Standard Installation Combination Fire/Smoke Damper Models: FS1, FS2, FT1, FT2, FA1, FA2, TA1, TA2, FS2C2 Fire Damper Models: MD19, MD39, MA19, MA39

Similar documents
Standard Installation Combination Fire/Smoke Damper Models: FS1(SS), FS2(SS) Fire Damper Models: MD19(SS)

Standard Installation Combination Fire/Smoke Damper Models: FS1, FS2, FT1, FT2, FA1, FA2, TA1, TA2 Fire Damper Models: MD19, MD39, MA19, MA39

Standard Installation Fire/Smoke Damper Models: FR1, FR2 Smoke Damper Models: SR1, SR2

Standard Installation Fire Damper Models: 319, 319(SS), D39

LLOYD INDUSTRIES INC.

INSTALLATION INSTRUCTIONS MODEL KFD-555

MODEL 151B FIRE DAMPER

Part # Installation,Operation and Maintenance Instructions

RECEIVING AND HANDLING INSTALLATION SUPPLEMENTS WARRANTY SAFETY WARNING:

COMBINATION FIRE/SMOKE DAMPER - CLASS F MODEL BMFSD (3 HR) / MODEL BEMFSD (1½ HR)

B. Fabricate in accordance with ASHRAE handbooks and SMACNA duct manuals. A. Submit in accordance with Division-1 and Section

SMOKE DAMPER - CLASS F MODEL BMSD

AMCA International. Guide for Commissioning and Periodic Performance Testing of Fire, Smoke and Other Life Safety Related Dampers

Fire Dampers Catalogue

CFSD Series. Product Description

Fire, Smoke, and Combination Fire Smoke Dampers

Installation, Operation and Maintenance Manual

SMOKE DAMPERS SMOKE DAMPERS SMOKE DAMPERS

BC 03. Fire Dampers FD-GB-30-AS LISTED

Installation, Operation and Maintenance Manual

Smoke Dampers. Installation Instructions

PRODUCTS BULLETIN PRODUCTS CATALOGUE

Life Safety Dampers. Fire Combination Fire Smoke Smoke Ceiling Radiation

Model SMD-302M. Modulating Smoke Damper. Application. Steel Airfoil Blades UL 555S Leakage Class II. Ratings. Size Limitations.

FSD36, FSD36LP COMBINATION FIRE AND SMOKE DAMPER 1 1 /2 HOUR UL555 RATED, UL555S LEAKAGE CLASS 2

table of contents PRODUCT SUMMARY 2

BC Motorized Fire Smoke Dampers MSFD-GB-30C1-A MSFD-GB-30C1-A LISTED

Installation, Operation, and Maintenance Manual. Automatic Fire Damper

Model FSD-211. Combination FIRE SMOKE DAMPERS Steel 3-V Blades UL 555S Leakage Class I UL Hour Fire Resistance Rating

Motorized Fire Dampers

SMD-201M. Application. Modulating Smoke Dampers Steel 3V Blades UL 555S Leakage Class I. Ratings. Operational Rating. Size Limitations.

We make dampers easy for you!

Installation, Operation and Maintenance Instructions

FSD60, FSD60LP CoMBINAtIoN FIRe AND SMoKe DAMPeR

Model CFSD-211. Corridor Ceiling FIRE SMOKE DAMPER Steel 3V Blades UL 555S Leakage Class I

Model FD-350. Static Rated Fire Dampers 3 Hour Fire Resistance Rating. Application. Ratings. Construction Standard Optional.

FAN POWERED TERMINAL UNITS

Introduction to Johnson Controls Dampers

SD-1250 and SD-1600 Series Smoke Dampers

SECTION AIR TERMINAL UNITS

MODEL 8682 SUREFLOW ADAPTIVE OFFSET CONTROLLER

B. Base occupied space sound level estimates on ARI 885. C. Terminal heating coils shall conform to ARI 410.

FAN POWERED TERMINAL UNITS

SMD-201. Application. Smoke Dampers Steel 3V Blades UL 555S Leakage Class I. Ratings. Operational Rating. Size Limitations.

Model FSD-212. Combination FIRE SMOKE DAMPERS

ATU PRODUCT CATALOG AIR TERMINAL UNITS FCI-600 CONSTANT VOLUME FAN TERMINAL UNIT Metal Industries, Inc.

