GREEN LIGHT TO USE WHEN YOU LIKE. Hawker XFC TM Bloc battery solutions for small traction applications

Similar documents
Small traction motive power. NexSys. Technical Manual Designed to change the way you work

Small Traction powerbloc powerbloc dry Hawker XFC TM

Traction batteries Hawker XFC Fast charge battery system. Plug & Play power solution

ADVANCED BATTERY SOLUTIONS NEXSYS BATTERIES POWER WHEN YOU NEED IT

Technical data Smart chargers Lifetech XFC TM

Instructions for use. Hawker Premier

Small Traction powerbloc powerbloc dry Fiamm Motive Power XFC TM

PRODUCT GUIDE Publication No: EN-SBS-PG-001 February 2003

ADVANCED BATTERY SOLUTION HAWKER WATER LESS LESS WATERING MORE CUSTOMER BENEFITS

Product Guide. An Invensys company

PowerSafe OPzV Operation Guide for Solar Applications

PowerSafe OPzV Operation Guide for Solar Applications

Technical data Smart chargers Hawker Lifetech

EcoSafe EOPzV. Operation Guide for Solar Applications

Instructions for use. Hawker evolution ATEX

Technical data Smart chargers Hawker Lifeplus Powertech

Instructions for use. Fiamm Motive Power energy dry ATEX

SYSTEM SERVICE ACCESSORIES ASIA MOTIVE POWER PRODUCTS

HAWKER MODULAR CHARGERS

POWER FOR TOMORROW. Motive Power. Network Power. Chargers. Bloc Batteries. Accessories. Service

F R O N T T E R M I N A L PRODUCT GUIDE Publication No: EN-VFT-PG-001 February 2003

CHARGING SOLUTION. NexSys COMpact. Life COMpact POWER ON DEMAND

Small Traction powerbloc powerbloc dry

POWERBLOC POWERBLOC DRY

Hawker industrial batteries for rail applications: Energy solutions with system. evo rail batteries. perfect rail batteries. Ni-Cd rail batteries

Motive Power. Network Power. Chargers. Bloc Batteries. Accessories. Service

Pure Lead-Tin Technology

Batteries and more. Powered by (CE, UL & ISO9001 APPROVAL)

EUROBAT EUROBAT GUIDE FOR MOTIVE POWER VRLA BATTERIES

Motive Power. Network Power. Chargers. Bloc Batteries. Accessories. Service

Battery Range Summary

Dependable power for mission critical operations

Aircraft batteries Hawker

Technical data 50 Hz chargers Données techniques Chargeurs 50 Hz Technische Daten 50 Hz Ladegeräte Tekniska data 50 Hz laddare ME/ME II/TE 8MSE/8TSE

Deep Cycle Battery Safety. First. Battery Handling, Maintenance & Test Procedures

NorthStar Battery Company DCN: SES DCR: 1548-S09 Date:

EXTREME POWER AND ENDURANCE

Valve Regulated Lead Acid Batteries

PERFORMANCE SPECIFICATIONS

CELLYTE 12 PLF & 12PLT Range

The use of batteries in hazardous areas. 1. Type of batteries and technical evolution. March 2018

Wide operating temperature range: Our battery will operate from -30C to (-22F) to 60C when it is fully charged.

SPA AGM VRLA batteries

Automatic Battery Charger Switching mode with Micro-controlled Input: Vac / Output: 12Volt DC

FIAMM Industrial Batteries December 2012 FIAMM AGM Valve Regulated Recombination Batteries: FLX Series- Engineering Manual TABLE OF CONTENTS

EnergyCell FLA Series. Owner s Manual

INSTRUCTION MANUAL. Maintenance-free Absorbent Glass Mat technology and valve-regulated batteries. (AGM / VRLA)

Automatic Battery Charger Switching mode with Micro-controlled Input: Vac / Output: 12Volt DC

Small Traction powerbloc powerbloc dry

1. Introduction Technical Features Construction Standards Certification Technology...

UZB GENERAL DESCRIPTION 2. SHORT-FORM DATA 3. ORDER NUMBERS 4. MARKINGS BATTERY REPLACEMENT BATTERY REPLACEMENT 12V, 12AH 1/6.

