PowerChute TM Network Shutdown in Redundant UPS Configurations

Similar documents
APC APPLICATION NOTE #98

PowerChute TM Network Shutdown v3.1. User Guide. VMware

PowerChute TM Network Shutdown v4.0. User Guide. VMware

User Guide. PowerChute Network Shutdown v4.1 Standard D /2015

PowerChute Network Shutdown v4.2 Release Notes

Smart-UPS: legendary uninterruptible power. Intelligent, reliable protection for servers and networks

Smart-UPS with APC SmartConnect Maintain business certainty with intelligent network power protection

Smart-UPS On-Line Lithium-ion UPS 230V

Smart-UPS: legendary uninterruptible power. Intelligent, reliable protection for servers and networks

Smart-UPS On-Line Lithium Ion UPS 230V. Single-phase, double conversion online UPS with Li-Ion batteries and advanced management features

Unity output power factor single-phase double-conversion, online UPS with advanced management features

Smart UPS On Line 120/208 V

Smart UPS On Line 120/208 V

Smart-UPS On-Line 230 V

Galaxy VM. From 160 kva to 1000 kva. Three-phase power protection. Galaxy VM trusted partner for your business continuity. schneider-electric.

Galaxy VM. From 160 kva to 1000 kva, 160 kva or 200 kva modular approach. Three-phase power protection

APC Smart-UPS. GUIDE SPECIFICATIONS FOR 1000VA & 2000VA Smart-UPS 230VAC Uninterruptible Power Supply

S2000 PRODUCT RANGE. Ultra compact

IBM UPS Extend Run Battery Pack Operation and Setup Guide

Integration of PowerChute Business Edition with EcoStruxure IT

Operation. Symmetra PX 48, 96, and 160 kw 400 V 100 kw 208 V

Maintain business certainty with intelligent and efficient network power protection for your network closets and server rooms.

Back-UPS 650 VA 230 V with AVR (BX650CI-ZA)

Web/SNMP Management Card Event Support Chart

Galaxy VM. From 160 kva to 1000 kva Three-phase power protection. apc.com/products

Emerson SmartCabinet for DELL VRTX Technical Guide

Allen-Bradley. User Manual for 8000/10000 VA UPS. Tower/Rack-Mount 6U Uninterruptible Power Supply

QUICK INSTALLATION GUIDE

Operation Manual. Smart-UPS. Uninterruptible Power Supply VA Short-depth Rack-Mount with Lithium-ion batteries. 120 Vac

SecureUPS On-Line 120V AC Output, 1300VA

Symmetra PX. 48, 96, and 160 kw 400 V 100 kw 208 V. Operation 09/

3000VA 120/208/230VAC

User Manual Back-UPS BX650CI-MS 230 Vac with AVR

APC Smart-UPS RT. GUIDE SPECIFICATIONS FOR 2400VA and 3000VA Smart-UPS RT 100 and 120VAC Uninterruptible Power Supply

Installation Guide Smart-UPS On-Line SRT1000/1500 UXI-NCLI, SRT1000/1500 UXI-LI, Tower/Rack-Mount

Operation Manual. Smart-UPS. Uninterruptible Power Supply. 750/1000/1500 VA Short-depth Rack-Mount with Lithium-ion batteries.

Smart-UPS RC External Battery Pack Tower/Rack-Mount 4U

for OpenVMS APC Corporate 132 Fairgrounds Road P.O Box 278 West Kingston, RI Tel: (800) 800-4APC or Fax:

Operation Manual. Smart-UPS. Uninterruptible Power Supply. 750/1000/1500/2200/3000 VA Tower / Rack-Mount 2U. 120 Vac/230 Vac

Allen-Bradley. User Manual for 3000/5000 VA UPS. Tower/Rack-Mount 3U Uninterruptible Power Supply

Relay Driver Applications Guide

Up to 98% efficient under full load Similar runtimes to the previous 3u model

Start UP Guide. Symmetra LX Tower Rack-Mount. UPS Models 200 V, 4-8 kva 208/240 V, 4-8 kva 220/230/240 V, 4-8 kva

APC by Schneider Electric Smart-UPS OnLine with Lithium Ion Batteries Uninterruptible Power Supply 1 kva, 1.5 kva 230 V Solution

APC by Schneider Electric Smart-UPS On-Line SRT Guide Specification 5 kva 6 kva, 8 kva, 10 kva models 208 V, 240 V Solution

{ The uniflow Release Station }

Smart-UPS VT APC Smart-UPS VT 30kVA 208V w/4 Batt. Modules, Start-Up 5X8, Internal Maintenance Bypass

