VOC Duct and Rough Service Sensor

Similar documents
VOC Room Sensor in the BAPI-Stat 3 Enclosure with Differential Ground Configuration

CO 2 Room Sensor in the BAPI-Stat Quantum Prime Style Enclosure

BAPI-Stat 4 Room Humidity Sensor (BA/ B4 -H200 Series)

CO 2 Room Sensor in the BAPI-Stat 3 Enclosure with Common Ground Configuration

BAPI-Stat Quantum Temperature Sensor with Display and Slider Setpoint

BAPI-Stat Quantum Temperature Sensor with Display, Button Setpoint, Fan or System Mode Control

AD592/592-10K Non-Room Sensors in BAPI-Box, BAPI-Box 2 or BAPI-Box 4 BA/592-x-(BB, BB2, BB4) Temperature Sensor Instructions & Operation

Duct Averaging Transmitters BA/T#-A Temperature Transmitter Installation & Operations

AD592/592-10K Non-Room Units with a Junction Box, Weatherproof (WP) or Weather Tight (EU) Enclosure

Submersible Averaging Duct Transmitters BA/T#SA Temperature Transmitter Installation & Operations

BAPI-Stat 3 Room Sensor

Temperature Transmitters

BAPI-Com, Two Wire Multifunction Sensor with Setpoint Slider (BA/BS4SCOM) Temperature/Humidity Sensor

BAPI-Com, Two Wire Multifunction Sensor BA/BS4SCOM Temperature/Humidity Sensor Installation and Operating Instructions

Low Pressure Sensor. Overview. Specifications. Installation and Operation

GE Measurement & Control

Compact Low Pressure Sensor

Aurora Universal Protocol Converter (UPC) Zone Sensors. Submittal Data English Language/IP Units SD1582EW 06/18

Carbon Monoxide Transmitter

Differential Pressure Switch

M9106-AGx-2N0x Series Electric Non-spring Return Actuators

GS-AQ1000 VOC Indoor Air Quality Sensors

Aurora Universal Protocol Converter (UPC) Zone Sensors. Submittal Data English Language/IP Units SD1582EW 10/14

MODEL 8682 SUREFLOW ADAPTIVE OFFSET CONTROLLER

SB 2000 PUSH TO SEARCH NEXT STAG E. Aerotech, Inc. FORM: QM 1320

Immersion Temperature Sensors

SEN and SEN Outdoor Air Temperature Sensors

D-70, D-140, D-210, and D-280 Series Electric Non-Spring Return Actuators

Product Manual MNX10015 / REV B MODEL SB142, SB242. Dual Output Series Switch Boxes

Application Engineering

ComfortPoint Programmable Lon, VAV/Unitary Controllers

Safety & Installation Instructions

DPS/MPS/RAH/RPS/SWP Space Sensor

Advanced Outdoor Airflow Control, DCV Control and Alarm Solution for OA Applications Document Name: QG_EAC1100_A_R3A

Installation Instructions & Users Manual

MODELS DSH/KSH/DSV/KSV R-410A LOW-AMBIENT KIT

User Manual. Solar Charge Controller 3KW

Start-Up, Operation and Service Instructions

OPEN/CLOSE SERVICE ELECTRIC ACTUATORS OPERATION AND MAINTENANCE MANUAL COMMERCIAL AND INDUSTRIAL VALVES AND AUTOMATION

MANUAL TROUBLESHOOTING. ECM Motor. ECM / ECM-DX Series. v100 Issue Date: 08/15/ Price Industries Limited. All rights reserved.

