MEDIUM VOLTAGE PRODUCTS. Fault Current Limiters I S. -limiter and FC-Protector The worldʼs fastest switching devices

Similar documents
Fuse-links type CEF-VT Rated voltages 3/7.2 kv - 10/24 kv Rated current 0.5 A 6.3 A

ZX-Family Gas-insulated medium voltage switchgear

Fuse-links type CEF-S Rated voltages: 6/12 kv 30/40.5 kv Rated currents: 6.3 A 63 A

Modular Standardized Electrical and Control Solutions for Fast Track Projects

Product Brochure. Generator Circuit-Breaker HVR-EBCB For hydro or pump storage power plant

ZX-Family Gas-insulated medium voltage switchgear

Product brochure Generator circuit-breaker HVS-63S System type GCB with innovative built-in monitoring

Voltage limiting device HVL

SACE Emax 2/ML Low-voltage air circuit breakers for naval applications

Voltage limiting device HVL

Thermal overload relay TF140DU and TF140DU-V1000

Brochure. Modular Systems wind portfolio Power Collection and Grid Connection products

Electronic overload relay EF65, EF96 and EF146

Electronic overload relays EF205 and EF370

ZX2 Gas-insulated medium voltage switchgear

When grids get smart ABB your partner for developing Smart Grids solutions

System pro M compact Miniature Circuit Breaker SU200M for branch circuit protection acc. to UL 489

EMPAC Metal enclosed capacitor bank for wind applications

ABB AG - EPDS. Ultra-Fast Earthing Switch UFES active internal arc protection

System pro M compact Supplementary protector S 200 PR for ring-tongue applications acc. to UL1077

1ZSC AAA EN, REV. 7. Transformer bushings type GSBK Technical guide

Thermal overload relay TF65 and TF96

Surge arrester POLIM-H.. ND

Outdoor live tank SF6 circuit breaker EDT with integrated current transformer up to 72.5 kv

Manual motor starters Overview and benefits

Overview Overvoltage protection

Selective main circuit breakers S 750 series Technical Data

Surge arrester POLIM-C.. HD

Low Voltage Systems MNS and MNS is PowerCenter

MEDIUM VOLTAGE PRODUCT. TJC 4 Indoor voltage transformers

System pro M compact Miniature Circuit Breaker S 200 M UC for DC and AC applications

Dead Tank Circuit Breaker 145PM40-C Compact design with enhanced reliability

Surge arrester POLIM-H..SD

Low voltage capacitors CLMD Improving power factor and enhancing power quality of your network

Manual motor starter magnetic only MO325

Semi-pantograph disconnector type DSSP, up to 300 kv Maximum reliability and minimal maintenance

Ultra Fast Earthing Switch UFES retrofit Overview

PRODUCT BROCHURE. ABB Ability Wireless Monitor for surge arrester Enabling reliability and availability of power supply

Protection and Connection Motorized and automatic transfer switches IEC Technical guide

SU200M Datasheet. Branch protection acc. to CSA C22.2 No.5 / UL 489

School of Electrical and Information Engineering. ELEC High Voltage. University of Sydney. Dr Keith Mitchell. Engineering

Manual motor starter MS132

Redundancy unit CP-C.1-A-RU Accessory for CP-C.1 range power supplies

MEDIUM VOLTAGE PRODUCT. KECA 250 B1 Current Sensor Instructions for installation, use and maintenance

LOW VOLTAGE WIND CONVERTERS. ABB wind turbine converters ACS880, 800 kw to 8 MW

System pro M compact Miniature Circuit Breaker S 200 M UC for DC and AC applications

ABB central inverters PVS to 2091 kva

Operational Experience with Startup Optimization for Steam Boilers. E.ON s Staudinger, Heyden, Ingolstadt und Zolling Power Plants

US Panorama. New SACE Emax 2 UL 1066 From Circuit Breaker to Power Manager

ABB DRIVES SERVICE. Optimize your wind economy. Wind Converter Services

Control and Automation. AC500 - your PLC for solar systems Change for more energy efficiency

