CL Series Centrifugal Fire Pumps Installation Instructions

Similar documents
With PA Series Transmission: S101 Series Midship Pumps: With C20 Series Transmission:

With WB Series Transmission: With PA Series Transmission: With K Series Transmission:

Operation and Maintenance. S100 Series Centrifugal Fire Pumps. Table of Contents. Visit us at F /22/02 6/21/18

HL Series Centrifugal Fire Pumps Installation Instructions

Operation and Maintenance. CG Series Centrifugal Fire Pumps. Illustrations

HL Series Centrifugal Fire Pumps Operation and Maintenance Instructions

Operation and Maintenance. CS Series Centrifugal Fire Pumps. Table of Contents. Visit us at F /14/95

CH-4 Series Fire Pumps Overhaul Instructions

Overhaul Instructions. S100 Series Centrifugal Fire Pumps. Table of Contents F /22/02 1/19/18

S200-P Series Centrifugal Fire Pumps Operation and Maintenance Instructions

CP-1, CP-2, CP-2L & CPD-2 Series Overhaul

TC20 Chain Driven Power Take-Off Overhaul Instructions

S200-G Series Centrifugal Fire Pumps Operation and Maintenance Instructions

Eclipse GEN 2.0 CAFSystem, Model 150-ECL CAFS PTO Kit Installation Instructions

C21 Series Transmission Operation and Maintenance Instructions

Installation. Installation. 12. System Diagram... 10

Eclipse GEN 2.0 CAFSystem, Model 150-ESECL as used with TC20 Series PTO Installation Instructions

WATEROUS CX SERIES PUMPS. Model Intake Discharge

CXV Series Fire Pump Dimensional Drawings

K, T, TK, TA and KC Series Operation and Maintenance Instructions

CL Series Impeller Shaft Assembly Service Parts List

Priming Systems Installation Instructions

W & Y Series Split Shaft Transmission Operation & Maint.

High Rise Fire Pumps CM/CGV Series, CMU/CGV Series. Operation and Maintenance

Introduction... 2 Water/Foam Solution Distribution Components... 3, 4 Lubrication:

PB18 SERIES PORTABLE PUMPS

CXV Series Pump Body Service Parts List

Principals of Operation... 1 Rotary Vane Priming Pump VPE and VPES... 2 Rotary Vane Priming Pump VPO and VPOS Priming Valve...

KC Transmission Overhaul

MGA and RGA SERIES SPLIT-SHAFT PTO DRIVE GEARBOX INSTALLATION MANUAL

WATEROUS PRESSURE CONTROL SYSTEMS DESCRIPTION: WATEROUS HAS TWO SYSTEMS AVAILABLE FOR CONTROLLING PUMP PRESSURE AS FOLLOWS:

WATEROUS CS SERIES PUMPS DESCRIPTION: MIDSHIP MOUNTED SINGLE STAGE CENTRIFUGAL FIRE PUMP

S200-P Passport Series Fire Pump Service Parts List

Shift Units Installation Instructions

Table of Contents Illustrations

CP-1, CP-2, CP-2L & CPD-2 Series Overhaul

Waterous S100 Single Stage Pump

INSTALLATION OF TYPE ZSP PTO DRIVEN Fire Pump

Plumbing. Controls, Drains, Piping, Flanges, Couplings, Caps and Plugs

AQUIS Foam System. Installation, Operation, and Maintenance Instructions AQUIS 1.5, AQUIS 3.0, and AQUIS 6.0

Superior Performance

CM Body Assembly Service Parts List CM 93 and CM 04 Body Styles

Complete Disassembly of Pump. Replacement of Packing or Mechanical Seals Without Disassembling the Pump

PB18 Series Portable Pump Assembly Service Parts List

DANKO STOCK B DANKO XL SKID UNIT 250 Gallon UPF Defender Poly Tank

B&M / INTRODUCTION

FOAM MANIFOLD CONFIGURATION and PRICE GUIDE Including Darley AutoCAFS AIR (Air Injection Regulator) Air distribution manifold assembly

SECTION V ASSEMBLY CAUTION THE FOLLOWING SAFETY PRECAUTIONS SHOULD BE THOROUGHLY UNDERSTOOD BEFORE ATTEMPTING MACHINE ASSEMBLY.

