Figure 1. Kearney Type HX cutout.

Similar documents
COOPER POWER SERIES. HX-CB loadbreak fuse cutout installation instructions. Fusing Equipment MN132011EN

COOPER POWER SERIES. K-Limiter back-up current-limiting fuse installation instructions. Fusing Equipment MN132010EN

S Fault Indicators. S.T.A.R. Type TPR Faulted Circuit Indicator Installation Instructions. Contents INSTALLATION PROCEDURES

S Voltage Regulators GENERAL. Contents. Acceptance and Initial Inspection. Handling and Storage. Standards

COOPER POWER SERIES. Surge arrester interchangeable fuse cutout combination installation instructions. Surge Arresters MN235004EN

COOPER POWER SERIES. UltraSIL polymer-insulated D-73P disconnect switches installation instructions. Switches MN008004EN

COOPER POWER SERIES. RTE EL-BAY-O-NET FUSE Re-Fusing Instructions. Fusing Equipment MN132024EN

COOPER POWER SERIES. 200 A loadbreak junction 15 and 25 kv class installation instructions. Loadbreak Connectors MN650015EN

Effective November 2016 Supersedes September 1998 (S )

COOPER POWER SERIES. S.T.A.R. Hot line voltage indicator installation instructions. Fault Indicators MN320011EN. Indicator boot.

COOPER POWER. SERIES ELF Current-Limiting Dropout Fuse Installation Instructions. Fusing Equipment MN132028EN. Pull ring. Housing

COOPER POWER SERIES. ELSG Full-Range Current-Limiting Fuse Re-Fusing Instructions. Fusing Equipment MN132017EN

Effective June 2016 New Issue

COOPER POWER. SERIES CMU Medium voltage power fuse installation instructions. Fusing Equipment MN132032EN

COOPER POWER SERIES. Edison Modular Fuse (EMF) Installation Instructions. Fusing Equipment MN132031EN

COOPER POWER SERIES. Expulsion fuse installation instructions. Capacitors MN230005EN. Effective November 2016 Supersedes November 2001 (S )

COOPER POWER SERIES. 600 A 15, 25, and 35 kv Class Cleer Loadbreak Bushing Insert Installation Instructions. Loadbreak/Deadbreak Connectors MN650016EN

COOPER POWER SERIES. Testing a motor capacitor on a voltage regulator procedure instructions. Voltage Regulators MN225064EN

Effective March 2015 Supersedes S August 2012

COOPER POWER SERIES. Current-Limiting Type NXC (C-Rated) Fuse Installation Instructions. Fusing Equipment MN132014EN

COOPER POWER SERIES. QD5 Quik-Drive tap-changer reversing neutral stationary contact asssembly kit A26 installation instructions

S Voltage Regulators PRODUCT INFORMATION GENERAL. Contents. Acceptance and Initial Inspection. Handling and Storage

Figure 1. HX cutout fuseholders. Positive Interruption

COOPER POWER SERIES. Pad-mounted Switchgear MN285019EN. Effective March 2017 Supersedes February 2007 (S )

S Voltage Regulators PRODUCT INFORMATION GENERAL. Contents. Acceptance and Initial Inspection. Handling and Storage.

COOPER POWER SERIES. 200 A Fused Loadbreak Elbow Connector Replacement Fuse Installation Instructions. Fusing Equipment MN132021EN

Figure 1. HX cutout fuseholders.

Effective November 2016 Supersedes February 2012 (S )

COOPER POWER SERIES. KA1169R Closing Coil Transfer-Switch Accessory Operation. Reclosers MN280069EN

COOPER POWER SERIES. S.T.A.R. type LVR faulted circuit indicator installation instructions. Fault Indicators MN320005EN

S Voltage Regulators GENERAL. PRODUCT INFORMATION Introduction. Contents. Acceptance and Initial Inspection. Handling and Storage.

This Kit Is for Use with Types RE, RVE, WE, WVE, VWE, VWVE27, and VWVE38 Reclosers.

