MN280070EN

COOPER POWER SERIES. Expulsion fuse installation instructions. Capacitors MN230005EN. Effective November 2016 Supersedes November 2001 (S )

High-voltage primary bushings installation instructions

Effective May 2017 Supersedes January 2003 (S )

Effective May 2017 Supersedes December 2004 (S )

COOPER POWER SERIES. 600 A 15/25 kv class T-OP II connector assembly installation instructions. Deadbreak Apparatus Connectors MN650048EN

COOPER POWER SERIES. KA146W5 single pole-mounting hanger; KA146W2 tank lifting windlass assembly and installation instructions. Reclosers MN280039EN

COOPER POWER SERIES. Mercury switch to microswitch retrofit kit KA349WE installation instructions. Reclosers MN280022EN

COOPER POWER SERIES. Electronic control battery testing, charging, and replacement instructions. Reclosers MN280074EN

COOPER POWER SERIES. Quick Connect Assembly (QCA) Retrofit Kit, General Electric Installation Instructions. Voltage Regulators MN225075EN

COOPER POWER SERIES. Surge arrester interchangeable fuse cutout combination installation instructions. Surge Arresters MN235004EN

COOPER POWER SERIES. Types VWE, VWVE27, VWVE38X, WE, WVE27, and WVE38X; threephase electronically controlled; installation and operation instructions

COOPER POWER SERIES. 600 A 15/25 kv class BOL-T and separable splice connector assembly installation instructions

COOPER POWER SERIES. 600 A 15 kv and 25 kv class BT-TAP connector system installation instructions. Deadbreak Apparatus Connectors MN650004EN

This Kit Is for Use with Types RE, RVE, WE, WVE, VWE, VWVE27, and VWVE38 Reclosers.

COOPER POWER SERIES. 600 A 35 kv class BT-TAP connector system installation instructions. Deadbreak Apparatus Connectors MN650003EN

COOPER POWER SERIES. Fused loadbreak elbow connector installation instructions. Loadbreak Apparatus Connectors MN650014EN

COOPER POWER SERIES. Metal-enclosed capacitor banks installation instructions. Power Capacitors MN230010EN

COOPER POWER SERIES. Manually-Operated M-Force Switch Installation and Operation Instructions. Switches and Disconnects MN008003EN

KFE10002-E. Reclosers. Type KFE and KFVE Electronically Controlled Vacuum Recloser Installation Instructions. Service Information

S Voltage Regulators GENERAL. Contents. Acceptance and Initial Inspection. Handling and Storage. Standards

COOPER POWER SERIES. Metal-enclosed, pad-mounted capacitor banks installation instructions. Power Capacitors MN230009EN

S Fault Indicators. S.T.A.R. Type TPR Faulted Circuit Indicator Installation Instructions. Contents INSTALLATION PROCEDURES

S Voltage Regulators PRODUCT INFORMATION GENERAL. Contents. Acceptance and Initial Inspection. Handling and Storage

S Voltage Regulators PRODUCT INFORMATION GENERAL. Contents. Acceptance and Initial Inspection. Handling and Storage.

Installation Instructions for Interlocking Trip Indicator with Remote Reset for Magnum Low Voltage Circuit Breakers

Factory Authorized Mechanism Enhancement (FAME)

S Voltage Regulators GENERAL. PRODUCT INFORMATION Introduction. Contents. Acceptance and Initial Inspection. Handling and Storage.

Figure 1. Kearney Type HX cutout.

