Refrigerant Changeover Guidelines. Leading the Industry with Environmentally Responsible Refrigerant Solutions

Similar documents
Copeland Screw TM Compressors

HCFCs Refrigeration Retrofit Guidelines

MODULOAD CAPACITY CONTROL FOR 3D COMPRESSORS

AE R5 February 1997 Reformatted November 2010

Copeland Screw Compressors Semi-Hermetic Compact Operating Instructions

R-22 R-404A/R-502/R-507A R-12/

TECHNICAL SUPPORT MANUAL Coils for Manufactured Housing EMA2X, EMA4X

CHILLER START UP PROCEDURE FORM DOC. N (DOC.N BELOW TO BE RETURN TO AERMEC)

ADK Filter Drier. Alco Controls. Filter Drier. Features

Repair any problems or leaks before retrofitting. Affix labels to the vehicle showing conversion status. Observe all safety recommendations.

Danfoss Commercial Compressors Towards more eco-friendly commercial refrigeration systems

Retrofit Guidelines for DuPont ISCEON MO79 (R-422A) Refrigerant

FDB Filter Drier. FDB Filter Drier. Technical Data

Application Engineering

INSTALLATION, START-UP AND SERVICE INSTRUCTIONS

High Performance Vacuum Pump Model 15120A/15121A Operating Manual...

Copeland Scroll X-Line

Forane 427A Refrigerant

Technical brochure Electrically operated expansion valves, type ETS 6

Operating Manual. High Performance Vacuum Pump Models and 15600

Electric expansion valves Type ETS 6

VACUUM AND CHARGING HOSES

HCFC-22 Retrofits. There has been increased emphasis on retrofitting R-22

OEZ IEZ NOMENCLATURE STANDARD FEATURES FACTORY INSTALLED OPTIONS

WATER COOLED HERMETIC & SCROLL CONDENSING UNITS 1/2 TO 6 HP

March, 2005 K4 REFRIGERATION COPELAND SCROLL COMPRESSORS HORSEPOWER AE R6 APPLICATION GUIDELINES FOR

Models

FDB Filter Drier. Alco Controls. FDB Filter Drier. Features. Introduction. Moisture removal capability. Construction

Application Engineering

Thermo -Expansion Valves Series TX7

FREON 134A CURVA TABLA

2014 Buick Encore. Fig. 2: Replacing Measured Compressor Oil Courtesy of GENERAL MOTORS COMPANY

Water-Cooled Condensing Units. Shell & Tube Condenser Low Operating Cost Durable Construction Built in Receiver

MACHINES RECOVERY. 99 Washington Street Melrose, MA Phone Toll Free SYSTEMS SUPEREVAC

Alco Controls. Components for the Refrigeration Industry. Product Selection Catalogue

SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS DESCRIPTION FEATURES H2CA300, 360, 480 & THRU 50 NOMINAL TONS

Technical Information

THE INDUSTRY STANDARD

BITZER Liquid Injection Guidelines for CSH Compressors

Installation Instructions

FREON 134A CURVA TABLA

BFK Bi-flow Filter Drier

UX330 Compressor Service Manual

F and D Line Copeland Scroll air-cooled condensing units

Electrical Control Valves Series EX4, EX5, EX6, EX7 & EX8

Air Cooled Condensing Units - Technical Catalog. Featuring CopelandTM Compressors 404A and 507 Refrigerants

t EVAPORATOR PRESSURE REGULATING VALVES

ZR61KC-TFD. Electrical. Alternate Applications

Pulse Width Modulation Valves. Models SPW-0 thru -7

EMERSON CLIMATE TECHNOLOGIES

6. Document tasks performed during visit and report any observations to the appropriate

Hot gas bypass regulator type CPCE Liquid gas mixer type LG (accessory)

TAKE-A-PART SHELLS TOTALINE LIQUID & SUCTION LINE REPLACEABLE SHELLS P505-8 SERIES PART NUMBER SIGNIFICANCE

SUNLINE 2000 SPLIT-SYSTEM AIR-COOLED CONDENSING UNITS 50 AND 60 HZ DESCRIPTION FEATURES

Crankcase pressure regulator Type KVL

DCY. Anti-acid filter driers Refrigeration & Climate Components Solutions. n Applications

Semi-Hermetic Condensing Units KL

Engineers Tables SI Units

Solubility, Miscibility, and Liquid Viscosity of Lubricants with CO 2 and Propane

AE R5 August 2015

ZR125KC-TFD. Electrical. Alternate Applications

Tranquility (TBW) Water-To-Water Series. WATER-TO-WATER SYSTEMS SIZES 036, 060, AND 120 [8.7, 13.5 and 26.9 kw]

Application Bulletin 141. H82J Series OVAL HOUSING ROUND HOUSING. BENCHMARK Compressor with Refrigerant R410A. (33,000 50,000 BTU/Hr.