COOPER POWER SERIES. KA662R tank-lifting windlass assembly and installation instructions. Recloser Mountings MN280071EN

COOPER POWER SERIES. Screened Separable Connectors MN650023EN. Effective October 2016 Supersedes March 2012 (IS )

COOPER POWER SERIES. High-voltage primary bushings installation instructions. OEM Equipment MN800008EN

COOPER POWER SERIES. Screened Separable Connectors MN650024EN. Effective October 2016 Supersedes March 2012 (IS )

High-voltage primary bushings installation instructions

Type NR oil switch installation and operation instructions

Installation and Operation

COOPER POWER SERIES. 600 A 15/25 kv class T-OP II connector assembly installation instructions. Deadbreak Apparatus Connectors MN650048EN

COOPER POWER SERIES. Types 4H single-phase and 6H three-phase vacuum interrupter conversion kits. Reclosers MN280014EN

COOPER POWER SERIES. Electronic control battery testing, charging, and replacement instructions. Reclosers MN280074EN

COOPER POWER SERIES. Dielectric grease application to recloser cable instructions. Reclosers MN280070EN

COOPER POWER SERIES. KA716L7001 adjustable control valve kit for Types L, E, 4E, V4E, and V4L reclosers installation and adjustment instructions

COOPER POWER SERIES. Manually-Operated M-Force Switch Installation and Operation Instructions. Switches and Disconnects MN008003EN

Effective May 2017 Supersedes December 2004 (S )

COOPER POWER SERIES. Mercury switch to microswitch retrofit kit KA349WE installation instructions. Reclosers MN280022EN

COOPER POWER SERIES. KA146W5 single pole-mounting hanger; KA146W2 tank lifting windlass assembly and installation instructions. Reclosers MN280039EN

Effective May 2017 Supersedes January 2003 (S )

GWI Rev. 1 October 2007 Supersedes Rev. 0 Dated February 2004

COOPER POWER SERIES. Fused loadbreak elbow connector installation instructions. Loadbreak Apparatus Connectors MN650014EN

Installation Instructions For Motor Control Center (MCC) Units

COOPER POWER SERIES. 600 A 15 kv and 25 kv class BT-TAP connector system installation instructions. Deadbreak Apparatus Connectors MN650004EN

COOPER POWER SERIES. Quick Connect Assembly (QCA) Retrofit Kit, General Electric Installation Instructions. Voltage Regulators MN225075EN

COOPER POWER SERIES. 600 A 35 kv class BT-TAP connector system installation instructions. Deadbreak Apparatus Connectors MN650003EN

Disconnect & ByPass Switches

KFE10010-E. Reclosers. Contents. Type KFVE and KFVME (27kV) Bus Bar Kit KRK710-1 Installation Instructions. Cooper Power Systems

Type 2 Arc Resistant WL Low Voltage Metal-Enclosed Switchgear

COOPER POWER SERIES. Instructions for oil-filled, single-phase overhead distribution transformers. Distribution Transformers MN201003EN

COOPER POWER SERIES. 600 A 15/25 kv class BOL-T and separable splice connector assembly installation instructions

COOPER POWER SERIES. Types D and DV recloser installation instructions. Reclosers MN280030EN

SIEMENS. XJ-L Busway Systems. Storage, Installation and Maintenance Instructions for... Piece No. 32-J Rev 3

Type L Cutouts. UltraSIL Polymer-Insulated and Porcelain Type L Open Distribution Cutout. Description

S Voltage Regulators. Contents. QD3 Quik-Drive Voltage Regulator Tap-Changer Manual. Figure 1B. QD3 Tap-changer. Figure 1A. QD3 Tap-changer.

Vacuum Circuit Breaker (Vehicle)

COOPER POWER SERIES. Metal-enclosed capacitor banks installation instructions. Power Capacitors MN230010EN

S Contents. Applicable to Serial Numbers A101 and above or beginning with CP57.

PAD-MOUNTED SWITCHGEAR INSPECTION & MAINTENANCE RECOMMENDATIONS TYPE PSI/II. 15kV 25kV. Qualified Persons

Fusing Equipment. Kearney Fuse Links. general. Internal Construction. tin element

Wheel Horse. 36 Tiller. Model No & Up. Operator s Manual

Installation Instructions LINK---C

IB PowlVac ITE-HK Remote Racking Device

Hubbell has a policy of continuous product improvement. Please visit hubbellpowersystems.com to confirm current design specifications.