Factory Packaged Controls. OE (AAON Part No. V12090) MODGAS-X Controller Field Technical Guide

Installation, Operation and Maintenance Manual

COMMERICAL SPLIT SYSTEM KITS AND ACCESSORIES /2014 Supersedes 8/2012

User Manual. PolyGard AT-3300_V2. Catalytic bead analog combustible Gas Transmitter Serial no. AT _V2. July 23, 2007 GAAT3300I05V2

HGM-MZ Multi-Zone Monitor Annual Maintenance And Troubleshooting Guide

MicroTech III Water Source Heat Pump Wall-Mounted Room Temperature Sensors

Silver Series Thermal Dispersion Airflow Measurement Technology

Inlet Controller TC5-ITA USER'S MANUAL. M rev. 02 K rev. 00

The IAQ50 Air Damper/Monitor Installation and Maintenance Manual

Hardware Installation. Tracer AH541 Version 2 Air-Handler Controller CNT-SVN02B-EN

Mount directly to 1.05 jackshafts. (new ZG-120 bracket shown) EFB24-S N4, EFX24-S N4(H) EFB24-S, EFX24-S (p. 21)

ZONE PRESENCE SENSOR FEATURES SPECIFICATIONS TABLE OF CONTENTS. VAV system using a Zone Presence Sensor.

Installation Instructions

Direct-Coupled ControlSet Actuators (120/180/320 in-lbs.) Installation Guide 2-7/16"

ACSI MODEL 1440 POWER SUPPLY INSTALLATION INSTRUCTIONS

Combined Ventilation Controller RVWS-T-224HA

General Description. Product Specification. Document Digital Temperature Interlock

Application Engineering

Excel 15 W7760A BUILDING MANAGER

User Manual Solar Charge Controller 3KW

Output signal active note. Measuring range rel. pressure. Electrical Data Power supply DC V, ±10%, 1.1 W

E Series CE Approved Intermittent Pilot Ignition Control

DA-053 Series. Overview. Applications. Features & Benefits. Datasheet. 53lb-in (6 Nm), Non-Spring Return Damper Actuators

Insertion Temperature/Humidity/ Dewpoint temperature Sensor HTY78X3/HY78X3/HTY78X6/HY78X6/HY79X3

Product Overview. Product Identification. Amps One CT Two CTs Three CTs

Electric Actuator Instructions

ELECTRIC ACTUATOR HVAC/BAC ELECTRIC IOM. E024, EO25, E026, EO29 & E030 Installation Operation and Maintenance Instructions TABLE OF CONTENTS

GE Sensing & Inspection Technologies

Accutrol, LLC Product Sheet H-AVC5000. US Patents 6,991,177 & 7,543,759. Specially Made for Vivarium Cage Racks

VA-908x Series Electric Rotary Actuators for Two-Position and Modulating Service

2-Color Display High-Precision Digital Pressure Switch

AE012 Enclosure for E5x Series Energy Meters With Swing Panel Kit Product Overview

FOR USE IN SOLUTION AIR HANDLING UNITS

TEGAM HTRHSERIES. High Temperature, Relative Humidity/ Temperature Probe Transmitter

Introducing NJK Precision Airflow Measuring Stations

PowerLogic High Density Metering System 4-Meter Enclosure Installation Guide

Installation Manual. Mixing Box Control Systems Installation, Operation, and Maintenance Manual. 605 Shiloh Road Plano, Texas

Output signal active humidity DC V 22DTH-51MB DC V, DC V DC V DC V DC V DC V

Manual Installation & Operation

TE-6300 Series Temperature Sensors

Condensed Version of Operator s Manual For The VI/VP700 Series Flowmeter and VI800 Series Flowmeter

Installation Instructions

The 4HR-UPS 220V ac output is provided via a Pure Sine Wave inverter, allowing it to be backed up by 2x 12V standby batteries.