Replaceable solid cores filter driers type CSR

Copeland Scroll TM compressors. for commercial applications

See Page 4 for details

Manufactured in the USA in our ISO 9001 registered facility. All accumulators are UL listed (SA4835) and CSA approved (LR41494).

LUI / LUO. Condensing Units

Electric expansion valves Types AKVA 10, 15 & 20

Crankcase pressure regulator Type KVL

FILTER DRIERS - SPORLAN

MT/MTZ 50 Hz R22 R407C R134a R404A / R507

TV-Line Condensing Units

MODEL SCS REMOTE CONDENSER

Rack Oil regulation and System Oil Failures

EVAPORATOR PRESSURE REGULATORS

1/2 TO 6 HP MULTI-REFRIGERANT AIR COOLED CONDENSING UNITS

1/2 TO 6 HP INDOOR WATER COOLED CONDENSING UNITS

A Series UP90 UP120 UP150 UP170 Compressor Service Manual

HUDSON TECHNOLOGIES REFRIGERANTSIDE SOLUTIONS OTHER SERVICES PRODUCTS

FILTER DRIERS PART NUMBER SIGNIFICANCE LIQUID LINE FILTER DRIERS TOTALINE LIQUID LINE FILTER DRIER PHYSICAL DATA DIMENSIONS

FSP Fan Speed Power Module Technical Data

Operating Instructions - Electric Pow'r-Riser Models

Electronic suction modulating valves type KVS

Next-Gen MiniCon 1/2 TO 6 HP MULTI-REFRIGERANT AIR COOLED CONDENSING UNITS

Copeland condensing unit

Electrical Control Valves

Next-Gen MiniCon 1/2 TO 6 HP MULTI-REFRIGERANT AIR COOLED CONDENSING UNITS

STANDARD MOTOR PRODUCTS, INC. TEMPERATURE CONTROL DIVISION (SMP BLUE STREAK ) WARRANTY STATEMENT

Crankcase pressure regulator Type KVL

Operation and Maintenance Manual for Pumps and Systems

AK Application. Features. Applicable Literature. Positive Positioner Pneumatic Relay General Instructions

MANUAL FLUID EXTRACTOR

Product Guide for HFO / HFO Blends. R448A/R449A R450A/R513A R1234ze. R134a R407A/F R404A/507 R12/502

Crankcase Pressure Regulating Valves

Emerson Climate Technologies, Inc., 1675 W. Campbell Road, Sidney, OH EmersonClimate.com

Retrofit Guidelines for HFC-23. Table 1 HFC-23 Physical Properties and Operating Performance. Physical Property Units HFC-23 R-503 R-13

Centrifugal Chiller PE046, PE047, PE048, PE050 PEH PF083, PF096, PF105, PF116 PH PHH PL

ZF Copeland Scroll Compressor Range for Low Temperature Refrigeration using R407A/F, R448A/R449A and R404A

348002K/348012K Manifold Block Style Service Manual 12/2000

Transcription:

Refrigerant Changeover Guidelines HCFC R-22 to HFC R-422A/D for Medium and Low Temperature Applications Leading the Industry with Environmentally Responsible Refrigerant Solutions