COOPER POWER SERIES. Metal-enclosed, pad-mounted capacitor banks installation instructions. Power Capacitors MN230009EN

Instruction and Installation Guide

UltraSIL polymer-insulated and porcelain loadbreak Type LB open distribution cutout

Replacement of 600-Ampere Bushing and 200-Ampere Bushing-Well Adapters

Kearney fuse links. Technical Data General. Effective December 2013 Supersedes November 2009

ibusway for Data Center

SecoVac * Ground & Test Device

Before equipment use, please read this operation manual carefully. Serial Number: Date Purchased:

S&C Vista Underground Distribution Switchgear

Vacuum Circuit Breakers (Vehicle)

M-Force three-phase switch

SM-1700 Secondary Shunt Trip Coil Assembly. Powered by Safety

Kearney fuse links. Technical Data General. Effective March 2014 Supersedes December 2013

M-Force three-phase switch

SPECIFICATIONS GENERAL SAFETY RULES PERSONAL SAFETY. Save This Manual TOOL USE AND CARE WORK AREA

CCP2-FLR1-21_ flange-rod operating mechanism

Porte 150 Users Manual Swing Gate Opener 24V DC

1250 LB. CAPACITY MECHANICAL WHEEL DOLLY

Fusing Equipment. Sidewall-Mounted and Cover-Mounted Bay-O-Net Fuse Assembly GENERAL INSTALLATION

INSTRUCTIONS Ç CAUTION. S&C Power Fuses Types SMD-1A, SMD-2B, SMD-2C, and SMD-3. For Field Assembly and Installation NOTE INSTRUCTION SHEET

GE Industrial Solutions. DEH Installation and Maintenance Manual AKD-20 AR / Entellisys AR Exhaust Plenum System

Package Contents Part A (3) I-Beam (1) Base (2) Other parts

ELB ES. Product Installation Instructions

Figure 1. Non-removable buttonhead Edison Links. TABLE 1 Edison Link Fuse Designs. System Fuse Ampere Rating Type Rating

Vacuum Circuit Breakers (Vehicle) Type HKR 7.5kV to 15kV. Instructions Installation Operation Maintenance SGIM-9928C

COOPER POWER SERIES. Type MOST Fluid-Insulated Switchgear; Installation, Operation, and Maintenance Instructions

IMPORTANT SAFETY INSTRUCTIONS

Transcription:

Fusing Equipment Kearney Open Distribution Cutouts Type HX Installation Instructions Service Information KS010-01-1 CONTENTS Product Information...........................1 Safety Information............................2 Mounting Kearney Cutout or Disconnect........3 Installing Fuse Holder or Disconnect Blade.......3 Cutout Opening Breaking Loads...............4 Cutout-Arresters.............................4 Installing Fuse Links in 100 A Fuseholder........4 Installing Fuse Links in 200 A Fuseholder........5 Maintenance.................................6 CAUTION: The Cooper Power Systems Kearney HX Cutout is designed to be operated in accordance with normal safe operating procedures. These instructions are not intended to supersede or replace existing safety and operating procedures. The HX cutout should be installed and serviced only by personnel knowledgeable of good safety practices and fully trained on the installation and application of HX cutout fuses. Refer to appropriate ANSI or other industry standards for guidelines in operating and maintaining this equipment. These standards should be followed in addition to this instruction and instruction for fuse holders. PRODUCT INFORMATION Cooper Power Systems Kearney HX Cutouts can be quickly and economically adapted to double current rating or higher interrupting ratings as load and system capacity increases dictate. Simple blade changeout makes 300 A disconnects out of HX design. Fuseholders and blades are only stock items required for this broad versatility. Figure 1. Kearney Type HX cutout. These instructions do not claim to cover all details or variations in the equipment, procedure, or process described, nor to provide directions for meeting every contingency during installation, operation, or maintenance. When additional information is desired to satisfy a problem not covered sufficiently for the user s purpose, please contact your Cooper Power Systems sales engineer. May 2003 New Issue Printed in U.S.A. 1