Pallet Pro On-Board Power System and 6 Volt Group 27 Deep Cycle Bloc Batteries GB A Division of Exide Technologies

DataSafe HX Top Terminated Batteries 6 and 12 Volt HX

ODYSSEY PERFORMANCE SERIES BATTERIES ODYSSEY EXTREME SERIES BATTERIES

Renewable Energy Storage Solutions

Haze Battery Company Ltd

12 VOLT 30 AMP DIGITAL SOLAR CHARGE CONTROLLER

INSTRUCTIONS FOR USING METAL ilites

Haze Battery Company Ltd. Sealed Lead Acid 2 Volt Bloc. Gelled Electrolyte Range

Battery Performance Specifications

Product Guide. An Invensys company

Modular Max Range BATTERY SOLUTIONS. NEBS qualified. Reliable capacities. EverExceed power your applications

Guidelines for Battery Electric Vehicles in the Underground

AINO MICRO RANGE VRLA. Compact energy for increased security BATTERY SOLUTIONS. EverExceed power your applications

Chapter 6. Batteries. Types and Characteristics Functions and Features Specifications and Ratings Jim Dunlop Solar

IEEE IAS Atlanta Chapter

Battery. Student booklet

Vented fibre structure Nickel Cadmium batteries for stationary systems

Technical manual. Hawker SmarTech. three phase

MP V 8A Electronic Smart Charger. Instruction and Information Manual

NorthStar Battery (NSB) Telecom Application Manual

Installation & Maintenance Manual

Charging of HOPPECKE OPzV solar.power battery in Solar Applications

ADVANCED ENERGY STORAGE SOLUTIONS FOR A CHANGING WORLD

Automatic Battery Charger Switching mode with Micro-controlled Input: Vac / Output: 12Volt DC

Vehicle battery BATTERY WARNING SYMBOLS BATTERY CARE

8 Step Fully Automatic Intelligent BATTERY CHARGER 12V 5A USER S MANUAL. Charges & Maintains. Flooded (WET), MF, VRLA, AGM, GEL & Calcium batteries

Art. No. EC-315. Art. No. EC-330. Art. No. EC-340 SWITCH-MODE BATTTERY CHARGER CONTENTS IMPORTANT SAFETY PRECAUTIONS... 2

A Legacy of Excellence Since 1921

MB V 3-IN-1 JUMP STARTER WITH SPIRAL WOUND BATTERY

EXTREME POWER AND ENDURANCE

5 IN 1 JUMP START OPERATION & MAINTENANCE INSTRUCTIONS MODEL NO: JS5IN1 PART NO: LS0810

HAZE 6/12 Volt. STATIONARY 6/12 Volt BATTERIES. HAZE Battery Co. INSTALLATION and OPERATING INSTRUCTIONS. Supplied Worldwide by :

LITHIUM IRON PHOSPHATE BATTERY Multi-application - LiFePO4 Power

CONGRATULATIONS ON YOUR PURCHASE OF YOUR THUNDER BATTERY CHARGER! For your personal safety read, understand and follow the information provided in

Battery charger , A, B

PALLET PRO ON-BOARD POWER SYSTEM AND 6 VOLT GROUP 27 DEEP CYCLE BLOC BATTERIES

OPERATION & MAINTENANCE INSTRUCTIONS

30,000mWh LITHIUM-POLYMER CAR JUMP STARTER USER S MANUAL PLEASE READ THIS MANUAL CAREFULLY BEFORE OPERATION

Operating conditions of VRLA batteries in HVCBS and LVDBS Systems

Modular Max AGM Range VRLA

INSTALLATION AND OPERATING INSTRUCTIONS FOR FLOODED TUBULAR-HP AND TUBULAR-LM FAST CHARGE MOTIVE POWER BATTERIES

LITHIUM IRON PHOSPHATE BATTERY Multi-application - LiFePO4 Power

Requirements for battery discharge indicators for lead acid traction batteries

Charge Voltage(V/cell) Set point (V) (V)

User s Manual. Automatic Switch-Mode Battery Charger

Installation and Operating Procedures For C&D Technologies TRUE Front Access TEL Series Batteries