B-1125 DANKO STOCK. DANKO XL SKID UNIT UPF Defender Poly Tank

<THESE INSTRUCTIONS MUST BE GIVEN TO THE END USER> B&W Trailer Hitches 1216 Hawaii Road / PO Box 186 Humboldt, KS P: F:

70-35-GP Portable CAFS Unit Service Parts List

This information covers the proper procedure for replacing the Volvo D16F engine in a VT or VNL chassis.

PV Series E, J, & L Piston Pump Installation Tips and Procedures

Vickers 45. VMQ Series 30 Vane Pumps. Fixed Displacement, For Industrial and Mobile Applications (4.188)

Spool Valve Hydraulic Motors. Spool Valve motors incorporate the proven orbit motor principle to provide high torque at low speeds.

P SERIES PUMPS. 18mm Versions Nickle-Aluminum Bronze Models: P , P , P , P , P , P , P

<THESE INSTRUCTIONS MUST BE GIVEN TO THE END USER> B&W Trailer Hitches 1216 Hawaii Road / PO Box 186 Humboldt, KS P: F:

Model &

RS Multi-Stage, Ring Section Pumps

Owner smanual. Banks Ram-Air Super-Scoop Chevy/GMC Pickups. with Installation Instructions

Section 10 Chapter 17

OPERATION, MAINTENANCE AND OVERHAUL INSTRUCTIONS FOR PB18 SERIES PORTABLE PUMPS

CAFS Air Compressor Service Parts List Models 100-D, 120-D, 150-D, 200-D

ARC GPM MAX WARNING BEFORE BEGINNING INSTALLATION OF THIS APSCO PRODUCT READ AND FOLLOW ALL INSTALLATION INSTRUCTIONS

Centrifugal PTO Pumps. 2 nd Edition

One Step CAF System Operation and Maintenance Instructions

CAUTIONS AND WARNINGS

Low Profile J Series Power Unit with Vane Pump

CM, CMU, CS, CSU Separable Impeller Shaft 2, 3 CXV, CXS Non-Separable Impeller Shaft 4, 5. Input and Output Shaft.

MAINTENANCE MANUAL FOR THERMOSTATIC TEMPERATURE REGULATING VALVE TRAC STYLE P

RUFNEK 80 DESIGN SERIES 001 SERVICE MANUAL INTRODUCTION AND THEORY OF OPERATION...2 ASSEMBLY NUMBER EXPLANATION...2 WINCH MODEL CODES...

OPERATING INSTRUCTIONS

Fisher 585C Series Piston Actuators

Pyrolance, LLC PTO-HYDRAULIC DRIVEN ULTRA HIGH PRESSURE FIRE FIGHTING SYSTEM B 2000 M-P

Chrysler TorqueFlite Shift Improver Kit Part No A-727 (V-8) A-904 (V-8) (A-998 & A-999)

Spool Valve Hydraulic Motors Series J

9 POWER TAKE-OFF 9.1 REAR ENGINE POWER TAKE-OFF (REPTO) ASSEMBLY FRONT MOUNTED POWER TAKE-OFF

CAB TILT HYDRAULIC SYSTEM

<THESE INSTRUCTIONS MUST BE GIVEN TO THE END USER> B&W Trailer Hitches 1216 Hawaii Road / PO Box 186 Humboldt, KS P: F:

Pumps & Motors GRESEN INDEX

Air Compressor Service Parts List One-Step CAFS Model 150-OS Eclipse GEN 2.0 CAFS Model 150-ECL Pump Models HL200K, HL300K, HL400K Index:

HYDRAULIC VARIABLE PUMPS

Caterpillar Engine 01.00

Installation and Maintenance Instructions Falk Wrapflex (Page 1 of 7) 1. General Information. 2. Safety and Advice Hints DANGER! Type 10R.