Kearney Open Distribution Cutouts Type HX Installation Instructions SAFETY FOR LIFE SAFETY FOR LIFE Cooper Power Systems products meet or exceed all applicable industry standards relating to product safety. We actively promote safe practices in the use and maintenance of our products through our service literature, instructional training programs, and the continuous efforts of all Cooper Power Systems employees involved in product design, manufacture, marketing, and service. We strongly urge that you always follow all locally approved safety procedures and safety instructions when working around high-voltage lines and equipment and support our Safety For Life mission. SAFETY FOR LIFE The instructions in this manual are not intended as a substitute for proper training or adequate experience in the safe operation of the equipment described. Only competent technicians, who are familiar with this equipment should install, operate, and service it. A competent technician has these qualifications: Is thoroughly familiar with these instructions. Is trained in industry-accepted high- and low-voltage safe operating practices and procedures. Is trained and authorized to energize, de-energize, clear, and ground power distribution equipment. Is trained in the care and use of protective equipment such as flash clothing, safety glasses, face shield, hard hat, rubber gloves, hotstick, etc. Following is important safety information. For safe installation and operation of this equipment, be sure to read and understand all cautions and warnings. SAFETY INFORMATION Safety Instructions Following are general caution and warning statements that apply to this equipment. Additional statements, related to specific tasks and procedures, are located throughout the manual. DANGER: Hazardous voltage. Contact with high voltage will cause death or severe personal injury. Follow all locally approved safety procedures when working around high- and lowvoltage lines and equipment. WARNING: Before installing, operating, maintaining, or testing this equipment, carefully read and understand the contents of this manual. Improper operation, handling or maintenance can result in death, severe personal injury, and equipment damage. This manual may contain four types of hazard statements: DANGER: Indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. WARNING: Indicates a potentially hazardous situation which, if not avoided, could result In death or serious injury. Hazard Statement Definitions CAUTION: Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. CAUTION: Indicates a potentially hazardous situation which, if not avoided, may result in equipment damage only. WARNING: This equipment is not intended to protect human life. Follow all locally approved procedures and safety practices when installing or operating this equipment. Failure to comply may result in death, severe personal injury and equipment damage. WARNING: Power distribution equipment must be selected for the intended application. It must be installed and serviced by competent personnel who have been trained and understand proper safety procedures. These instructions are written for such personnel and are not a substitute for adequate training and experience in safety procedures. Failure to properly select, install or maintain this equipment can result in death, severe personal injury, and equipment damage. 2

MOUNTING KEARNEY CUTOUT OR DISCONNECT Step 1 INSPECT PORCELAIN Before mounting the cutout, make sure the porcelain is not cracked or chipped. Do not install a cutout if any hardware is loose, bent, distorted or out of alignment. Step 2 MOUNT CUTOUT Mount the cutout on a suitable mounting bracket. Position the lock washers as shown in Figure 2. Note: DO NOT mount this cutout in vaults or other enclosed areas. Ionized gases are generated during fault clearing operations and may cause electrical flash in enclosed spaces. Step 3 POSITION CUTOUT Pivot the cutout in a position that will provide ease of operation, maximum electrical clearance and venting clearance before securely tightening the carriage bolt nut. INSTALLING FUSE HOLDER OR DISCONNECT BLADE CAUTION: Only qualified personnel should operate and inspect an open cutout. Such personnel must observe company safety procedures and wear protective equipment. Operator should be positioned away from the exhaust path when closing cutout. Step 1 INSERT SWITCHSTICK HOOK Insert the hook of the switchstick into the lifting loop. The fuse holder or blade will hang on the hook in a position to be installed. Step 2 GUIDE FUSE HOLDER Guide the fuse holder lower casting trunnion into the cutout hinge and disengage switchstick. Figure 3. Step 3 CLOSE FUSE HOLDER Place the hook of switchstick under the pull ring and swing the fuse holder to a 45 angle from the closed position. Then with head down and to one side of vent exhaust pattern, quickly and with a vigorous thrust on switchstick, push fuse holder to a closed position. Figure 4. Figure 2. Figure 3. PULL RING LOCK WASHER NUT EXTERNAL TOOTH LOCK WASHER MOUNTING BRACKET CUTOUT CONTACT SWITCH STICK LOWER CASTING TRUNNION LIFTING LOOP SWITCH STICK Figure 4. 3

