Journal of American Science 2015;11(11) Integration of wind Power Plant on Electrical grid based on PSS/E

Similar documents
Wind Farm Evaluation and Control

FAULT ANALYSIS OF AN ISLANDED MICRO-GRID WITH DOUBLY FED INDUCTION GENERATOR BASED WIND TURBINE

Statcom Operation for Wind Power Generator with Improved Transient Stability

Workshop on Grid Integration of Variable Renewable Energy: Part 1

ASSESSING BEHAVOIR OF THE OUTER CROWBAR PROTECTION WITH THE DFIG DURING GRID FAULT

Comparative Analysis of Integrating WECS with PMSG and DFIG Models connected to Power Grid Pertaining to Different Faults

Battery Energy Storage System addressing the Power Quality Issue in Grid Connected Wind Energy Conversion System 9/15/2017 1

CHAPTER 5 FAULT AND HARMONIC ANALYSIS USING PV ARRAY BASED STATCOM

Fuzzy based STATCOM Controller for Grid connected wind Farms with Fixed Speed Induction Generators

Integration of Large Wind Farms into Electric Grids

ENHANCEMENT OF ROTOR ANGLE STABILITY OF POWER SYSTEM BY CONTROLLING RSC OF DFIG

Wind Power Plants with VSC Based STATCOM in PSCAD/EMTDC Environment

Squirrel cage induction generator based wind farm connected with a single power converter to a HVDC grid. Lluís Trilla PhD student

IMPROVEMENT IN DOUBLY FED INDUCTON GENERATOR UNDER FAULT USING INDUCTOR

Effect of crowbar resistance on fault ride through capability of doubly fed induction generator

Voltage Sag Mitigation in IEEE 6 Bus System by using STATCOM and UPFC

APPLICATION OF STATCOM FOR STABILITY ENHANCEMENT OF FSIG BASED GRID CONNECTED WIND FARM

Wind Generation and its Grid Conection

Performance Analysis of Transient Stability on a Power System Network

ECEN 667 Power System Stability Lecture 19: Load Models

CONTROL AND PERFORMANCE OF A DOUBLY-FED INDUCTION MACHINE FOR WIND TURBINE SYSTEMS

Grid Code Testing of Wind Turbines by VSC-based Test Equipment

EPE97 OPTIMIZED DESIGN OF VARIABLE-SPEED DRIVES BASED ON NUMERICAL SIMULATION

J.-J.Simond*, A.Sapin**, B.Kawkabani*, D.Schafer***, M.Tu Xuan*, B.Willy***

A Variable Speed Wind Generation System Based on Doubly Fed Induction Generator

Dynamic Behaviour of Asynchronous Generator In Stand-Alone Mode Under Load Perturbation Using MATLAB/SIMULINK

EFFECT OF WIND TURBINE GENERATORS ON THE SMALL SIGNAL STABILITY OF POWER SYSTEMS. Kamel A. Shoush, Member, IEEE

Use of STATCOM for Improving Dynamic Performance of Wind Farms Connected in Power Grid

Modelling and Simulation of DFIG with Fault Rid Through Protection

EE 742 Chap. 7: Wind Power Generation. Y. Baghzouz Fall 2011

Design and Control of Lab-Scale Variable Speed Wind Turbine Simulator using DFIG. Seung-Ho Song, Ji-Hoon Im, Hyeong-Jin Choi, Tae-Hyeong Kim

Research on Transient Stability of Large Scale Onshore Wind Power Transmission via LCC HVDC

Transient Stability Improvement of Squirrel Cage Induction Wind Turbine Generator using Plugging Mode

Robust Control Technique for Grid-connected Power Conditioner

Hamdy S. K. El-Goharey, Walid A. Omran, Adel T. M. Taha

COMPARISON OF DIFFERENT METHODS FOR EXCITATION OF SYNCHRONOUS MACHINES

Computer Aided Transient Stability Analysis

(by authors Jouko Niiranen, Slavomir Seman, Jari-Pekka Matsinen, Reijo Virtanen, and Antti Vilhunen)

Performance Analysis of Transmission Line system under Unsymmetrical Faults with UPFC

