KoldLok Integral Raised Floor Grommet

Similar documents
Determining static vacuum pressure required to ventilate Opti Carousel racks at various flow rates. Eric Corell. Page 1

EXPERIMENT PITOT TUBE

VOLU-probe. Pitot Airflow Traverse Probes. amca. Accurate airflow measurement for demanding applications. CERTIFIED RATInGS

FAN POWERED SERIES FCI-600 CONSTANT VOLUME FAN TERMINAL UNIT SPECIFIABLE FEATURES

ATU PRODUCT CATALOG AIR TERMINAL UNITS FCI-600 CONSTANT VOLUME FAN TERMINAL UNIT Metal Industries, Inc.

VOLU-probe/SS. Stainless Steel Pitot Airflow Traverse Probes

Introduction: Supplied to 360 Test Labs... Battery packs as follows:

Bisnet Solutions for Tomorrow, Today! The Die Casting Process Planner. Users Manual. August 5, A Product By: Bisnet - 1 -

500-YVI PARALLEL FAN-POWERED AIR TERMINAL UNIT FORM EG3 (404)

Protector XStream Laboratory Hood is shown with SpillStopper Work Surface , Protector Acid Storage Cabinet and Protector

FAN POWERED TERMINAL UNITS

SECTION HVAC AIR CLEANING DEVICES

500-YCI SERIES FAN-POWERED AIR TERMINAL UNIT FORM EG2 (404)

AD592/592-10K Non-Room Sensors in BAPI-Box, BAPI-Box 2 or BAPI-Box 4 BA/592-x-(BB, BB2, BB4) Temperature Sensor Instructions & Operation

Design and Application Details

PH SERIES SINGLE DUCT ATU PERFORMANCE DATA

Catalog Air Terminal Units. Models MQTH, MQFCI and MQFVI. Model MQTH. Model MQFCI. Model MQFVI

fan powered terminals

Requires Ductwork and Blower

General Purpose Walk-In Fume Hood

SINGLE DUCT AIR TERMINAL UNITS

Svetlana 3CX2500H3 Medium-Mu Power Triode

Chapter 17. Work Performers of Pneumatic Systems. Cylinders, Motors, and Other Devices

VORTAB FLOW CONDITIONERS. For Flow Meters, Pumps and Other Flow Profile Critical Equipment

Electronic Cooling Solutions Inc. 612 National Avenue, Mountain View, CA Phone: (650) Fax: (650)

SFI SPECIFICATION 28.1 EFFECTIVE: AUGUST 25, 2017 *

FAN TERMINAL UNITS Constant Volume (Series Flow), Standard Design

General Purpose Walk-In Fume Hood

Introduction to Johnson Controls Dampers

TM-1620 OPERATING INSTRUCTIONS AND OWNERS MANUAL

KVR Capture Jet. KVR- Capture Jet Round Island Hood with Perimeter Jets. Round Island Hood with Perimeter Jets

BOOST POWER 1212 Product Description

SINGLE DUCT TERMINAL UNITS 30X/HQX SERIES

FAN POWERED TERMINAL UNITS

INFINITY ZONING QUICK START GUIDE

CENTROIDTM. AC Brushless Drive. Product Spec Sheet

2. provide data indicating what types and sizes of particles are not removed by used PHEAF devices, and

Product Data. Features/Benefits. 35K Bypass Terminal. 110 to 4400 cfm

Product Guide. An Invensys company

Dual Duct Terminal Units DPS, DDS Series, DPQ, DDQ Series, DPV, DDV Series, DPM, DDM Series, DPUQ, DDUQ Series

Introducing NJK Precision Airflow Measuring Stations

Remote Control Helicopter. Engineering Analysis Document

Fan - Powered Terminal Unit Series Flow

SECTION CENTRIFUGAL HVAC FANS

Volume 2 Charts, Formulas, and Other Useful Information

Svetlana 3CX15,000H3 Medium-Mu Industrial Power Triode

Battery Capacity Versus Discharge Rate

2008 International ANSYS Conference

Fan Efficiency Grades and System Effect and Their Effects on HVAC Systems

AN EXPLANATION OF CIRCUITS CARTER YH HORIZONTAL CLIMATIC CONTROL CARBURETER

DOWNFLO II DUST COLLECTORS

A. Each cabinet must be constructed and installed in accordance with EN12469:2000.

Load Cell Troubleshooting

Factors Influencing the Performance of Ball and Rolling Bearings

Direct Gas-Fired Heating

Model 2500 Horsepower Computer System User Manual

Product Data. 35J Single-Duct Retrofit Terminal Units for Variable Air Volume Systems. 40 to 3700 cfm