Edelbrock Victor II Intake Manifold. For Chrysler 5.7L (Eagle) and 6.1L Gen III HEMI Engines Part #7179

3" & 4" Cast Iron Self-Priming Centrifugal Pump Instruction Manual

Introduction. Installation. Maintenance. Bill of Materials

Table 6-1. Problems and solutions with pump operations. No Fluid Delivery

J Series (129-) Highlights

Valtek Flow Boosters

Troubleshooting. Pull Type Clutches - Poor Release

Scheduled/Special Inspections & Recommended Support Parts

Centrifugal Pumps (Part Nos. PS2SS PS73SS) PS2SS

Foam Generator Service Parts List One-Step CAFS

Model 8329 Table of Contents

TRAILER INSTALLATION INSTRUCTIONS

Suspension Upgrade System RS66152 (Upper Adjustable Control Arms)

HIGH VELOCITY PUMP PUMP END

Variable Displacement Piston Pumps for Industrial Applications

ITEM 1 ROLLIGON CORPORATION MODEL TPT-2250 TRAILER MOUNTED FRACTURING UNIT

Transcription:

CL Series Centrifugal Fire Pumps Installation Instructions Table of Contents Safety Information... 1 Introduction... 2 Pump Mounting... 2 Pump Mounting-CLK Series (Optional Mounting Brackets) 3 Optional Suspension Pin Mounting Kit (K520)..4 Pump Mounting CLT Series... 5 Pump Mounting CLD Series... 6 Pump Mounting CLPA Series... 7 Installation of Foam Manager... 8 Optional Corrosion Protections... 8 Final Checks... 9 Lubrication: K Transmission... 9 T Transmission... 9 PA Transmission... 9 Testing... 9 Read through the safety information and operating instructions carefully before using your Waterous Fire Pump. F-1031, Section 3020 (4/10/17) Waterous Company, 125 Hardman Avenue South, South St. Paul, Minnesota 55075 USA (651) 450-5000 www.waterousco.com

Safety Information Read through and communicate safety information to the end user of this Waterous Fire Pump. Death or serious personal injury might occur if proper operating procedures are not followed. The pump operator, as well as individuals connecting supply or discharge hoses to the apparatus must be familiar with these pump operating instructions as well as other operating instructions and manuals for the apparatus, water hydraulics and component limitation. Pressure Hazard. May result in personal injury. Prior to connection or removal of hoses, caps or other closure with pump intake or pump discharge connections, relieve pressure by opening drains or bleeder valves. Bleeder valves should also be used while filling a hose connected to an intake with water. Scalding Water Hazard. May result in serious burns. When operating the pump, be sure to open at least one discharge valve slightly to prevent the pump from overheating. If the pump runs for a few minutes completely closed, it may heat the water enough to scald someone when the valve is opened. Overheating can damage the packing, seals and other pump parts. If the apparatus builder has installed a by-pass system or other provision designed to prevent overheating, opening a discharge valve may be unnecessary. Rotating Parts Hazard or Unexpected Truck Movement. May result in serious personal injury or death. Stop the engine, set parking brake and chock the wheels before going under the truck to adjust packing or to check packing gland temperatures. OEM Installation Warning Unexpected Truck Movement. May result in serious personal injury or death. Failure to properly install the pump shift control and pump shift indicator system in the apparatus or failure to incorporate in the Pump Operator s Panel Engine Speed Interlock System may result in unexpected truck movement which may result in serious personal injury or death. Inability to Pump Water. May result in personal injury or death. Failure to properly install the pump shift control and pump shift indicator system in the apparatus or failure to incorporate in the Pump Operator s Panel Engine Speed Interlock System may result in unexpected truck movement which may result in serious personal injury or stress. Exceeding Power Train Torque Ratings. May result in inability to pump water causing serious personal injury or death. This fire pump may have the capability under certain pumping conditions to exceed the torque rating of the powertrain. A means to control the engine output to a torque level no greater than the power train s continuousduty torque rating must be considered when specifying power train components and engine control system parameters. F-1031, Section 3020 Page 1 of 9