ENHANCEMENT OF TRANSIENT STABILITY OF SMART GRID

Experience on Technical Solutions for Grid Integration of Offshore Windfarms

Simulation Modeling and Control of Hybrid Ac/Dc Microgrid

A STUDY ON ENERGY MANAGEMENT SYSTEM FOR STABLE OPERATION OF ISOLATED MICROGRID

Modelling of Wind Generators for WT3 Transient Stability Analysis in Networks

Power Flow Simulation of a 6-Bus Wind Connected System and Voltage Stability Analysis by Using STATCOM

Modelling and Simulation of DFIG based wind energy system

Performance Analysis of SCIG Coupled With Wind Turbine with and Without Fault Using RLC Load

Faults Mitigation Control Design for Grid Integration of Offshore Wind Farms and Oil & Gas Installations Using VSC HVDC

Published by: PIONEER RESEARCH & DEVELOPMENT GROUP ( 201

PERFORMANCE ANALYSIS OF SQUIRREL CAGE INDUCTION GENERATOR USING STATCOM

CHAPTER 3 TRANSIENT STABILITY ENHANCEMENT IN A REAL TIME SYSTEM USING STATCOM

AMERICAN ELECTRIC POWER 2017 FILING FERC FORM 715 ANNUAL TRANSMISSION PLANNING AND EVALUATION REPORT PART 4 TRANSMISSION PLANNING RELIABILITY CRITERIA

Study of DFIG based Wind Turbine for Reactive Power Generation Capability

Grid Stability Analysis for High Penetration Solar Photovoltaics

Fault Rid Through Protection of DFIG Based Wind Generation System

Enhancement of Transient Stability Using Fault Current Limiter and Thyristor Controlled Braking Resistor

Power Quality and Power Interruption Enhancement by Universal Power Quality Conditioning System with Storage Device

Analysis of Low Voltage Ride through Capability of FSIG Based Wind Farm Using STATCOM

PSO project EaseWind Enhanced ancillary services from Wind Power Plants. Anca D. Hansen DTU Wind Energy

Frequency Control of Isolated Network with Wind and Diesel Generators by Using Frequency Regulator

POWER QUALITY IMPROVEMENT BASED UPQC FOR WIND POWER GENERATION

COMPARISON BETWEEN ISOLATED AND GRID CONNECTED DFIG WIND TURBINE

DYNAMIC BEHAVIOUR OF SINGLE-PHASE INDUCTION GENERATORS DURING DISCONNECTION AND RECONNECTION TO THE GRID

Anupam *1, Prof. S.U Kulkarni 2 1 ABSTRACT I. INTRODUCTION II. MODELLING OF WIND SPEED

Abstract. Benefits and challenges of a grid coupled wound rotor synchronous generator in a wind turbine application

Matlab Modeling and Simulation of Grid Connected Wind Power Generation Using Doubly Fed Induction Generator

Using energy storage for modeling a stand-alone wind turbine system

Intensification of Transient Stability in Grid Connected Squirrel Cage Induction Generator Using Plugging Mode Operation

New York Science Journal 2017;10(3)

Power System Stability Analysis on System Connected to Wind Power Generation with Solid State Fault Current Limiter

Analysis of Grid Connected Solar Farm in ETAP Software

Co-Ordination Control and Analysis of Wind/Fuel Cell based Hybrid Micro-Grid using MATLAB/Simulink in Grid Connected Mode

Power Balancing Under Transient and Steady State with SMES and PHEV Control

THE IMPORTANCE OF INTEGRATING SYNCHRONOUS COMPENSATOR STATCOM IN WIND POWER PLANT CONNECTED INTO THE MEDIUM VOLTAGE GRID

Islanding of 24-bus IEEE Reliability Test System

Coordinated Control of DFIG under Grid Fault Condition in Wind Energy Conversion System

INVESTIGATION OF THE IMPACT OF SWITCHING A HEAVILY LOADED TRANSMISSION LINE ON OPERATION OF A POWER PLANT WITH TURBINE-GENERATOR UNITS

A Dual Stator Winding-Mixed Pole Brushless Synchronous Generator (Design, Performance Analysis & Modeling)