MGE Galaxy PW kva 480 V. Operation

Smart-UPS RC External Battery Pack Tower/Rack-Mount 4U

Symmetra PX 100 kw. Scalable from 10 kw to 100 kw Modular, scalable, high-efficiency power protection for data centers

User Manual Digital Energy Uninterruptible Power Supply ML Series UPS VA GE Digital Energy Power Quality

Symmetra PX. Industry-leading efficiency, availability, and performance for small, medium, and large data centers and mission critical environments

Deploying Smart Wires at the Georgia Power Company (GPC)

Quick Setup Guide. WARNING! Connect this product to an AC power source whose voltage is within the range specified on the product's nameplate.

User s Manual. English. APC Smart-UPS RT. 3000/5000 VA VAC 3U Tower/Rack Mount Uninterruptible Power Supply

User Manual. Digital Energy Uninterruptible Power Supply ML Series UPS VA. GE Digital Energy Power Quality. GE imagination at work

Operation Manual. Smart-UPS. Uninterruptible Power Supply. 750/1000/1500/2200/3000 VA Tower 100/120/230 Vac. 500 VA Tower 100 Vac

Symmetra PX 96/160. Scalable from 16 kw to 160 kw Modular, scalable, high-efficiency power protection for data centers

POWER+ PREMIUM CBS. BS-EN Emergency electrical installations Electric power systems Emergency lighting Escape lighting

Model ES VA to VA SINGLE PHASE UNINTERRUPTIBLE POWER SYSTEM

Installation and Operation

ValveLink SNAP-ON Application

Operation. Smart-UPS TM VT Rack-mounted kva 200/208 V

APC Smart-UPS RT UX. User s Manual. Models SURT1000UXI and SURT2000UXI 220/230/240 Tower/Rack Mount Uninterruptible Power Supply.

Installation Guide Smart-UPS X 2000/2200/3000 XL Tower/Rack-Mount 4U

Installation and Operation Smart-UPS SUA500PDR

One Solution You Can Trust!

Operation Manual. Smart-UPS Uninterruptible Power Supply. Rack-Mount 2U. 750/1000/1500 VA 120/230 Vac VA 120 Vac. 100/120/208/230 Vac

Match 19" GE Digital Energy. Uninterruptible Power Supply VA. Technology for the Digital World. Match 19" UPS.

Installation Guide Smart-UPS On-Line SRT1000/SRT1500 XLA Tower/Rack-Mount

Operation Manual. Smart-UPS. Uninterruptible Power Supply. Rack-Mount 1U. 1200/1500 VA 100/120/230 Vac

Back-UPS Intelligent, reliable protection for your home or small business Certainty in a Connected World

MKN-DSP SERIES - THREE PHASE

Installation and Operation

APC Smart-UPS RT UXI/UXICH

Features and Benefits

An ISO 9001:2008 Registered Company

License Model Schedule Actuate License Models for the Open Text End User License Agreement ( EULA ) effective as of November, 2015

Installation and Operation Manual Smart-UPS Tower 220/230/240 Vac SRC1000ICCIND; SRC1000UXIND

Symmetra PX 250/500. Scalable from 100 kva kw to 500 kw, parallel capable up to 2,000 kw

User Manual. English. APC Smart-UPS. 750/1000/1500 VA 100/120/230 Vac 2U Rack-Mount Uninterruptible Power Supply

Back-UPS ES APC Back-UPS ES, 6 outlet 350VA, 120V, without auto shutdown software

IBM CMM Quick Reference Guide

Vanpool Regional Administration

Operation Manual. Smart-UPS Uninterruptible Power Supply. 1000/1500/2200/3000 VA 220 Vac. Rack-Mount 2U

Installation Guide Smart-UPS 1200/1500 VA 100/120/230 Vac Rack-Mount 1U

POWERCOMMAND CLOUD REMOTE MONITORING SYSTEM

One-Stop Service: Monitoring and Managing.

PRODUCT PORTFOLIO. Electric Vehicle Infrastructure ABB Ability Connected Services

Hand-Held and Electronic Logging Devices (ELDs)

Symmetra PX. 48, 96, and 160 kw 400 V 100 kw 208 V Operation 07/2017.