Life Safety Dampers - International. Fire Combination Fire Smoke Smoke Ceiling Radiation

Model SMD-301. Smoke Damper Steel Airfoil Blades UL 555S Leakage Class I. Application. Ratings. Size Limitations. Features

Model FSD-331. Combination Fire Smoke Dampers. Application. Ratings. Features

Model FSD-331 Combination Fire Smoke Dampers

Model FSD-211. Application. Combination Fire Smoke Damper Steel 3V Blades UL 555S Leakage Class I UL /2 Hour Fire Resistance Rating.

CURTAIN TYPE FIRE DAMPER

MOTORIZED VOLUME DAMPER

SECTION HVAC POWER VENTILATORS

Positive Seal Damper Blades with Vinyl Gaskets 2.5" SERIES 3000 SIDE MOUNT - NO FLANGE ORDERING METHOD FOR BACKDRAFT & MOTORIZED BACKDRAFT DAMPERS

Series HCD Airfoil Control Damper

MODELS TSX AND TSX-S SINGLE DUCT ROUND AIR TERMINALS

MODELS SGX AND SSX SINGLE DUCT ROUND AIR TERMINALS

Fusible Link (replaceable) Horizontal Mount

SECTION DUCTWORK ACCESSORIES

SINGLE DUCT AIR TERMINAL UNITS

SECTION HVAC CONTROL SYSTEM PART 1 GENERAL 1.01 SUMMARY. A. Section Includes:

Model DFD-230 Multi-Blade Fire Damper Steel 3V Blades UL555 3 Hour Fire Resistance Rating

Model ABV Pressure Independent Automatic Balancing Valve. Application: Standard Construction: Performance: Configurations Available:

A. Product Data: For each type of product. TLC ENGINEERING FOR ARCHITECTURE - PROJECT NO AIR DUCT ACCESSORIES

Product Data. Features/Benefits. 35K Bypass Terminal. 110 to 4400 cfm

Fusible Link (replaceable) Horizontal Mount

Installation, Operation and Maintenance Manual

FAN POWERED SERIES FCI-600 CONSTANT VOLUME FAN TERMINAL UNIT SPECIFIABLE FEATURES

SECTION CENTRIFUGAL HVAC FANS

INSTRUCTION SHEET Replacement of Prefco McCabe Link Dampers with EMB2 MultiProducts Motor with Belimo FSxx Series

Model SSFSD-211. Combination Fire Smoke Damper 304 Stainless Steel 3V Blades UL 555S Leakage Class I UL Hour Fire Resistance Rating

Model DW Series Positive Pressure Guidelines for Engine Exhaust Systems

VOLUME CONTROL / REGULATING DAMPERS

Installation, Operation and Maintenance Manual

Installation, Operation, and Maintenance Instructions

MULTI-BLADE FIRE DAMPERS

4 Installation Guidelines

Variable Air Volume Dampers

HOW TO SPECIFY SDV UNITS

FSD36, FSD36LP COMBINATION FIRE AND SMOKE DAMPER

The Premium Quality Fan Coil Units for Horizontal Application Hydronic or Electric Heat

FSD60, FSD60LP COMBINATION FIRE AND SMOKE DAMPER 1 1 /2 HOUR UL555 RATED, UL555S LEAKAGE CLASS 1

Installation STUD JOIST A237R SPECIFICATIONS. Width Height Depth Weight Max. Spacing between Mounts Max. Load

RECEIVING AND INSPECTION EXAMINE ALL COMPONENTS FOR POSSIBLE SHIPPING DAMAGE PRIOR TO INSTALLATION.