Exclusively Square. Exclusively Powerful. Exclusively Ironclad

Matson Jump Starter Operator s Manual

OPERATION & MAINTENANCE INSTRUCTIONS

Transcription:

GREEN LIGHT TO USE WHEN YOU LIKE Hawker XFC TM Bloc battery solutions for small traction applications

CONTENTS Introduction... 2 Safety Precautions... 2 Recombination Technology... 3 Range Summary... 3 Orientation...4 Battery Configurations... 4 Capacity... 4 Transportation... 4 State of Charge... 4 Storage Hawker XFC blocs only... 4 Storage Hawker XFC blocs installed in equipment... 5 Commissioning... 5 Operation... 5 Operating Temperature... 5 Discharging... 5 Discharge Characteristics... 6 Charging...12 Opportunity Charging...13 Cycle Life...13 Disposal...13 INTRODUCTION Since its introduction in the early 1990s, thin plate pure lead (TPPL) batteries have been established as a premium high performance battery suitable for a wide range of demanding applications. Today, the TPPL technology can be found in applications as diverse as emergency power, avionics, medical, military and consumer equipment. Hawker XFC TM batteries utilise the principles of advanced thin plate pure lead technology, to achieve exceptionally high performance, energy density and cycling capability. These characteristics make the Hawker XFC range ideal for use in motive power applications such as Floor-care, Pallet Trucks, AGV s, Personnel Carriers and Utility Vehicles. This manual describes the Hawker XFC product range, physical characteristics and the basic information on storage operation and maintenance. SAFETY PRECAUTIONS Motive power batteries for small traction Valve Regulated Lead Acid (VRLA) monoblocs Hawker XFC series: TPPL technology. Hawker XFC batteries are designed using proven gas recombination technology, which removes the need for regular water addition. The use of gas recombination technology for lead acid batteries has completely changed the concept for motive power. This new technology gives the user greater freedom to use valve regulated lead acid batteries in a much wide range of applications. The minimal level of gas emissions from this type of battery allows the battery to be utilised in applications where previous restrictions might have been enforced. The Hawker XFC range is considered to be maintenance free, therefore there is no need for any routine water refilling to be carried out on the battery. Pay attention to the operating instructions and keep them close to the battery. Work on batteries must only be carried out by skilled personnel! Use protective glasses and wear safety clothing when working on batteries. Adhere to the current accident prevention rules in the country where the battery is used or DIN EN 50272-3, DIN EN 50110-1. Keep children away from batteries! No smoking! Do not expose batteries to naked flames, glowing embers or sparks, as it may cause the battery to explode Avoid sparks from cables or electrical apparatus as well as electrostatic discharges. Acid splashes into the eyes or on the skin must be washed immediately with an abundance of clean water. After abundant flushing consult a doctor immediately! Clothing contaminated by acid should be washed in water. Risk of explosion and fire Avoid short circuits: do not use non-insulated tools, do not place or drop metal objects on top of the battery. Remove rings, wristwatches and articles of clothing with metal parts that might come into contact with the battery terminals. Electrolyte is highly corrosive. In the normal operation of this battery, contact with acid isn t possible. If the cell containers are damaged, the immobilised electrolyte (absorbed in the separator) is corrosive like liquid electrolyte. Batteries and monoblocs are heavy. Ensure secure installation! Use only suitable handling equipment. Lifting hooks must not damage the blocs, connectors or cables. Do not place batteries in direct sunlight without protection. Discharged batteries can freeze. For that reason, always store in a frost-free zone. Dangerous electrical voltage! Avoid short circuits: Hawker XFC batteries are capable of high short circuit currents. Caution - metal parts of the battery are always live: do not place tools or other objects on the battery! Pay attention to the hazards that can be caused by batteries Warning: Do not use any type of oil, organic solvent, alcohol, detergent, strong acid, strong alkali or petroleum based solvent or ammonia solution to clean the monoblocs. Such materials may cause permanent damage to the monobloc casing. 2