Electric Vehicles Coordinated vs Uncoordinated Charging Impacts on Distribution Systems Performance

Modeling of doubly fed induction generator (DFIG) equipped wind turbine for dynamic studies

IJSER. 1. Introduction. 2. Power flow of Doubly fed Induction Generator (DFIG) K. Srinivasa Rao 1 G. Kamalaker 2

Electrical grid stability with high wind energy penetration

A Comparative Study of Constant Speed and Variable Speed Wind Energy Conversion Systems

Experiences with Wind Power Plants with Low SCR

Wind Generators Evolving Technology

Possibilities of Distributed Generation Simulations Using by MATLAB

STABILIZATION OF ISLANDING PEA MICRO GRID BY PEVS CHARGING CONTROL

Studies regarding the modeling of a wind turbine with energy storage

Aspects of Wind Power Plant Collector Network Layout and Control Architecture

Impact of Photovoltaic Power Plant on the Transient Stability Compared With Synchronous Generator.

The Effect Of Distributed Generation On Voltage Profile and Electrical Power Losses Muhammad Waqas 1, Zmarrak Wali Khan 2

Power Quality Improvement Using Statcom in Ieee 30 Bus System

International Journal of Scientific & Engineering Research, Volume 6, Issue 10, October ISSN

Grid code Compliance and Renewable Energy Projects. Mick Barlow, Business Development Director, S&C Electric, United Kingdom

CONTROL OF DOUBLY FED INDUCTION GENERATOR BASED WIND ENERGY CONVERSION SYSTEM

Simulation and Analysis of a DFIG Wind Energy Conversion System with Genetic Fuzzy Controller

Grid Integration Issues for Large Scale Wind Power Plants (WPPs)

Critical Clearing Time and Voltage Stability of DG Integration in Lebanon: A Simulation Using MATLAB/SIMULINK

GRID CONNECTION ISSUES FOR DISTRIBUTED GENERATION REVIEW & STANDARDS

Advanced Inverter Design

Transcription:

Integration of wind Power Plant on Electrical grid based on PSS/E S. Othman ; H. M. Mahmud 2 S. A. Kotb 3 and S. Sallam 2 Faculty of Engineering, Al-Azhar University, Cairo, Egypt. 2 Egyptian Electricity Hold Company, Cairo, Egypt. 3 Egyptians Atomic Authority, Egyptian 2 nd Research Reactor, Cairo, Egypt. salah_sllm@yahoo.com Abstract: The capacity of electrical power system in Egypt will increase rapidly in the coming twenty years. The conventional energy sources such as oil, natural gas, coal are finite and generate pollution. Alternatively, the renewable energy sources like wind, fuel cell, solar, biogas/biomass, tidal, geothermal, etc. are clean and abundantly available in nature. In the year 23 will reach the generation of electricity from wind generation plants to about 2% of the electrical network loads according to the forecast of the Egyptian government. This paper concerned on PSS/E modeling of wind power generation of Doubly-fed Induction Generator (DFIG) type and their impact on issues of Egyptian electrical grid. Since Wind Turbine Generators (WTG) doesn't have the same characteristics as synchronous generators, the appropriate modeling of wind farms is requisite for transmission system operators to analyze the best options of transmission grid reinforcements as well as to evaluate the wind power impact on reliability and security of supply. In case of grid faults wind turbines have to supply a definite reactive power depending on the instantaneous voltage and to return quickly to normal operation. [S. Othman; H. M. Mahmud S.; A. Kotb and S. Sallam. Integration of wind Power Plant on Electrical grid based on PSS/E. J Am Sci 25;():3-]. (ISSN: 545-3). http://www.jofamericanscience.org. Keywords: Power System transients, PSS/E dynamic simulation DFIG. Introduction The large scale development of wind turbines/farms becoming a significant part of the generation capacity in some area, which requires that the power system treats the wind turbines/farms like a power source, not only an energy source. The wind power penetration would result in variations of load flows in the interconnected systems, as well as redispatch of conventional power plants, which may causes the reduced reserve power capacity [, 2]. Integration of large scale wind power may have severe impacts on the power system operation. Stable, reliable and economic operation of the power system under the massive integration of wind power is a big challenge to power system operators. The technical specifications, grid codes, for grid connection of wind turbines have been produced to specify the requirements that wind turbines must meet in order to be connected to the grid. Examples on such requirements include capabilities of contributing to frequency and voltage regulation by continuously controlling the active power and reactive power supplied to the power system, and the low voltage ride-through capability [3, 4, and 5]. This paper present the most significant characteristic and specific aspects of detailed DFIG modeling containing variable speed wind turbine units. A specific case study is analyzed in order to identify the main requirements for wind farm connection to the Egyptian electrical grid. This paper will not address the detailed mathematics of PSS/E WTG user models which have been covered in many publications. Not with standing the provisions of the Egyptian Transmission System Code (the Grid Code), this Wind Farm Grid Connection Code specifies the special requirements for the connection of Wind Farms to the High and Extra High Voltage transmission system (the Grid). The modelling approach of wind farms is based on Wind Grid Code Requirements. The aim of Wind Grid Code is to provide a self-contained description of the technical and operational requirements that are to be met by the developers and operators of Wind- Powered Generating Stations (WPGS) that wish to connect to the Egyptian electricity grid [4]. The Wind Code applies to all WPGSs that are or have applied to be connected to the transmission grid, with installed capacity of more than 7 GW until 23. Developers of WPGSs intending to apply for connection to the transmission grid should be aware that they are required to provide Project Planning data at this level of detail at the time of filing the application in order for the TSO (Transmission system operator,) to carry out the relevant connection design and impact studies. The Grid Operator is authorized to change one or more of the following requirements or to give further requirements, if it is necessary for a safety and stable operation of the Grid. In case of a deviation of the voltage ranges at the Grid Connection Point from its permissible voltage range, the Wind Farm shall be able to deliver Available Active Power according to wind conditions 3

