DIN Rail UPS Model: DIN-UPS 48-5 Installation/Operation Manual

Similar documents
DIN Rail UPS Model: DIN-UPS Installation/Operation Manual

DIN Rail UPS DC UPS/Battery Detection System Model: BDS-DIN-UPS Installation/Operation Manual

DIN Rail UPS Model: DIN-UPS Installation/Operation Manual

READ AND FOLLOW ALL SAFETY INSTRUCTIONS! SAVE THESE INSTRUCTIONS!

DIN Rail DC UPS DC UPS/Battery Detection System Model: BDS-DIN-UPS Installation/Operation Manual

DIN-Rail DC UPS. Powers Loads and Charges Back-Up Battery, Ideal for Automation and Wireless System Transmitter Applications

User s Manual. Automatic Switch-Mode Battery Charger

Art. No. EC-315. Art. No. EC-330. Art. No. EC-340 SWITCH-MODE BATTTERY CHARGER CONTENTS IMPORTANT SAFETY PRECAUTIONS... 2

Power Distribution System User s Manual. Model: PDS-100

User Manual. Solar Charge Controller 3KW

Solar Hybrid Power Generating System CPS1200EOH12SC CPS2200EOH24SC CPS3000EOH24SC. User s Manual K01-C

INSTRUCTION MANUAL CAUTION

AUTO CHARGE 4000 MODEL #: LOW PROFILE CHARGER AUTOMATIC DUAL OUTPUT BATTERY CHARGER INSTRUCTION MANUAL

CBI All in One DC UPS Power Solutions

All In one uninterruptible power supply solutions

Pure Sine Wave Inverter Charger

AC CONVERTER / BATTERY CHARGER

PUMP PLUS 1200 MODEL #: AUTOMATIC SINGLE OUTPUT BATTERY CHARGER INSTRUCTION MANUAL

LPC 20 MODEL #: LOW PROFILE CHARGER AUTOMATIC SINGLE OUTPUT BATTERY CHARGER INSTRUCTION MANUAL

LPC 40 MODEL #: LOW PROFILE CHARGER WITH PLC AUTOMATIC SINGLE OUTPUT BATTERY CHARGER INSTRUCTION MANUAL

AUTO CHARGE 3 STEP AUTOMATIC BATTERY CHARGER

LC BATTERY CHARGER OPERATION & MAINTENANCE GUIDE

AUTO CHARGE LPC SERIES

Intelligent Charging System Series

CX-SERIES ADVANCED BATTERY CHARGER

PUMP PLUS 2000 PLC MODEL #: PP AUTOMATIC DUAL OUTPUT BATTERY CHARGER INSTRUCTION MANUAL

SOLAR LIGHTING CONTROLLER SUNLIGHT MODELS INCLUDED IN THIS MANUAL SL-10 SL-10-24V SL-20 SL-20-24V

Innovative Circuit Technology Ltd.

SECTION DC POWER SUPPLY/BATTERY CHARGER

SAVE THESE INSTRUCTIONS

SMT. Installation and Operation Manual. Model:SMT WITH MPPT TECHNOLOGY

User Manual Solar Charge Controller 3KW

PUMP PLUS 1000 PLC MODEL #: PP AUTOMATIC SINGLE OUTPUT BATTERY CHARGER INSTRUCTION MANUAL

ST - II Series POWER SUPPLIES USER INSTRUCTIONS

BBC-3140 USER MANUAL DC-DC CHARGER / BATTERY EQUALIZER / VOLTAGE REDUCER

Document: PRODSPEC-140 Revision: G DCN No Date: October 1, 2014 Product: 10-amp EnerGenius NRG Battery Charger

Eclipse Solar Suitcase

IV. PROOF OF PURCHASE: A warranty claim must be accompanied by proof of the date of purchase.

User Manual 1.5KVA-3KVA INVERTER / CHARGER. Version: 1.1

BC-1230P/ 1240P/ 1260P Multi-Stage Battery Chargers User Manual

7 Stage Automatic Smart Battery Charger (FOR CHARGING 12V / 24V AGM, GEL,SLA AND WET BATTERIES) USER MANUAL

BC12M248 7 Stage Automatic Smart Battery Charger, Desulfator & Maintainer 12V, 2 / 4 / 8A FOR AGM, GEL AND WET BATTERIES USER MANUAL