RECOMBINATION TECHNOLOGY RECOMBINATION EFFICIENCY How gas recombination works: When a charge current flows through a fully charged conventional lead acid cell, electrolysis of water occurs to produce hydrogen from the negative electrode and oxygen from the positive electrode. This means that water is lost from the cell and regular topping up is needed. However, evolution of oxygen gas and hydrogen gas does not occur simultaneously, because the efficiency of recharge of the positive electrode is not as good as the negative electrode. This means that oxygen is evolved from the positive plate before hydrogen is evolved from the negative plate. At the same time that oxygen is evolved from the positive electrode, a substantial amount of highly active spongy lead exists on the negative electrode before it commences hydrogen evolution. Recombination efficiency is determined under specific conditions by measuring the volume of hydrogen emitted from the battery and converting this into its ampere hour equivalent. This equivalent value is then subtracted from the total ampere hours taken by the battery during the test period, and the remainder is the battery s recombination efficiency and is usually expressed as a percentage. As recombination is never 100%, some hydrogen gas is emitted from Hawker XFC TM batteries through the self-regulating valve; the I gas value for this technology of battery is 1A/100 Ah C 5. RANGE SUMMARY Therefore, provided oxygen can be transported to the negative electrode, conditions are ideal for a rapid reaction between lead and oxygen: i.e. This oxygen is electrochemically reduced on the negative electrode according to the following scheme, 2e - + 2H + + 1 / 2 O 2 H 2 O and the final product is water. The current flowing through the negative electrode drives this reaction instead of hydrogen generation which would occur in a flooded cell. This process is called gas recombination. If this process was 100% efficient no water would be lost from the cell. By careful design of the constituents within the cell, gas recombination up to 99% is achieved. A B Principle of the oxygen Reduction Cycle Hawker XFC TM C Figure 1 - Principle of the oxygen Reduction Cycle RANGE SUMMARY Available Table 1 Hawker XFC specifications Monobloc Nominal Nominal KW Dimensions Weight (1) No. of Terminal Terminal Type Voltage Capacity rating L W Box Terminal [Kg] cycles (2) Type Layout [V] [C 5 ] Height Height [mm] [mm] [mm] [mm] 12XFC25 12 25 0.059 250 97 147 144 9.6 1200 M6 F (3) A 12XFC35 12 35 0.085 250 97 197 194 13.2 1200 M6 F (3) A 12XFC58 12 58 0.14 280 97 264 248 19.1 1200 M8 F C 12XFC82 12 82 0.197 395 105 264 248 27.2 1200 M8 F C 12XFC85 12 85 0.198 302 175 223 227 31.5 1200 M6 F (3) B 12XFC115 12 115 0.273 338 173 272 273 43.0 1200 M6 F (3) B 12XFC130 12 130 0.312 455 173 238 238 47.6 1200 M6 F C 12XFC155 12 155 0.373 455 173 273 263 53.1 1200 M6 F C 12XFC158 12 158 0.383 561 125 283 263 50.8 1200 M8 F (4) C 12XFC177 12 177 0.433 561 125 317 297 58.8 1200 M8 F (4) C (1) +/- 3% (2) 60% Depth of discharge max (3) Can be fitted with SAE terminal (4) Can be fitted with M6 Male front terminal 3