when the voltage at the Grid Connection Point remains within the ranges from.9 to. per unit.. Any automatic disconnection of the Wind Farm from the Grid shall be prohibited due to the deviation within the voltage ranges, expressed by the voltage at the Grid Connection Point related to nominal voltage. In case of a deviation of the grid frequency from its permissible value, any automatic disconnection of the Wind Farm from the Grid shall be prohibited due to the deviation within the frequency range of 47.5 Hz until 5.5 Hz. Voltage unbalance is defined as the deviation between the highest and lowest line voltage divided by the average line voltage of three phases. Wind Farms shall be able to withstand voltage unbalance not exceeding 3%. The voltage fluctuations in a Wind Farm can occur because of the switching operations (capacitor banks, wind turbine generator start/stop), inrush currents during wind turbine generator starting etc. The maximum voltage fluctuation is 5% from the voltage nominal value. The wind turbine generators of the Wind Farm shall only connect to the Grid (start-up), if the frequency and the voltage at the Grid Connection Point are within the following limits: Frequency: 48 Hz f 5 Hz and Voltage arrowed.95 per unit U.5 per unit.[6] 2. Egyptian Electrical National Grid The Egyptian Electrical National Grid (EENG) in Egypt is divided into five geographical regions, namely, Alexandria, Delta, Cairo, Canal, and Upper Egypt. The Egyptian Electricity transmission system is composed of 5 kv, 4 kv, 22 kv, 32 kv, and 66 kv levels [7]. A proposal of wind power plant will be located in the Canal Zone. Figure (2) shows the section from the Canal Zone which contain the wind power plant. 3. Wind turbine model The DFIG wind turbine generator model is defined in Behnke [8]. The complete WTG model is divided into four functional blocks, as indicated in Figure (). This paper is primarily concerned with the dynamic interactions of the wind turbine and electrical grid under transient fault. Fig.. WTG dynamic model connectivity, from [8]. The power system modeling including wind turbines for steady state analysis in PSS/E version33 is fairly simple, as shown in figure (2). Each individual wind turbine generator (WTG) is connected to a 69V bus and the WTGs are connected to the wind farm internal network through their.69/35 kv step-up transformers. The internal network is organized in eight rows or sections with five WTGs in each section. Within these rows, the wind turbines are connected through 35kV underground cables of different lengths and capacities depending on the location of each unit and the distance to the 35kV collector bus. The load flow solution provides the initial conditions for subsequent dynamic simulations. The maximum and minimum limits of active and reactive power must be respected in order to achieve a successful initialization. Inconsistencies between the power flow and the dynamic model will result in an unacceptable initialization. The proposed wind frame connection on Canal Zone as shown in figure (2). 4