COOPER POWER SERIES. Instructions for oil-filled, single-phase overhead distribution transformers. Distribution Transformers MN201003EN

COOPER POWER SERIES. Externally fused block banks installation instructions. Capacitors MN230004EN

Instructions for VCP-W Simple Electrical Ground & Test Device (SEG&TD) with simplified interlock scheme - bottom terminal set version

TRINETICS CSD SERIES OIL SWITCH INSTALLATION INSTRUCTIONS

Removal/installation instructions for Series NRX (IZMX) drawout levering (racking) mechanism

Reprogramming guide. Power Defense ICCB. Instructional Leaflet IL EN WARNING WARNING. Instructions apply to:

Installation Instructions For Motor Control Center (MCC) Units

COOPER POWER SERIES. VFI tester operating instructions. Underground Distribution Switchgear MN285001EN

Instruction Booklet for the Installation, Operation and Maintenance of Type 5-15 kv VCP-WG Vacuum Circuit Breaker 4000A MiniMod

S Contents. Applicable to Serial Numbers A101 and above or beginning with CP57.

KFE10010-E. Reclosers. Contents. Type KFVE and KFVME (27kV) Bus Bar Kit KRK710-1 Installation Instructions. Cooper Power Systems

COOPER POWER SERIES. Type VSA12, VSA12B, VSA16, VSA20, and VSA20A operation and installation instructions. Reclosers MN280063EN

CCP2-FLR1-21_ flange-rod operating mechanism

3-way multi-family drawout cable interlock kit - type 32 - RF

VariSTAR Type AZE station-class surge arresters for systems through 345 kv IEEE certified

Installation and removal instructions for Series NRX RF fixed breaker three-way Type 32 cable interlock kit

S Reclosers. Contents. Types VXE15 and VXE27 Electronically Controlled, Single-Phase Recloser Maintenance Instructions

Two-way cable interlock kit for Magnum drawout circuit breakers

Installation Instructions for KPS and KPH Circuit Breakers and Molded Case Switches

www. ElectricalPartManuals. com Instructions for Field Testing of Ground Fault Systems Utilizing Cutler-Hammer Magnum DS Circuit Breakers

COOPER POWER SERIES. Type PST Model-9 Automatic Source Transfer Switchgear with ist Control; Installation, Operation, and Maintenance Instructions

Type DTU De-energized Tap Changer Application, Installation & Selection Guide. IL A Instruction Leaflet Page 1 September, 2003

Types VSA12, VSA12B, VSA16, VSA20, and VSA20A; three-phase; air-insulated; electronically controlled recloser

Instructions for using Functional Test Kit on Digitrip 520 and 1150 family of Power Circuit Breaker Trip Units and Series G and FD MCCB Trip Units

O & M Manual for the EATON Generator Ready Loadcenter

Advanced Test Equipment Rentals ATEC (2832)

S Voltage Regulators. Contents. QD3 Quik-Drive Voltage Regulator Tap-Changer Manual. Figure 1B. QD3 Tap-changer. Figure 1A. QD3 Tap-changer.

COOPER POWER SERIES. Type PST Model-9 automatic source transfer switchgear with ist control installation, operation, and maintenance instructions

IB PowlVac ITE-HK Remote Racking Device

Effective May 2017 Supersedes October 2002 (S )

II DISTRIBUTION & SUBSTATION TYPE C

Effective October 2016 Supersedes January 2014 (S )

100 A externally operated one-, twoand three-phase tap-changer switch

Two-way cable interlock kit for Magnum fixed circuit breakers

Simple Electrically Operated Ground & Test Device For use in Type VCP-W Switchgear rated up to 15kV, 25 and 40kA UPPER TERMINAL SET VERSION

Edison modular fuse, vault application products

Digitrip Retrofit System for General Electric AKR/AKRU-6D/7D-30S Series Breakers

Digitrip Retrofit System for the ITE LG-3000 (Frameless) Circuit Breaker

600 A 15 and 25 kv class Cleer grounding elbow

S Fault Interrupters. Type CI; Three-Phase Installation and Operation Instructions. Service Information

COOPER POWER SERIES. RVAC Fluid-insulated Vacuum Switchgear; Installation, Operation, and Maintenance Instructions. Switchgear MN285005EN