RECEIVING AND INSPECTION

OSU PROJECT NO PAGE 1 02 NOV 2006 SECTION DUCTWORK ACCESSORIES

SP Standard Profile. In Duct or Flanged to Duct Install Types OPPOSED ACTION PARALLEL ACTION. Extended Rear Flange Install Type

Prefco Internal Pulley-Cable with Multiproducts Motor and damper blade springs Replacement with Belimo FS Series Actuators

Fire/combustion gas damper EKO-JBG

Model DW Series Positive Pressure Guidelines for Engine Exhaust Systems

Product Data. 35J Single-Duct Retrofit Terminal Units for Variable Air Volume Systems. 40 to 3700 cfm

Electromagnetic Door Holder/Releases

MODEL 8631-CRM/8631-CRC PRESSURA CLEAN ROOM PRESSURE MONITOR/CONTROLLER

Fire/combustion gas damper EKO-JBL

FIREGARD GILBERTS. Curtain Fire Dampers FEATURES DAMPERS 4 SFB (57.9) X UDC AUGUST 2006

Table of Contents WARRANTY...3 APPLICATION...4 MECHANICAL...5 Joint Sealant...5 Grease Duct Standard Connection...6 Collar and Adjustable Duct

SINGLE DUCT TERMINAL UNITS

2507 (IBC 2006 ONLY) 3054 (IBC 2006 ONLY) Supreme Framing System Product Catalog

VOLUME CONTROL DAMPERS

Transcription:

Standard Installation Combination Fire/Smoke Damper Models: FS1, FS2, FT1, FT2, FA1, FA2, TA1, TA2, FS2C2 Fire Damper Models: MD19, MD39, MA19, MA39 APPLICATION These dynamically rated fire/smoke and fire s are intended to restrict the passage of flame. The dynamically rated fire/smoke s are also intended to restrict the passage of smoke. When the is intended to be used as a fire rated, the standard installation requires that the is positioned so that the closed plane of the blades is within the fire rated masonry/concrete or metal or wood framed gypsum wallboard barrier. When the is to be used as a leakage rated only, the is to be installed within 24" of the smoke barrier and upstream of any duct outlets. This may be mounted in the vertical or horizontal position with the blades running horizontally. can be from either direction. When mounted in the vertical position, the may be mounted right side up or upside down and can be mounted in a fire barrier constructed of masonry/concrete or metal or wood framed gypsum wallboard materials. When mounted in the horizontal position, the must be mounted with the actuator on the top side of the floor and can only be mounted in a fire barrier constructed of masonry/concrete materials. The Model FS2C2 is approved and labeled for use in the following applications. For sizes not exceeding 24"W x 24"H the Model FS2C2 is approved and labeled for use as a vertically mounted or horizontally mounted, 1½ hour rated Fire/Smoke Damper. When used as a Fire/Smoke Damper, the installation instructions stated in this pamphlet apply. The Model FS2C2 is also approved and labeled for use as a horizontally mounted, 1 hour rated Corridor Damper. When used as a Corridor Damper, the installation instructions stated by II-FS2C-08.11 shall apply. MULTIPLE PANEL SIZE LIMITATIONS Page 1 of 6 Model Model Actuation Electric Orientation Assembly Max Panel Horizontal Max Assy 250 Max Assy 350 Max Panel Vertical Max Assy 250 Max Assy 350 FS1, FS2 36"Wx48"H 72"Wx48"H 72"Wx48"H 36"Wx48"H 48"Wx36"H 144"Wx70"H 128"Wx62"H FT1, FT2 30"Wx48"H 36"Wx48"H 60"Wx48"H 60"Wx48"H 36"Wx30"H 42"Wx36"H 126"Wx48"H 126"Wx48"H FA1, FA2 32"Wx48"H 96"Wx96"H 96"Wx96"H 32"Wx48"H 128"Wx96"H 128"Wx96"H TA1, TA2 30"Wx48"H 60"Wx48"H 60"Wx48"H 30"Wx48"H 60"Wx48"H 60"Wx48"H FS2C2 24"W x 24"H 24"W x 24"H n/a 24"W x 24"H 24"W x 24"H n/a Actuation Pneumatic Orientation Assembly Max Panel Horizontal Max Assy 250 Max Assy 350 Max Panel Vertical Max Assy 250 Max Assy 350 FS1, FS2 36"Wx48"H 72"Wx48"H 72"Wx48"H 36"Wx48"H 108"Wx48"H 108"Wx48"H FT1, FT2 30"Wx48"H 36"Wx48"H 60"Wx48"H 60"Wx48"H 36"Wx30"H 42"Wx36"H 126"Wx48"H 126"Wx48"H FA1, FA2 32"Wx48"H 96"Wx96"H 96"Wx96"H 32"Wx48"H 128"Wx96"H 128"Wx96"H TA1, TA2 30"Wx48"H 60"Wx48"H 60"Wx48"H 30"Wx48"H 60"Wx48"H 60"Wx48"H Model Actuation Orientation Horizontal Non-ized Assembly Max Panel Max Assy 165 Max Assy 212 Max Panel Max Assy 165 Max Assy 212 72"Wx60"H 72"Wx60"H MD19 36"Wx48"H 72"Wx48"H 72"Wx48"H 36"Wx48"H 126"Wx48"H 126"Wx48"H 30"Wx48"H MD39 60"Wx48"H 60"Wx48"H 36"Wx48"H 126"Wx48"H 126"Wx48"H 36"Wx30"H 64"Wx36"H 64"Wx36"H 64"Wx36"H 64"Wx36"H MA19 32"Wx48"H 32"Wx48"H 32"Wx72"H 32"Wx72"H 32"Wx72"H 32"Wx72"H MA39 32"Wx48"H 60"Wx36"H 60"Wx36"H 32"Wx48"H 60"Wx36"H 60"Wx36"H Vertical SUPPLEMENTAL INSTALLATION INSTRUCTIONS / SUBMITTAL DATA One-Side s (II-FSOS) Out-of-Wall/Floor Sleeve Extension Integral Duct Access Door Electric or Pneumatic Heat Response Device (SD-EHRD or SD-PHRD) Integral Dual Position Indication (SD-IDPI) Electric or Pneumatic Sensotherm (SD-ESOT or SD-PSOT) Flow-Rated Smoke Detector (SM-501) No-Flow Smoke Detector (2151) Transitions (SD-TRFS) Sleeves (SD-SLVFS)

