TeSys Motor Starter Solutions for the North American Market

Similar documents
Short-Circuit Current Ratings

Multistandard offer for OEM applications. Single solution source for business without borders

GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Standard Features

Introduction. Standard Features. GV2, GV3, and GV7 Manual Motor Starters, Controllers, and Protectors Introduction

ECET Circuit Design Motor Loads. Branch Circuits. Article 210

PowerPact Circuit Breakers for Control Panel Disconnects Class 0611

Devices for Branch Circuits and Feeders

Certi cation Record INDUSTRIAL CONTROL EQUIPMENT Motor Controllers Magnetic

Bussmann series Quik-Spec Power Module Switch elevator disconnect

The Enclosed Altistart 22 Soft Start/Soft Stop Motor Controller

Protectors. Manual motor. Types MS116, MS132, MS45x, MS49x. MS Series. Manual motor protectors. Type MS116. Type MS132. Type MS45x.

Selection Guide. Control Circuit and Load Protection

Compact Circuit Protector (CCP) Application Note

TeSys GV2 - GV3 Manual Starters and Protectors

KT7. Methods. of Applying. & Molded Case Circuit Breakers F119. Motor Circuit Controllers

Overcurrent Protection According to the 2011 NEC

Advanced Guide To Understanding Assembly Short-Circuit Current Rating WITH ENGINEERING SOLUTIONS AND OVERCURRENT PROTECTION DEVICES TO ENHANCE SCCR

Current Ratings. Standards & codes note 1. Introduction. interest. By Steve Hansen Sr. Field Engineer

Bulletin 1489 Circuit Breakers. Selection Guide

GJL 100 A Molded Case Circuit Breaker GJL 75 A Motor Circuit Protector

3RV1011-0DA15 CIRCUIT-BREAKER, SIZE S00,

Simplified Guide To Understanding Short-Circuit Current Rating FIND IT, FIX IT, FORGET IT

1489-M Circuit Breakers

Self-protected Combination Starters System PKZ 2-SP

PowerPact B. Molded case circuit breakers and switches from A

A. This Section includes Low Voltage Switchgear Work, as indicated on the drawings, and as specified herein.

A. Provide a complete system of overcurrent protective devises as indicated on the drawings, and as specified herein.

Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931

Manual motor protectors Type MS116 Type MS325 Type MS45X Type MS49X

C E R T I F I C A T E O F C O M P L I A N C E

XT IEC Power Control Manual Motor Protectors

Protection Equipment. 5/2 Introduction

AF series contactors (9 2650)

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

Selection Guide Motor Control Device Solutions

ECET 211 Electric Machines & Controls Lecture 8 Motor Control Circuits (1 of 2) Lecture 8 Motor Control Circuits

Quick Start Guide TS 910 & TS 920

Motor Controllers + Circuit Breakers

A. Submit manufacturer's literature and technical data before starting work.

Types of Motor Starters There are several types of motor starters. However, the two most basic types of these electrical devices are:

Enhancing Short Circuit Selective Coordination with Low Voltage Circuit Breakers

DATASHEET - DILMC9-10(24VDC) Technical data General. Contactor, 3p+1N/O, 4kW/400V/AC3. Catalog No Eaton Catalog No. XTCEC009B10TD.

PowerPact Q-Frame Molded Case Circuit Breakers and Switches (Types QB, QD, QG and QJ)

Protectors. 35mm DIN rail snap-on mounting. Wide range of accessories

Series KTU7 UL489 Molded Case Circuit Breakers

Understanding National Electric Code (NEC) tap rules How do they apply to circuit breaker terminals?

SUPPLEMENTAL CORRECTION SHEET FOR SOLAR PHOTOVOLTAIC SYSTEMS - ELECTRICAL

1. The term "withstand" means "the unit will remain in place without separation of any parts from the device when subjected to the seismic forces.

Altivar 61/71 Adjustable Speed Drives Plastic Kits and Power Terminal Kit

Bussmann series Quik-Spec Coordination Panelboard

F Motor Circuit Controllers. Series KT7 Motor Circuit Controllers. KT4 Manual Motor Starters. General Description...F2

ALTIVAR FLEX58 Chassis Drive Controller Product Selection

Control Circuit Protection

Enclosures. See Section Typical Description

AF series contactors (9 2650)

Product index. 4 - Manual motor protectors. Manual motor protectors. Manual motor protectors Low Voltage Products & Systems 4.

Bulletin 190-M Compact Starters. Selection Guide

3. Coils shall be of molded construction

Bulletin 140M Motor Protectors

1.1. Contactors and Starters... Contents Description Relays and Timers... Miniature Controls... Manual Motor Protectors. XT IEC Power Control

Series KTU7 UL489 Molded Case Circuit Breakers

File E47705 Project 97ME August 21, 1997 REPORT. MOTOR CONTROLLERS, MANUAL Amberg, FED REP Germany

LPSRK100SP 100A 600V TD Dual Elem Class RK1 Low Peak Fuse

LPSRK30SP 30A 600V TD Dual Elem Class RK1 Low Peak Fuse

Industrial Generator Set Accessories. Standard Features. Line Circuit Breakers kw

S-Flex 212. Adjustable Speed Enclosed Drive Instruction Bulletin Rev. 07, 10/2018. Retain for future use.

Altivar 31 AC Drives. Simply Smart! For 3-phase asynchronous motors from 0.25 to 20 HP

SECTION MOTOR CONTROL

Quik-Spec Electrical Gear

KT4 Manual Motor Starter

Certificate of Compliance

Applying More Than One ArmorStart Motor Controller in a Single Branch Circuit on Industrial Machinery

Switchboards Instant Service

Panel SCCR 50kA RMS Symmetrical 480V Maximum

Low-Peak 600V Class RK1

2016 Photovoltaic Solar System Plan Review List

Mipco Connections for Refrigerated Containers. No One Does It Like Mipco. The Mipco. Advantage. Reliability. Safety. Easy Installation & Service

Series L9 UL-489 Miniature Circuit Breakers

NEMA Contactors & Starters (Freedom)

Features 1 Phase HP/Volts 1/6 HP AT 230 V 3 Phase HP/Volts 1/2 HP AT 200/230 V, 1-1/2 HP AT 460/575 V

Design Standards NEMA

Certifications UL Listed (File No. E 14841, Guide NLRV; File No. E 47426, Guide WHTY) CSA Certified (File No. LR1234) CE

Technical data OT16E3 OT160E3 UL & CSA

Fuseology. Fuse Holders, Fuse Blocks, Power Distribution Blocks & Surge Suppression. Optima Fuse Holders & Overcurrent Protection Modules.

SIGNAL WORDS QUALIFIED PERSON

Bulletin 194R Next Generation Global Fused and Non-Fused Disconnects

Protection Equipment

Poles 3 Starter Size NEMA 3 NON ALUMINUM LINE TERMINAL, LOAD TERMINAL

IN2 Enclosed Switches and Circuit Breakers

Interchangeable Built-in Fixed thermal Adjustable thermal Magnetic Fixed Adjustable Adjustable Electronic RMS 7 LS LSI

Product index. 4 - Manual motor protectors. Phone: Fax: Web: -

1.1. Contactors and Starters... Contents Description Relays and Timers... Miniature Controls... Manual Motor Protectors. XT IEC Power Control

Motor Starter Protectors

Instructions for A200, A210, A250 size 6, two- or three-pole non-reversing or reversing motor controllers

File E47705 Vol. 7 Sec. 9 Page 1 Issued: and Report Revised:

Manual motor protectors Type MS116 Type MS325 Type MS45X Type MS49X

DESIGN GUIDELINES LOW VOLTAGE SWITCHGEAR PAGE 1 of 5

ALTIVAR 58 AC Drives

Technical catalog February 2017 Low Voltage Switchboards and Panelboards UL/CSA

Data Bulletin. Wire Temperature Ratings and Terminations INTRODUCTION WHY ARE TEMPERATURE RATINGS IMPORTANT?