1ZSE EN, REV. 4. Wall bushings type GSA-AA Technical guide

Product brochure. Gas-insulated switchgear ELK-04 C, 145 kv Modular and reliable

FUSES. Safety through quality

PQC - STATCON The ultra fast Power Quality Compensator

MEDIUM VOLTAGE PRODUCT. KECA 80 D85 Current Sensor Instructions for installation, use and maintenance

1ZSE EN, REV. 7. Oil SF 6. bushings type GOEK Technical guide

Low voltage bushings for pad-mounted distribution transformers Technical information guide

More power for railway lines Maximum efficiency with proven system behavior

BRIDGE-BOY Load limitation electronics with 1 or 3 set points

Brochure. Synchronous generators for steam and gas turbines Proven generators reliable power

Switchgear and Distribution Systems for Engineers and Technicians

Emergency-off application Manual motor starter MS116/MS132 Undervoltage release UA1

Thermal Overload Relays

Independent Testing Laboratory for High Voltage Equipment

Mini contactors B6, BC6 with 3 pole

Surge arrester POLIM-H..N

Product information. ECOSS Electronic compact starter for wound rotor drives

Type SIMOPRIME A4, up to 24 kv, Air-Insulated Medium-Voltage Switchgear

Catalogue March InLine II - ZLBM/ZHBM Fuse Switch Disconnector

Exceeding the standards with MNS

ABB Low voltage systems MNS Platform

voltage switchgear ZX ABB ZX Family 1

Use of High-Power Thyristor Technology for Short-Circuit Current Limitation in High Voltage Systems

NXPLUS C Single busbar. Maintenance-free for lifetime

Manual motor starter MS116

Switchgear Type 8BT1, up to 24 kv, air-insulated. Medium Voltage Switchgear Catalog HA 26.

Safe and secure power distribution Arc fault protection solutions

Medium-voltage fuses 3 kv 40.5 kv, 0.4 A 315 A

TRANSFORMER SERVICE. ABB Ability inspection for transformers TXplore Oil-filled transformer internal inspection service

Manual motor starter MS132

TriLine PowerModules Overview with Planing Examples

Product brochure. Gas-insulated switchgear ELK-04 C, 145 kv Modular and reliable

MEDIUM VOLTAGE CE-B36 METAL CLAD SWITCHBOARDS. CE - B36 - C - en - REV

ZX2.2 Gas-insulated medium voltage switchgear

Manual motor starter MS132

NEXT STEP B) SAFETY :

Extensible Unit - VCE2a

MEDIUM VOLTAGE PRODUCT. KECA 80 C85 Current Sensor Instructions for installation, use and maintenance

Benefits, typical uses

Breaker-failure protection RAICA

US CATALOG. ProLine Panelboard and breakers

Unit Protection System for Pumped-Storage Power Stations

MEDIUM VOLTAGE CE-B METAL CLAD SWITCHBOARDS. CE - B - C - en - REV

The University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 2

Applications. Distribution transformers up to 2000 kva High-voltage motors up to 3 MW Capacitors up to1200 kvar MV voltage transformers Cable feeders

Medium voltage products. Fuses

Marine generators Proven generators for reliable power on board

ZF SERIES HV GAS INSULATED SWITCHGEAR (GIS) tgood.com. Energy. Fast.

HHD. High Voltage Fuses German DIN Standard. The temperature limiting function of the fuse striker pin. Design and construction.

Transcription:

MEDIUM VOLTAGE PRODUCTS The worldʼs fastest switching devices

2 FAULT CURRENT LIMITERS THE WORLDʼ S FASTETST SWITCHING DEVICES The worldʼs fastest switching devices ABBʼs fault current limiters disconnect the fault affected part of the system extremely fast so that the short-circuit withstand capability of the system is not violated. Why are short-circuit fault levels increasing? The growing energy demand and the need for stable power supply are one of the major challenges faced by consumers, power producers and network operators. With the rising demand for energy worldwide, existing power distribution systems and power grids are being expanded and get more and more meshed. This might be a possible solution for reliable supply but the short-circuit fault levels increase, causing another challenge for all concerned parties. How is the short-circuit current characterized? Short-circuit currents can be defined by the initial three-phase symmetrical short-circuit current, also referred to as, and the peak short-circuit current, also referred to as i p. The thermal stress to which electrical system components are exposed to is associated with the initial three-phase symmetrical short-circuit current. The dynamical-mechanical stress to which these are exposed is associated with the peak short-circuit current. Why do short-circuit currents occur? There are several reasons for short-circuits to occur. The most common reasons are human errors, defective equipment, overvoltage, pollution and animals. Short-circuits can happen anywhere without advance intimation. Does my equipment withstand a short-circuit fault? Electrical equipment is usually tested according to the relevant standards to withstand the permissible short-circuit currents. Those are the rated peak withstand current, the short-time withstand current and the rated short-circuit duration. If one of these parameters is exceeded, the equipment will most probably face severe destruction. Flexibility as well as reliability of systems can be increased manifolds with the application of ABB s fault current limiters. What do ABB s fault current limiters do? The -limiter and the FC-Protector limit the short-circuit current before the first current peak is reached such that the equipment rating is not exceeded. They isolate the fault affected part of the network within micro seconds (µs) and ensure that the short-circuit level is not exceeding the systems withstand capability. They facilitate flexible power distribution, power system expansion, independent power production, reactor replacement and many more such applications without considering the equipment short-circuit withstand capability as a constraint. Why must short-circuit currents be limited? Each equipment in an electrical network has a certain permissible short-circuit withstand capability, which if exceeded will have hazardous consequences for equipment, personnel and environment. If electrical equipment like switchboards, switches, transformers or cables are subjected to short-circuit currents higher than their withstand capability they can be destroyed by the dynamic and thermal stresses.

3 01 Total operating time of a conventional circuit-breaker indicated on short-circuit current waveform i Destruction No destruction t T 0 T 1 T 2 Relay time Breaking time Arcing time T 0 T 1 T 2 40-60 ms 40-80 ms 10-20 ms 02 Total operating time of ABBʼs FCL indicated on shortcircuit current waveform i Destruction No destruction T t T 0 T 1 T 2 Current flow time by use of ABBʼs FCL: T = 5-10 ms The will limit the short-circuit current in less than 1 ms after detection! With ABB ʼs FCL customer has an option to decide for which current direction or protection area tripping is required. Why are circuit-breakers not able to mitigate the fault level? The highest dynamical force and stress on the system is caused by the first peak of the shortcircuit current. Circuit-breakers do not operate fast enough to protect the electric system from first shortcircuit current peak. Under consideration of the relay operating time (T 0 ), the circuit-breaker breaking (T 1 ) and arcing (T 2 ) a circuit-breaker can only interrupt the shortcircuit current after the first peak, in approx. 40-80 ms. By the time a circuit-breaker interrupts, irreversible damage has already been done. The solution to this problem is the installation of a fault current limiter (FCL) in a system that is able to detect a fault current during its first rise and limit the fault current before the peak is reached. Why are reactors not sufficient? Reactors are impedances that are aimed to limit the current to a certain value in case of a shortcircuit fault. As they are in the main current path in normal operation, they continuously generate power losses. This will cause high operating costs and undesired voltage drops for the customer. Since reactors do not interrupt the current but only reduce them, their fault current limiting capability is very restricted. They cannot be used in systems in which no fault level margin is left. Each reactor is designed for the existing short-circuit currents of a system. This means that in case of later extension the reactor must probably be replaced, whereas ABB s FCLs can be easily modified for such changes.

4 FAULT CURRENT LIMITERS THE WORLDʼ S FASTETST SWITCHING DEVICES The worldʼs fastest switching devices 1 Insert holder 1.1 Insulator 1.2 Insulator with impulse transformer 2 Insert 2.1 Main current path 2.2 HV HRC fuse 2 2.2 2.1 1.1 1 1.2 Operating principle The -limiter and the FC-Protector consist of a tailor made application based control unit that detects the short-circuit. The main current path (hollow copper bus) inside a detachable insert carries the continuous current in normal operating condition. In case of a short-circuit the main current path is immediately opened by a charge element, which is triggered by the control unit. The short-circuit current commutates to a parallel fuse with high breaking capacity, which limits the short-circuit current during the first rise before the first current peak is reached. Our major customers ABB s fault current limiters, the -limiter and the FC-Protector provide a large range of solutions for various applications and industries. Our main customers are: High power industries such as refineries, chemical plants, paper mills, steel or aluminum mills, cement plants, oil and gas, Utilities such as energy suppliers and power plants, Green energy such as waste heat recovery plants, combined heat production, hydro power, biomass generators, wind mills and solar plants, Highly sensitive systems such as data centers, offshore installations, platforms, laboratories, banks and hospitals.