ORIENTATION CAPACITY Hawker XFC TM batteries can be mounted in any orientation except inverted. BATTERY CONFIGURATIONS Hawker XFC blocs may be configured into a battery comprising series/parallel arrays, with the maximum number of parallel strings limited to 2. It is paramount that the cable lengths within each string are equal. Only EnerSys approved components/ parts must be used in conjunction with Hawker XFC product. The nominal capacity of the Hawker XFC TM bloc series is rated in Ah at the 5 hour discharge rate [Ah C 5 ]. Table 2 provides available capacity as function of discharge rates. Capacities / Ah at T = 30 C Monobloc C1 C3 C5 Type (U end = 1.6 Vpc) (U end = 1.7 Vpc) (U end = 1.7 Vpc) 12XFC25 20.3 23.5 25 12XFC35 28.9 33.6 35 12XFC58 45.8 55.8 58 12XFC82 65 76.5 82 12XFC85 67 80 85 12XFC115 85.2 106.3 115 12XFC130 98.1 120.3 130 12XFC155 117 145.5 155 12XFC158 124 150.6 158 12XFC177 138 168.5 177 Table 2 Capacity at different discharge rates TRANSPORTATION Hawker XFC batteries are classified as non-spillable wet electric storage batteries and may be shipped by air or ground transportation without restriction. STATE OF CHARGE The open circuit voltage of the individual Hawker XFC bloc prior to installation can be used as an approximate guide to the state of charge (SOC) of the bloc. Figure 2 also shows the influence of storage temperature on the charge retention characteristics. Hawker XFC batteries are in compliance with requirements of: 1) US Dept of Transportation - 49 CFR Section 173.159 para d 2) ICAO/IATA Packing Instruction 872, Special Provision A67 3) IMDG Class 8, UN ID 2800 special provisions 238 4) ADR 2011 and RID 2011 Special Provisions 238, 295 and 598 and are classified as Non-spillable and exempt from hazardous goods regulations when securely packed and protected against short circuits. OPEN CIRCUIT VOLTAGE 13.20 13.14 13.08 13.02 12.96 12.90 12.84 12.78 12.72 12.66 12.60 12.54 12.48 12.42 12.36 12.30 12.24 STATE OF CHARGE AS A FUNCTION OF OPEN CIRCUIT VOLTAGE 0 5 10 15 20 25 30 35 40 MONTHS 20 C 30 C 40 C 100 96 92 87 83 79 74 70 65 61 57 52 48 44 39 35 STATE OF CHARGE [%] Figure 2 Open circuit voltages state of charge STORAGE INDIVIDUAL HAWKER XFC BLOCS This data in this section only apply to batteries in storage not fitted to equipment. Batteries are dispatched from the manufacturer in a fully charged condition. The state of charge will decrease with storage. All batteries lose their stored energy when allowed to stand open-circuit, due to parasitic chemical reactions. Self- discharge is also strongly influenced by temperature; high temperatures greatly reduce storage life (fig.2 above). It is recommended that the fully charged battery should be stored in a cool dry place, ideally below 20 C. The battery has a maximum inspection-free storage life of 2 years, if stored at or below 20 C, after which a refresh charge should be administered. However, it is advisable to conduct an inspection and open circuit voltage check after 12 months. If the open circuit voltage falls below 12.6 volts the battery should be recharged using an approved EnerSys XFC charger. The battery may be stored for up to 5 years without degradation of performance provided that an open circuit voltage (OCV) check is conducted every 12 months. When stored in temperatures in excess of 30 C (86 F), the battery should be OCV checked every 6 months. 4