Transcription:

TeSys Motor Starter Solutions for the North American Market Data Bulletin 8536DB0901

Tesys Motor Starter Solutions 8536DB0901 Table of Contents 11/2009 Table of Contents Introduction... 3 Overview of U.S. Standards and Regulations... 3 Certification Process... 3 Acceptance of Electrical Equipment in the U.S.... 3 Structure of a Motor Starter in Accordance with UL508A... 4 Feeder Circuits and Branch Circuits... 4 Group Motor Installations... 5 Required Functions of Combination Starters... 6 Types of Combination Starter Constructions... 7 Disconnecting Means on a Feeder Circuit... 7 TeSys Motor Starters... 8 Disconnecting Means... 8 Industrial Machinery requirements (NFPA79 Section 5.3.3.1 and UL508A Section 65, 66)... 8 TeSys Solutions... 9 UL98/489... 9 TeSys GS Disconnect Switches... 9 UL508 Type E... 10 Manual Self-Protected Combination Motor Controller, TeSys GV... 10 Self-Protected Combination Motor Controller, TeSys U... 11 UL508 Type F... 11 Combination Motor Controller, TeSys GV... 11 UL508 Group Motor Installations... 12 Manual Combination Motor Controller, TeSys GV... 12 UL508 Contactors... 14 TeSys K, D, and F Specifications... 14 UL248 TeSys DF Fuse Holder Characteristics... 17 Short Circuit Protection for Drives... 17 GV2P Controllers and ATV21 Drives... 18 Recommended Branch-Circuit Protection Devices... 18 GV2P or GV3P Controllers with ATV31 Drives... 20 GV2P or GV3P Controllers with ATV61 or ATV71 Drives... 21 Self-Protected Manual Combination Starter Values Meeting UL 508 Type E... 21 SCCR requirement in UL508A... 23 Specific Requirements for the Canadian Market... 24 Installation and Product Standards... 24 Certification Process... 24 Technical Differences between Canadian and U.S. Standards... 24 Average Full-Load Currents of Asynchronous Squirrel Cage Motors 25 2 2009 Schneider Electric All Rights Reserved

8536DB0901 TeSys Motor Starter Solutions 11/2009 Introduction Certification Process Introduction Overview of U.S. Standards and Regulations TeSys motor starters from Schneider Electric offer a wide range of solutions to meet your motor control and protection needs. This data bulletin contains information on applying TeSys motor starters in the United States and Canada. Figure 1 outlines the national standards governing electrical installations in the U.S. Figure 1: Standards Installation standard NEC = NFPA70 NOTE: UL508A is both an application and a product standard. Application standard NFPA79 UL508A Product UL489 UL98 UL508 UL508A UL508C UL512 UL248 UL1077 standard National Electrical Code (NEC), NFPA70: Electrical Installation NFPA79: Electrical Standard for Industrial Machinery UL508A: Industrial Control Panel UL489: Molded-Case Circuit Breaker, Molded-Case Switches UL508: Industrial Control Equipment UL508C: Power Conversion Equipment UL98: Enclosed and Dead-Front Switches UL512: Fuse Holders UL248: Low Voltage Fuses UL1077: Supplementary Protectors Certification Process Acceptance of Electrical Equipment in the U.S. A nationally recognized testing laboratory (NRTL) can list or certify the equipment according to these applications or product standards. NRTLs include UL, CSA, ETL, TUV, and others listed at the following website: http://www.osha.gov/dts/otpca/nrtl/index.html#nrtls The process for acceptance is as follows: 1. The equipment is listed or the manufacturer is certified: a. For mass production equipment, the industrial control panel itself is listed by an NRTL b. For custom or low-volume equipment, the manufacturer or supplier of the industrial control panel is certified 2. A local inspector under the authority having jurisdiction (AHJ) inspects and approves the electrical equipment and the installation prior to commissioning. The product listing or labeling may be used to assist in the inspection. 2009 Schneider Electric All Rights Reserved 3

TeSys Motor Starter Solutions 8536DB0901 Structure of a Motor Starter in Accordance with UL508A Feeder Circuits and Branch Circuits 11/2009 Structure of a Motor Starter in Accordance with UL508A Feeder Circuits and Branch Circuits The feeder circuit includes all power conductors and components from the incoming feeder disconnect to the line side of the last branch short-circuit protection device (SCPD). The branch circuit includes all power conductors and components from the load side of the branch circuit SCPD to the controller load-side connections. Each branch circuit should be protected by its own disconnect and SCPD. Figure 2: Feeder Circuit and Branch Circuit Table 1: Circuit Components 1 Load provided in the field 14 2 Field wiring terminals 15 Control transformer ground (for 1000 VA max. control transformer) Control circuit devices and wiring Class 1 circuit isolated secondary circuit 3 Alternate field terminals 16 Solenoid or other control device provided in the field 4 Field wiring 17 Supplementary protection 5 Internal wiring of the power circuit 18 Class 2 transformer 6 Overload relay and heater elements 19 Class 2 circuit 7 Contactor or controller 20 8 Starter 21 9 Combination motor controller 22 Power transformer fuse branch circuit protection Power transformer for motor load and control protector Control circuit Class 1 circuit common control circuit 10 Branch circuit protection 23 Equipment ground and equipment ground terminal 11 Fused disconnect switch or circuit breaker 24 Bonding conductor bonding jumper 12 Control transformer 25 Grounding electrode conductor terminal 13 Control transformer fuse or supplementary protection 26 Grounding electrode conductor provided in the field 4 2009 Schneider Electric All Rights Reserved

8536DB0901 TeSys Motor Starter Solutions 11/2009 Structure of a Motor Starter in Accordance with UL508A Feeder Circuits and Branch Circuits Group Motor Installations In a group motor installation, a single disconnecting means and SCPD can be used for a group of motors. The specific rules are described in NEC Sections 430-112 and 430-53. A. Group installations are primarily used in the following applications: 1. Fractional hp motors NEC Section 430.53 (A): For several motors, each rated 1 hp maximum on a branch circuit of 600 V maximum, a single SCPD not exceeding 15 A is permitted under the following circumstances: No single motor is rated greater than 6 A The branch short-circuit device rating marked on any controller (UL508 circuit breaker, switch or contactor) is not exceeded Appropriate motor overload protection is used 2. Smallest rated motor protected NEC Section 430.53 (B): The SCPD is sized for the motor in the group with the lowest rating 3. Other group installations NEC Section 430.53 (C): Two or more motors of any rating, or one or more motors and other loads, where all the following conditions are met: Each motor controller and overload protection device carries a Motor Group Installation listing. Each circuit breaker (if used) is listed and is of the inverse time type. The SCPD (fuse or circuit breaker) is sized for the largest motor plus the sum of all other motors and loads. The sizing of the SCPD (fuse or circuit breaker) does not exceed the maximum allowed for overload protection of the smallest motor. Appropriate overcurrent protection is provided for non-motor loads. B. The tap conductor sizing rules for group motor installations are governed by NEC Section 430.53 (D). Conductors from the load side of the SCPD for the motor group must comply with one of the following: The ampacity is not less than that of the branch circuit conductors. The ampacity is not less than 1/3 that of the branch circuit conductors, and the length is not more than 7.5 m (25 ft). The ampacity is not less than 1/10 that of the SCPD for the motor group, the length is not more than 3 m (10 ft), and the manual motor controller is marked Suitable for Tap Conductor Protection in Group Installations. Products certified for motor grouping must carry the markings on the product label or instruction sheet required by NEC and UL (such as Suitable for Tap Conductor Protection in Group Installations ). 2009 Schneider Electric All Rights Reserved 5