User Manual SOLARMAX 1KVA/ 2KVA/ 3KVA INVERTER / CHARGER

Battery Care the new Battery Charger Philosophy Battery Charger and Battery Tester. Charge & Testing. Integrated Electronic Solutions

ACC Series Power Conditioner OPERATION & INSTALLATION MANUAL

SBC / 2140 / Stage Battery Charger User Manual

User Manual 4KVA/ 5KVA INVERTER / CHARGER. With MPPT Controller

VC-4820 Programmable DC-DC Converter with Battery Charger function USER'S MANUAL

Installation Instructions

AUTO CHARGE DUAL MODEL #: AUTOMATIC DUAL OUTPUT BATTERY CHARGER INSTRUCTION MANUAL. Ph: Fax:

OD10 10A Outdoor Solar Charge Controller

User Manual 1KVA/ 2KVA/ 3KVA INVERTER / CHARGER

Instruction Manual. Duo-battery Solar Panel Controller EPIP20-DB series For Both 10 and 20 amp. Controllers (for use with solar panels only) + -

Duo Battery Charge Controller

GXSeries. User Guide DANGER

CX Series User s Manual

User Manual 1KVA-5KVA INVERTER / CHARGER

The Power of Reliability INSTRUCTION MANUAL

HPP1 MK6-15A/20A R00 Owners Manual

IMPORTANT SAFEGUARDS READ THIS MANUAL AND FOLLOW ALL SAFETY INSTRUCTIONS THOROUGHLY BEFORE OPERATING THE EMIU INVERTER SYSTEM SAVE THESE INSTRUCTIONS

TP-BC AC to DC24V UNINTERRUPTED POWER SUPPLY User Manual. DC power output 8A Charge current 7.5A

User Manual 1KVA-5KVA INVERTER / CHARGER

Advanced Battery Charger 0 ~ 15A 0 ~ 25A 0 ~ 35A 0 ~ 50A 0 ~ 80A. 3 - stage charging capability (IUOU) 90 ~ 264VAC (refer to de-rating curve)

BatteryMINDer 1500* & BatteryMINDer Plus 1510*

FUM-24xxCBP Series 3 Stage Battery Charger User Manual

Unity Low Voltage Disconnect & Monitor

Dycon D2430 EN54-4 Fire Alarm Power Supply Series

Solar Hybrid Inverter SP Efecto Series

AUTOMATIC BATTERY CHARGER

Installation Instructions

AUTOMATIC BATTERY CHARGER MODELS SEC A SEC A OWNER S MANUAL

MPPT Controller PVTS Series User Manual. User Manual. 800W-4000W Hybrid solar inverter. Version: 1.4

HPP1 MK5 Owner s Manual

AUTO CHARGE D PUMP PLUS

MDX-300 Series. For 12-volt automotive starting batteries and starting/charging systems INSTRUCTION MANUAL

BATTERY SAVER LOW RIPPLE HO

AUTO CHARGE 12 HO MODEL #: MODEL #: MODEL #: AUTOMATIC SINGLE OUTPUT BATTERY CHARGER INSTRUCTION MANUAL

User Manual Digital Energy Uninterruptible Power Supply ML Series UPS VA GE Digital Energy Power Quality

Battery Management Innovation. For 12-volt automotive starting batteries and starting/charging systems INSTRUCTION MANUAL

User Manual 1.5KVA-3KVA INVERTER / CHARGER

User manual. Solar Hybrid 1-5KVA. Uninterruptible Power Supply / Charger

1KVA/ 2KVA/ 3KVA/ 4KVA/ 5KVA MS, LV MPPT INVERTER / CHARGER. User Manual. Version: 2.3

Advanced Battery Charger. 3 - stage charging capability (IUoU) 25A

Special Specification 6058 Battery Back-Up System for Signal Cabinets

C.E. Niehoff & Co. C653/C653A and C625 Alternators Troubleshooting Guide NOTICE. Hazard Definitions. Battery Charge Volt and Amp Values

Specification of Soneil Battery Charger

A6Z OPERATING MANUAL

General Precautions. Personnel Precautions

VC-30 / VC-40 Programmable DC-DC Converter with Battery Charger function USER'S MANUAL

BE SURE POWER IS DISCONNECTED PRIOR TO INSALLATION! FOLLOW NATIONAL, STATE, AND LOCAL CODES! READ THESE INSTRUCTIONS ENTIRELY BEFORE INSTALLATION!