STORAGE HAWKER XFC BLOCS INSTALLED IN EQUIPMENT Some equipment will continue to draw very low power loads from the battery when not in service resulting in battery discharge rate greater than shown in figure 2 and described in the previous section. Consequently all sources of electrical power drain must be removed from the battery whilst in transit, storage or extended periods of time out of service. This includes disconnecting the Wi-iQ (if fitted) from the battery. Failure to comply with the above will result in premature battery failure. Also refer to comments in opportunity charging section relating to short storage periods between equipment usage. COMMISSIONING The Hawker XFC series monoblocs are supplied in a charged condition. The battery should be inspected to ensure it is in perfect physical condition. Check: 1. The battery cleanliness. Before installing, the battery compartment has to be cleaned. 2. All cables and crimped connectors are in good condition to support high electrical currents. 3. The battery and cables have a good contact to terminals and the polarity is correct. Otherwise the battery, vehicle or charger could be severely damaged. 4. Ensure that all insulation covers are fitted correctly. 5. It is extremely important to ensure the integrity of battery connections. Soldered connections are preferred for battery plugs and post clamps. If soldering is not possible, multi-point crimping must be used. NOTE: Flexible cable or braid connectors must be used for all monobloc connections. Appropriate fastener kits must be used and approved parts. These can be supplied in EnerSys approved accessory kits. Integral to the fasteners system is an appropriate locking washer spring or flat washers must not be used. Connectors must be adequately fastened (see table 3) with the locking washer in place to maintain contact integrity when exposed to operational shock/vibrations. Monobloc Terminal torque [Nm] Terminal torque [Nm] Type Standard Terminal Terminal Adapter 12XFC25 12XFC35 M6 Female 6.8 Nm SAE 6.8 Nm 12XFC85 12XFC115 12XFC58 M8 Female 9.0 Nm Not applicable 12XFC82 12XFC130 M6 Female 9.0 Nm Not applicable 12XFC155 12XFC158 M8 Female 9.0 Nm M6 Male 9.0 Nm 12XFC177 Front Terminal between +5 C and +45 C, outside of this range must be approved by the EnerSys Technical department. Optimal battery life is obtained with the battery at a temperature of 25-30 C Higher temperatures shorten the life of the battery (according to IEC1431 technical report), lower temperatures reduce the available capacity. The upper temperature limit is +55 C and batteries should not be operated above this temperature. The capacity of the battery changes with temperature and falls considerably under 0 C. The optimum lifetime of the battery depends on the operating conditions (moderate temperature and moderate depth of discharge e.g. 40-60% C 5 ). It is mandatory that the depth of discharge does not exceed 80% of the nominal C 5 capacity. Figure 5 and 6 show relationship between depth of discharge and cycle life. The battery obtains its full capacity after about 3 charging and discharging cycles. OPERATING TEMPERATURE Hawker XFC TM batteries and EnerSys approved chargers are designed for use within an ambient temperature range of +5 C to +45 C. For use outside this range, you should consult with EnerSys APPLICATION ENGINEERING AUTHORITY. Applications outside the recommended temperature range will be considered but it will be mandatory to use an EnerSys charger with communication capability (Life iq TM ) and the battery must be equipped with Wi-iQ monitoring device to manage the charge profile in accordance with the battery temperature. The upper temperature limit is +55 C and batteries should not be operated above this temperature. DISCHARGING The valves on the top of the battery must not be sealed or covered. Electrical connections (e.g. plugs) must only be made or broken in the open circuit condition. Discharges over 80% of the rated capacity are categorised as deep discharges and are not acceptable as they reduce considerably the life expectancy of the battery. Discharged batteries MUST be recharged immediately and MUST not be left in a discharged condition. Note: The following statement only applies to partially discharged batteries. Discharged batteries can freeze. Limit the discharge to 80% DOD. The presence of a discharge limiter is mandatory and cut-off voltage must be set at the value detailed in table 4, when discharging with currents in the range of I 0.5 to I 5. At lower currents please seek advice from the EnerSys Application Engineering Authority. Table 4 - Cut-off voltage limits Cut-off voltage setting [Vpc] 60% DOD 1.96 V 80% DOD 1.92 V Table 3 Torque settings Use special coding systems for maintenance free batteries for the charging plug-and-socket devices to prevent accidental connection to the wrong type of charger. Never directly connect an electrical appliance (for example: warning beacon) to a part of the battery. This could lead to an imbalance of the cells during the recharge, i.e. a loss of capacity, the risk of insufficient discharge time, damage to the cells and VOIDS THE BATTERY WARRANTY. Charge the battery before commissioning. Only blocs with the same state of charge should be connected together. The specified torque loading for the bolts/screws of the end cables and connectors are detailed in the table 3. OPERATION DIN EN 50272-3 Safety requirements for secondary batteries and battery installations. Part 3 traction batteries is applicable to this product range. The nominal operating temperature is 30 C. The optimum lifetime of the battery depends on the operating conditions (temperature and depth of discharge). The ambient temperature range of use for the battery is 5

DISCHARGE CHARCTERISTICS The following graphs show detailed discharge characteristic of the Hawker XFC range to an end point voltage of 1.75Vpc @ 30 C. 12XFC25 PERFORMANCE DATA @ 30 C 12XFC35 PERFORMANCE DATA @ 30 C Constant current Discharge [A] 34.7 19.9 7.76 4.95 3.21 2.67 1.48 Constant current Discharge [A] 48.8 29.3 11.1 7.01 4.65 3.82 2.08 6