Secure Power Solution international guide

Vehicle Use Case Task Force E: General Registration & Enrollment Process

Operation Manual. Smart-UPS Uninterruptible Power Supply. 750/1000/1500/2200/3000 VA 100/120/230 Vac. 500 VA 100 Vac. Tower

MODULYS RM GP. Rack-mounted modular UPS system. Green Power 2.0 range up to 4 x 25 kw

MODULYS RM GP. Rack-mounted modular UPS system Green Power 2.0 range up to 4 x 25 kw

Network and Datacenter Power Solutions Smart-UPS DP (4 to 10 kva)

Features and Benefits

On Line UPS. LUC 1000E / LUC 2000E / LUC 3000E User Manual

DEPARTMENT OF TRANSPORTATION. National Highway Traffic Safety Administration. [Docket No. NHTSA ; Notice 2]

Transcription:

PowerChute TM Network Shutdown in Redundant UPS Configurations By Sarah Jane Hannon ABSTRACT PowerChute TM Network Shutdown software works in conjunction with the UPS Network Management Card to provide graceful, unattended shutdown of multiple computer systems over a network. UPS s can support the load in several different physical configurations. This Application Note explains the differences between Single and Redundant configurations and how PowerChute Network Shutdown works under various shutdown scenarios in a Redundant-UPS configuration. Applications IT Server Rooms, Data Centers, Remote Branch Offices, Distributed Networks. Introduction Each APC UPS in a single or redundant configuration has a UPS Network Management Card (NMC); an AP9630, AP9631 or AP9635 inserted. Each server protected by a UPS needs to have PowerChute Network Shutdown installed and registered to the NMC(s). Communication between the UPS and the server is handled over the network using the UPS NMC(s). Customer Benefits Graceful network-based shutdown Sequenced server shutdown Integration with VMware & Hyper-V Intuitive PowerChute setup wizard Browser accessible Command file integration Event logging HTTPS communications IPv6 support PowerChute Network Shutdown receives PCNS packets of data (every 25 seconds) from the UPS NMC describing the state of the UPS. PowerChute Network Shutdown then parses the PCNS data packet for various events to which it may respond, by notifying administrators or users, or by gracefully shutting down the system 1. The user configures which events require action, depending on their requirements, using the PowerChute Network Shutdown Configure Events screen. 1 See Application Note #20 (AN-20) The Communications Process of PowerChute Network Shutdown

Definitions Single UPS Configuration Each server or group of servers is protected by a single UPS. Each server has one PowerChute Network Shutdown Agent communicating with a single NMC inserted in the UPS. This single UPS provides the full power capacity of the load for all connected servers. When an event that requires shutdown occurs, PowerChute Network Shutdown receives the notification and triggers a graceful shutdown command for all connected servers. This application of PowerChute Network Shutdown includes all servers receiving power through the same UPS. PowerChute Network Shutdown responds to all the UPS events. Single UPS Configuration: All servers are protected by a single UPS. The UPS Network Management Card (NMC) communicates with each server that has PowerChute installed. Redundant UPS Configuration PowerChute Network Shutdown recognizes a group of up to four UPS s as a single UPS. In this configuration, one PowerChute Network Shutdown Agent on a server communicates with up to four NMCs (depending on the number of UPS s in the configuration). Typically, the servers have multiple power cords. Each UPS has its own NMC, which has a unique IP address. In addition, all the NMCs use the same HTTP port and the same administrator user name and authentication phrase. Each UPS has the capacity to supply power to the load on its own. The first UPS provides all the power for the load, the additional UPS(s) act as reserve. When the first UPS in unable to supply power, the server switches over to take power from the next UPS. As a result, if one of the UPS s goes down, for whatever reason, the other UPS(s) can continue to supply power to the load and therefore provide redundancy between UPS s. PowerChute Network Shutdown recognizes that the UPS s are set-up in a Redundant-UPS configuration and listens to all the UPS NMCs for a shutdown command. 2 February 2017

Redundant UPS Configuration: Two or more UPS s protect each server. Each UPS can support the server load on its own. All NMC s communicate with each server that has PowerChute installed. Table 1 Supported UPS s in a Redundant-UPS Configuration Redundant (Minimum) Redundant (Maximum) Smart-UPS Smart-UPS VT Galaxy 3500 (3:1 & 3:3) Symmetra 1-Phase Symmetra 3-Phase All UPS s in a Redundant-UPS configuration must be from the same UPS Family as opposed to the same UPS model. For example; SMX, SMT or SUA Smart-UPS can be mixed together but an SMX Smart-UPS cannot be mixed with an SURT or SRT model which belongs to the Smart-UPS On-Line Family. Each UPS must have enough battery power to support the entire load in the event of a power outage. While up to four UPSs can be supported, the Redundancy level is set so that if two UPS s in the configuration have a critical UPS event, then a graceful shutdown will be triggered. 3 February 2017