Manual Installation & Operation

Liebert PowerSure PSI UPS

AUTO CHARGE D2 MODEL #: AUTOMATIC TRIPLE OUTPUT BATTERY CHARGER INSTRUCTION MANUAL

Battery Chargers Sealed or Valve Regulated Lead Acid Batteries Model: PSC AP

R820 REV2 SERIES SCR POWER CONTROLS NOVEMBER 2017

Automatic taper of charge rate for superior battery life through good equalization of cells and low water use rate.

Cruising Charger Series OWNER S MANUAL

27.6 Vdc 1 Amp Switch Mode Power Supply for Fire EN54-4:1997 +A1 +A2

DC AC POWER INVERTER. LIV 10 / LIV 20 / LIV 30 User Manual

ST Charger. Industrial Battery Charger

Transcription:

DI Rail US Model: DI-US 48-5 Installation/Operation Manual Table of Contents Section age Section age Quick Start 2 1) General Information 4 Materials rovided 4 Optional quipment 4 2) Safety Information 4 3) Installation/Wiring 4 A) Mounting 4 ) Wiring 5 1. Input 5 2. Output 5 C) Alarm Contacts, Form C 5 D) Temperature Compensation Sensor 6 4) Settings 6 A) attery Type/Charge Curve 6 ) Time Charge Current Limit/attery Charge Level 7 C) System Setttings 7 5) Operation 8 A) Status Indicator LD s 8 ) LVD 9 6) rotection 9 7) Specifications 9 8) Troubleshooting 10 9) Warranty 10 1 M-DIUS485 AS OF 012216 Automation DC ower owering the etwork hone: 714-751-0488

Quick Start Guide Figure 1: Quick Start 1) 2) F C D 3) H A) Input: Wire Input lock (lettered left to right) a) Hot 230 V: no jumper installed across j1 & j2 Hot 115 V: wire jumper across j1 and j2 b) eutral c) arth Ground j1 & j2) Jumper these two inputs for 115 V operation See page 5 for details. ) attery Output: one terminal each for plus and minus. See page 5 for details. C) attery Charge Current Limit: Allows setting maximum current flow to battery during recharge cycle, use when low amp-hour batteries are applied to system to prevent overheating when recovering dead batteries. Adjustment range 20-100% of available charge current. (Available charge current = unit output rating of 10 amps - load demand. ote: the unit has a load priority circuit, all a b j1 j2 c A G produced power is made available to the load, remaining power is available for battery charging). See page 6 for details. D) attery Temperature Sensor (optional): lug in port (RJ-45). See page 6 for details. ) Output to Load: The unit has a load priority circuit, all produced power is made available to the load, remaining power is available for battery charging. See page 5 for details. F) Form C Contacts: Activate upon: a. power fail b. Low battery or poor battery condition See page 5 for details. Mounting DI DC USto DI Rail Removing DI DC US from DI Rail A A Twist Twist Insert flat head screwdriver in slot of bottom tab and twist to extend bracket 2 Automation DC ower owering the etwork hone: 714-751-0488