12XFC58 PERFORMANCE DATA @ 30 C Constant current Discharge [A] 80.7 47.4 18.5 11.7 7.59 6.18 3.17 12XFC82 PERFORMANCE DATA @ 30 C Constant current Discharge [A] 105.0 62.7 25.4 16.3 11.2 9.21 5.09 7

1000 12XFC85 PERFORMANCE DATA @ 30 C 100 10 1 0.1 1 10 100 Constant current Discharge [A] 116.0 67.0 26.7 17.0 11.5 9.5 5.0 1000 12XFC115 PERFORMANCE DATA @ 30 C 100 10 1 0.1 1 10 100 Constant current Discharge [A] 140.3 85.2 35.4 23.0 14.9 12.2 6.4 8

1000 12XFC130 PERFORMANCE DATA @ 25 C 100 10 1 0.1 1 10 100 Constant current Discharge [A] 165 98.1 40.1 26.7 18.2 15 7.7 1000 12XFC155 PERFORMANCE DATA @ 25 C 100 10 1 0.1 1 10 100 Constant current Discharge [A] 195.00 117.00 48.50 31.00 20.80 17.03 9.16 9

12XFC158 PERFORMANCE DATA @ 30 C Constant current Discharge [A] 196.1 120.0 49.5 31.8 21.1 17.2 9.35 12XFC177 PERFORMANCE DATA @ 30 C Constant current Discharge [A] 217.9 133.5 55.4 35.6 23.6 19.3 10.5 10

CHARGING Charging the Hawker XFC TM batteries correctly is a critical factor to its life expectancy and performance, failure to do so will result in premature failure. To ensure that the Hawker XFC batteries are correctly charged, EnerSys has developed a fast charge algorithm for cyclic applications to rapidly and safely charge this technology of batteries. EnerSys have a full range of chargers available that can be purchased to be used with your Hawker XFC battery. Charging must only be carried out where adequate ventilation is available and must not be carried out in confined spaces. Refer to DIN EN 50272-3 section 6. Hawker XFC batteries can be quickly charged with an approved EnerSys XFC charger. Figures 3 and 4 below show their exceptional fast charge characteristics at varying levels of DOD and inrush currents. TIME TO 80% STATE OF CHARGE AS A FUNCTION OF DEPTH OF DISCHARGE & RECHARGE CURRENT TIME TO 80% STATE OF CHARGE (HRS) 2.4 2.0 1.6 1.2 0.8 0.4 0.32C 5 Amps 0.4C 5 Amps 0.5C 5 Amps 0.6C 5 Amps 0.7C 5 Amps 0 0 10% 20% 30% 40% 50% 60% 70% 80% 90% % DEPTH OF DISCHARGE Figure 3 Recharge time return 80% of discharged Ah s As an example, consider a 100Ah battery discharged by 60Ah (to 60% Depth of Discharge), leaving residual capacity of 40Ah. 48Ah will be returned after 0.8hrs of charge with inrush current 0.6C 5 A. Battery state of charge after 0.8 hours will be approximately 86% as the recharge process is not 100% efficient. TIME TO 100% STATE OF CHARGE AS A FUNCTION OF DEPTH OF DISCHARGE & RECHARGE CURRENT 4.5 TIME TO 100% STATE OF CHARGE (HRS) 4 3.5 3 2.5 2 1.5 1 0.5 0.32C 5 Amps 0.4C 5 Amps 0.5C 5 Amps 0.6C 5 Amps 0.7C 5 Amps 0 0 10% 20% 30% 40% 50% 60% 70% 80% 90% % DEPTH OF DISCHARGE Figure 4 Recharge time return 100% of discharged Ah s Note: Hawker XFC TM bloc batteries are designed to be charged with charging rates in range 0.32C 5 to 0.7C 5. Charging at rates outside this range can affect the performance and life expectancy of the battery. Contact EnerSys before using rates outside this range. 11