TeSys Motor Starter Solutions 8536DB0901 Structure of a Motor Starter in Accordance with UL508A Required Functions of Combination Starters 11/2009 Required Functions of Combination Starters Combination starters are the most common type of packaged motor controllers. They are called combination because of their construction and combined functions. NEC Article 430 defines the required functions of combination starters. Underwriters Laboratories, Inc. (UL) specifies the tests and verifications that the components must pass before they can be listed as suitable for use for those functions. Figure 3 depicts the four component functions that compose a complete motor branch circuit as defined by the NEC. Figure 3: Required Functions of Combination Starters Motor Disconnect Motor Branch Circuit Protection Motor Controller Motor Overload Protection 6 2009 Schneider Electric All Rights Reserved

8536DB0901 TeSys Motor Starter Solutions 11/2009 Structure of a Motor Starter in Accordance with UL508A Types of Combination Starter Constructions Types of Combination Starter Constructions UL 508 is the UL safety standard for industrial control equipment. Part IV defines the component functions, construction, testing, and performance requirements of six styles of combination starters. Each of the six styles meets the requirements of NEC Article 430 for the motor disconnecting means, the motor branch circuit short-circuit and ground-fault protection, the motor controller, and the motor overload (OL) protection. Each provides adequate protection against fire or personal injury under fault conditions. The UL 508 type designations are differentiated by the actual components used to protect the motor branch circuit as illustrated in Table 2. Table 2: UL Combination Starter Type Designations Traditional Combination Starters from the 1980s and earlier UL Combination Starter Type A B C D Device Used for Component Function Disconnect UL 98 Manual Disconnect Branch Circuit Protection UL 248 Fuses UL 508 Motor Short Circuit Protector UL 489 Inverse Time Circuit Breaker UL 489 Instantaneous Trip Circuit Breaker Motor Controller UL 508 Magnetic or Solid State Controller Motor OL Relay UL 508 Motor Overload Relay UL98 Disconnect switch: TeSys GS UL 248 Fuses UL508 Controller: TeSys LC UL 508 Overload relay: TeSys LR UL489 Circuit Breaker: Compact NSF or Powerpact UL508 Controller: TeSys LC UL 508 Overload relay: TeSys LR Recognized 1990 E UL 508 Self-Protected Combination Controller UL 508 Type E Self-Protected Combination Starter: TeSys U UL 508 Type E Manual Self-Protected Combination Starter: TeSys GV.P Recognized 2002 F UL 508 Manual Self-Protected Combination Controller UL 508 Magnetic or Solid State Controller UL 508 Manual Self- Protected Combination Controller UL 508 Type F Combination Starter: TeSys GV + LC1D Disconnecting Means on a Feeder Circuit The disconnecting means on the feeder circuit, ahead of the last SCPD, must be a UL98 disconnect switch or UL489 circuit breaker. UL508 switches or motor protectors are not acceptable. On the branch circuit, the following are permitted as the disconnecting means when installed between the final motor branch circuit short circuit protection and the motor: any UL508 switch, suitable as a motor disconnect (according to NEC Section 430.81), that is used to start and stop a motor, a manual motor controller that is suitable as a motor disconnect (according to NEC Section 430.109). 2009 Schneider Electric All Rights Reserved 7

TeSys Motor Starter Solutions 8536DB0901 Disconnecting Means TeSys Motor Starters 11/2009 TeSys Motor Starters Figure 4: Power Supply Circuit or TeSys GS UL98 or Compact NSF or Powerpact UL489 Compact NSF or Powerpact or C60 UL489 LC1D if needed M M M M M M Other Loads TeSys U UL508 Type E TeSys GV2P + LC1D GV3P + LC1D UL508 Type F TeSys GV2ME + LC1D UL508 Group Installation TeSys GV2P or GV3P UL508 Type E + LC1D if needed + ATV drives Disconnecting Means Industrial Machinery requirements (NFPA79 Section 5.3.3.1 and UL508A Section 65, 66) A disconnecting means must be provided for each incoming supply (branch) circuit, and must open each ungrounded conductor of the supply circuit. This disconnecting means could be one of the following: UL489 inverse-time or instantaneous-trip circuit breaker UL489 molded-case switch UL98 switch unit, either open type or enclosed For a motor starter, the disconnecting means could be a UL508 type E selfprotected combination motor controller. The sizing of the disconnecting means must meet UL508A Section 30.2. A UL508 manual motor controller or switch (such as the TeSys Vario device) is certified for use on the load side of a motor's branch circuit protection. This is commonly called a load break switch. These requirements cover industrial control panels for industrial machinery (NFPA 79-2002, Electrical Standard for Industrial Machinery). The following types of machines are identified as industrial machinery: Metalworking machine tools, including machines that cut or form metal Plastics machinery, including injection molding, extrusion, blow molding, specialized processing, thermoset molding, and size reduction machines Wood machinery, including woodworking, laminating, and sawmill machines Assembly machines Material handling machines, including industrial robots and transfer machines Inspection and testing machines, including coordinate measuring and inprocess gauging machines 8 2009 Schneider Electric All Rights Reserved

8536DB0901 TeSys Motor Starter Solutions 11/2009 TeSys Solutions UL98/489 An operating mechanism for the disconnecting means must have the following characteristics: Readily accessible when the enclosure doors are in the open or closed position Installed so that its operation is not restricted by the enclosure door while in the open position Operable independent of the door position without the use of accessory tools or devices Lockable in the Off position independent of the door position and when the mechanism is locked, the disconnect cannot be closed The UL98 TeSys GS disconnect switches meet these requirements. The TeSys GS1 disconnect switch requires the use of operating mechanism GS1AD010 and GS1AD020. The TeSys GS2 disconnect switch provides these features (effective in the fourth quarter of 2009). The UL489 NSF and PowerPact Circuit breakers meet these requirements when used in conjunction with a Class 92 or 91L operating mechanism and 91LH79 handle. TeSys Solutions UL98/489 TeSys GS Disconnect Switches Table 3: TeSys GS Horsepower and SCCR Ratings Ampere Rating (A): General Purpose Rated Enclosure Horsepower Rating (hp) SCCR @ 600 Vac (ka) Fuse Type Max. Fuse Rating (A) Wire Range (AWG) Catalog Number 3Ø Vac Vdc 220/240 440/480 600 125 [1] 250 [1] 30 7.5 15 20 3 5 65 CC 30 14 10 GS1DDU3 30 7.5 15 20 3 5 65 J 30 14 10 GS1DU3 30 7.5 15 20 3 5 100 CC 30 14 10 GS2EEU3 30 7.5 15 20 3 5 100 J 30 10 3 GS2EU3 60 15 30 50 3 10 200 J 60 10 3 GS2GU3 100 30 60 75 7.5 20 200 J 100 14 2/0 GS2JU3 200 60 125 150 15 40 200 J 200 6 3/0 GS2MU3 400 125 250 350 20 50 200 J 400 2 x 2 AWG 600kcmil GS2QU3 600 200 500 500 200 J 600 2 x 2 AWG 600kcmil GS2SU3 800 200 500 500 200 L 800 2 x 2 AWG 600kcmil GS2TU3 [1] 2 poles in series. 2009 Schneider Electric All Rights Reserved 9