G) System Settings: via plug-in jumper programing terminals located on bottom of the unit. a. Install jumper per illustration below (Table 1) to: i. Select float voltage per attery Type and enable Absorption Charge (see page page 7 for details) ii. nable attery Test (Functional Setting) See page 7 for details on functional settings. H) Status Indicator LD s 1. Fail: Operating on battery back-up power (LD On). LD extinguishes when is present. 2. Low battery, or poor battery condition 3. Charger Output Status and Fault Mode Diagnosis: by blink code: Charge Status link Code: ulk: 5 blink/second - Recovery Absorption: 2 blink/second - ulk Float: 1 blink/second Fault Mode Diagnosis link Code: Reverse olarity: 1 blink, pause attery ot Connected: 2 blink, pause Overload or Short Circuit: 4 blink, pause ad attery Wire Connection, or ad attery (internal impedance): 5 blink, pause ad Thermal Sensor: 7 blink, pause and diagnostic See page 8 for details. Table 1: System Settings: attery Selection/Absorption Charge and Functional Settings attery Type Selection Float Charge/ Jumper Insert osition Absorption Charge nable/ Jumper Insert osition Open Lead (Default) one os. 5 53.5 VDC Sealed Lead Low Insert Jumper: os. 1 os. 1 os. 5 54.0 VDC Sealed Lead High Insert Jumper: os. 2 os. 2 os. 5 54.5 VDC Gel attery Insert Jumper: os. 3 os. 3 os. 5 55.2 VDC * ote: voltages above are at 20 C with no battery temp. sensor connected. Function Setting attery Test O Insert Jumper: os. 4 os. 4 Insert jumper at position 4 to enable eriodic attery condition test process. (Fault reported by LD diagnosis blink code, see Table 6): attery wiring connection attery efficiency/sulfation (impedance test) Shorted Cell 3 Automation DC ower owering the etwork hone: 714-751-0488

1) General Information This DI rail mount DC US Combines all system power functions: power supply, battery charger, US circuitry and status monitoring in one compact unit that produces 48 volt, 5 amps allocated via outputs for load and battery: Load output: load priority distribution ensures power is dedicated fi rst to the load, with remainder then allocated to battery charging, thus preventing a discharged battery from impacting operation of critical loads. attery output: 3 step charging for rapid battery recovery, programmable for battery type, with optional temperature compensation sensor attery automatically on line to support load anytime fails Low voltage disconnect protects battery from total discharge Automatic periodic battery health diagnosis High operating temperature range to 70 C Alarm contacts: fail, battery status/condition Materials rovided: 1 ea. DI-US unit with integral DI rail mount clip 3 ea. Jumper tabs for programming 1 ea. Jumper wire (orange) for 115 volt input operation Optional quipment: Temperature Compensation Sensor, /: 468-4510-0 2) Safety Information WARIG xplosion Hazard. Do not disconnect loads or battery unless input and battery have been switched off. WARIG xplosion Hazard. Substitution of components may impair suitability for class I, Division 2. WARIG Switch off or remove input and battery power before wiring the DI-US 48-5. ever work on the DI US when it is connected to input and battery. The DI US must be installed in accordance with UL508 or local electrical codes depending upon the application. The DI US should have a suitability sized input circuit breaker feeding its input. See specification section for maximum input draw for your input voltage for circuit breaker sizing. CAUTIO: Hot surface. Avoid touching the DI US case while operating at or near its full load capacity. Remove and battery power and allow DI US at least 10 minutes to cool before removing from DI Rail. 3) Installation/Wiring A) Mounting: The unit is designed for 35 mm DI rail mounting in an enclosure and relies on convection (free air) cooling, thus must have a minimum vertical and horizontal distance to adjacent surface of 4 (10 cm) to this power supply in order to assure suffi cient air flow. ote, that depending on the ambient temperature and load of the device, the temperature of the case can become hot to the touch. The unit is designed for vertical mount (+/- 5 ) and has an integral clip on the back to secure it to the rail. To mount, place the top tabs over the top of the DI rail, and using a long slotted screw driver insert it in the groove at the bottom of the bracket and twist which will extend the spring loaded mounting bracket downward allowing the unit to be positioned against the DI rail, release the bracket with DI US positioned vertically and the rail will be captured and the unit secured. Figure 2: Mounting Figure 3: Removing A A 4 Insert flat head screwdriver in slot of bottom tab and twist to extend bracket Twist Twist Insert flat head screwdriver in slot of bottom tab and twist to extend bracket Automation DC ower owering the etwork hone: 714-751-0488