Emerson Climate Technologies, Inc. does not advocate the wholesale changeover of HCFCs to HFCs. If a system is not leaking refrigerant to the atmosphere, and is operating properly, there is no technical reason to replace the HCFC refrigerant. In fact, changing the refrigerant may void the U.L. listing of the system. However, once the decision has been made to make the change from HCFC R-22 to HFC R-422A/D, the following guidelines are recommended. The following guidelines only apply to Copeland brand Discus compressors in existing refrigeration medium and low temperature systems. Copeland Scroll compressors are being evaluated for their acceptance of these refrigerants in similar medium and low temperature refrigeration systems. These refrigerants are not approved for use in any air conditioning systems using Copeland brand compressors. For any updates contact Emerson Climate Technologies, Inc. CONSIDERATIONS 1. Retrofi tting systems that employ compressors manufactured prior to 1973 is not recommended. This is due to the different materials used in motor insulation that have not been evaluated for compatibility with the new refrigerants and lubricants. Failure to heed this advice will violate the U.L. Standard For Field Conversion/Retrofi t Of Alternate Refrigerants In Refrigeration and Air Conditioning Equipment (U.L.2170-2172). 2. HFC refrigerants have generally required the use of polyol ester (POE) lubricants in order to ensure oil return. However, R-422A/D contains a small percentage of isobutane that promotes adequate oil return in properly piped systems with oil separators and no change out of the mineral oil or alkylbenzene is required. Minor equipment modifi cations such as replacement or adjustment of the expansion device may be required in some applications. Oil return is determined by a number of design and operating conditions. In some systems a small amount, up to 5%, of POE may need to be added to assist in oil return. While 422A/D will operate properly with an oil charge of 100% POE, the POE can dislodge debris in older systems requiring liquid line fi lter drier change outs to keep the system free of this debris. 3. The system capacity and effi ciency will be somewhat different with R-422A/D than with HCFC R-22. In most multiple compressor racks, there should still be adequate capacity. However, it is strongly recommended that system capacity verifi cation be done using the refrigerant manufacturer published comparison factors. The RLA values for R-422A/D are higher than those for HCFC-22. The values are similar for those of HFC-404A. The sizing of wires, contactors, and breakers should be checked to ensure that they are adequate. 4. R-422A/D can be used in either low or medium temperature systems. R-422A/D should not be mixed with any other refrigerant! 5. When retrofitting from R-22 to R-422A the expansion valves will need to be replaced with a valve suitable for R-404A. In some cases only the power element of the expansion valve can be changed, but where this is not possible the entire valve must be replaced with the equivalent capacity R-404A model. When retrofitting from R-22 to R-422D, the expansion valve will likely not require replacement; however, it is recommended that the valve loadings be evaluated to verify that they are adequate. Following the retrofi t, superheat should be checked and adjusted if necessary. 6. Filter-driers must be changed at the time of conversion. This is proper air conditioning/ refrigeration practice. a. Solid core driers such as Emerson Climate Technologies ADK are compatible with either HCFC R-22 or R-422A/D. WARNING: Use only Emerson Climate Technologies Inc. approved refrigerants and lubricants in the manner prescribed by Emerson Climate Technologies Inc. In some circumstances, other refrigerants and lubricants may be dangerous and could cause fi res, explosions or electrical shorting. Contact Emerson Climate Technologies Inc., Sidney, Ohio for more information.

b. Compacted bead type driers such as the Emerson Climate Technologies EK series are also compatible. c. Loose fi ll type driers are not recommended and should be replaced with the types referenced in a. and b. above. 7. Pressure regulators such as EPR valves may have to be reset. Contact the EPR manufacturer for the correct settings. 8. R-422A exhibit higher pressures than HCFC R- 22 at normal condensing temperatures. This may require that the high pressure safety controls be reset in order to operate as intended. 9. Systems that use a low pressure controller to maintain space temperature may need to have the cut in and cut out points changed. Although R-422A/D does exhibit glide, the average evaporator or condenser temperature is within 0.5ºF of the saturated vapor temperature; therefore no correction is required. 10. Systems using R-422A/D should have approximately the same system pressure drop as with HCFC R-22. Check with the manufacturer of any pressure regulators and pilot operated solenoid valves used in the system to be sure that they will operate properly. NOTE: R-422A/D is not compatible with the seal material used in the HCFC R-22 Moduload Unloading system of 3D compressors. If your system has Moduload, the valve plate assembly MUST be changed. Consult your Emerson Climate Technologies wholesaler for the proper part numbers. Many other system seals such as elastomeric seals, gaskets, and valve packing may be affected by the change over from HCFC R-22 to R-422A/D. The part manufacturer should be contacted for their recommendations as to whether the seals need to be changed or replaced. Before starting the changeover, it is suggested that at least the following items be readily available: 1. Safety glasses 2. Gloves 3. Refrigerant service gauges 4. Electronic thermometer 5. Vacuum pump capable of pulling 250 microns 6. Thermocouple micron gauge 7. Leak detector 8. Refrigerant recovery unit including refrigerant cylinder 9. Proper container for removed lubricant 10. New liquid control device 11. Replacement liquid line fi lter-drier(s) 12. New Mineral Oil lubricant 13. R-422A/D pressure temperature chart 14. R-422A/D refrigerant CHANGEOVER PROCEDURE 1. The system should be thoroughly leak tested with the HCFC R-22 refrigerant still in the system. All leaks should be repaired before the R-422A/D refrigerant is added. 2. It is advisable that the system compressor operating conditions be recorded with the HCFC R-22 still in the system. This will provide the base data for comparison when the system is put back into operation with the R422A/D. 3. Disconnect electrical power to system. 4. Properly remove the HCFC R-22 from the compressor. Measure and note the amount removed. 5. Replace the liquid line fi lter-drier with one that is compatible with R-422A/D. 6. Replace the expansion valve or power element to a model approved for R-404A (only required when retrofi tting from R-22 to R-422A). 7. Evacuate the system to 250 microns. A vacuum decay test is suggested to assure the system is dry and leak free. 8. Recharge the system with R-422A/D. 9. Charge the system with R-422A/D. Charge to 90% of the refrigerant removed in item 4. R-422A/D must leave the charging cylinder in the liquid phase. It is suggested that a sight glass be connected between the charging hose and compressor suction service valve. This will permit adjustment of the cylinder valve to assure the refrigerant enters the compressor in the vapor state. 10. Operate the system. Record the data and compare to the data taken in item 2. Check and adjust thetev