COOPER POWER SERIES. Type MOST Fluid-Insulated Switchgear; Installation, Operation, and Maintenance Instructions

Transcription:

Reclosers MN280030EN Effective December 2015 Supersedes S280-20-1 February 1979 Types D and DV recloser installation instructions COOPER POWER SERIES

DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY The information, recommendations, descriptions and safety notations in this document are based on Eaton Corporation s ( Eaton ) experience and judgment and may not cover all contingencies. If further information is required, an Eaton sales office should be consulted. Sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eaton selling policies or other contractual agreement between Eaton and the purchaser. THERE ARE NO UNDERSTANDINGS, AGREEMENTS, WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY, OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES. ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON. THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES. In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability or other-wise for any special, indirect, incidental or consequential damage or loss whatsoever, including but not limited to damage or loss of use of equipment, plant or power system, cost of capital, loss of power, additional expenses in the use of existing power facilities, or claims against the purchaser or user by its customers resulting from the use of the information, recommendations and descriptions contained herein. The information contained in this manual is subject to change without notice. ii

Contents SAFETY INFORMATION Safety instructions...iv PRODUCT INFORMATION Introduction...1 Quality standards................................................................................1 Acceptance and initial inspection...1 Handling and storage...1 Guarantee...1 Shipment...1 Handling and storage...1 DESCRIPTION Description...1 Specifications and ratings...3 Dimensions and weights...3 Operating levers and indicators...4 Closing solenoid...4 ADJUSTMENTS Operations to lockout...5 Number of fast operations...5 Retarded-timing characteristics...6 INSTALLATION AND OPERATION Preliminary checks...7 Mounting hardware...8 Main wiring...10 Initial operation...10 Manual operation...10 Non-reclosing operation...11 TESTING Test equipment required...12 Test procedure-electrical closing...14 iii

! SAFETY FOR LIFE Safety for life! SAFETY FOR LIFE Eaton meets or exceeds all applicable industry standards relating to product safety in its Cooper Power series products. We actively promote safe practices in the use and maintenance of our products through our service literature, instructional training programs, and the continuous efforts of all Eaton employees involved in product design, manufacture, marketing, and service. We strongly urge that you always follow all locally approved safety procedures and safety instructions when working around high voltage lines and equipment, and support our Safety For Life mission. Safety information The instructions in this manual are not intended as a substitute for proper training or adequate experience in the safe operation of the equipment described. Only competent technicians who are familiar with this equipment should install, operate, and service it. A competent technician has these qualifications: Is thoroughly familiar with these instructions. Is trained in industry-accepted high and low-voltage safe operating practices and procedures. Is trained and authorized to energize, de-energize, clear, and ground power distribution equipment. Is trained in the care and use of protective equipment such as arc flash clothing, safety glasses, face shield, hard hat, rubber gloves, clampstick, hotstick, etc. Following is important safety information. For safe installation and operation of this equipment, be sure to read and understand all cautions and warnings. Hazard Statement Definitions This manual may contain four types of hazard statements: DANGER Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. WARNING Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. CAUTION Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. CAUTION Indicates a potentially hazardous situation which, if not avoided, may result in equipment damage only. Safety instructions Following are general caution and warning statements that apply to this equipment. Additional statements, related to specific tasks and procedures, are located throughout the manual. DANGER Hazardous voltage. Contact with hazardous voltage will cause death or severe personal injury. Follow all locally approved safety procedures when working around highand low-voltage lines and equipment. G103.3 WARNING Before installing, operating, maintaining, or testing this equipment, carefully read and understand the contents of this manual. Improper operation, handling or maintenance can result in death, severe personal injury, and equipment damage. G101.0 WARNING This equipment is not intended to protect human life. Follow all locally approved procedures and safety practices when installing or operating this equipment. Failure to comply can result in death, severe personal injury and equipment damage. G102.1 WARNING Power distribution and transmission equipment must be properly selected for the intended application. It must be installed and serviced by competent personnel who have been trained and understand proper safety procedures. These instructions are written for such personnel and are not a substitute for adequate training and experience in safety procedures. Failure to properly select, install or maintain power distribution and transmission equipment can result in death, severe personal injury, and equipment damage. G122.2 iv