Introduction This instruction covers the installation of a Waterous CL Series fire pump. The CL is rated at 500 gpm. Table 1 shows the three different CL models available. Table 1. CL Models Model CLR CLV CLD Descriptions Intake: 4 in. NH or BSP thread Discharge: Head with 2-1/2 in. flanges, 3 in. NPT tapped flange, 3 in. Victaulic or blank (without head or tapped flange or Victaulic fitting) Intake: 4 in. Victaulic Discharge: Head with 2-1/2 in. flanges, 3 in. NPT tapped flange, 3 in. Victaulic or blank (without head or tapped flange or Victaulic fitting) Direct drive with automatic piston primers. Intake: 4 in. or 4-1/2 in. flanged or threaded Discharge: 3 in NPT tapped flange or blank The following installation instructions are available: Priming System, F-1031, Section 3006 Manifold Drain Valves, F-1031, Section 3008 Pressure Control System, F-1031, Section 3010 Separately Mounted Foam Manager Manifold, F-1031, Section 3012 Overheat Protection Manager, F-1031, Section 3015 Before proceeding with the installation of the CL, read the instructions carefully. Check the appropriate dimensional drawings in the Engineering Manual as needed. The CLR and CLV pumps are available with the following transmissions: K Series - The K transmission is a gear driven transmission designed primarily to be driven by a power take-off or power divider. (see Figure 1). T Series - The T transmission is a gear driven transmission designed to be mounted directly to the engine bell housing. This provides a clean, compact arrangement and allows for complete pump and roll capability. (See Figure 3). PA Series - The PA transmission is an aluminum chain drive transmission designed to be driven off the ten-bolt power take-off (PTO) provision available on the left side of the Allison MD or HD automatic transmission. (See Figure 5). Pump Mounting - General Information Select a mounting location which will make the pump and its accessories readily accessible for maintenance. Table 2 gives maximum universal joints angles for installations where propeller shaft flanges are parallel and yokes are aligned. Refer to this table when positioning a pump to determine proper shaft angles. Be sure to keep at least a minimum of 1 U-joint operating angle, but do not exceed those specified in the table. This is the preferred method of propeller shaft installation. For additional information on this method, or for alternative methods, see driveshaft installation guidelines such as Spicer /Driveshaft Installation Techniques, J-3311. CAUTION Be sure the propeller shafts used are of the slip-joint design. Frame deflection, temperature changes and similar factors may cause a propeller shaft without slip-joints to produce sever axial loads on the bearings and damage the pump. Table 2. Maximum U-joint Operating Angles Driveshaft RPM Maximum Operating Angle 5000 3.2 4500 3.7 4000 4.2 3500 5.0 3000 5.8 2500 7.0 2000 8.7 1500 11.5 NOTE: The angles shown in Table 2 are the maximum recommended U-joint operating angles and are directly related to the speed of thedriveshaft. Any U-joint operating angle greater than 3 will lower the U-joint life and may cause vibration. 1 From Spicer Driveshaft Installation Techniques, Form J-3311. F-1031, Section 3020 Page 2 of 9

Pump Mounting - CLK Series Figure 1 shows the mounting areas on a CLK pump. To mount the pump/transmission to the vehicle chassis, construct a bracket that will span the frame rails of the vehicle and attach to the transmission mounting holes (several locations are provided). NOTE: Before installation, make sure your pump has the right rotation as compared to the driveshaft rotation (see dimensional drawings for correct rotation configurations). Position the pump/transmission within the vehicle frame rails and secure the brackets (not supplied) to the vehicle frame. Support the pump by constructing brackets (not supplied by Waterous) and mount them to the the mounting plates located on either side of the pump. NOTE: Tighten the mounting screws to standard torque specifications. Finally, provide adequate support for any intake and discharge piping assemblies. Figure 1. CLK Mounting Diagram Pump Mounting Plate (2) Mounting Holes (7/16-14 UNC-2B x.625 in. deep) (6) Mounting Holes (7/16-14 UNC-2B x.625 in. deep) IL2400 F-1031, Section 3020 Page 3 of 9