Fig. (2) Proposed wind frame connection in Canal Zone 4. Dynamic model of DFIG The variable speed wind turbine using DFIG are more popular technology which is used word-wide due to advantages such as high energy efficiency and controllability. DFIG is basically a standard, wound rotor induction generator with a voltage source converter connected to the slip-rings of the rotor. The stator winding are coupled directly to the grid and the rotor winding is connected to power converter as Shown in figure (3) [8, 9, ]. Fig. (3) Double- Fed induction generator 5

5. Simulation Result Effect Electrical disturbance on wind power plant - Fault on Bus 57 (WPP) A three-phase short circuit is applied to the generator terminal on bus 57 (wind power plant) when t= 2 sec and cleared when t = 2.2 sec, with the line being tripped at the same time. The simulation result is shown in Figure (4). As shown from Figure (4.a-e), when the fault can be cleared correctly, the system can run stable and the wind power plant can operate without dropping the unit. The change in mechanical power, change in active power, change in reactive power, change in the generator speed and change in the bus voltage. The mechanical power of power generators is shown in Figure (4.a). Clearly, short circuit occurrence at its bus changes the mechanical power of generators. They oscillate severely during the fault start to damp from t = 2.2 sec till sec and goes to steady state situation which is the same as the new initial conditions. Figure (4.b) shows the change in generators active power surrounding generators active power violations, the active power to zero P.U clearance, the active power starts to recover the same initial condition at t=8 sec. Figure (4.c) shows the surrounding generator reactive power oscillations start to damp from t = 2.2 sec till 8 sec and goes to steady state situation which is the same as the initial conditions. The speed generators are shown in Fig (4.d). Clearly, short circuit occurrence at its bus changes the speed generators. They oscillate severely during the fault start to damp from t = 6 sec. till sec. and goes to steady state situation which is the anther initial conditions. Figure (4.e) shows the surrounding buses voltage violations, the voltage dips to zero P.U suddenly during the fault time. After fault clearance, the voltage starts to recover itself. mechanical power (pu ).9 5 bus 57- bus 57-2 bus 57-3 bus 57-4 Active power (pu) bus 57- bus 57-2 bus 57-3 bus 57-4.75 2 4 6 8 Reactive power (pu) 5.5 (a) Mechanical power -.5 2 4 6 8 (c) Reactive generation power bus 57- bus 57-2 bus 57-3 bus 57-4 Change of speed (pu).9.8.7.6 2 3 4 5 6 7 8 9 (b) Change in Active generation power bus 57- bus 57-2 bus 57-3 bus 57-4.5 2 4 6 8 (d) Change generator Speed 6