KS010-01-1 Step 4 REMOVE SWITCHSTICK Carefully remove switchstick from fuse holder to avoid pulling fuse holder open. CAUTION: Fuse holder should not be left hanging in the open position, as it may retain water. CUTOUT OPENING BREAKING LOADS WARNING: Use proper load breaking devices to open energized cutouts. Injury and damage to cutout is possible if load-breaking devices are not used. When replacing damaged expendable CAPS they should be replaced with like expendable caps. Loadbreaking Device The cutouts may be equipped with "hooks" for use with an approved loadbreak tool or other device designed for opening cutouts under load. Refer to the instructions with the device for their operation. CUTOUT-ARRESTERS Kearney cutout-arrester combinations consist of a Cooper distribution arrester and Kearney HX cutout mounted on a common L bracket to be installed as a completed assembly; Unigap Surge Arrester with ground lead disconnect in combination with Type "HX" cutouts. (See Figure 6.) During shipping and rough handling the units may get out of adjustment. Before mounting or during mounting, the arrester should be in same plane as the cutout with all nuts and bolts tight. Type "HX" cutout may be equipped with a permanent outdoor interrupter for breaking loads. Instructions for operating the "HX-CB" loadbreak are shown on KS1.1-01-1, which is supplied with the loadbreak unit. SWITCH STICK LINK BREAK ARM Figure 5. Fuse Link Breaking The 100 ampere Type "HX" cutout may be equipped with a linkbreak fuse holder and if so, these instructions apply. Fuse links up to 100 ampere rating can be broken. Place the hook of switchstick on linkbreak arm. Pull sharply downward with a fast rapid motion. See Figure 5. Figure 6. Cutout-Arrester combination. INSTALLING FUSE LINKS IN 100 A FUSEHOLDER Step 1. REMOVE CAP/INSTALL LINK Remove cap and operated link. Replace link with appropriate rating in fuse tube. Make sure the contact button is secured on the fuse link and carefully straighten the fuse cable. 4

KS010-01-1 Step 2. REPLACE CAP Slide the straightened fuse link cable end into the fuse holder, replace and tighten the cap. PUSH DOWN FLIPPER FLIPPER THUMB SCREW & WASHER Step 4. SECURE FUSE LINK Dress fuse link cable around post on flipper and then around thumbscrew in a clockwise direction. Maintain tension on fuse link cable and with flipper firmly depressed, cross the fuse cable over itself and tighten the thumbscrew. See Figure 8. Step 5. CLIP EXCESS CABLE Clip excess fuse cable to within approximately 1 /2" of the thumbscrew washer. INSTALLING FUSE LINKS IN 200 A FUSEHOLDER CAUTION: Use only the ampere size and types of fuse links specified by your company. Figure 7. Step 1. CHECK FUSE LINK Make sure the contact button is secured on the fuse link and carefully straighten the fuse cable. Step 3. LOOSEN THUMB SCREW AND DEPRESS FLIPPER Loosen thumb screw and remove old cable. Install fuse cable under thumbscrew washer. Press flipper downward on the lower tube casting. Hold in this position for step 4. See Figure 7. POST Figure 9. Figure 8. Step 2. CLAMP BOLT ASSEMBLY Loosen the clamping bolt to raise the link clamp. Do not try to remove clamping bolt. 5

Kearney Open Distribution Cutouts Type HX Installation Instructions Step 3. REMOVE CAP Remove the cap from fuse holder and slide the straightened fuse link cable into the fuse tube and through the fuse link clamp terminal, replace the cap. See Figure 9. CAUTION: Do not use a 100 ampere or smaller fuse link in 200 ampere fuse holders. Such application could lead to failure of the cutout to clear fault currents. Replace operated or partially operated expendable caps with new expendable caps. Step 4. SECURE FUSE LINK With link clamp held down over the tube bore, pull the end of the fuse cable tightly and tighten clamping bolt. See Figure 10. Step 5. CLIP EXCESS CABLE Clip excess fuse cable to within approximately 1 /2" of the box terminal. MAINTENANCE Refer to appropriate ANSI or other industry standards for maintenance. Figure 10. 2003 Cooper Industries, Inc. Kearney is a trademark of Cooper Industries, Inc. IEEE Standard C37.48 is a trademark of the Institute of Electrical and Electronics Engineers, Inc. ANSI is a registered trademark of the American National Standards Institute. Rev. 0 P.O. Box 1640 Waukesha, WI 53187 www.cooperpower.com 6 MI 5/03