) Wiring 1. Input: Terminal lock (lettered left to right) - Figure 4 a) Hot (note: install jumper provided across terminals O j1 and j2 for 115 V input) b) eutral c) arth Ground j1 & j2) Jumper these two terminals for 115 V operation and apply 115V hot to term a and neutral to b Recommended wire size: 16 AWG Figure 4: Input Terminal lock T M R, CA USA IUTS L Jumper FOR 115 Vac a b j1 j2 c 2. Output The unit has two outputs: one connects to the Load and the other to the back-up battery. ote: the unit has a load priority circuit, all produced power fi rst is made available to the load with remaining power made available for battery charging. The DI US is isolated from the case, thus you may apply to a positive or negative ground system. attery Output: See page 3, Section G for programming per battery type. Figure 5: Output Terminals Load Output attery Output Output to Load: terminals for plus and minus. 1 2 3 4 5 6 7 8 9 10 Fuse note: We recommend a 15 amp fuse be installed on the hot leg at battery. OUT LOAD ATTRY LOW ATTRY OR ATTRY RLMT attery/output wires size (recommended): 16 AWG Terminal lock maximum wire size (recommended): 10 AWG C) Alarm Contacts, Form C (Isolated): i LOW ATTRY OR ATTRY RLMT DIAGOSIS MI MAX ATTRY CHARGIG LVL T M R O Form C Contacts for remote monitor: Activate upon: a. Main or back up power fail b. Low battery, or poor battery condition, CA USA L IUTS Jumper FOR 115 Vac DI-US 48-5 IUT: 115-230Vac OUTUT: 48Vdc 5A 5 Automation DC ower owering the etwork hone: 714-751-0488

Table 2: Alarm Contacts Contact Input 5-6 5-7 8-9 8-10 Relay Contact Rating: Max. DC: 30 VDC, 1 amp; : 60 V, 1 amp: Resistive load ( 60947-4-1) Min.1mA at 5 VDC D) Optional attery Temperature Compensation Sensor /: 468-4510-0 To install, remove the access tab in the front panel decal labeled AUX 1, install the Temp. Sensor into the RJ-45 connector. Attach 2 L sensor to side of battery using RTV silicone. 6 7 8 9 10 The sensor will vary the battery charging voltage OUT depending ATTRY on the battery s temperature and charge program setting. LOAD Table 3: Absorption Charge Voltage & Float Charge Voltage Settings MI MAX ATTRY Float Voltage = Voltage @ 20 C - ( Sensor DIAGOSIS Temp - 20 ) x.003 x CHARGIG number of LVL cells) Fast Charge = Voltage @ 20 C - i( Sensor Temp - 20 ) x.005 x number of cells) 1 2 3 4 g. Sensor Temp = 60 OUT ATTRY Voltage @ 20 = 53.5 (Open Lead) LOAD attery Cells = 24 Float: 50.64V = 53.5V - (40 x.003 x 24) If the battery temperature is less than -20 C or greater than +60 C, an outside its range (temp. sensor) alarm is signalled T with code 7 blink. M LOW ATTRY OR ATTRY RLMT If the sensor is not connected or if the sensor is defective, the LD Low att will MIilluminate MAX and the R LD Diagnosis LD O ATTRY continues to show the status of the battery, i.e., trickle charge, fast charge DIAGOSIS or recovery CHARGIG LVL i charge., CA USA Jumper FOR 4) Settings Figure 115 Vac9: attery Type DI-US 48-5 IUTS A) attery Type/Charge Curve Charge curve per battery type: via programing jumpers insterted on bottom panel of unit right side. 1 Fail LD Using programming jumper tabs provided and a small needle nose pliers, insert programming jumpers to select float voltage and enable absorption voltage per battery type. Caution, do not program unit while connected to power. 6 2 Fault attery* LD 3 Diagnosis LD only closed open open closed off on 2 link-ause + att closed open closed open off off 1 link/sec att only open closed closed open on off off Low att open closed open closed on on off * Labeled Low attery or attery Replacement on Front anel LOW ATTRY OR ATTRY RLMT L, CA USA L IUTS DIAGOSIS LOW ATTRY OR ATTRY RLMT Figure 8: attery Temperature Sensor Access Tab Access Tab Figure 6: Alarm Contacts Terminals, Form C (Isolated) Figure 7: Status Indicator LDs 1 3 1 2 3 4 OUT LOAD ATTRY, CA USA 5 6 7 8 9 10 Jumper FOR 115 Vac IUTS IUT: 115-230Vac OUTUT: 48Vdc 5A Jumpers 5 6 7 8 9 10 Jumper FOR 115 Vac i T M R O LOW ATTRY OR ATTRY RLMT DI-US 48-5 IUT: 115-230Vac OUTUT: 48Vdc 5A DI-US LOW ATTRY 48-5 OR ATTRY RLMT IUT: 115-230Vac OUTUT: 48Vdc 5A 1 2 3 4 OUT LOAD Insert jumper tabs for battery selection on bottom panel. T M R O LOW ATTRY OR ATTRY RLMT L 26.76 VDC ATTRY, CA USA IUTS MI C Automation DC ower owering the etwork hone: 714-751-0488