ALTERNATOR REQUESTED INFORMATION. Vehicles With Dual Generator [ Engine Mount - LH ] 2007 Ford Pickup 6.0L Eng F350 Super Duty

32XR. 3 Phase Duplex Pump Control Panel (Level Transmitter Based) Quick Start Guide

Beck. The differential pressure transmitter for air with IP65

OPTIONS BLANK = No Options B = BACnet MS/TP D = Internal Transmitter Display (Ref Note 4)

ELECTRIC ACTUATOR 94OE IOM. E024, EO25, E026, EO29 & E030 Installation Operation and Maintenance Instructions TABLE OF CONTENTS

MODEL 235P INSTALLATION INSTRUCTIONS. Revision B1 Rapid City, SD, USA, 08/2009 II_235P_B1

SAVE THESE INSTRUCTIONS

SMT. Installation and Operation Manual. Model:SMT WITH MPPT TECHNOLOGY

P200 P/I Transducer. Installation, Operation, and Maintenance Instructions INTRODUCTION

Setup and Configuration Guide Universal Switch Interface

24 Volt Eco Flex LED Neon Part Numbers: LFN-2700K, LFN-5800K

Model 8144NC Fresh Air Ventilator

LTX RF LEVEL SENSOR. Instruction Manual

C50254A PH3 AIR INTAKE SHUT-OFF VALVE DODGE 6.7L CUMMINS WITH POWERGUARD SMART OVERSPEED LIMITER

Networkfleet 3500 Product Line Installation Guide

Installation Manual. English. French

Aurora Wind Interface Box

Transcription:

Overview and Identification Humans respirate Volatile Organic Compounds (VOCs) as well as CO 2. The BAPI sensor measures these VOCs and indicates space occupancy just as well as a CO 2 sensor. The advantage of the VOC sensor is that it measures air contaminants from other sources besides respiration, such as building materials, cleaners, perfumes and furniture and carpet off-gassing. Using this sensor for Demand Controlled Ventilation then is a way of achieving true indoor air quality, rather than just CO 2 dilution. A further benefit is that it requires no additional work on your part. That s because the sensor converts the VOC reading to a CO 2 equivalent level. This lets you use ASHRAE s CO 2 -based VRP schedule to ventilate. BAPI s VOC Duct Sensor samples duct air using an aspiration tube. Moving air from the duct enters the tube, is forced into the BAPI- Box enclosure and exits through the other half of the tube. The Rough Service unit features a ventilated BAPI-Box and is ideal for rough service areas such as outdoor air plenums, equipment rooms, attics, green houses and warehouses. Fig. 1: Duct VOC Sensor Fig. 2: Rough Service VOC Sensor Rough Service Unit Mounting Mount the Rough Service sensor on a solid, non-vibrating surface. Wall mounting in a room should be 3 to 5 feet above floor level. The Rough Service VOC transmitter may be mounted in any orientation. If you are mounting inside a duct or mixing box, mount with the latch facing into the moving air. Refer to local codes for further sensor/transmitter installation information. See BAPI s Coverage Area Application Note for further mounting recommendations. To get to this application note, go to www.bapihvac.com, select Resource Library from the banner. Click on Application Notes then scroll down the page to the heading Air Quality Related and chose Coverage Area and Mounting Recommendations for BAPI Indoor Air Quality Sensors. 1. BAPI recommends #10 (M5) screws of a type and length suitable for the mounting surface. Four mounting screws keeps the box from twisting, twisting may prevent the latch from operating properly. A pilot-hole makes mounting easier. Use the enclosure mounting feet to mark the pilot-hole locations. 2. Snug up the screws so that the foam backing is depressed but do not overtighten or strip the screw threads. 3. Place the provided #6 screws into the holes on each site of the lid latch to make the cover tamper resistant. Fig. 3: Mounting the Rough Service sensor to a wall Fig. 4: Drill Template, center 7/8 hole for rear conduit entry 1 of 5