Product information Introduction Service Information MN280030EN provides installation instructions for Eaton s Cooper Power series Types D and DV reclosers. Prior to the installation or calibration process, carefully read and understand the contents of this manual. Read this manual first Read and understand the contents of this manual and follow all locally approved procedures and safety practices before installing or operating this equipment. Additional information These instructions cannot cover all details or variations in the equipment, procedures, or process described nor provide directions for meeting every possible contingency during installation, operation, or maintenance. For additional information, contact your Eaton representative. Quality standards ISO 9001 Certified Quality Management System Acceptance and initial inspection Each recloser is completely assembled, inspected, tested, and adjusted at the factory and is filled to the correct level with insulating fluid. It is in good condition when accepted by the carrier for shipment. Upon receipt of a recloser: 1. Inspect the recloser thoroughly for damage and loss of parts or fluid incurred during shipment. If damage or loss is discovered, file a claim with the carrier immediately. 2. Check for fluid leakage and tighten all bolts that may have loosened during shipment, especially the bolts attaching the head to the tank. Handling and storage Be careful during handling and storage of the time-delay unit to minimize the possibility of damage. If the unit is to be stored for any length of time prior to installation, provide a clean, dry storage area. Handling and storage If the recloser is to be stored for an appreciable time before installation, provide a clean, dry storage area. Locate the recloser so as to minimize the possibility of mechanical damage, particularly the bushings. Description Types D and DV reclosers sense and interrupt fault currents on single-phase lines of distribution systems. The recloser automatically recloses and restores service if the fault is temporary. If the fault is permanent, the recloser locks open after the second, third, or fourth interruption depending upon its setting. The recloser may be made non-reclosing (locks open after the first interruption) by actuating an external lever. Sensing of fault currents is provided by a trip coil which is connected in series with the recloser contacts and can carry its rated line current. Continuous current and minimum trip values of the recloser can be changed by changing the coil. Contact closing energy, as well as energy to charge the opening springs, is supplied by a high-voltage closing solenoid which is connected phase-to-ground on the source side of the recloser. A low-voltage closing solenoid, which is energized by an auxiliary AC or DC low-voltage source, is also available. The opening sequences of the recloser can be all fast, all retarded, or a combination of both. In addition, one of four different time-current characteristics is available for the retarded opening sequences (Figure 1). WARNING Do not operate this equipment if energized parts are not immersed in dielectric fluid. Operation when parts are not properly immersed in dielectric fluid may result in internal flashovers that will damage the equipment and can cause death or severe personal injury. G104.4 Guarantee Performance guarantees shall be limited to correction by repair or replacement, at Eaton s option, of such equipment or components that may fail due to defects in material or workmanship within a period of one year from date of shipment. The guarantee is valid only if the recloser has been properly inspected upon receipt, properly installed,and has not been subjected to abnormal conditions. The company will not, however, be liable for consequential damages or any expenses incurred in installation or transportation. 1