Voltage (pu).6 bus 57 bus 999 2 4 6 8 (e) Bus Voltage Fig (4) Effect the fault from 2 to 2.2 sec on bus 57 on WPP and Grid 2- Fault on Bus 59 (WPP) A three-phase short circuit is applied to the generator terminal on bus 59 (wind power plant) when t= 2 sec and cleared when t = 2.2 sec, with the line being tripped at the same time. The simulation result is shown in Figure (5). As shown from Figure (5.a-e), when the fault can be cleared correctly, the system can run stable and the wind power plant can operate without dropping the unit. The change in mechanical power, change in active power, change in reactive power, change in the generator speed and change in the bus voltage. The mechanical power of power generators is shown in Fig (5.a). They oscillate during the fault start to damp from t = 2.2 sec till sec and goes to steady state situation which is the same as the new initial conditions. Figure (5.b) shows the change in generators active power surrounding generators active power violations, the active power to zero P.U clearance, the active power starts to recover the same initial condition at t=7 sec. Figure (5.c) shows the surrounding generator reactive power oscillations start to damp from t = 2.2 sec till 8 sec and goes to steady state situation which is the same as the initial conditions. The speed generators are shown in Figure (5.d). Clearly, short circuit occurrence at its bus changes the speed generators. They oscillate during the fault duration (from t = 2 to 2.2 sec). then, the oscillations start to damp from t = 9 sec till sec and goes to steady state situation which is the anther initial conditions. Figure (5.e) shows the surrounding buses voltage violations, the voltage dips to zero P.U clearance, the voltage starts to recover itself. mechanical power (pu) bus 59- bus 59-2 bus 59-3 bus 59-4 bus 59-5 real power (pu) 5 5 5 5 bus59- bus 59-2 bus 59-2 bus 59-4 bus 59-5.76 2 3 4 5 6 7 8 9 (a) Mechanical power.5 2 3 4 5 6 7 8 9 (b) Active generation power reactive power (pu) 5.5 bus 59- bus 59-2 bus 59-3 bus 59-4 bus 59-5 change of speed (pu) 5.95.9.85 bus 59- bus 59-2 bus 59-3 bus 59-4 bus 59-5.8 -.5 2 3 4 5 6 7 8 9 (c) Reactive generation power.75 2 3 4 5 6 7 8 9 (d) Change generator Speed 7

bus voltage (pu).6 bus 59 bus 999 2 3 4 5 6 7 8 9 (e) bus voltage Fig. (5) Effect the fault from 2 to 2.2 sec on bus 59 on WPP and Grid Functions 3- Fault on Bus 528 (WPP) A three-phase short circuit is applied to the generator terminal on bus 53 (wind power plant) when t= 2 sec and cleared when t = 2.2 sec, with the line being tripped at the same time. The simulation result is shown in Figure (6). As shown from Fig. (6, a, b, c, d, e), when the fault can be cleared correctly, the system can run stable and the wind power plant can operate without dropping the unit. The change in mechanical power, change in active power, change in reactive power, change in the generator speed and change in the bus voltage. The mechanical power of power generators is shown in Figure (6.a). They oscillate during the fault start to damp from t = 2.2 sec. till sec. and goes to steady state situation which is the same as the same initial conditions. Figure (6.b) shows the change in generators active power surrounding generators active power violations, the active power to zero P.U clearance, the active power starts to recover the same initial condition at t=8 sec. Figure (6.c) shows the surrounding generator reactive power oscillations start to damp from t = 2.2 sec till 8 sec and goes to steady state situation which is the same as the initial conditions. The speed generators are shown in Fig (6.d). Clearly, short circuit occurrence at its bus changes the speed generators. They oscillate during the fault duration (from t = 2 to 2.2 sec). Then, the oscillations start to damp from t = 9 sec. till sec. and goes to steady state situation which is the anther initial conditions. Figure (6.e) shows the surrounding buses voltage violations, the voltage dips to zero P.U clearance, the voltage starts to recover itself. 5 reactive power (pu) mechanical power (pu) bus 528- bus 528-2 bus 528-3 bus 528-4 bus 528-5 bus 528-6 bus 528-7.75 2 4 6 8 5 5.5 (a) Mechanical power bus 528- bus 528-2 bus 528-3 bus 528-4 bus 528-5 bus 528-6 bus 528-7 real power (pu) change of speed (pu) 5 5.5 bus 528- bus 528-2 bus 528-3 bus 528-4 bus 528-5 bus 528-6 bus 528-7 2 3 4 5 6 7 8 9 5.95.9.85.8.75 (b) Active generation power bus 528- bus 528-2 bus 528-3 bus 528-4 bus 528-5 bus 528-6 bus 528-7 2 3 4 5 6 7 8 9 (c) Reactive generation power 2 3 4 5 6 7 8 9 (d) Change generators Speed 8