Table 4: attery Selection/Absorption Charge attery Type Selection Float Charge/ Jumper Insert osition Absorption Charge nable/ Jumper Insert osition Open Lead (Default) one os. 5 53.5 VDC Sealed Lead Low Insert Jumper: os. 1 os. 1 os. 5 54.0 VDC Sealed Lead High Insert Jumper: os. 2 os. 2 os. 5 54.5 VDC Gel attery Insert Jumper: os. 3 os. 3 os. 5 55.2 VDC * ote: voltages above are at 20 C with no battery temp. sensor connected. ) attery Charge Current Limit/attery Charge Level Allows setting maximum current flow to battery during recharge cycle- use when low amp-hour batteries are applied to system to prevent overheating when recovering dead batteries. Adjustment range 20-100% of available charge current. (Available charge current = unit output rating of 10 amps minus load demand. ote: the unit has a load priority circuit, all produced power is made available to the load, remaining power is available for battery charging). To set, use small slotted screw driver to rotate selector dial. Set dial between 10 to 20% of battery capacity (Amp Hours). Figure 10: Current Limit/attery Charge Level - Dial C) System Settings Via plug-in jumper programing terminals located on bottom right of the unit. Install jumper per illustration below to nable attery Test. Table 5: Functional Settings Function Setting attery Test O Insert Jumper: os. 4 os. 4 Insert jumper at position 4 to enable eriodic attery condition test process. (Fault reported by LD diagnosis blink code, see Table 6): attery wiring connection attery efficiency/sulfation (impedance test) Shorted Cell 7 Automation DC ower owering the etwork hone: 714-751-0488

5) Operation A) Status Indicator LD s 1. ower source: Mains or back up i. OK ( Fail LD Off) or ii. Fail: Operating on battery backup power (LD On) red 2. Low battery, or battery replacement LD illuminates when: Low attery (capacity less than 30%) ad connection to battery attery requires replacement 3. Diagnosis LD. Charger output status system diagnosis and Fault mode diagnosis: by blink code (Table 6 below). Figure 11: Status Indicator LDs 1 2 3 i LOW ATTRY OR ATTRY RLMT DIAGOSIS FA Table 6: Status Indicator LDs Monitoring Control State LD Diagnosis (o.8) LD attery Fault o.7) Float 1 link/sec OFF Charging Type Absorption 2 link/sec OFF, CA USA ulk 5 link/sec OFF IUTS Reverse polarity or 1 link/pause* O high battery Voltage L attery ot connected, 2 link/pause O no output power attery shorted cell 3 link/pause O Over Load or short 4 link/pause O circuit on the load ad battery; Internal 5 link/pause O impedance ad or ad battery wire connection attery Life test not 6 link/pause O possible Temp. Sensor outside 7 link/pause O System Auto Diagnosis its range oost condition; battery 8 link/pause O discharge after 4 min. of overload. Internal fault 9 link/pause O Low battery detected 10 link/pause O when system activated by battery start button with no ac input Life test not possible; 12 link/pause arallel mode on Slave Device ad battery wire connection; arallel mode on Slave Device 13 link/pause * ause: 1 Second Jum 11 8 Automation DC ower owering the etwork hone: 714-751-0488