TeSys Motor Starter Solutions 8536DB0901 TeSys Solutions UL508 Type E 11/2009 Table 4: UL508 TeSys Vario Load Break Switch Horsepower Ratings Ampere Rating (A): General Purpose Rated Enclosure Horsepower Rating (hp) 3Ø Vac 1Ø Vac 200 208 240 480 600 120 200 208 240 480 600 10 2 2 2 5 5 0.33 1 1 1 2 2 V02 16 3 3 3 7.5 7.5 0.5 1.5 1.5 1.5 3 3 V01 20 3 5 5 10 10 0.75 2 2 2 5 5 V0 20 3 5 5 10 10 0.75 2 2 2 5 5 V1 25 3 5 5 10 15 1 2 2 3 5 7.5 V2 45 7.5 7.5 10 20 30 3 5 5 7.5 15 20 V3 63 10 10 15 30 40 3 5 5 7.5 15 20 V4 100 20 20 25 50 50 V5 115 25 25 30 50 60 V6 Catalog Number UL508 Type E Manual Self-Protected Combination Motor Controller, TeSys GV Manual Self-Protected Combination Starter Meeting UL508 Type E UL File E164871 Table 5: TeSys GV2P Horsepower and SCCR Ratings In combination with line spacer GV2GH7 (stand-alone starters) or GV1G09 and GV2G busbars (multiple starters) Standard Motor Ratings @ 50/60 Hz (hp) 1Ø 3Ø 120 V 240 V 200 V 240 V 480 V 600 V Associated Cable, AWG 75 C, Cu Manual Self-Protected Starter Overload Trip Range (A) 10 GV2P01 0.1 0.16 100 10 GV2P02 0.16 0.25 100 10 GV2P03 0.25 0.4 100 10 GV2P04 0.4 0.63 100 0.5 10 GV2P05 0.63 1 100 0.75 10 GV2P06 1 1.6 100 0.5 0.5 1 10 GV2P07 1.6 2.5 100 0.75 1 2 10 GV2P08 2.5 4 100 1.5 1.5 4 10 GV2P10 4 6.3 100 0.5 1 2 3 5 7.5 10 GV2P14 6 10 100 1 2 3 3 10 10 8 GV2P16 9 14 10 1 3 5 5 10 15 8 GV2P20 13 18 10 2 3 5 7.5 15 20 6 GV2P21 17 23 10 2 3 5 7.5 15 20 6 GV2P22 20 25 10 SCCR (ka) 480Y/277V 10 2009 Schneider Electric All Rights Reserved

8536DB0901 TeSys Motor Starter Solutions 11/2009 TeSys Solutions UL508 Type F Table 6: TeSys GV3P Horsepower and SCCR Ratings In combination with line spacer GV3G66 and GVAM11 (magnetic trip unit) for stand-alone starters Standard Motor Ratings @ 50/60 Hz (hp) 1Ø 3Ø 120V 240 V 200 V 240 V 480 V 600 V Associated Cable, AWG 75 C, Cu Manual Self-Protected Starter Overload Trip Range (A) 480Y / 277 V SCCR (ka) 1 2 3 3 7.5 10 8 GV3P13 9 13 100 25 1 3 3 5 7.5 10 8 GV3P18 12 18 100 25 2 3 5 7.5 15 20 6 GV3P25 17 25 100 25 2 3 7.5 7.5 20 25 6 GV3P32 23 32 100 25 3 5 10 10 25 30 3 GV3P40 30 40 65 25 3 7.5 10 10 30 40 3 GV3P50 37 50 65 25 5 10 15 15 40 50 3 GV3P65 48 65 65 25 600Y / 347 V Self-Protected Combination Motor Controller, TeSys U Meeting UL508 Type E UL File E164871 Table 7: TeSys U Horsepower and SCCR Ratings In combination with line spacer LU9SP0 (stand-alone starters) or GV1G09 and GV2G busbars (multiple starters) Standard Motor Ratings @ 50/60 Hz (hp) 1Ø 3Ø 120 V 240 V 200 V 240 V 480 V 600 V UL508 Type F Associated Cable, AWG 75 C, Cu Self-Protected Combination Starter Overload Trip Range (A) 480Y / 277 V SCCR (ka) 480 V with LUALB1 Limiter 1.5 2 3 3 10 10 8 LUB12 0.15 12 65 130 65 2 5 10 10 20 25 6 LUB32 0.15 32 65 130 65 When Limiter block LUALB1 is used, SCCR apply for stand alone starter or with GV1G09 and GV2G busbar for multistarter 600 V with LUALB1 Limiter Combination Motor Controller, TeSys GV Manual Self-Protected Combination Starter Meeting UL508 Type F UL File E164871 Table 8: TeSys GV2P Horsepower and SCCR Ratings In combination with line spacer GV2GH7 (stand-alone starters) or GV1G09 and GV2G busbars (multiple starters) Standard Motor Ratings @ 50/60 Hz (hp) Associated Cable, AWG 75 C, Cu Manual Self-Protected Starter Overload Trip Range (A) Type of Contactor Required 1Ø 3Ø 120 V 240 V 200 V 240 V 480 V 600 V 10 GV2P01 0.1 0.16 100 10 GV2P02 0.16 0.25 100 10 GV2P03 0.25 0.4 100 10 GV2P04 0.4 0.63 100 0.5 10 GV2P05 0.63 1 100 0.75 10 GV2P06 1 1.6 100 0.5 0.5 1 10 GV2P07 1.6 2.5 100 0.75 1 2 10 GV2P08 2.5 4 100 1.5 1.5 4 10 GV2P10 4 6.3 100 0.5 1 2 3 5 7.5 10 GV2P14 6 10 100 1 2 3 3 10 10 8 GV2P16 9 14 LC1 or D18 1 3 5 5 10 15 8 GV2P20 13 18 LC1 or D18 2 3 5 7.5 15 20 6 GV2P21 17 23 LC1D25 or D32 2 3 5 7.5 15 20 6 GV2P22 20 25 LC1D25 or D32 SCCR (ka) 480Y / 277 V 2009 Schneider Electric All Rights Reserved 11

TeSys Motor Starter Solutions 8536DB0901 TeSys Solutions UL508 Group Motor Installations 11/2009 Table 9: TeSys GV3P Horsepower and SCCR Ratings In combination with line spacer GV3G66 and GVAM11 (magnetic trip unit) for stand-alone starters Standard Motor Ratings @ 50/60 Hz (hp) 1Ø 3Ø 120V 240V 200V 240V 480V 600V Associated Cable, AWG 75 C, Cu Manual Self- Protected Starter Overload Trip Range (A) Type of Contactor Required SCCR (ka) 480Y/277V 600Y/347V 1 2 3 3 7.5 10 8 GV3P13 9 13 LC1D18 65 25 1 3 3 5 7.5 10 8 GV3P18 12 18 LC1D18 65 25 2 3 5 7.5 15 20 6 GV3P25 17 25 LC1D25 65 25 2 3 7.5 7.5 20 25 6 GV3P32 23 32 LC1D32 65 25 3 5 10 10 25 30 3 GV3P40 30 40 LC1D40A/ 50A/65A 65 25 3 7.5 10 10 30 40 3 GV3P50 37 50 LC1D50A/65A 65 25 5 10 15 15 40 50 3 GV3P65 48 65 LC1D65A/80 65 25 UL508 Group Motor Installations Manual Combination Motor Controller, TeSys GV GV2ME: UL File E164864 GV2RT: UL pending, CSA accepted (MC 164581, Report 1012350, Project 2152063) Table 10: TeSys GV2ME or GV2RT Horsepower and SCCR Ratings In association with LC1D contactors, suitable for Group Installation when protected by fuses or a circuit breaker (including multi starter with GV1G09 or GV2G05 blocks plus GV2G busbars) Standard Motor Ratings @ 50/60 Hz (hp) 1Ø 3Ø 120 V 240 V 200 V 240 V 480 V 600 V Associated Cable, AWG 75 C, Cu Manual Motor Starter Overload Trip Range (A) 10 GV2ME01 0.1 0.16 10 GV2ME02 0.16 0.25 10 10 0.5 10 0.75 10 0.5 0.5 1 10 0.75 1 2 10 1.5 1.5 4 10 0.5 1 2 3 5 7.5 10 1 2 3 3 10 10 8 1 3 5 5 10 15 8 GV2ME03 GV2RT03 GV2ME04 GV2RT04 GV2ME05 GV2RT05 GV2ME06 GV2RT06 GV2ME07 GV2RT07 GV2ME08 GV2RT08 GV2ME10 GV2RT10 GV2ME14 GV2RT14 GV2ME16 GV2RT16 GV2ME20 GV2RT20 0.25 0.4 0.4 0.63 0.63 1 1 1.6 1.6 2.5 2.5 4 4 6.3 6 10 9 14 13 18 2 3 5 7.5 15 20 6 GV2ME21 GV2RT21 17 23 2 3 5 7.5 15 20 6 GV2ME22 20 25 2 5 10 10 20 30 6 GV2ME32 24 32 Contactor 240 / 480 V LC1 or D18 LC1 or D18 LC1D25 or D32 LC1D25 or D32 LC1D25 or D32 600Y / 347 V 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 22 10 65 22 10 65 10 10 65 10 10 65 5 5 65 SCCR (ka) 480 V with GV1L3 Limiter Contactor LC1D32 or D38 LC1D32 or D38 LC1D32 or D38 LC1D32 or D38 LC1D32 or D38 600 V with LA9LB920 Limiter 12 2009 Schneider Electric All Rights Reserved