voltage (pu).9.7.6 bus 528 bus 3999 2 3 4 5 6 7 8 9 (e) Change in bus voltage Fig. (6) Effect the fault from 2 to 2.2 sec on bus 528 on WPP and Grid Functions 4- Fault on Bus 53 (WPP) A three-phase short circuit is applied to the generator terminal on bus 53 (wind power plant) when t= 2 sec and cleared when t = 2.2 sec, with the line being tripped at the same time. The simulation result is shown in Figure (7). As shown from Figure (7, a, b, c, d, e), when the fault can be cleared correctly, the system can run stable and the wind power plant can operate without dropping the unit. The change in mechanical power, change in active power, change in reactive power, change in the generator speed and change in the bus voltage. The mechanical power of power generators is shown in Fig (7.a). They oscillate during the fault start to damp from t = 2.2 sec. till sec. and goes to steady state situation which is the same as the new initial conditions. Figure (7.b) shows the change in generators active power surrounding generators active power violations, the active power to zero P.U clearance, the active power starts to recover the same initial condition at t=9 sec. Figure (7.c) shows the surrounding generator reactive power oscillations start to damp from t = 2.2 sec till 8 sec and goes to steady state situation which is the same as the initial conditions. The speed generators are shown in Figure (7.d). Clearly, short circuit occurrence at its bus changes the speed generators. They oscillate during the fault start to damp from t = 7 sec till sec and goes to steady state situation which is the anther initial conditions. Figure (7.e) shows the surrounding buses voltage violations, the voltage dips to zero P.U suddenly during the fault time. After fault clearance, the voltage starts to recover itself. mechanical power (pu).9.7.6 bus 53- bus 53-2 bus 53-3 bus 53-4 bus 53-5 bus 53-6 bus 53-7 real power (pu) 5 5 5 5.5 bus 53- bus 53-2 bus 53-3 bus 53-4 bus 53-5 bus 53-6 bus 53-7 2 3 4 5 6 7 8 9 (a) Mechanical power 2 3 4 5 6 7 8 9 (b) Active generation power Reactive power (pu) 5 5 5 bus 53- bus 53-2 bus 53-3 bus 53-4 bus 53-5 bus 53-6 bus 53-7 Change of speed (pu) 5.95.9.85 bus 53- bus 53-2 bus 53-3 bus 53-4 bus 53-5 bus 53-6 bus 53-7.5.8.75 -.5 2 3 4 5 6 7 8 9 (c) Reactive generation power 2 4 6 8 (d) Change generator Speed. 9

Bus voltage (pu).9.7.6 2 4 6 8 (e) Change in bus voltage Fig. (7) bus 53 bus 3999 Conclusion Power flow, short circuit and dynamic analyses were carried out in order to check the influence of the proposal wind farm on the Egyptian electrical grid in respect of the Grid Code requirements. The large scale PSS/E model was used for the computer simulations. The PSS/E wind turbine stability model WT3 was used for the dynamic simulation with the objective of simulating the dynamic performance of DFIG technology WTGs. The overall conclusion of these analyses is that the proposal wind farm project does have an influence on the transmission system, but all of the requirements of the Grid Code relating to the wind farm connection were satisfied. References. Amin A. M. "Improvement Integration of Zafarana Egypt Wind Farm Connected to the Unified Power Grid." International Electrical Engineering Journal (IEEJ) Vol. (2) No., pp. 54-522 ISSN 278-2365 54. 2. Kabashi G. "Wind Farm Modeling for Steady State and Dynamic Analysis" World Academy of Science, Engineering and Technology Vol:5 2-2-2. 3. Ramtharan G., "Frequency support from doubly fed induction generator wind turbines" IET Renew. Power Gener., 27,, (), pp. 3 9. 4. Wind Turbine Grid Connection and Interaction, Deutsches Windenergie-Institut GmbH Germany Tech-wise A/S Denmark DM Energy United Kingdom. 5. Ian A. Hisken "Dynamics of Type-3 Wind Turbine Generator Models", IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 27, NO., FEBRUARY 22. 6. Wind Farm Grid Connection Code in addition to the Egyptian Transmission Grid Code (ETGC), Version: Final Draft 5th January, 22. 7. Report of actual data for Egyptian Network, 23. 8. M. Behnke, "Generic Type-3 Wind Turbine- Generator Model for Grid Studies", Version., WECC Wind Generator Modeling Group, Sep. 26. 9. WECC Wind Power Plant Dynamic Modeling Guide, WECC Renewable Energy Modeling Task Force, Nov. 2.. PSS/E manual, version 33. /3/25