Figure 1. Types D and DV time-current characteristics, 100-amp coil. 2

Specifications and ratings Table 1. Basic Recloser Data Description Type D Type DV Nominal voltage (kv) 2.4-14.4 24.9-34.5 Maximum design voltage (kv) Impulse withstand (BIL), 1.2 x 50 microsecond wave, crest (kv) 15.5 110 38 150 60-hz, withstand (kv rms) Dry, one minute Wet, ten seconds 50 45 70 60 Maximum continuous current (amps) 560 560 Reclosing time (seconds) 2 2 Bushing creepage distance (inches) 115/8 17 Table 2. Minimum Trip and Interrupting Ratings Trip Coil Minimum Interrupting Ratings (rms symmetrical apps) Ratings Continuous amps Trip Ratings (amps) Types D @4.8 kv @8.32 kv @14.4 kv Type DV @24.9 34.5kv 100 200 6000 6000 6000 6000 140 280 8400 8400 8400 8000 160 320 9600 9600 9600 8000 185 370 11100 10000 10000 8000 225 450 12000 10000 10000 8000 280 560 12000 10000 10000 8000 400 800 12000 10000 10000 8000 400x 560 12000 10000 10000 8000 560 1120 12000 10000 10000 8000 560x 750 12000 10000 10000 8000 Dimensions and weights Figure 2 shows the essential dimensional information for the Types D and DV reclosers, along with weights and fluid capacities. Weights and Fluid Capacities Type D Type DV Weight, dry (lb) 210 255 Weight, with fluid (lb) 360 480 Fluid capacity (gal) 20 30 Figure 2. Dimensional Information. 3

Operating levers and indicators The operating levers and indicators for the reclosers are located under the sleet hood (Figure 3). This handle is trip-free. If the recloser is closed against a fault, it will continue to trip and reclose until the handle is allowed to drop to the open position. Non-reclosing lever The non-reclosing lever provides the recloser with the capability of locking out on the first trip operation for added safety during downline, hot-line work. This lever is also hookstick operated. Contact position indicator The red flag is coupled to the recloser mechanism and shows the position of the main contacts. When the flag is down, the main contacts are open; when the flag is up, the main contacts are closed. Operations counter A three-digit counter which records all trip operations is located under the sleet hood. Figure 3. Operating levers and indicators. Manual operating handle The manual operating handle (painted yellow) permits manual opening and closing of an energized recloser. Pulling down the handle trips and locks open the main contacts of the recloser. Lifting up the handle closes the closingcoil contactor and, if the closing circuit is energized, the closing coil will close the main contacts. The handle can be operated with a hookstick. Closing solenoid The recloser is closed by a high-voltage solenoid connected phase to the solid multi-grounded neutral. The solenoid coil must be replaced if the recloser is to be operated at a voltage other than that shown on the nameplate. Low-voltage d-c coils (125 or 250 volts) are available for the closing solenoid. Rectifier kits to operate the d-c coils from a 120 or 240 Vac source, as applicable, are also available. Electrical power for low-voltage closing is supplied through a connector mounted on the recloser head. Connection diagrams for the various modes of operation are shown in Figure 4. Figure 4. Recloser connection diagrams. 4

Figure 5. Operations to lockout and sequence selection. Adjustments The operating characteristics of the Types D and DV reclosers are preset and tested at the factory and are stamped on the nameplate. However, if the recloser is relocated or the coordination scheme is modified, these characteristics can be easily changed in the field. The adjustments are accessible under the head casting after the tank has been lowered. Operations to lockout The recloser can be set for 2, 3, or 4 operations to lockout. The lockout lever assembly is shown in Figure 5. To set operations to lockout, index the lever to the slot corresponding to the number of operations desired. Number of fast operations The tripping sequence to lockout can be all fast, all retarded, or a combination of fast operations followed by retarded operations. To set the number of fast operations (0, 1, 2, 3, or 4), depress the spring-loaded sequence selector cam (Figure 5) to disengage the indexing pin. Move the cam until the desired number of fast operations is opposite the arrow point. Be sure the indexing pin is seated when the cam is released. Setting the fast operations also determines the number of retarded operations that will remain in the total operating sequence. For example, if the recloser is set for four total operations to lockout and the sequence setting is made at 2F, two retarded operations remain in the operating sequence. 5