INSTALLATION Page 2 of 6 1. General: The installation of the and all duct connections to the sleeve shall conform to NFPA-90A and the SMACNA Fire, Smoke and Radiation Damper Installation Guide. All duct connections shall also conform to UL555 when the is intended to be used as a fire. 2. Actuators: Dampers must be supplied with factory mounted actuators (except Model MD19, MD39 and MA19, MA39) and are intended to close automatically when sensing heat or upon loss of electrical power or release of air pressure. When this is used as a leakage rated only, it shall be arranged to operate automatically and is to be controlled by a smoke detector. See additional instructions, which detail actuator sequence of operations. Multiple actuators in a mechanically linked section that are factory wired/plumbed together have only one heat response device and one supply connection point. The supply connection point must be at the "master" actuator package, which contains the heat response device. The heat response device must be wired/plumbed between the supply connection point and the master actuator and all slave actuators. 3. Multiple Panel / Multiple Section Assembly: Large assembly sizes may require multiple factory assembled modules that ship separately. Refer to page 4 for details. 4. Sleeves: Sleeves are required for the proper installation of fire rated s, but need not be factory mounted. Dampers with factory mounted external actuators can be supplied without sleeves, but require sideplates. Dampers with factory mounted internal actuators can be supplied without sleeves or sideplates. Sleeves shall be the same gauge or heavier as the duct to which it is attached. Gauges shall conform to SMACNA or ASHRAE duct standards. A field supplied sleeve is attached to the frame with 3/16" diameter steel rivets, 1/4" diameter steel bolts, #10 steel sheet metal screws, or ½" long welds. Fasteners shall be staggered on each side of the frame on 6" maximum centers and 3-½" maximum from each corner. For Class I Fire/Smoke s, approved caulking (reference note 7) shall be applied along the perimeter between the sleeve and the on both sides. For Class II Fire/Smoke s, approved caulking (reference note 7) shall be applied along the perimeter between the sleeve and the on only one side. 5. Expansion Clearance: The opening in the wall for the fire rated shall be sized to provide expansion clearance between the sleeve and the opening. The minimum expansion clearance shall be the greater of 1 /4" or 1 /8" per foot of overall /sleeve width and height. The maximum expansion clearance shall not exceed 1 /8" per foot of overall /sleeve width and height plus 2". Example: For a with exact outside dimensions of 36"W x 48"H, the gap at the top plus the gap at the bottom must be between 0.50" and 2.5". The gap at the left side plus the gap at the right side must be between 0.375" and 2.375". The can be located anywhere in the opening and need not be centered. 6. Attachment: retaining angles shall increase in size, proportionately, so there will be a minimum of 1" overlap on the wall, including at the corners. The angles shall be flush against the barrier. The leg attached to the can turn away from or into the opening. In metal frame construction, the angles can be mounted under or over the gypsum board. In wood frame construction, the angles must be mounted over the gypsum board. The perimeter mounting angles shall be fastened on all four sides and on both faces of the to the sleeve only, with 3 /16" diameter steel or stainless steel nuts and bolts or by tack welding with beads 1 /2" ± 1 /4" in length or with #10 steel or stainless steel sheet metal screws or 3 /16" steel or