Optional Suspension Pin Mounting Kit (K520) An optional mounting technique on the CLK pump is the Suspension Pin Mounting Kit. The kit consists of a bracket, two 7/16 screws, two lock washers, two cotter pins and the suspension pin. To mount the transmission using this kit, follow the instructions below: 1. Mount the bracket to the transmission using the top two mounting holes. Secure the bracket with the two 7/16 screws and lock washers. 2. Insert the suspension pin into the bracket. 3. Line up the hole in the bracket with the hole in the suspension pin and insert a cotter pin. Figure 2. Suspension Pin Mounting 4. Construct a bracket that will span the vehicle's chassis. Cut out a hole in the bracket that will allow the suspension pin to pass through. 5. Install the bracket on the suspension pin and hold in place by inserting a cotter pin through the hole on the suspension pin. 6. Support the pump by constructing brackets (not supplied by Waterous) and mount them to the the mounting plates located on either side of the pump. Cotter Pin, 5/16 x 2-1/2 Hex Hd Screw, 7/16-14 x 1-1/4 Lock Washer, 7/16 Suspension Pin Mounting Bracket from SPL81614 Cotter Pin Suspension Pin Pump Mounting Plate IL2397 F-1031, Section 3020 Page 4 of 9

Pump Mounting - CLT Series Figure 3 shows the CLT pump. The CLT is a direct-engine mounted pump. The bellhousing attaches to the vehicles flywheel housing. NOTE: The design of the T transmission relies on the engine flywheel to control the axial and radial movement of the drive shaft. Prior to installation on the engine, the allowable axial movement of the pump drive (input) shaft is.273 in. (7 mm). NOTE: Before installation, make sure your pump has the right rotation as compared to the driveshaft rotation (see dimensional drawings for correct rotation configurations). To install the CLT pump, perform the following: 1. Provide for an input shaft support bearing. NOTE: Input shaft support bearing is not supplied by Waterous. 2. Install the drive plate assembly according to the manufacturer's instructions NOTE: Drive plate may be purchased as an option from Waterous or from another manufacturer. 3. With a suitable hoist, guide the pump drive shaft into the drive plate and pilot bearing. Align screws holes in the pump mounting flange with those in the flywheel housing. Install the twelve (12) screws and tighten securely. 4. Finally, provide adequate support for any intake and discharge piping assemblies. NOTE: Tighten the mounting screws to standard torque specifications. Figure 3. CLT Mounting Diagram IL2398 from DPL82527 F-1031, Section 3020 Page 5 of 9

Figure 4 shows the mounting areas on a CLD pump. To mount the pump to the vehicle chassis, construct a bracket that will span the frame rails of the vehicle and attach to the bearing housing mounting holes (four locations are provided). NOTE: Before installation, make sure your pump has the right rotation as compared to the driveshaft rotation (see dimensional drawings for correct rotation configu rations). Position the pump within the vehicle frame rails and secure the brackets to the vehicle frame. Figure 4. CLD Mounting Diagram Pump Mounting - CLD Series Support the pump by constructing brackets (not supplied by Waterous) and mount them to the the mounting plates located on either side of the pump. NOTE: Tighten the mounting screws to standard torque specifications. Finally, provide adequate support for any intake and discharge piping assemblies. Pump Mounting Plate (4) Mounting Holes (3/8-16) IL2399 F-1031, Section 3020 Page 6 of 9