Retarded-timing characteristics Retarded-timing characteristics are determined by the sealed hydraulic time-delay unit shown in Figure 6. To insure reliable timing, the time-delay unit operates with special aircraft hydraulic fluid, which is about four times less subject to temperature changes than transformer fluid. Two separate time-delay units are available; each provides two retarded time-delay characteristics. Thus, it is necessary to select one unit for B and C time-current curves or the other for D and E curves. The time-current curves for the various trip-coil ratings are shown in R280-91-4, Types D and DV Reclosers Time-Current Curves, pages 1 through 10. To change the retarded time characteristic of the time-delay unit, loosen the thumbscrew, index the desired marked adjustment bracket hole to the protruding pin on the timedelay unit, and then retighten the thumbscrew. Figure 6. Adjustments of time-delay unit to change time-current characteristics. 6

Installation and operation Preliminary checks Before installing the recloser, check for proper fluid level. With the mechanism removed from the tank, the fluid level should be: Type D Recloser...3-1/2 inches from top of tank Type DV Recloser...2-1/4 inches from top of tank If the recloser has been stored for any length of time, the dielectric strength of the fluid should be checked. See Reference Bulletin R280-90-1, Oil Specifications and Test, for test procedures and acceptable test values. Fluid that does not meet specifications should be refiltered or replaced. Figure 7. Dimensions for direct pole mounting. 7

Mounting hardware Direct mounting The Types D and DV reclosers can be mounted directly on a pole or substation structure as shown in Figure 7. Mounting hardware is to be furnished by the customer. Two sets of mounting plates are furnished with each recloser. For direct pole mounting, the curved plates are installed between the pole and the mounting brackets of the recloser. For mounting on a substation truss or a polemounted channel, add the flat adapter plates between the curved plates and the mounting surface. Figure 8. Location and position of curved mounting plates used for direct pole mounting. Cluster mounting Three Type D reclosers can be mounted on a pole with the aid of a cluster rack as shown in Figure 10. Use both the curved mounting plates and the flat adapter plates when mounting the reclosers to the rack. Hardware for mounting the reclosers to the rack is provided with the rack. Hardware for mounting the rack to the pole is to be furnished by the customer. It is recommended that the reclosers be assembled to the rack on the ground, and the entire assembly hoisted and secured to the pole. Lifting When lifting the recloser for mounting or any other purpose, follow approved safety practices with lifting methods and equipment. Lift the load smoothly and do not allow it to shift. The single lifting lug provided on the recloser is intended for vertical lifting of the recloser only. Lifting of attached frames or other equipment by means of the recloser lifting lug reduces the designed safety factor is not recommended. Figure 9. Add flat adapter plates on curved plates for flat channel mounting. 8

Figure 10. Dimensions for cluster mounting. 9

Main wiring It is desirable to provide the recloser with bypass switches and surge protection as shown in Figure 11. Surge protection on both sides of the recloser is advisable. However, if protection is provided on only one side, it should be located on the source side for line installations and on the load side for substation installations. Connect the primary leads to the recloser in accordance with head-casting markings, SOURCE and LOAD. To facilitate connection, the cover of the recloser can be rotated in 60-degree increments with respect to the tank and its mounting. The universal clamp-type terminals accept no. 1/0 through 500 MCM conductors. To furnish operating energy to the high voltage closing solenoid, the ground terminal on the top of the cover casting must be connected to the multi-grounded neutral of the system. This also is a universal clamp type terminal and has a conductor range of no. 8 solid to no. 2/0 stranded. Operating energy for the low-voltage closing accessory is furnished through a two-pin receptacle and plug mounted on the recloser head. The outer portion of the plug is a weather-proof cable grip for 9/16 to 5/8-inch-oaf cables. For AC low-voltage closing, the solenoid coil draws 35 amps at 120 volts and 23 amps at 240 volts. Since the coil is energized for only a few cycles during each reclosing operation, voltage drop in the cable rather than thermal rise is of primary concern. Initial operation With the recloser connected as shown in Figure 11, close the source-side disconnect switch. Move the yellow manual operating handle under the sleet hood to the CLOSE position as indicated on the head cover. The recloser should immediately close. Close the load-side disconnect switch and open the bypass switch. The recloser is now in service. To remove from service, close the bypass switch and open the disconnect switches. NNote: For low-voltage closing, make sure that the auxiliary power is available at the recloser before starting the above procedure. Manual operation To manually operate an energized Type D or Type DV recloser involves only a hookstick engagement of the yellow operating handle located under the sleet hood. When the handle is pulled down, the mechanism is tripped to open the main contacts. When the handle is pushed up, the closing solenoid is energized to latch the main contacts in the closed position. A manual closing tool is available for closing a de-energized recloser. Remove the pipe plug on the side of the cover casting to provide access for the reclosing tool to engage the main operating shaft of the recloser mechanism. A de-energized recloser is tripped open merely by pulling down the yellow operating handle. Figure 11. Suggested connection diagram, high-voltage closing. 10