stainless steel pop rivets. All connections shall be spaced on 6" maximum centers and 3" maximum from each corner (a minimum of 2 fasteners are required per side). For perimeter angle mounting on one side of the fire barrier only, reference Installation Instruction II-FSOS. retaining angles shall be a minimum of 1-1 /2" x 7 /8" x 16-GA steel. Corners of angles are not welded together for s with width or height dimensions exceeding 24". For s 24"W x 24"H or smaller, the corners of the perimeter mounting angles can be welded. Some local codes may not allow welded corners. Attachment of these angles must not restrict operation of the. retaining angles and their mounting fasteners are not typically supplied with the. 7. Caulking: Caulk shall be one of the following: Dow Corning RTV732, Silco Sil-Bond RTV 4500, General Electric IS808, or Novagard RTV300. Caulking is allowed between the retaining angles and the sleeve, and between the retaining angles and the face of the floor or wall construction. Caulking is not allowed between the sleeve and the wall or floor inside the opening. Breakaway flange caulking shall be Design Polymeric's DP1010 or Precision's PA2084T 8. Duct Connections: All connecting ducts shall not be continuous, but shall terminate at the fire sleeve. Duct connections not listed as breakaways shall be considered rigid. For rigid type duct connections, the sleeve shall be a minimum of 16-GA on s not exceeding 36" wide or 24" high or 24" diameter and 14-GA on larger units. Maximum sleeve thickness shall not exceed 10-GA galvanized steel. Dampers supplied with thinner sleeves require a breakaway connection. The following breakaway duct-to-sleeve connections may be used: Plain S Slip, Double S Slip, Inside Slip, Hemmed S Slip, Standing S Slip, Standing S Slip (Bar Reinforced), Standing S Slip (Angle Reinforced), and Standing S Slip (Alternate Bar). Breakaway joints shall have no more than two No. 10 sheet metal screws on each side and on the bottom. The screws shall penetrate both sides of the slip pocket. When a breakaway joint is used along the top and bottom duct connection, a flat drive slip no longer than 20 inches is permitted on the two sides. The is normally supplied with a factory attached sleeve (see Note 4 when field supplied sleeve). The standard factory supplied sleeve is 20-GA galvanized steel (18-GA on s wider or higher than 84") and assumes that a breakaway type duct connection will be employed. Plain "S" Slip Double "S" Slip Inside Slip Joint Hemmed "S" Slip Standing "S" Slip Standing "S" Slip (Bar Reinforced) Standard "S" Slip (Angle Reinforced) Standard "S" Slip (Alternate Bar) The factory supplied round/oval transition provides the breakaway connection if the following conditions are satisfied. 1. Round duct diameter is no larger that 36". 2. Oval duct size is no larger than 71"W x 30"H. 3. Duct gauges conform to the SMACNA or ASHRAE standard. 4. An oval duct or round duct less than or equal to 24" is attached to the transition collar with #8 sheet metal screws (a minimum of 4 fasteners per connection). A round duct diameter greater than 24" is attached to the transition collar with #10 sheet metal screws (a minimum of 5 fasteners per connection). Dampers with round/oval transitions that fall outside of these restrictions must use a 4" wide drawband connection as shown in the SMACNA Fire, Smoke, and Radiation Damper Installation Guide. 9. Maintenance: Dampers shall be maintained at intervals as stated in NFPA 90A and 92A. Local codes or building conditions may require more frequent inspections and maintenance. A duct access door is to be located on the jackshaft side of each for periodic inspection and maintenance.