Duct Unit Mounting 1. BAPI recommends placing the sensor in the middle of the duct wall, away from stratified air, to achieve the best reading. The unit should also be a minimum of 3 duct diameters from an elbow, damper or other duct restriction. 2. Drill a 1 hole for the aspiration probe. 3. Position the box so that airflow is directly into the holes on one side of the aspiration probe. There are no upstream or downstream holes, the air direction is not important. 4. Mount the enclosure to the duct using BAPI recommended #10 screws through a minimum of two of the mounting feet on opposite corners. A 1/8 pilot screw hole in the duct makes mounting easier. Use the enclosure mounting feet to mark the pilot-hole locations. 5. Snug up the screws until the foam backing is compressed about 50% to prevent air leakage but do not over-tighten. 6. Use the provided #6 screws to secure the cover for IP66 rating. 7. BAPI recommends sealing the conduit opening with fiberglass insulation. Fig. 5: Duct unit mounting Termination BAPI recommends using twisted pair of at least 22AWG and sealant filled connectors for all wire connections. Larger gauge wire may be required for long runs. All wiring must comply with the National Electric Code (NEC) and local codes. BAPI recommends wiring the product with power disconnected. Proper supply voltage, polarity and wiring connections are important to a successful installation. Not observing these recommendations may damage the product and void the warranty. Terminal Description PWR...Power, referenced to GND 12 to 24 VDC, 200 ma Peak 18 to 24 VAC, 12 VA Peak GND...To controller Ground [GND or Common] OUT...Voltage Output, VOC Signal (0 to 2,000 ppm), referenced to GND Fig. 6: Circuit Board The VOC outputs may be field configured for 0 to 5 VDC or 0 to 10 VDC outputs at any time. Set the jumpers on J3 as shown in Figures 7 and 8. Fig. 7: J3 set for 0 to 10 VDC output Fig. 8: J3 set for 0 to 5 VDC output 2 of 5

VOC Duct and Rough Service Sensor Keeping the Enclosure Air Tight After Termination For the sensor to work correctly, the wiring entrance must remain air tight. If the VOC transmitter is mounted to a hollow wall and wired through its back, or wired with conduit, it is possible that a draft of clean air may fill the enclosure through the wiring opening. This draft may prevent the unit from measuring ambient VOCs. BAPI recommends either a liquid-tight fitting or plugging the conduit at the enclosure. Liquid-Tight Fitting BAPI s Liquid-Tight Fitting (BA/LTF) allows wire cables of 0.1 to 0.3 inch outside diameter to enter the box. Tightening the collar onto the wire cable keeps the wiring entrance air tight. Fig. 9: Wires Through Foam Plug Conduit Included with the VOC transmitter is a foam plug to seal the ½ inch EMT. Place the wires into the plug as shown in Fig. 9 and then insert the plug into the conduit sealing the conduit. Sensor Start-Up At each power up, the sensor enters the start-up period for 15 minutes. The VOC output will follow the timing shown in Figure 10. During the start-up period, an optional verification/commissioning test, described below, may be performed. This test is not mandatory. It is necessary only if building commissioning requires sensor verification or if verification of VOC output is required for later troubleshooting. Optional Sensor Performance Verification and Commissioning BAPI s VOC sensor contains an adaptive, self adjusting, Volatile Organic Compound (VOC) sensor element that provides a CO 2 equivalent control signal output. When incorporated into a control strategy based on ASHRAE s Demand Control Ventilation algorithm, ventilation using this sensor will achieve true indoor air quality and not just CO 2 dilution. The fundamental performance criterion of the VOC sensor element is its dynamic sensing range. The VOC sensor element requires a minimum dynamic range of 30% for proper operation. During BAPI s verification/commissioning test, the dynamic range is tested. BAPI recommends installing the sensor and powering it for at least 48 hours before the first verification test is performed. BAPI further recommends ventilating the space such that the sensor reads 750 ppm or less CO 2 equivalent before any verification test is performed. Wait at least one hour before repeating the test. 1. Start Automatic Verification/Commissioning Test A. Remove sensor power for at least one minute and reapply. The VOC sensor will set the VOC output to zero volts. (Power ON in Fig. 10) B. Wait four minutes fifteen seconds. Fig. 10: Sensor Start-up Timeline C. The VOC sensor will set the VOC output voltage to 5% of full scale (0.25 VDC for 0 to 5 VDC, 0.5 VDC or 0 to 10 VDC outputs). Continued on next page... 3 of 5