Figure 12. Manual closing tool of de-energized recloser. Non-reclosing operation When the non-reclosing lever has been manually pulled down into the non-reclosing position, any current over minimum trip rating will automatically lock open the recloser on the first trip operation instead of cycling through the normal operating sequence. This immediate lockout protection is especially desirable for hot-line work in the higher load density areas served by the Types D and DV reclosers. The non-reclosing lever does not interfere with manual recloser operation. The recloser can be opened or closed manually regardless of the position of the non-reclosing lever. 11

Testing Types D and DV reclosers are carefully tested and adjusted at the factory to operate according to the published data. Well equipped test facilities, a detailed testing procedure, and trained personnel assure accurate calibration. Permanent records are kept of each recloser s test performance. Thus, each recloser leaves the factory ready for installation, and preinstallation testing is not necessary. However, should verification of recloser operation prior to installation be desired, the following characteristics can be checked: 1. Number of operations to lockout. 2. Number of fast openings. 3. Satisfactory operation of closing solenoid. 4. Minimum trip current. 5. Reclosing time. The test findings should concur with the information shown on the data plates and nameplates located on the sleet hood. The application of the Types D and DV reclosers equipped with high-voltage closing is limited to wye systems with a multi-ground neutral; therefore, the test connections must simulate field application with the phase-to-ground-neutral connection. The recloser can be test tripped with a low voltage AC source but, for automatic closing, a high-voltage AC source is required. For personnel safety, the recloser and high voltage transformer should be enclosed in a test cage to prevent accidental contact, and all grounding precautions should be observed. All metering and measuring equipment should be located outside of the test cage. WARNING Do not operate this equipment if energized parts are not immersed in dielectric fluid. Operation when parts are not properly immersed in dielectric fluid may result in internal flashovers that will damage the equipment and can cause death or severe personal injury. G104.4 NNote: For reclosers equipped with low-voltage closing, the elaborate high-voltage shielding is not required. However, good, sound testing practices and precautions should be followed. Test equipment required A suggested test circuit is shown in Figure 13. The following equipment is required for this circuit: 1. For reclosers equipped with high-voltage closing: At least four standoff insulators with a platform of wood or bakelite to provide isolation so that the tests can be performed with both high- and low-voltage sources connected to a common ground at the source side terminal. Standoff insulator ratings should be above the ratings of the closing coil. 2. Variable autotransformer 240 volts, 20 amps. 3. Low-voltage transformer T2 Ratio and kva size depend upon size of recloser trip coil and maximum current to be used. 4. Ammeter Full-scale deflection should be at least 300% of reclosing rating. Use of current transformer may be required. 5. Cycle counter or other timing device. 6. For high-voltage closing,transformer T1. Low-side rating should equal voltage of available test source. High-side source equal voltage rating of recloser. IMPORTANT A 50 kva transformer having an impedance of about three percent will be satisfactory if the source impedance is reasonably low, the recloser may not be able to latch closed is a smaller transformer is used. Equally important, the transformer supply must be capable of delivering the required power. Be sure that minimum allowable voltages shown in Table 3 can be maintained at recloser terminals during the two- to five-cycle interval the closing solenoid is energized. 7. For low-voltage closing, substitute an appropriate source of power for Transformer T, and connect to the receptacle mounted on the head casting. A 5 kva source generally is adequate. 12