Figure 5 shows the mounting areas on a CLPA pump. To mount the pump/transmission to the vehicle chassis, fashion a bracket that will span the frame rails of the vehicle and attach to the transmission mounting holes. Position the pump/transmission within the vehicle frame rails, blocking temporarily to provide correct shaft angularity. With the pump/transmission in the correct position, secure the brackets (not supplied) to the vehicle. Support the pump by fashioning a bracket (not supplied by Waterous) and mount it to the intake side of the pump using the existing intake mounting screw holes. Figure 5. CLPA Mounting Diagram Mounting Holes on Pump Intake Pump Mounting - CLPA Series Remove the screw(s) and install bracket (not supplied by Waterous). Tighten bracket to the intake of the pump using 3/8 in. screw(s). Note: Use longer 3/8 in. screws to secure the bracket to the pump than were originally supplied with the pump to compensate for the thickness of the bracket. NOTE: You will need to remove one or more intake mounting screws from the intake side of the pump and replace them with longer screws to compensate for the thickness of the bracket. NOTE: Tighten the mounting screws to standard torque specifications. Finally, provide adequate support for any intake and discharge piping assemblies. Mounting Holes on Transmission Intake Side of CL Pump Eight (8) Mounting Holes Eight (8) Intake Mounting Screws (3/8-16 UNC-2B x.500 Deep) Anti-seize should be applied to the shaft threads before installing end yoke or companion flange. Do not reuse self-locking nuts. Torque to 275-325 lb.-ft. F-1031, Section 3020 Page 7 of 9

Installation of Foam Manager If the fire pump is supplied with a Foam Manager (500 or 1000 GPM) the foam manifold and a FoamPro foam proportioner are shipped loose from the factory. Refer to the FoamPro Installation and Operation Manual (P/N L-0825) for controller wiring and foam concentrate inlet plumbing instructions. Optional Corrosion Protection Zinc Intake Screens Waterous offers zinc intake screens that fit 4, 4-1/2, 5 and 6 inch intake fitting sizes. The screen is designed to fit in the counter bore in the inside diameter of the fittings. There must be a strong electrical contact between the screen and the intake fitting. Remove any corrosion, debris or paint from the counter bore that will insulate the screen from the intake fitting. If the screen does not fit tightly, adjust the gap of the slot on the outside diameter of the screen to ensure a tight fit. NOTE: Zinc intake screens are die-cast which results in a slight taper from one side to the other. Install the screen with the thinner cross-section facing out to minimize flow restriction. Figure 6. Zinc Intake Screen Figure 7. Zinc Anodes - Pads Machined with 2-1/2 in, 4-bolt Mounting Pattern IL269 5 Figure 8. Zinc Anodes - Pads Machined with 2-1/2 in or 3 inch NTP Taps Zinc Anodes Zinc anodes may be mounted in the intake piping or, if no intake pads are available, in the discharge piping. NOTE: The zinc must make contact with water to be effective. Do not paint or use any type of coating on the zinc element. Zinc anodes are available for the following: Pads machined with 2-1/2 inch, 4-bolt mounting patterns, see Figure 7. Pads machined with 2-1/2 or 3 inch NTP taps, see Figure 8. F-1031, Section 3020 Page 8 of 9

Final Checks After the pump, accessories, piping and miscellaneous connections are completely installed, check the points listed be low: Lubrication K & T Transmissions Add any type of SAE 80W-90 gear oil through the fluid level hole or by removing the breather. Approximately 1 quart is required to fill the transmission when completely drained. The fluid should be level with bottom of the fluid level hole. Testing Perform the tests listed in F-1031, Section 1000, Centrifugal Fire Pump Principles of Operation, Inspection Tests and Troubleshooting Guide. During the running tests, monitor the smoothness of operation, listen for unusual noises and check for leaks. PA Transmissions Add any type of automatic transmission fluid (ATF) through the fluid level hole or by removing the breather. Approximately 1 quart is required to fill the transmission when completely drained. The fluid should be level with bottom of the fluid level hole. CLD Primers Add any type of 10W-30 motor oil through the primer oil dipstick. Approximately 1/2 quarts (.5 Liters) is required to fill the primers when completely drained. CAUTION Be sure the propeller shafts used are of the slip- joint design. Frame deflection, temperature changes and similar factors may cause a propeller shaft without slip- joints to produce severe axial loads on the bearings and damage the pump. F-1031, Section 3020 Page 9 of 9