Event Handling PowerChute Network Shutdown aggregates the events from all the UPS s in the Redundant configuration to form one virtual UPS System. These events are always considered critical: Low Battery UPS Off UPS Turn off Initiated It is possible to configure other events to be considered critical by enabling the Shutdown action on the Configure Events screen. The critical event type and combination will impact the shutdown delays (if any) that are counted. 2 identical critical events such as Low Battery OR UPS Turn Off Initiated occurring in succession on 2 UPS devices will cause a shutdown; the shutdown will be immediate and no configured delay is counted down. 2 identical configured critical events such as UPS: On Battery occurring in succession on 2 UPS devices will cause a shutdown; any configured delay time will be counted down first. 2 different critical events such as Low Battery and PowerChute cannot communicate with the Management Card occurring in succession on 2 UPS devices will cause the event called Multiple Critical Events occurred which always leads to a shutdown. A 10 second delay prior to the PowerChute shutdown process starting will be counted. No additional configured delay time for the events themselves is counted down. Additionally, in a Redundant-UPS configuration, PowerChute Network Shutdown will always recognize and report the following events even if they occur on only one UPS: Runtime exceeded. Any event generated by an Environmental Monitoring Card. As the above events are not aggregated, if for example an environment threshold exceeded event is configured for shutdown, it will initiate a shutdown even if only 1 UPS has that threshold exceeded. All other events are aggregated (read in combination from all the UPS s) and need to occur on at least two UPS s before they are recognized and reported. Shutdown Scenarios (Note: Same rules apply if there are 2, 3 or 4 UPS s in a Redundant UPS Configuration) Scenario 1: Two UPS s supporting a load the same critical events occur on each UPS: UPS 1 reaches a critical event such as Low Battery; the UPS Network Management Card in that UPS will log the shutdown notification - no event is logged, no shutdown occurs. The same critical event occurs on UPS 2 and its UPS Network Management Card sends the shutdown notification the event is logged and an immediate shutdown occurs. No shutdown delay is counted. Figure 1 Two identical critical events, one in each UPS will trigger a graceful shutdown of the server with no shutdown delay counted. 4 February 2017

Shutdown Scenarios Scenario 2: Two UPS s supporting a load the same configured critical events occur on each UPS: UPS 1 reaches a configured critical event such as UPS: On Battery; the UPS Network Management Card in that UPS will log the shutdown notification However, no event is logged and no shutdown occurs. The same configured critical event occurs on UPS 2 and its UPS Network Management Card sends the shutdown notification the event is logged and shutdown occurs. Any configured delay time will be counted down first. Figure 2 Two identical configured critical events, one in each UPS will trigger a graceful shutdown of the server with any configured delay time counted down first. Scenario 3: Two UPS s supporting a load Different critical events occur on each UPS: UPS 1 reaches an event such as UPS: On Battery or Low Battery (may or may not be a configured critical event). The UPS Network Management Card in that UPS will log the shutdown notification - no event is logged, no shutdown occurs. A different critical event (such as UPS Turn Off Initiated) occurs on UPS 2, its UPS Network Management Card sends the shutdown notification the event is logged and shutdown occurs. As the critical events are different for both UPS s, a 10 second shutdown delay is counted. No other shutdown delays are counted down. Figure 3 Two different critical events (whether configured or not), one in each UPS will trigger a graceful shutdown of the server. A 10 second shutdown delay is counted down first. Scenario 4: Two UPS s supporting a load A critical event only occurs on one of the UPS s: If UPS 1 reaches Low Battery and eventually turns off but no events occur on UPS 2 and the UPS stays online, PowerChute Network Shutdown will not begin a shutdown as the second UPS is capable of supporting the entire load itself. Figure 4 Critical events in one UPS will not trigger a graceful shutdown of the server if no critical events occur on the second UPS. 5 February 2017

Conclusion In a Redundant-UPS configuration, each UPS must be able to support the entire load itself. A critical event must occur on two of the UPS s to trigger PowerChute Network Shutdown to initiate a graceful server shutdown. When PowerChute Network Shutdown combines or aggregates critical events from the UPS s, it only reports an event if the systems ability to support the load is at risk. In a Redundant-UPS system, this means that two UPS s must report the issue before PowerChute Network Shutdown will report the event and initiate the required safe server shutdown actions. While PowerChute Network Shutdown supports up to four UPS s of the same UPS Family in a Redundant-UPS configuration, PowerChute will trigger a graceful shutdown if a critical event occurs on two or more UPS s. 6 February 2017