Page 3 of 6 STANDARD MOUNTING DETAILS Vertical, 2-Side Retaining, Masonry Horizontal, 2-Side Retaining, Masonry Expansion Clearance Non- Non- Expansion Clearance Vertical, 2-Side Retaining, Metal Stud Vertical, 2-Side Retaining, Wood Stud Expansion Clearance Expansion Clearance Non- Non-

MULTIPLE PANEL / MULTIPLE SECTION INSTALLATION DETAILS Page 4 of 6 Fire/Smoke Dampers (Models FS1, FS2, FT1, FT2, FA1, FA2, TA1, TA2) 1. Damper assemblies ordered without factory mounted sleeves are limited in size, so that the entire assembly ships as a single section. 2. Multiple panel high assemblies are electrically/pneumatically, but not mechanically linked between top and bottom panels if assembled within a common sleeve. Large sizes may require multiple sleeve sections - multiple sleeve sections are not mechanically or electrically/ pneumatically linked. 3. Multiple panel wide assemblies are mechanically and electrically/pneumatically linked if assembled within a common sleeve. Large sizes may require multiple sleeve sections - multiple sleeve sections are not mechancially or electrically/pneumatically linked. 4. Damper assembly sections that are not mechanically or electrically/pneumatically linked each have their own heat response device and their own supply connection point, such that they operate independently. Multiple actuators within a linked section are factory wired/plumbed together. 5. Damper assembly sections that are mechanically and electrically/pneumatically linked share a single heat response device and a single supply connection point. Multiple actuators within a linked section are factory wired/plumbed together. 6. Damper assemblies that ship in multiple sections shall be fastened together using 1 /4" diameter steel bolts, lockwashers, and nuts. Fasteners shall be on 6" maximum centers on both faces of the frame. Fire Dampers (MD19, MD39, MA19, MA39) 1. Damper assemblies ordered without factory mounted sleeves are limited in size, so that the entire assembly ships as a single section. 2. Multiple panel high assemblies are not mechanically linked between top and bottom panels. 3. Multiple panel wide assemblies are not mechanically linked between panels. 4. Damper assembly sections that are not mechanically linked each have their own heat response device, such that they operate independently. 5. Damper assemblies that ship in multiple sections shall be fastened together using 1 /4" diameter steel bolts, lockwashers, and nuts. Fasteners shall be on 6" maximum centers on both faces of the frame. ELECTRIC WIRING SCHEMATICS Notes 1. All wiring to be in accordance with N.E.C. (NFPA 70). 2. Refer to actuator label for appropriate voltage. 3. Connect incoming ground to the actuator assembly. 4. If the actuator remains electrically energized, yet the remains in the closed position, check to ensure that the reset button on the heat response device is depressed. Electric Heat Response Device (EHRD) Integral Dual Position Indication (IDPI) Temp. Disc Blue Red Yellow Gray Black Red or White NC Smoke Detector actuator mounting location Integral Dual Position Indication (IDPI) Wiring Chart full open full close closed circuit mid-stroke external left red / blue yellow / gray none L1 (Hot) See Actuator for Appropriate Voltage L2 (Neutral) external right yellow / gray red / blue none internal left yellow / gray red / blue none internal right red / blue yellow / gray none * This wiring is opposite if the actuator is rotated 90º, so that it is parallel to the duct.