8536DB0901 TeSys Motor Starter Solutions 11/2009 TeSys Solutions UL508 Group Motor Installations Table 11: TeSys GV2P Horsepower and SCCR Ratings In association with LC1D contactors, suitable for Group Installation when protected by fuses or a circuit breaker (including multi starter with GV1G09 or GV2G05 blocks plus GV2G busbars) Standard Motor Ratings @ 50/60 Hz (hp) 1Ø 3Ø 120 V 240 V 200 V 240 V 480 V 600 V Associated Cable, AWG 75 C, Cu 10 Manual Motor Starter Overload Trip Range (A) Contactor 480 V GV2P01 0.1 0.16 10 GV2P02 0.16 0.25 10 GV2P03 0.25 0.4 10 GV2P04 0.4 0.63 0.5 10 GV2P05 0.63 1 0.75 10 GV2P06 1 1.6 0.5 0.5 1 10 GV2P07 1.6 2.5 0.75 1 2 10 GV2P08 2.5 4 1.5 1.5 4 10 GV2P10 4 6.3 0.5 1 2 3 5 7.5 10 GV2P14 6 10 1 2 3 3 10 10 8 GV2P16 9 14 LC1 or D18 1 3 5 5 10 15 8 GV2P20 13 18 LC1 or D18 2 3 5 7.5 15 20 6 GV2P21 17 23 LC1D25 or D32 2 3 5 7.5 15 20 6 GV2P22 20 25 LC1D25 or D32 2 5 10 10 20 30 6 GV2P32 24 32 LC1D25 or D32 SCCR (ka) 600Y / 347 V with GV1L3 Limiter 480 V Contactor with LA9LB920 Limiter 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 65 22 18 65 LC1D32 or D38 22 18 65 LC1D32 or D38 22 18 65 LC1D32 or D38 22 18 65 LC1D32 or D38 5 5 65 LC1D32 or D38 600 V Table 12: TeSys GV3P Horsepower and SCCR Ratings In association with LC1D contactors, suitable for Group Installation, when protected by fuses or a circuit breaker Standard Motor Ratings @ 50/60 Hz (hp) Associated Overload SCCR (ka) Manual 1Ø 3Ø Cable, AWG Trip Range Contactor Motor Starter 480Y / 600Y / 120V 240V 200V 240V 480V 600V 75 C, Cu (A) 277 V 347 V 1 2 3 3 7.5 10 8 GV3P13 9 13 LC1D18 65 25 1 3 3 5 7.5 10 8 GV3P18 12 18 LC1D18 65 25 2 3 5 7.5 15 20 6 GV3P25 17 25 LC1D25 65 25 2 3 7.5 7.5 20 25 6 GV3P32 23 32 LC1D32 65 25 3 5 10 10 25 30 3 GV3P40 30 40 LC1D40A/50A/65A 65 25 3 7.5 10 10 30 40 3 GV3P50 37 50 LC1D50A/65A 65 25 5 10 15 15 40 50 3 GV3P65 48 65 LC1D65A/80 65 25 These values are derived from the UL508 Type F certification (E164871). 2009 Schneider Electric All Rights Reserved 13

TeSys Motor Starter Solutions 8536DB0901 TeSys Solutions UL508 Contactors 11/2009 UL508 Contactors TeSys K, D, and F Specifications Table 13: TeSys K Ratings Standard Motor Ratings @ 50/60 Hz (hp) Associated Cable, AWG 75 C, Cu Max. Inductive AC3 Current (A) Max. Continuous Current (A) 1 Ø 3 Ø Contactor 115 V 230/240 V 200/208 V 230/240 V 460/480 V 575/600 V 0.5 1.5 1.5 1.5 3 3 10 6 15 LC1K06 0.5 1.5 2 3 5 5 10 9 20 LC1K09 0.5 1.5 3 3 7.5 10 10 12 20 LC1K12 Table 14: TeSys D Ratings Standard Motor Ratings @ 50/60 Hz Associated Cable 75 C, Cu Max. Inductive AC3 Current (A) Max. Continuous Current (A) Type of Contactor Required 1 Ø 3 Ø 115 V 230/240 V 200/208 V 230/240 V 460/480 V 575/600 V 0.5 1 0.5 2 0.5 2 0.5 5 7.5 10 AWG 9 20 LC1D09 1 2 3 3 7.5 10 10 AWG 12 25 LC1 1 3 5 5 10 15 8 AWG 18 32 LC1D18 2 3 5 7.5 15 20 6 AWG 25 40 LC1D25 2 5 7.5 10 20 30 6 AWG 32 50 LC1D32 3 5 10 10 30 30 3 AWG 40 60 LC1D40A 3 7.5 15 15 40 40 3 AWG 50 70 LC1D50A 5 10 20 20 40 50 3 AWG 65 80 LC1D65A 7.5 15 25 30 60 60 2 AWG 80 125 LC1D80 7.5 15 25 30 60 60 250 mcm 95 125 LC1D95 30 40 75 100 250 mcm 115 200 LC1D115 40 50 100 125 250 mcm 150 200 LC1D150 High-Fault Short-Circuit Rating Suitable For Use On A Circuit Capable Of Delivering Not More Than 100,000 rms Symmetrical Amperes, 600 Volts Maximum when protected by Class J time-delay fuse sized not larger than 225% of motor FLA: LC1D09,, D18, D25, D32, D40, D56, D65, D80, D115, D150 14 2009 Schneider Electric All Rights Reserved