Optional Sensor Performance Verification and Commissioning continued... D. The 5% output voltage confirms that the VOC sensor is in its verification/commissioning test. (Apply Test Gas in Fig. 10.) 2. Apply Verification Stimulus A. Apply the stimulus gas during the first minute after the output voltage is set to 5% (See Stimulus Preparation and Application). B. Read and record the VOC output voltage approximately 2 to 4 minutes following the stimulus gas application to determine the dynamic range measurement. (Dynamic Range Estimate period in Fig. 10) C. Use the graph in Fig. 8 to determine dynamic range. 3. Termination of Verification Mode A. For the last 7 minutes of the start-up period the sensor adapts to its ambient environment. The VOC sensor will maintain its output voltage at 450 ppm CO 2 equivalent. B. At 15 minutes the VOC sensor will terminate the start-up period and begin normal operation. C. The VOC output will now report the VOCs present as CO 2 equivalents. 4. Result Analysis and Recommendations The VOC algorithm requires a dynamic range of greater than 30% for proper operation. Sensors reporting a dynamic range of 30% or less should be considered for replacement. (See Fig. 12) Stimulus Preparation and Application Customer supplied 70% minimum Isopropyl Alcohol. Place 50ml of the Isopropyl Alcohol into a 200ml bottle (2oz in an 8oz bottle) with stopper and allow to reach room temperature (65 to 80 F, 18 to 27 C), a minimum of 15 minutes. 1. Using a medical grade syringe, remove the stopper from the alcohol bottle, place the tip of the syringe at least half-way into the bottle and withdraw a 60 ml sample of the ALCOHOL VAPOR. (NO LIQUID) 2. Replace the stopper on the alcohol bottle. 3. Place the end of the syringe under, or into the bottom ventilation slot of the VOC monitor s housing. 4. Empty the syringe into the sensor using one continuous motion. Fig. 11: Alcohol Bottle and Syringe included in the VOC Verification Kit (BA/VOC-KIT) Fig. 12: Acceptable Dynamic Range Output Graph 4 of 5

Diagnostics Possible Problems: General Troubleshooting Incorrect VOC Reading VOC Duct and Rough Service Sensor Possible Solutions: - Determine that the input is set up correctly in the controller and BAS software. - Check wiring at the sensor and controller for proper connections. If there is corrosion on any terminations, clean off the corrosion, re-strip the interconnecting wire and reapply the connection. In extreme cases, replace the controller, interconnecting wire and/or sensor. - Label the VOC sensor wire terminals at the sensor and controller ends. Disconnect the wires and measure the resistance from wire-to-wire with a multimeter. The meter should read greater than 10 Meg-ohms, open or OL depending on the meter. Short the wires at one end and measure the resistance from wire-to-wire at the other end. The meter should read less than 10 ohms (22 gauge or larger, 250 feet or less). If either test fails, replace the wire. - Check the power supply and controller voltage supply. - Disconnect sensor and check power wires for proper voltage (see power specs below). - Wait 15 minutes after a power interruption. - Check all software parameters. - Determine if the sensor is exposed to an external environment different from the room (conduit draft). Specifications Power: 12 to 24 VDC, 200 ma Peak 18 to 24 VAC, 12 VA Peak Sensing Elements: Micro-machined Metal Oxide Mounting: Duct or Surface Mount - screws provided VOC Detection Range: 0 to 2,000ppm CO 2 Equivalent, Analog Output Response Time: Less Than 60 Seconds (after start-up) Start-up Time: 15 minutes Operating Environment: 32 to 122 F (0 to 50 C) 5 to 95%RH non-condensing Analog Outputs: 0 to 5, or 0 to 10VDC >10KΩ impedance LED VOC CO2 Equivalent Indicator: Good, Green < 1,000 ppm Fair, Yellow = 1,000 to 1,500 ppm Poor, Red > 1,500 ppm Dimensions: See images on page 1 Material: ABS Plastic, Material Rated UL94V-0 Certifications: RoHS Warranty Period: Two years from manufacture date 5 of 5