Figure 13. Suggested test diagram, low-voltage tripping high-voltage closing. 13

Table 3. Closing Solenoid electrical constants and Minimum Voltage Closing Solenoid Rating (kv) Voltage Code No. DC Resistance (ohms) 2.4 21 8 2040 4.16-4.8 22 30 3536 7.2-7.62 23 83 6120 8-8.32 24 94 6800 11.5 25 206 9770 14.4 27 324 12340 20.0 29 573 17000 Test procedure - electrical closing Min. Allowable Voltage at Recloser When Solenoid is Energized (volts) Operation of closing coil Assemble and connect the equipment as shown in Figure 13. Trip the recloser manually and then move the manual operating handle to the CLOSE position. Energize the closing solenoid (T, or low-voltage source). The recloser should close immediately, indicating correct operation of the closing solenoid. Minimum trip current With the recloser closed, slowly raise the variable autotransformer voltage and note the ammeter reading. As the trip coil plunger starts to move, the trip-coil impedance will rise and cause a decrease in current. The maximum reading before the current decreases is the minimum trip current. Operating sequence and reclosing time With the recloser closed and the variable autotransformer set high enough to cause the recloser to operate readily (300% of rated trip-coil current is suggested), energize the low-voltage tripping circuit. The number of fast operations and the number of operations to lockout can be checked by observing the operation of the red contact position indicator located under the sleet hood. Reclosing time can be read from the timing device arranged to record the period during which current is not flowing. Test procedure - manual closing The closing tool (Figure 12) permits manual closing of the main contacts for test purposes when a high-voltage source for closing is not available. The minimum trip current and operating sequence can be verified in this manner. To close the recloser manually, remove the pipe plug in the head casting and insert the manual closing tool to engage the main lever-and-shaft assembly of the head mechanism. Turn the tool clockwise to close the contacts. The tool is trip-free operating. Be sure to replace the pipe plug before placing the recloser into service. Minimum trip current Connect the low-voltage tripping source to the recloser as shown in Figure 13. (Since high-voltage closing is not used, the high-voltage isolation and shielding are not required.) Close the recloser with the manual closing tool and slowly raise the voltage of the variable autotransformer while observing the ammeter reading. As the trip-coil plunger starts to move, the trip-coil impedance will rise and cause a decrease in the current. The maximum reading before the current decreases is the minimum trip current. Operating sequence With the variable autotransformer set high enough to cause the recloser to operate readily (300% of rated trip-coil current is suggested), close the recloser with the manual closing tool. The recloser will trip. In approximately two seconds, the closing solenoid contactor will reclose (indicated by an audible click). Immediately close the recloser manually for the next trip operation. When lockout is reached, the yellow operating handle under the sleet hood will drop down and the manual reclosing mechanism will become inoperative. NNote: It is important to manually close the recloser immediately after the closing solenoid contactor closes. otherwise, the additional time may cause the resetting mechanism to allow one or more extra tripping operations before lockout is reached. 14

This page is intentionally left blank. 15

! SAFETY FOR LIFE Eaton 1000 Eaton Boulevard Cleveland, OH 44122 United States Eaton.com Eaton s Cooper Power Systems Division 2300 Badger Drive Waukesha, WI 53188 United States Eaton.com/cooperpowerseries 2015 Eaton All Rights Reserved Printed in USA Publication No. MN280030EN KA2048-009 Rev. 1 Eaton is a registered trademark. All trademarks are property of their respective owners. For Eaton's Cooper Power series product information call 1-877-277-4636 or visit: www.eaton.com/cooperpowerseries.