) LVD) The unit contains a low voltage load disconnect that activates at 36 volts (1.5 vpc) which is factory set and cannot be user modified. 6) rotection On the Input: the device is equipped with an internal fuse. If the internal fuse is blown, it is most probable that there is a fault in the unit. If this occurs, the unit must be returned to the factory. On the DC Ouput attery and Load: The device is electrically protected. Reverse polarity: the module is automatically protected against reverse of battery polarity and connection of reverse polarity. Over current and output short circuit: the unit limits the output current. Low voltage disconnect protects battery from deep discharge. Thermal protection Operating temperature range -12 to 70 C. Unit will produce full rated power on continuous basis to 50 C, however; system load must be reduced by 2.5% per 1 for continuous operation above 50 C. If the temperature reaches 70 C, the unit will reduce its maximum output to approximately 50% of its rating. If the temperature exceeds 70 C, the unit will shut off and restart once temperature drops. 7) Specifications Input: Voltage: 90-135/ 180-305 47-63 hz Amperage: 3.3 @ 120 V / 2.2 @ 230 V Output: 48 volts, 5 amps total available to power loads and charge battery, with load priority distribution. eak: 15 amps 4 seconds (with battery power boost) Low Voltage Disconnect oint: 36 VDC Output ground isolated from case, may be used in positive ground applications. LVD function is lost Front anel LD Indicators: ower Source: operating on back up red LD attery and System Diagnostics (via blink code) Settings/Selectors: attery Type: AGM (Sealed Lead High), Sealed Lead (Low) Acid, Gel-Cell & Open Lead (Flooded Cell) attery Charge Current Limit: 20-100% of charge amperage rating Alarm Contacts (form C): Active: On back-up power/ Fail attery abnormal condition (summary contact): Discharged, damaged, disconnected, sulfated/short circuit, reverse polarity, bad thermal sensor Operating Temperature: -12 to 70 C. Continuous to 50, de-rate 2.5% per C >50 C Cooling: Free air convection fficiency: 83% Humidity: to 95%, to 25 C rotection: Low Voltage disconnect at 1.5 volts per cell (36 VDC) Internal fuse Current limiting Short circuit Reverse polarity Thermal overload shut down and recovery I 20 Designed to UL 1950 Terminal locks: Screw type Mounting: DI Rail racket 35 mm 9 Automation DC ower owering the etwork hone: 714-751-0488

8) Troubleshooting Symptom ossible Cause Corrective Action Section A. attery requires excessive re-charge time. Load turns off after a couple of seconds when running on battery C. o absoprtion voltage D. Unit does not turn on 1.Load at or near max. recommended load providing minimal current available for charging 2.Charging level current set to low 1.Time buffer set to incorrect position 2.atteries not charged, due to high load demand 1.Reduce load or split load between two separate DI US units 2.Adjust attery Charging Level control knob to higher level 1.Verify correct setting with manual 2.Reduce load or split load between two separate DI US units 1. Absorption jumper not installed 1. Install provided jumper in position 5 1. input is 115 V, no jumper wire installed 1. Install 115V jumper wire across j1 and j2. Trips input breaker 1. shorted to case 1. Verify correct input wiring 2. Defective unit 2. Contact technical service F. o output G. o voltage on battery output terminals 1. DC output wired backwards or shorted 1. Remove input and check DC wiring 2. o input 2. Verify correct input and jumper wire installed if powering from 115 V 3. xcessive temperature or blocked ventilation 3. Improve ventilation, unblock vent holes 4. Defective unit 4. Contact technical service 1. o battery installed (voltage 1. Install batteries required for battery output to turn on) 2. Missing or blown battery wiring fuse 2. Replace missing or blown battery wiring fuse H. Diagnosis LDs always blinking 1. ormal operation 1. Refer to Chart 2: Diagnosis Table 9) Warranty ewmar warrants that the DI-US 48-5 DI Rail US to be free from defects in material and workmanship for two years from date of purchase. If a problem with your DI-US 48-5, or if you have any questions about the installation and proper operation of the unit, please contact WMAR s Technical Services Department: hone: 714-751-0488 - From the hours of 7:30 a.m. to 5:00 p.m. weekdays,.s.t.; -mail: 10 Automation DC ower owering the etwork hone: 714-751-0488