8536DB0901 TeSys Motor Starter Solutions 11/2009 TeSys Solutions UL508 Contactors Table 15: UL/CSA Lighting Ratings @ 575 / 600V Device Ballast Tungsten LC1D09 (AC coil only) 20 A 20 A LC1 (AC coil only) 25 A 20 A LC1D18 (AC coil only) 32 A 25 A LC1D25 (AC coil only) 40 A 40 A LC1D32 (AC coil only) 50 A 50 A LC1DT20 (AC coil only) 20 A 20 A LC1DT25 (AC coil only) 25 A 25 A LC1DT32 (AC coil only) 32 A 32 A LC1DT40 (AC coil only) 40 A 40 A LC1D40A 60 A 60 A LC1D50A 70 A 70 A LC1D65A 80 A 70 A LC1D80, LC1D80004 100 A 100 A LC1D115, LC1D1150004 115 A 115 A LC1D150, LC1D1500004 150 A 150 A Table 16: Elevator Duty Ratings (hp) Catalog 1 Ø 3 Ø Number 230/240 V 200/208 V 230/240 V 460/480 V 575/600 V LC1 (AC) 1.5 2 3 7.5 7.5 LC1D25 (AC) 3 5 7.5 15 20 LC1D32 (AC) 5 10 LC1D40A (AC) LC1D50A (AC) 7.5 10 15 25 30 LC1D65A (AC) 10 15 20 25 30 LC1D80 15 25 30 50 50 LC1D95 LC1D115 LC1D150 15 25 30 65 75 Table 17: Definite Purpose Ratings, 3-Phase, Breaking All Lines Hermetic Refrigeration Compressor Device FLA LRA 240V 480V 600V LC1D09 (AC coil only) 9 54 45 36 LC1 (AC coil only) 12 72 60 48 LC1D18 (AC coil only) 18 108 90 72 LC1D25 (AC coil only) 25 150 125 100 LC1D32 (AC coil only) 32 192 160 128 LC1D40A 40 240 200 160 LC1D50A 50 300 250 200 LC1D65A 65 390 325 260 LC1D80 75 450 375 300 LC1D95 LC1D115 115 690 575 460 LC1D150 150 900 750 600 2009 Schneider Electric All Rights Reserved 15

TeSys Motor Starter Solutions 8536DB0901 TeSys Solutions UL508 Contactors 11/2009 Table 18: TeSys F Ratings Standard Motor Ratings @ 50/60 Hz (hp) Associated Cable 75 C, Cu Max. Inductive AC3 Current (A) Max. Continuous Current (A) Contactor [1] 3Ø 200/208 V 230/240 V 460/480 V 575/600 V 30 40 75 100 14 2/0 AWG 115 200 LC1F115 40 50 100 125 6 3/0 AWG 150 250 LC1F150 50 60 125 150 6 3/0 AWG 185 275 LC1F185 6 3/0 AWG 225 315 LC1F225 60 75 150 175 6 AWG 300 MCM 265 350 LC1F265 75 100 200 250 6 AWG 300 MCM 330 400 LC1F330 100 125 250 300 4 AWG 500 MCM 400 500 LC1F400 150 200 400 500 2 x 2 AWG 600 MCM 500 700 LC1F500 250 300 600 800 3 x 2 AWG 600 MCM 630 1000 LC1F630 450 800 900 3 x 2 AWG 600 MCM 800 1000 LC1F800 Table 19: UL/CSA Lighting ratings @ 460 / 480V 3-Pole or 4-Pole Contactor Tungsten Rating Ballast Rating LC1F115 115A 115A LC1F150 150A 150A LC1F185 200A 200A LC1F265 265A 265A LC1F330 300A 300A Table 20: Elevator Duty Ratings (hp) Contactor 1Ø 3Ø 230/240 V 200/208 V 230/240 V 460/480 V 575/600 V LC1F185 20 25 30 75 75 LC1F265 40 40 LC1F330 50 50 LC1F400 60 60 LC1F500 75 75 LC1F630 100 100 Table 21: Definite Purpose Ratings, 3-Phase, Breaking All Lines Hermetic Refrigeration Compressor Contactor FLA LRA 240V 480V 600V LC1F115 135 800 800 520 LC1F150 150 900 750 700 LC1F185 220 1500 1500 1200 LC1F225 220 1500 1500 1200 LC1F265 270 1800 1900 1500 LC1F400 350 2000 2000 1800 LC1F500 700 4500 4500 00 LC1F630 880 5000 5000 4850 LC1F780 1330 7500 7500 7290 16 2009 Schneider Electric All Rights Reserved

8536DB0901 TeSys Motor Starter Solutions 11/2009 Short Circuit Protection for Drives UL248 TeSys DF Fuse Holder Characteristics UL248 TeSys DF Fuse Holder Characteristics Table 22: Fuse Holder Ratings Fuse Holder Standards Electrical Ratings in Accordance with UL512 DF10 DFCC DF14 DF22 IEC, UL (UL Recognized) IEC, UL (UL Listed) IEC, UL (UL Recognized) IEC, UL (UL Recognized) AC: For catalog numbers US10 and CMS10: 30 A, 800 Vac max, 200 ka current withstand DC: For catalog numbers US10 and CMS10: 30 A, 1000 Vdc max, 100 ka current withstand AC: 30 A, 800 Vac max, 200 ka current withstand DC: 30 A, 1000 Vdc max, 100 ka current withstand Voltage: 800 Vac, 1000 Vdc Amperes: CMS14 and US14 = 50 A max.; CMS22 and US22 = 125 A max. Voltage: 800 Vac, 1000 Vdc Amperes: CMS14 and US14 = 50 A max.; CMS22 and US22 =125 A max. Short Circuit Protection for Drives Drives are not rated for group motor applications. When a variable-speed drive is connected to a single-motor circuit, the branch-circuit protection provided must be of the type and size specified by the manufacturer's instructions that come with the drive. When the instructions do not specify the type and size, a branch-circuit fuse or inverse-time circuit breaker must be used and must be sized based on the input current rating of the drive multiplied by the percentage from UL508A Table 31.1. Schneider Electric tested drives in combination with the following: Fuses UL489 circuit breakers GV2P and GV3P UL508 Type E self-protected, manual combination starters The optimized solution for drives is the combination with UL508 Type E, TeSys GV self-protected, manual combination starters. This combination was tested for the following drives: ATV21 at 22 ka / 480 V ATV31, ATV61, and ATV71 at 65 ka / 480 V 2009 Schneider Electric All Rights Reserved 17

TeSys Motor Starter Solutions 8536DB0901 Short Circuit Protection for Drives GV2P Controllers and ATV21 Drives 11/2009 GV2P Controllers and ATV21 Drives Recommended Branch-Circuit Protection Devices Table 23: Circuit Breakers and Manual Motor Controllers for 208/230 V ATV21 Drives Drive Catalog No. Maximum Size Protective Device for SCCR SCCR, (ka) Thermal-Magnetic Circuit Breakers [1], [2] Manual Motor Controllers [3] Open [4] Enclosed [5] 208 V ATV21H075M3X FAL34015 HDL36015 GJL36015 GV2P08 22 22 ATV21H075M3X FAL34015 HDL36015 GJL36015 GV2PI0 22 22 ATV21HU15M3X FAL34015 HDL36015 GJL36015 GV2P14 22 22 ATV21HU22M3X FAL34020 HDL36020 GJL36020 GV2P16 22 22 ATV21HU40M3X FAL34040 HDL36040 GJL36040 GV2P20 22 22 ATV21HU55M3X FAL34050 HDL36050 GJL36050 GV2P22 22 22 ATV21HU75M3X FAL34070 HDL36070 GJL36070 GV2P32 22 22 ATV21HD11M3X FAL34100 HDL36100 GJL36100 22 22 ATV21HD15M3X HDL36125 22 22 ATV21HD18M3X JDL36175 22 22 ATV21HD22M3X JDL36200 22 22 ATV21HD30M3X JDL36250 22 22 230 V ATV21H075M3X FAL34015 HDL36015 GJL36015 GV2P08 22 22 ATV21H075M3X FAL34015 HDL36015 GJL36015 GV2PI0 22 22 ATV21HU15M3X FAL34015 HDL36015 GJL36015 GV2P10 22 22 ATV21HU22M3X FAL34020 HDL36020 GJL36020 GV2P14 22 22 ATV21HU40M3X FAL34035 HDL36035 GJL36035 GV2P20 22 22 ATV21HU55M3X FAL34045 HDL36045 GJL36045 GV2P21 22 22 ATV21HU75M3X FAL34060 HDL36060 GJL36060 GV2P32 22 22 ATV21HD11M3X FAL34090 HDL36090 GJL36090 22 22 ATV21HD15M3X HDL36125 22 22 ATV21HD18M3X HDL36150 22 22 ATV21HD22M3X JDL36175 22 22 ATV21HD30M3X JDL36225 22 22 [1] Square D Type FA, HD, or JD; or Merlin Gerin Type GJL. The third character of the Square D circuit breaker catalog number may be F (bus bar), L (line/load side lugs), M (line side lugs), or P (load side lugs). The fifth character of the Square D circuit breaker catalog number may be a 4 (480 V) or a 6 (600 V). [2] Square D circuit breakers with the following prefixes are also covered at the same amperage rating: FH, HG, HJ, HL, JG, JJ, JL, LH, and MH. These prefixes indicate higher interrupting ratings. [3] GV2 self-protected control device, UL 508 Type E. [4] Type 1 open drive with a conduit box installed. [5] Drive installed in a metallic enclosure, 8640 in³ minimum. 18 2009 Schneider Electric All Rights Reserved