High Performance Fan Coils FCHG Genesis Series Horizontal

Turning Air Into Solutions. PLUG FANS TYPE BCPL

SFI SPECIFICATION 7.2 EFFECTIVE: DECEMBER 15, 2006 *

RETROFIT TERMINAL UNITS

PowIRtab Mounting Guidelines

Model ND-2 Specification

THIS MATERIAL IS MEANT TO BE USED ALONG WITH OUR CATALOG IT IS NOT A SUBSTITUTE FOR THE CATALOG

Technical Data Sheet FT & FIT-1003 SERIES AIR VOLUME/ VELOCITY TRANSDUCERS. Features DESCRIPTION

Application Note AN-1203

Laboratory Room Single Duct Supply Air Terminal

Frameless High Torque Motors. Product Brochure

A proposed modification to the HSL flash composition test apparatus. Transmitted by the expert from the United States of America 1

Centrifugal Cabinet Fans Model BDF. Belt Drive Duct Fan

SFI SPECIFICATION 34.1 EFFECTIVE: January 13, 2017*

METEOROLOGICAL INSTRUMENTS

NOTICE. The above identified patent application is available for licensing. Requests for information should be addressed to:

Centrifugal Cabinet Fans Model BCF Belt Drive Low-Profile

Quarterly Progress Report

PACKAGED DOWNFLO EVOLUTION DUST COLLECTORS. The Complete Plug-and-Play Solution

FINAL REPORT MARCH 2008

Measurement and Analysis of the Operation of a Single-Phase Induction Motor

TubeTrace Tubing Bundles

Pulling & Support Grips

FC SERIES FLUID COOLERS THE LEADER IN THE INDUSTRY FOR ALL YOUR HVAC NEEDS. Replacement Coils Heat Exchangers Fan Coils

Centrifugal Roof Supply Fans Models RSF and RSFP. Forward Curved

TECHNICAL BULLETIN ACCESSORY INFORMATION

FILTERED AIR SUPPLY FANS

SOLAR HEATING SYSTEM

Application Guide TABLE OF CONTENTS: I. Introduction II. LHK Description III. Applications IV. Suggested Specification

EGG CRATE RETURN GRILLE

Chapter: Electricity

University of Delaware

INSTALLATION INSTRUCTIONS CWEH6-K WALL MOUNT HOOD

Magnetic Particle Brakes and Clutches

INSTALLATION INSTRUCTIONS EUROLINE/EUROLINE PRO WALL MOUNT HOOD

I Fan Powered Terminal Unit

ELEN 236 DC Motors 1 DC Motors

Centrifugal Roof Supply Fans Models RSF and RSFP. Forward Curved

FUNDAMENTALS OF ORIFICE METERING Ken Embry FMC Measurement Solutions

Satellite photo of cloud vortices caused by a mountain (Courtesy of our friends at NASA) tekvorx Operation Showing Simplified Construction

SolarSheat Wall Installation Manual

CAMS. Combustion Airflow Management System. Proven solutions for a tough industry. Precision Airflow Measurement An ONICON Brand

SUMMARY. St-jean-sur-Richelieu, 2016, January 12th Client : J.A. Roby Project :PI model : Polaris; Sirius; Véga; Antares; Centauri; Rigel

Transcription:

p r o d u c t c e r t i f i c a t i o n r e p o r t KoldLok Integral Raised Floor Grommet Model 1010 Updated May 1, 2002 Prepared for Upsite Technologies, Inc. 2904 Rodeo Park Drive East Santa Fe, New Mexico 87505 505.982.7800 Team Leader Robert F. Sullivan, Ph.D. Uptime Institute, Inc. 2904 Rodeo Park Drive East, Bldg. 100 Santa Fe, NM 87505 505.986.3900 TM