Page 5 of 6 Low Temp. Disc ELECTRIC WIRING SCHEMATICS (CONT.) Electric/Pneumatic Sensotherm (ESOT/PSOT) with included Integral Dual Position Indication (IDPI) High Temp. Disc or E.P. Valve or E.P. Valve Blue Red Yellow Gray Black Orange Red or White Damper Close NC L1 (Hot) Smoke Detector SPDT Center Damper Re-open See Actuator for Appropriate Voltage L2 (Neutral) actuator mounting location Integral Dual Position Indication (IDPI) Wiring Chart full open full close closed circuit mid-stroke external left red / blue yellow / gray none external right yellow / gray red / blue none internal left yellow / gray red / blue none internal right red / blue yellow / gray none ESOT/PSOT Wiring, Test, and Operating Instructions * This wiring is opposite if the actuator is rotated 90º, so that it is parallel to the duct. Damper is supplied with one low temperature thermal disc and one high temperature thermal disc. All s require a master control switch (supplied by others) for re-openable operation. CUSTOMER WIRING 1. Connect input power lead L1 from the normal closed position lead of the (MCS) switch to lead L1. Note: If a smoke detector or other sensing device is to be employed, its NC contact set should be wired in series between the (MCS) position switch normal wire and lead L1. 2. Connect incoming lead L2 to lead L2. 3. Connect the reopen switch lead from (MCS) to orange lead. 4. Connect the incoming ground lead to the wiring enclosure. 5. Install IDPI (if used) per the schematic. 6. Replace enclosure cover. CIRCUIT TEST 1. Place (MCS) switch in close position. 2. Apply power. Result: The closed indicator light (if used) should be on and the blades closed. 3. Transfer (MCS) switch to re-open position. Result: The blades should open; the closed indicator light (if used) should go off and the open indicator light (if used) should go on. 4. Transfer (MCS) switch to the normal position. Result: The blades should remain open and the open indicator light (if used) should remain on. 5. Transfer the (MCS) switch to the closed position. Result: The blades should close; the open indicator light (if used) should go off and the closed indicator light (if used) should go on. EMERGENCY OPERATION (SMOKE MANAGEMENT) 1. MCS closed position: Damper will close regardless of whether the thermal switch device has activated or not and regardless of the command from the smoke system. 2. MCS re-open position: If the has not been exposed to an elevated temperature higher than its rating, the will open. Also, the will open regardless of whether the low temperature thermal disc (165ºF or 212ºF) has activated or not and regardless of a command from additional sensing devices, such as a smoke detector. NOTE: If the master control switch (MCS) is in the re-open position and the high temperature thermal disc has not been tripped, the will remain open regardless of whether the low temperature thermal disc and/or other sensing devices have tripped or not. If the has been exposed to an elevated temperature higher than its temperature degradation rating, or if the electrical or pneumatic supply has been disconnected, the will close and remain closed regardless of any (MCS) position.

Page 6 of 6 FRAMING DETALS (METAL OR WOOD 1 HOUR AND 2 HOUR RATED BARRIERS) Ceiling Runner 12" 24" O.C. Max 16" O.C. Max Section A-A Runner 90º Bend B A A B Local Codes May Require Double Header Min. 2-1/2" Runner 2 Fasteners 2" Min. 2-1/2" Stud 2 Fasteners 2" Panhead Screws (Metal Studs) Nails (Wooden Studs) 4 Per 90º Bend Min. 1" Min. 1" Min. 2-1/2" Stud or Runner Section B-B (1 Hour Rated Fire Barrier) Min. 1/2" Thick Filler Piece (See Note 4) Min. 2-1/2" Stud or Runner Floor Runner Fire Damper Sleeve Section B-B (2 Hour Rated Fire Barrier) Min. 1/2" Thick Gypsum Wallboard Drywall Screws (Metal Studs) Dw Screws or Nails (Wood Studs) (May Be Reversed Providing Adequate Clearance is Maintained) (See Note 2) Min. 1/2" Thick Gypsum Wallboard Drywall Screws (Metal Studs) Dw Screws or Nails (Wood Studs) (May Be Reversed Providing Adequate Clearance is Maintained) NOTES: 1. These illustrated partition designs have successfully been tested in conjunction with 1-1/2 hour classified fire s, for additional designs, reference Underwriters Laboratories, Inc. Fire Resistance Directory. Specific framing requirements of openings may vary with the Local Authority that has jurisdiction. Specific framing requirements should be provided in the architectural and structural drawings. 2. Reference the 's installation instructions regarding the approved method of attaching the to the sleeve, attaching the retaining angles to the sleeve, required expansion clearances, sleeve gauge, etc. Type of framing does not affect the stated required expansion clearance. 3. Gypsum panels surrounding the opening are to be fastened to all stud and runner flanges, 12" o.c. maximum. 4. When wooden studs are used, filler pieces must be installed around the entire opening. Filler pieces are optional when metal studs are used (consult local codes to determine if filler pieces are required). Filler pieces are to be double screwed (or nailed to wooden studs) on 12" max. centers to the web of runners and studs. Min. 1/2" Thick Filler Piece (See Note 4) Fire Damper Sleeve (See Note 2) 5. Double jamb studding shown and required when opening width or length exceeds 36". Single jamb studding acceptable for openings 36"W x 36"H and smaller.