8536DB0901 TeSys Motor Starter Solutions 11/2009 Short Circuit Protection for Drives GV2P Controllers and ATV21 Drives Table 24: Circuit Breakers and Manual Motor Controllers for 480/460 V ATV21 Drive Drive Catalog No. Maximum Size Protective Device for Short-circuit Current Ratings SCCR (ka) Type 1 Metallic Enclosure Minimum Thermal-Magnetic Circuit Breakers [1], [2] Manual Motor Controllers [3] Open [4] Enclosed [5] Volume (in³) 480 Y/277 V ATV21H075N4 GV2P06 22 22 ATV21H075N4 GV2P07 22 22 ATV21HU15N4 GV2P08 22 22 ATV21HU22N4 GV2P10 22 22 ATV21HU30N4 GV2P14 22 22 ATV21HU55N4 GV2P16 22 22 ATV21HU75N4 GV2P20 22 22 ATV21HD11N4 GV2P21 22 22 ATV21HD15N4 GV2P22 22 22 ATV21HD18N4 GV2P32 22 22 ATV21HD22N4 22 ATV21HD30N4 22 460 V ATV21H075N4 FAL34015 HDL36015 GJL36015 22 ATV21HU15N4 FAL34015 HDL36015 GJL36015 22 ATV21HU22N4 FAL34015 HDL36015 GJL36015 22 ATV21HU30N4 FAL34020 HDL36020 GJL36020 22 ATV21HU55N4 FAL34025 HDL36025 GJL36025 22 ATV21HU75N4 FAL34030 HDL36030 GJL36030 22 ATV21HD11N4 FAL34045 HDL36045 GJL36045 22 8640 ATV21HD15N4 HDL34060 HDL36060 GJL36060 22 ATV21HD18N4 HDL34070 HDL36070 GJL36070 22 ATV21HD22N4 JDL34090 HDL36090 GJL36090 22 ATV21HD30N4 JDL36125 22 ATV21HD37N4 HDL36125 10 10 ATV21HD45N4 HDL36150 10 10 ATV21HD55N4 JDL36175 10 10 9792 [1] Square D Type FA, HD, or JD; or Merlin Gerin Type GJL. The third character of the Square D circuit breaker catalog number may be F (bus bar), L (line/load side lugs), M (line side lugs), or P (load side lugs). The fifth character of the Square D circuit breaker catalog number may be a 4 (480 V) or a 6 (600 V). [2] Square D circuit breakers with the following prefixes are also covered at the same amperage rating: FH, HG, HJ, HL, JG, JJ, JL, LH, MH. These prefixes indicate higher interrupting ratings. [3] GV2 self-protected control device, UL 508 Type E. [4] Type 1 open drive with a conduit box installed. [5] Drive installed in a Type 1 metallic enclosure, minimum volume as noted. 8640 2009 Schneider Electric All Rights Reserved 19

TeSys Motor Starter Solutions 8536DB0901 Short Circuit Protection for Drives GV2P or GV3P Controllers with ATV31 Drives 11/2009 GV2P or GV3P Controllers with ATV31 Drives Table 25: Input Line Voltage Type E Self-Protected Manual Combination Motor Starter Selection for 65 ka SCCR with a 3% Line Reactor hp Drive Catalog Number Self-Protected Control Devices [1] Type 12 Metallic Enclosure Min. Volume (in³) 0.25 ATV31H018M3X GV2P07 with GV2GH7 480 0.5 ATV31H037M3X GV2P08 with GV2GH7 480 0.75 ATV31H055M3X GV2P10 with GV2GH7 480 1 ATV31H075M3X GV2P10 with GV2GH7 [2] 480 1.5 ATV31HU11M3X GV2P14 with GV2GH7 784 2 ATV31HU15M3X GV2P14 with GV2GH7 [2] 784 3 ATV31HU22M3X GV3P18 with GV3G66 and GVAM11 GV3P13 with GV3G66 and GVAM11 [2] 784 208/240 Vac 3Ø ATV31HU30M3X GV3P18 with GV3G66 and GVAM11 [2] 1344 5 ATV31HU40M3X GV3P25 with GV3G66 and GVAM11 1344 7.5 ATV31HU55M3X GV3P40 with GV3G66 and GVAM11 GV3P32 with GV3G66 and GVAM11 [2] 2880 10 ATV31HU75M3X GV3P50 with GV3G66 and GVAM11 2880 15 ATV31HD11M3X GV3P65 with GV3G66 and GVAM11 4896 0.5 ATV31H037N4 GV2P07 with GV2GH7 784 0.75 ATV31H055N4 GV2P07 with GV2GH7 [2] 784 1 ATV31H075N4 GV2P08 with GV2GH7 784 1.5 ATV31HU11N4 GV2P08 with GV2GH7 [2] 784 2 ATV31HU15N4 GV2P10 with GV2GH7 [2] 784 3 ATV31HU22N4 GV2P14 with GV2GH7 1344 ATV31HU30N4 GV2P14 with GV2GH7 [2] 1344 480 Y / 277 Vac 3Ø 5 ATV31HU40N4 GV3P13 with GV3G66 and GVAM11 [2] 1344 7.5 ATV31HU55N4 GV3P18 with GV3G66 and GVAM11 [2] 2880 10 ATV31HU75N4 GV3P25 with GV3G66 and GVAM11 [2] 2880 15 ATV31HD11N4 GV3P32 with GV3G66 and GVAM11 [2] 4896 20 ATV31HD15N4 GV3P40 with GV3G66 and GVAM11 [2] 4896 [1] All specified GV accessories must accompany the GV motor control device to retain the Type E rating and to meet the specified SCCR. [2] When sizing the GV at 208 V or 220 V: if the required current exceeds the GV current rating, use the next higher approved combination. 20 2009 Schneider Electric All Rights Reserved