Product KoldLok Integral Raised Floor Grommet Product Number Model 1010 Serial Number Date of Testing April 14, 2002 Test Report Number 02-060 Test Location Sempliner Industrial Design, Douglaston, NY Test Conducted by Dr. Robert F. Sullivan, The Uptime Institute Arthur Sempliner, Sempliner Industrial Design Kenneth G. Brill, Upsite Technologies Disclosure The Uptime Institute, Computersite Engineering, and Upsite Technologies are a family of companies under common control. Each functions as an independent entity with careful consideration being given to conflicts of interest. The testing regimen developed by the Institute for KoldLok products is rigorous and repeatable should a third party want to conduct their own tests using the procedures outlined in this Report. Summary The Uptime Institute supervised performance testing of the KoldLok Integral Raised Floor Grommet Model 1010. The testing program had three objectives: 1) What is the KoldLok grommet s sealing effectiveness in preventing the loss of cooling air? 2) How effective is the KoldLok grommet in conducting static charge into the raised floor? and 3) Is the 4 by 8 net usable opening size of the KoldLok grommet sufficiently large to accommodate the density of cable concentrations likely to occur at most sites? 1. The KoldLok Integral Grommet successfully sealed simulated cable penetrations. When compared to a KoldLok frame with no sealing filaments (a totally open 5 by 8 cutout), the unpenetrated KoldLok assembly had a 100% sealing effectiveness up through a static pressure of 0.10 inches of water, which is the maximum static pressure anticipated in a computer room with a fully-sealed under floor. With the worst-case simulation of cable penetrations tested (four rods offset from the centerline of the KoldLok assembly), the sealing efficiency was 100% at 0.01 inches of water and 92% at 0.10 inches of water. 2. 3. The KoldLok Integral Grommet had a measured conductivity of one gigaohm, which is well within the accepted standards to assure safe dissipation of static charge for raised-floor applications. The gross opening of the KoldLok Integral Grommet allows the easy pass through of a 100-ampere, 208 volt, three phase RussellStoll plug and receptacle without causing a permanent set to the filaments. This plug is the largest currently found in a raised-floor environment. Four small signal cables, fifty-six Z\x SCSI cables, and two B\, power cables were passed through the KoldLok Integral Grommet. 2

Introduction and Background The KoldLok Integral Raised Floor Grommet assembly consists of a plastic frame that is mounted to the floor tile with screws. The frame holds two sets of opposing filaments of different lengths meeting in the middle of the assembly. These layers of different length filaments on each side of the frame are installed to minimize the airflow through the assembly. The smaller diameter filaments in the top layer provide better compliance to cables penetrating the assembly. The stiffer, larger diameter lower filaments support the thinner fibers used in the top layer. The bottom layer is designed to assist the top in minimizing airflow by providing a second layer of sealing and by limiting the effect of veeing (veeing of the filaments occurs naturally when cables are pulled tightly against the sides of the frame causing the filaments to form the shape of a V ). The stiffer bottom layer is also designed to direct cables to the center of the assembly, thereby minimizing the opening created by a cable penetration. A KoldLok product is intended to provide access for pulling cables and for cable passage through the raised floor while sealing the resulting openings to minimize air leakage. A KoldLok product is also designed to integrate into the static charge dissipation capability of the raised floor. The KoldLok frame and filaments are mildly conductive to bleed off any static charge buildup on the cables due to high velocity airflow under the raised floor. The objective of all Institute product testing is to create repeatable, engineering based, industry standard processes for performance testing. The processes are formulated such that a competent third party can replicate them. Testing needs to incorporate user inputs and needs on how the product will actually be installed and used in real world applications. Test Objectives The objectives of this project were to: 1. 2. 3. Photo 1. Integral KoldLok Grommet is installed in the raised floor tile providing NFPA required raw metal edge dressing, access to install and remove cables, and sealing around cables to prevent the escape of cooling air Test KoldLok airflow sealing performance, Test KoldLok conductivity to assure slow dissipation of static charge, and Test the gross and usable Grommet opening area to be sure a single size Grommet will fit 98% of cable opening requirements. Escape Airflow Measurement Testing The initial airflow test chamber proved to be inadequate for producing consistent measurements and had to be completely rebuilt before certified testing could be completed. Engineering problems overcome by the final test chamber included 1) Adding sufficient fan capacity to generate high volumes of airflow through a totally open test fixture at high static pressures, 2) Stabilizing static pressure to allow consistent and accurate measurements of escaping airflow, 3) Developing a method for making consistent and accurate static pressure measurements, 4) Reducing escape air turbulence in the discharge section to allow consistent and accurate airflow measurements, and 5) Developing a consistent and accurate means for measuring very low rates of escaping airflow. The custom made apparatus for testing KoldLok sealing effectiveness consisted of four major sequential sections: A) a static pressure generation chamber, B) a cable simulation test fixture that held penetrations in a fixed location, C) a test fixture for accurately holding the KoldLok Integral Grommet in a fixed location, and D) an escaping airflow measurement section. Photo 2. Apparatus used for testing KoldLok sealing effectiveness. The apparatus has four major sections. From left to right: A. Static pressure generation chamber, B. Cable penetration test station, C. KoldLok test station, and D. Escape airflow measurement section 3