As another example, consider a 100Ah battery discharged by 80Ah (to 80% Depth of Discharge), then recharged with a 0.5C 5 inrush current, 100% of the discharged Ah (80Ah) will be returned after approximately 2.5h recharge. Increasing inrush current to 0.7C 5 reduces this to 1.8 hours recharge. The recharge process is not 100% efficient and the battery will achieve approximately 97% state of charge following the above recharge procedure. A short absorption phase after recharging the 100% discharged Ahs is required to ensure full battery recovery. EnerSys chargers are programmed to achieve such recovery and deliver the recharge capabilities shown in Figs 3 and 4. OPPORTUNITY CHARGING Hawker XFC TM batteries are suitable for partial state of charge operation, however the depth of discharge must not exceed 80% of the rated C 5 capacity and opportunity charging must be applied whenever the batteries are not being discharged i.e. break / lunch times, shift handover etc. Equipment may continue to draw low power loads when not in service, which will reduce available battery capacity. To counter this, EnerSys recommend that the battery/charger remain connected to the main power supply between equipment usage periods. EnerSys approved chargers are designed to counter low power draw and preserve battery state of charge. The electrochemistry of the Hawker XFC series allows the battery to be recharged in a relatively short period of time with high inrush currents with no detrimental effect. This is possible as a result of its low internal impedance and exceptional charge acceptance. With these attributes, the SOC of the Hawker XFC battery can be maintained at almost 100% throughout the working day, making the equipment always available for use 24/7. Note: It is imperative that the battery receives a complete charge (returning the battery to 100% of its rated C 5 capacity) at least once per week. Failure to do so will have a detrimental effect on the performance and cycle life of the battery. CYCLE LIFE The life expectancy of the XFC series depends on the application and its duty cycle. While several factors affect the life of a battery, cycle life depends primarily on the depth of discharge (DOD). Depth of Discharge Cycles 10% DOD 8200 20% DOD 4096 30% DOD 2700 40% DOD 2000 50% DOD 1500 60% DOD 1200 70% DOD 900 80% DOD 700 Figure 5 illustrates this relationship between DOD and cycle life from full state of charge. HAWKER XFC, CYCLES AS A FUNCTION OF DEPTH OF DISCHARGE 10000 CYCLES 1000 100 0 10 20 30 40 50 60 70 80 90 % DEPTH OF DISCHARGE Figure 5 - CYCLE LIFE AS A FUNCTION OF DEPTH OF DISCHARGE 10%-80% (C 5 RATE) DISPOSAL Hawker XFC batteries are recyclable. Scrap batteries must be packaged and transported in accordance with prevailing transportation rules and regulations. Scrap batteries must be disposed of in compliance with local and national laws by a licensed or certified lead acid battery recycler. 12

Wherever you do business, EnerSys can support you with motive power energy. The Hawker branded battery range, matched chargers and systems provide trouble free performance under the most demanding service conditions. Our strategically located manufacturing plants are efficient and responsive with a culture of continuous improvement and added value for our business partners. EnerSys has an enviable position in technology leadership and with significant investment in research and development we intend to stay at the leading edge in product innovation. The recently developed energy solutions: IRONCLAD and Hawker XFC batteries, Lifetech, Life iq TM and LifeSpeed iq TM HF modular chargers, have defined new benefits for our customers: faster recharge, more machine availability, lower operating and investment costs, reduced carbon footprint. Our team of development engineers is driven by the desire to build the best energy solutions and works closely with our customers and suppliers to identify development opportunities. Our bias for rapid innovation means we get new products to market fast. EnerSys's integrated sales and service network is dedicated to providing our customers with the best solutions and aftersales support for their business. Whether you require 1 battery or a complete fleet of batteries, chargers, a battery handling system and a state of the art fleet management system, you can count on us. EnerSys is the world's largest industrial battery manufacturer and we are dedicated to being the best. EnerSys EMEA EH Europe GmbH Löwenstrasse 32 8001 Zürich Switzerland Phone: +41 44 215 74 10 Fax: +41 44 215 74 11 Local contact: Enersys Ltd Oak Court Clifton Business Park Wynne Avenue Swinton Manchester M27 8FF Phone: 0161 794 4611 Fax: 0161 727 3809 Please refer to the website address for details of your nearest EnerSys office: www.enersys-emea.com 2015 EnerSys. All rights reserved. All trademarks and logos are the property of or licensed to EnerSys and its affiliates unless otherwise noted. 09.2015 - Subject to revisions without prior notice. E&OE