8536DB0901 TeSys Motor Starter Solutions 11/2009 Short Circuit Protection for Drives GV2P or GV3P Controllers with ATV61 or ATV71 Drives GV2P or GV3P Controllers with ATV61 or ATV71 Drives Self-Protected Manual Combination Starter Values Meeting UL 508 Type E Altivar 61 and 71, 200 240 V Ratings A manual motor protector may be used as an overcurrent protective device (OCPD) for Altivar 61 and 71 drives with an input line voltage of 200 240 V and installed in a Type 12 metallic enclosure with a 3% minimum line reactor. Table 26 shows the maximum current value and associated manual motor protector catalog number required for a 65 ka SCCR. The UL 508 Type E rating requires the addition of the following line side insulating barriers: GV2GH7 for GV2P GV3G66 and GVAM11 for GV3P Table 26: Altivar 61 and 71, 200 240 V Drives Installed in Type 12 Metallic Enclosures, with 3% Minimum Line Reactor hp Catalog Number Minimum Enclosure Volume (in³) [1] OCPD Type 0.5 ATV71H037M3 1600 GV2P08 1 ATV61H075M3 ATV71H075M3 1600 GV2P10 2 3 5 7.5 10 15 ATV61HU15M3 ATV71HU15M3 ATV61HU22M3 ATV71HU22M3 ATV61HU30M3 ATV71HU30M3 ATV61HU40M3 ATV71HU40M3 ATV61HU55M3 ATV71HU55M3 ATV61HU75M3 ATV71HU75M3 ATV61HD11M3X ATV71HD11M3X 1600 GV2P14 [2] 1920 GV3P13 [2] or GV3P18 1920 GV3P18 [2] 1920 GV3P25 [2] 2880 GV3P32 [2] or GV3P40 4032 GV3P40 [2] or GV3P50 5760 GV3P50 [2] 20 ATV61HD15M3X ATV71HD15M3X 5760 GV3P65 [3] [1] Minimum enclosure volume that permits the stated SCCR. Application-specific thermal requirements may require a larger enclosure. [2] For systems at voltages lower than 240 V, use the next higher OCPD and associated drive combination if the required current exceeds the OCPD current rating listed in this table. [3] This combination is valid on 240 V systems only. Do not apply on systems with lower voltage ratings. 2009 Schneider Electric All Rights Reserved 21

TeSys Motor Starter Solutions 8536DB0901 Short Circuit Protection for Drives GV2P or GV3P Controllers with ATV61 or ATV71 Drives 11/2009 Altivar 61 and 71 480 V Ratings A manual motor protector may be used as an OCPD for Altivar 61 and 71 drives with an input line voltage of 480 Y / 277 V and installed in a Type 12 metallic enclosure with a 3% minimum line reactor. Table 27 shows the maximum current value and associated manual motor protector catalog number required for a 65 ka SCCR. The UL 508 Type E rating requires the addition of the following line side insulating barriers: GV2GH7 for GV2P GV3G66 and GVAM11 for GV3P Table 27: Altivar 61 and 71 480Y/277 V Drives Installed in Type 12 Metallic Enclosures, with 3% Minimum Line Reactor hp Catalog Number Minimum Enclosure Volume (in³) [1] OCPD Type 1 2 3 5 7.5 10 15 20 25 30 ATV61H075N4 ATV71H075N4 ATV61HU15N4 ATV71HU15N4 ATV61HU22N4 ATV71HU22N4 ATV61HU30N4 ATV71HU30N4 ATV61HU40N4 ATV71HU40N4 ATV61HU55N4 ATV71HU55N4 ATV61HU75N4 ATV71HU75N4 ATV61HD11N4 ATV71HD11N4 ATV61HD15N4 ATV71HD15N4 ATV61HD18N4 ATV71HD18N4 ATV61HD22N4 ATV71HD22N4 1600 GV2P08 1600 GV2P10 1600 GV2P14 1920 GV2P14 1920 GV3P13 2880 GV3P18 or GV3P25 2880 GV3P25 4032 GV3P32 or GV3P40 5760 GV3P40 or GV3P50 8640 GV3P40 or GV3P50 8640 GV3P50 40 ATV61HD30N4 ATV71HD30N4 10368 GV3P65 [1] Minimum enclosure volume that permits the stated SCCR. Application-specific thermal requirements may require a larger enclosure. 22 2009 Schneider Electric All Rights Reserved

8536DB0901 TeSys Motor Starter Solutions 11/2009 Short Circuit Protection for Drives SCCR requirement in UL508A SCCR requirement in UL508A NEC Article 409, NFPA 79, and UL508A require that the SCCR be marked on all control panels. The final builder or assembler of the equipment inside the panel is responsible for providing the SCCR for the overall panel, determined by one of the following three options: Testing each panel construction and recording the construction in the follow-up procedure. With the multitude of possible product combinations within a panel, this option can require much testing and maintenance. Third party testing and certification may also be required. Purchasing previously tested constructions (combinations) from a major supplier of equipment that can be tabulated in the control or machine panel builder's procedure. Once you have all the component ratings, either use an outside service or UL 508A, Supplement SB. Using a method described in UL 508A, Supplement SB. Important: Using the interrupting rating of the main OCPD for the panel is not an acceptable practice! WARNING INADEQUATE SHORT CIRCUIT INTERRUPTING RATING Do not use the interrupting rating of the main OCPD as the SCCR rating for the controller. Failure to follow these instructions can result in death, serious injury, or equipment damage. By using discrete components to assemble a combination motor controller within a panel, and providing UL508A combination motor controller data (some listed under the Square D brand name), Schneider Electric offers solutions for achieving an SCCR that is higher than the rating of the lowestrated individual discrete component. These combinations can be found at the following websites: Square D UL508A website: http://www.squared.com/us/products/motor_control.nsf/unid/beabdd3d2c 1FB03C85256EBE0047F560/$file/ul508aFrameset.htm (In the What s New area, select Fully UL508A Tested and Approved Combination Spreadsheets Now Available.) UL s UL508A Combination Motor Controller website: http://www.ul.com/controlequipment/shortcircuit.html 2009 Schneider Electric All Rights Reserved 23

TeSys Motor Starter Solutions 8536DB0901 Specific Requirements for the Canadian Market Installation and Product Standards 11/2009 Specific Requirements for the Canadian Market Installation and Product Standards Certification Process Technical Differences between Canadian and U.S. Standards The installation standard in Canada is the Canadian Electrical Code (CEC). The CEC and the NEC are similar but not 100% equivalent. The same is true for the CSA standards and corresponding UL standards (see Table 28). Some of the major differences are detailed below. As in the U.S., Nationally Recognized Testing Laboratories (such as CSA, ETL, TUV, and UL) are able to certify equipment according to these CSA standards. Refer to Acceptance of Electrical Equipment in the U.S. on page 3. The procedure is the same. Some examples of differences between the Canadian and U.S. standards that currently apply to motor starters are listed below. (Note that the TeSys product line is designed for compliance and capatibility with both the UL and the CSA requirements.) Type E combination motors starters are also recognized in Canada but Type F currently are not. Type E applications don't require the use of large spacing adapters as in the U.S. Group installation is recognized but the rules to define the common branch-circuit protection setting is quite different. Industrial control panels must meet CSA C22.2 No. 14 Elevator equipment appliances must comply with the specific CSA Nr. B44.1 standard. Product marking requirements differ slightly. Table 28: Comparison of CSA and UL Standards Standard Name CSA Standard UL Standard Enclosed and Dead-Front Switches CSA C22.2 No. 4 UL98 Low-Voltage Fuses: Part 1: General Requirements CSA C22.2 No. 248 UL248 Molded-Case Circuit Breakers, Molded-Case Switches, and CSA C22.2 No. 5 UL489 Circuit-Breaker Enclosures Industrial Control Equipment CSA C22.2 No. 14 UL508 Elevator Equipment CSA No. B44.1 Partially UL508 24 2009 Schneider Electric All Rights Reserved

8536DB0901 TeSys Motor Starter Solutions 11/2009 Average Full-Load Currents of Asynchronous Squirrel Cage Motors Installation and Product Standards Average Full-Load Currents of Asynchronous Squirrel Cage Motors These values conform to the NEC. They vary according to the type of motor, its polarity, and the manufacturer. 2009 Schneider Electric All Rights Reserved 25

Tesys Motor Starter Solutions Data Bulletin Schneider Electric and TeSys are trademarks or registered trademarks of Schneider Electric. Other trademarks used herein are the property of their respective owners. Schneider Electric USA 8001 Knightdale Blvd. Knightdale, NC 27545 1-888-SquareD (1-888-778-2733) www.schneider-electric.us Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this material. 8536DB0901 11/2009 2009 Schneider Electric All Rights Reserved