A. B. The static pressure generation chamber consists of a Plexiglas box 15 H x 15 W x 24.5 L, with two 12VDC fans mounted opposed to each other and orthogonal to the airflow direction. Fan speed was controlled from a DC power supply. This chamber was capable of generating a stable static pressure from 0.005 inches of water to 0.250 inches of water into a KoldLok frame having no filaments. A Z\, mesh screen was placed between the fans and the KoldLok test fixture to provide an airflow baffle to stabilize the static pressure. The penetration test station allowed accurate placement of penetrator assemblies that were inserted into the KoldLok frame. The standardized penetrator assemblies used to simulate cables and cable bundles passing through the KoldLok blocked openings were: Penetrator 0 KoldLok frame containing no filaments simulating an open cutout of 5 by 8 Penetrator 1 Four Z\x diameter wooden rods located on the vertical KoldLok centerline Penetrator 2 One 2 diameter wood rod on the vertical KoldLok centerline One B\, diameter wood rod located C\v to the right of the vertical KoldLok centerline Penetrator 3 One M\, diameter wood rod on the vertical KoldLok centerline One Z\x diameter wooden rod offset C\, to the left and two Z x diameter rods offset B\, to the right of the vertical KoldLok centerline C. D. The KoldLok test fixture section allowed accurate mounting of the KoldLok Integral assembly in a fixed location. Static pressure was measured in the immediate underside of the grommet assembly. The escape airflow measurement section consisted of a Plexiglas chamber 8Z\v W x 11 H x 21 L. Within the escape chamber is a 6 long, 35-cell (seven high by five wide), baffle and turbulence straightening assembly allowing more accurate exhaust air measurements, especially at low escape velocities. 2 3 1 Measurement Instruments Photo 3. These penetrator assemblies were used to simulate cables and cable bundles passing through a floor opening. Not shown is Penetrator 0 which was an Integral KoldLok frame with no filaments simulating an unmanaged cable cutout opening. A. B. Static Pressure. Static pressure was measured with two different instruments, a Dwyer 0 to 0.25 inches of water Magnahelic gauge (Catalog number 2000-00) and a Dwyer 0 to.6 inches of water Inclined Manometer (Catalog number 1227) Escape Airflow. Escaping airflow velocity was measured using a Shortridge Instruments Airdata Multimeter (Catalog ADM860 with a Velocity Grid Pressure Sensor the pressure sensing points of the Velocity Grid Pressure Sensor outside the escape airflow cross section were sealed to increase measurement accuracy). Escaping airflow was triple checked using an Extech Thermo-Anemometer (Model 45112) and a Dwyer Thermo-Anemometer (Model UT120). 4

Test Procedure KoldLok sealing performance was conducted using a specially fabricated test chamber allowing high volumes of airflow at static pressures of up to 0.250 inches of water, accurate measurement of the static pressure, a consistent means of mounting a KoldLok Grommet into the airflow, a consistent means of penetrating the KoldLok assembly with a variety of wooden rods to simulate standardized sets of cables and cable bundles passing through the KoldLok sealing filaments, and a means for measuring the volume of air escaping through the KoldLok assembly. The first test was to measure the airflow through an open KoldLok Integral frame (one without filaments installed). This frame had a 5 x 8 open area. A fully assembled KoldLok grommet was next tested without any cable penetrations. Finally a series of three different penetration assemblies were inserted through the filament sealing assembly to simulate cables passing through the KoldLok assembly. These penetrations were wooden rods ranging in diameter from Z\x to 2 inches. Some of the rods were installed on the filament centerline, while others were as far as C\v off the brush centerline, simulating cables being pulled to the side of the assembly. Each test was run with a series of static pressures ranging from 0.01 inches of water (the pressure typically found in many computer rooms) to 0.10 inches of water (the pressure estimated to be the maximum possible in a fully sealed computer room). Data collected included the test setup configuration, the static pressure, and escaping airflow velocity. Escape air volume in cubic feet per minute (CFM) was calculated using the measured airflow velocity and multiplying it by the cross section of the discharge area. Photo 4. Dr. Bob Sullivan testing KoldLok sealing effectiveness Data and Analysis The open KoldLok frame (no filaments installed) had an airflow that ranged from 148 CFM at 0.01 inches of water to 483 CFM at 0.10 inches of water. When the KoldLok assembly without any penetrations (Penetrator 0) was installed, the airflow through the assembly was reduced to 0 CFM from 0.01 inches of water to 0.10 inches of water. This is a sealing efficiency of 100% throughout the static pressure range expected in most computer rooms. Once rods penetrated the filament assembly, the results varied by the severity of the penetrations. With the Penetrator 1 the sealing remained at 100% for 0.01 inches of water. At 0.10 inches of water the flow was measured at 22 CFM for a 95% sealing efficiency. With the Penetrator 2 the sealing again remained at 100% at 0.01 inches of water. At 0.10 inches of water the flow was measured at 37 CFM for a 92% sealing efficiency. With the Penetrator 3 the sealing was still 100% at 0.01 inches of water. At 0.10 inches of water the measured airflow was 38 CFM for a 92% sealing efficiency. The entire set of test results are presented in Table 1. 5