5 IS Typical applications 01 -limiter installed on oil platform 02 IS -limiter installed as data center solution for higher reliability 03 IS -limiter especially certified for marine application 02 01 03

6 FAULT CURRENT LIMITERS THE WORLDʼ S FASTETST SWITCHING DEVICES Typical applications Typical applications The can be used in various applications providing very high and fast fault current breaking capability at high operating currents. The most common applications are: Connecting two independent systems without exceeding equipment short-circuit rating Bypassing a reactor Connecting an additional power source (e.g. generator or grid connection) Interfacing public networks and consumer owned power supply systems ABB will support you to identify the place of installation which provides most effective fault current limitation while maintaining operational reliability. Bypassing a reactor ABB s fault current limiters are used to eliminate the negative impacts of reactors where reactors cannot be avoided, as mentioned below: Avoiding copper losses and the associated operating costs of the reactor No voltage drop at the reactor Ensuring continuous power supply through reactor in case of FCL tripping Connection of an additional power source (e.g. generator or grid connection) ABB s fault current limiters are frequently used in case adding an additional power source would lead to a violation of the system short-circuit withstand capability. The main advantages of using ABB s fault current limiters are: System extensions without replacing electrical equipment such as circuit-breakers, switchgear, cable or transformers Improving availability of the power supply Coupling of independent systems ABB s fault current limiters are frequently used to connect two systems which would exceed their short-circuit withstand capability when connected through a coupling circuit-breaker. The main advantages of using ABB s fault current limiters in a coupling are: Increased operational flexibility by connecting independent systems Flexibility to choose low impedance equipment (e.g. transformers or generators) and reducing losses Optimized load flow with higher availability of systems and processes Increased reliability of the power supply Improved voltage stability when large motors are started Reduction of energy released in case of a fault System extension without replacing existing electrical equipment such as circuit-breaker, busbar, cable system.

7 ABBʼs reliable solution for short-circuit current challenges ABBʼs fault current limiter portfolio includes the. Together these two products cover a wide range of low and medium voltage applications, indoor as well as outdoor. Main technical parameters As every customer system is different it is possible to provide a tailor made solution. Both fault current limiters are available as loose components and in a panel configuration. ABB has experience in delivering fault current limiting solutions since 1958, having more than 3,000 installations in more than 85 countries. ABBʼs FCL Installation Outdoor Indoor Rated voltage 7.2 kv 17.5 kv 0.75 kv 40.5 kv Rated current 2500 A 5000 A Breaking capacity 63 ka RMS 210 ka RMS Optimizing your investments Eco- and cost-efficient fault current limiters Optimized load flow behavior Reduction of energy losses in the system Maximizing your output Increase uptime and redundancy of the power distribution systems Flexible connection to new and existing switchboards Installation in greenfield and brownfield projects Protecting your assets Type tested equipment Redundant control unit for additional safety World s fastest fault current limiters to protect systems and processes Fault current limitation in harsh environments More than 3,000 installations in more than 85 countries Additional information www.abb.com/medium-voltage/ apparatus/fault-current-limiting Contacts Feel always welcome to contact us if you have any questions.

ABB AG Calor Emag Medium Voltage Products Oberhausener Strasse 33 40472 Ratingen, Germany Phone: 02102 12-0 Telefax: 02102 12-17 77 DE-FCL@abb.com Additional information We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB AG does not accept any responsibility whatsoever for potential errors or possible lack of information in this document. We reserve all rights in this document and in the subject matter and illustrations contained therein. Any reproduction, disclosure to third parties or utilization of its contents in whole or in parts is forbidden without prior written consent of ABB AG. Copyright 2017 ABB. All rights reserved. Specifications subject to change without notice. DEABB 2562 en P0102 REV 01 printed in Germany (11.17- AMC)