superheat setting if necessary. Make adjustments to other controls as needed. Additional R-422A/D may have to be added to obtain optimum system performance. 11. Properly label the components. Tag the compressor with the refrigerant used (R-422A/D) and the lubricant used. The proper color code for R-422A is Yellow PMS (Paint Matching System) 128; for R-422D, Green, PMS 375. CAUTION: These guidelines are intended for use with R-422A/D only. Other refrigerants may not be compatible with the materials used in our compressors or the lubricants recommended in this bulletin resulting in unacceptable reliability and durability of the compressor. HFC R-422A Saturated / Pressure/Temperature Chart 3-40 -44 80 38 35 230 99 97 4-38 -42 85 41 38 235 100 98 6-34 -38 90 44 41 240 102 100 8-30 -34 95 47 44 245 103 101 10-27 -31 100 49 46 250 105 103 12-23 -27 105 52 49 255 106 104 14-20 -24 110 54 51 260 107 105 16-18 -21 115 57 54 265 109 107 18-15 -19 120 59 56 270 110 108 20-12 -16 125 61 59 275 111 110 22-10 -13 130 63 61 280 113 111 24-7 -11 135 66 63 285 114 112 26-5 -9 140 68 65 290 115 113 28-3 -6 145 70 67 295 116 115 30-1 -4 150 72 69 300 118 116 32 1-2 155 74 71 310 120 118 34 3 0 160 76 73 320 122 121 36 5 2 165 78 75 330 125 123 38 7 4 170 79 77 340 127 125 40 9 6 175 81 79 350 129 128 42 11 7 180 83 81 360 131 130 44 13 9 185 85 82 370 133 132 46 14 11 190 86 84 380 135 134 48 16 13 195 88 86 390 137 136 50 18 14 200 90 87 400 139 138 55 21 18 205 91 89 60 25 22 210 93 91 65 29 25 215 94 92 70 32 29 220 96 94 75 35 32 225 97 95

HFC R-422D Saturated / Pressure/Temperature Chart 2.5-40 -48 0-36 -45 2-32 -40 80 49 43 230 110 106 4-27 -36 85 52 46 235 111 107 6-23 -32 90 55 49 240 113 109 8-20 -28 95 57 52 245 114 110 10-16 -24 100 60 54 250 116 112 12-13 -21 105 63 57 255 117 113 14-10 -18 110 65 59 260 118 114 16-7 -15 115 67 62 265 120 116 18-4 -12 120 70 64 270 121 117 20-2 -9 125 72 67 275 122 119 22 1-7 130 74 69 280 124 120 24 3-4 135 76 71 285 125 121 26 6-2 140 79 73 290 126 123 28 8 0 145 81 76 295 127 124 30 10 3 150 83 78 300 129 125 32 12 5 155 85 80 310 131 128 34 14 7 160 87 82 320 133 130 36 16 9 165 88 84 330 136 132 38 18 11 170 90 85 340 138 135 40 20 13 175 92 87 350 140 137 42 21 15 180 94 89 360 142 139 44 23 16 185 96 91 370 144 141 46 25 18 190 97 93 380 146 144 48 27 20 195 99 94 390 148 146 50 28 21 200 101 96 400 150 148 55 32 25 205 102 98 60 36 29 210 104 99 65 39 33 215 105 101 70 43 36 220 107 103 75 46 40 225 108 104 The information contained herein is based on technical data and tests which we believe to be reliable and is intended for use by persons having technical skill, at their own discretion and risk. Since conditions of use are beyond Emerson Climate Technologies, Inc. control, we can assume no liability for results obtained or damages incurred through the application of the data presented.

1675 W. Campbell Road Sidney, OH 45365-0669 (937) 498-3011 EmersonClimate.com 2007CC-13 R1 (6/07) Emerson and Copeland are the trademarks of Emerson Electric Co. or one of its affi liated companies. 2007 Emerson Climate Technologies, Inc. All rights reserved. Printed in the USA.