Table 1. Lost Airflow (CFM) and Equivalent Lost Cooling (Watts)* under different test conditions KoldLok Test Results Static Pressure (Inches of H 2 O) Open KoldLok Frame (simulating a 5 x 8 unmanaged cable opening) 0.010 0.025 0.050 0.075 0.100 Lost Airflow (CFM) 148 239 325 407 483 Equivalent Lost Cooling (Watts) 703 1,134 1,543 1,932 2,292 KoldLok + Penetrator 0 (simulating no cable penetrations) Lost Airflow (CFM) 0 0 0 0 0 Percent Sealing (%) 100 100 100 100 100 Equivalent Lost Cooling (Watts) 0 0 0 0 0 KoldLok + Penetrator 1 (simulating four ½ cables on centerline) Lost Airflow (CFM) 0 0 0 0 0 Percent Sealing (%) 100 100 100 96.0 95.5 Equivalent Lost Cooling (Watts) 0 0 0 81 104 KoldLok + Penetrator 2 (simulating one large power cable pulled to one side and one cable on centerline) Lost Airflow (CFM) 0 6 25 32 37 Percent Sealing (%) 100 97.5 92.3 91.2 92.4 Equivalent Lost Cooling (Watts) 0 28 119 152 176 KoldLok + Penetrator 3 (simulating four offset cables) Lost Airflow (CFM) 0 21 27 33 38 Percent Sealing (%) 100 91.3 91.7 91.9 92.2 Equivalent Lost Cooling (Watts) 0 100 128 157 180 * Watts = 3,516 watts/ton x [measured airflow in CFM x Delta T across cooling coil in ºF (15ºF difference assumed) x 1.08] 12,000 Btu/ton = 4.7466 x measured CFM 6

Graph 1. Integral KoldLok Grommet Escape Airflow with Different Simulations of Cable Penetration 600 500 400 CFM 300 200 100 Losses through Unmanaged 5" x 8" Cable Opening KoldLok Sealed Opening with No Cables (Penetrator 0) KoldLok Sealed Opening with Four 1 /2" Cables (Penetrator 1) 0 0 0.025 0.050 0.075 0.100 0.010 Static Pressure (H2O") Graph 2. Integral KoldLok Grommet Sealing Effectiveness with Different Simulations of Cable Penetration 7

A graphical presentation is included in Graph 1 and Graph 2. Discussion of Results Absolute accuracy of the lowest velocity airflow measurements are not guaranteed, but all tests were run consistently using the same instrumentation and with the same readings on the static pressure gauges. KoldLok sealing effectiveness was calculated as the relative difference in escape airflow using different penetrators under the same test conditions thereby eliminating the need for absolute measurement accuracy. Static Charge Dissipation Testing The conductivity of a KoldLok Integral Grommet was tested using an AEMC 100 Megohmmeter. One weight was positioned on the underside of the filaments and the other contacting the top surface of the raised floor. Data and Analysis At an excitation of 500 volts, the KoldLok Integral Grommet conductivity measured 1 gigaohm. This is well within the accepted industry standard for raised floor conductivity of greater than 150,000 ohms and less than 20 gigaohms. Overall Conclusions The KoldLok Integral Raised Floor Grommet s sealing effectiveness is virtually 100% (provided cables are not under tension and pulled against the sides of the KoldLok frame) under the static pressures typically seen in many computer rooms today. Under the highest static pressure expected in a well-sealed computer room and with the worst-case simulated cable penetrations, a sealing efficiency of 92% was achieved. The static dissipation capability of the KoldLok Integral Grommet meets the accepted industry standard for raised floor applications. Recommendations for Additional Testing Best cable installation practice is to have some slack in the cables. If cables are under tension and are pulled against the edge of the KoldLok frame, veeing of the filaments will occur which will reduce sealing effectiveness. Over time, the filaments may take on the shape of a V and it could take some time for the filaments to return to their original fully sealed position after the cables are removed. This problem was observed while the test chamber was being reconstructed during which time the Penetrator 2 was left installed for a period of several months. When the penetrator was removed, the filaments took several weeks to partially resume their original position. A more rigorous resiliency testing process is now being designed. The static dissipation capability of an KoldLok Integral Grommet must be measured again when the grommet and tile are installed in an actual raised-floor environment. 8