NorthStar Battery Company DOC Code: SES DCR-721-S05 Date:

Similar documents
NorthStar Battery Company DCN: SES DCR: 1413-S08 Date:

NorthStar Battery Company DCN: SES DCR: 1548-S09 Date:

FAT. FAT Battery Range FIAMM.COM

NorthStar Battery (NSB) Telecom Application Manual

MHR VRLA batteries are manufactured in compliance with TL, NEBS, GR, SR, IEC, BS, UL, ISO, OSHAS and CE quality and performance standards.

Pure Lead-Tin Technology

PURE LEAD PLUS UPS APPLICATIONS. Valve Regulated Lead Acid Battery Designed for UPS Standby Power Applications Watts per Cell

PRODUCT GUIDE Publication No: EN-SBS-PG-001 February 2003

PURE LEAD PLUS UPS APPLICATIONS Valve Regulated Lead Acid Battery Designed for UPS Standby Power Applications Watts per Cell

Product Guide. An Invensys company

Modular Max Range BATTERY SOLUTIONS. NEBS qualified. Reliable capacities. EverExceed power your applications

AINO MICRO RANGE VRLA. Compact energy for increased security BATTERY SOLUTIONS. EverExceed power your applications

SPA AGM VRLA batteries

Haze Battery Company Ltd

Switchgear Utility specific gravity nominal sulfuric acid. 10 years, full float service at 77 F (25 C)

LIBERTY SERIES 1000 VALVE REGULATED LEAD-CALCIUM BATTERY For standby applications Capacities from 25 to 600 Ampere-hours

attery Application Handbook

Battery Selection Guide

INTRODUCING THE LEAD CRYSTAL BATTERY

Charging of HOPPECKE OPzV solar.power battery in Solar Applications

FEATURES & benefits. Constant Power Discharge Ratings - Watts per 77 F (25 F) Operating Time (in minutes) to 1.

Haze Battery Company Ltd. Sealed Lead Acid 2 Volt Bloc. Gelled Electrolyte Range

Battery Storage Systems

Modular Max AGM Range VRLA

Deep Cycle AGM Range VRLA

FLUSH EYES IMMEDIATELY WITH WATER. GET MEDICAL HELP FAST. SULFURIC ACID CAN CAUSE BLINDNESS OR SEVERE BURNS.

Battery Range Summary

Technical Manual NINTH EDITION

Valve Regulated Lead Acid (VRLA) Battery Series Designed for UPS Standby Power Applications FEATURES & BENEFITS

2 Volt AGM Range. Haze Battery Company Ltd

Charging pure lead-tin batteries:

Batteries and more. Powered by (CE, UL & ISO9001 APPROVAL)

EcoSafe EOPzV. Operation Guide for Solar Applications

SECTION

Prepared for 7 x 24 Exchange

Haze Battery Company Ltd. Sealed Lead Acid 6 & 12 Volt. AGM Range. Monobloc

F R O N T T E R M I N A L PRODUCT GUIDE Publication No: EN-VFT-PG-001 February 2003

Vented fibre structure Nickel Cadmium batteries for stationary systems

Technical Note. Management of Sealed Lead Acid Batteries in Reliable Small DC Standby Power Supply Systems

PowerStor Standby Battery Systems

SECTION

TECHNICAL BULLETIN Fig #1 - VRLA Battery Components. Intercell Welded Connection Strap joining neg. plates in parallel.

Features and Benefits

Sealed Lead-Acid Batteries

SBS T HE P OWER P LATE T HIN T ECHNOLOGY S PECIFIERS M ANUAL

Haze Battery Company Ltd. Sealed Lead Acid 6 & 12 Volt. Gelled Electrolyte Range. Monobloc

SSLA. SSLA Battery Range FIAMM.COM

Haze Battery Company Ltd. Sealed Lead Acid 6 & 12 Volt. AGM Range. Monobloc

SECTION A Division of Exide Technologies

SSLA. SSLA Battery Range FIAMM.COM

Power to keep you on the move

Powerterm L120C Single Output PSU/Battery Chargers Model C2199A-1 (12V/8A) or Model C2199A-2 (24V/6A)

Stationary Batteries: Why they fail and what can be done to prolong battery life

Polymer Gel Standby Battery (Front Access Design) OPERATION MANUAL

FIAMM Industrial Batteries December 2012 FIAMM AGM Valve Regulated Recombination Batteries: FLX Series- Engineering Manual TABLE OF CONTENTS

Tubular Gel Technology For Solar Applications

Charge Voltage(V/cell) Set point (V) (V)

PowerSafe OPzV Operation Guide for Solar Applications

CELLYTE 12 PLF & 12PLT Range

CALL FOR A QUOTE (877)

XHP. Low maintenance high performance batteries

UPS FEATURES & BENEFITS TECHNICAL DATA Valve Regulated Lead Acid Battery Designed for UPS Standby Power Applications.

Chapter 6. Batteries. Types and Characteristics Functions and Features Specifications and Ratings Jim Dunlop Solar

1. Introduction Technical Features Construction Standards Certification Technology...

2 VOLT STATIONARY BATTERIES INSTALLATION

Stationary Batteries and Battery Management

Specification Approval Sheet

PowerSafe OPzV Operation Guide for Solar Applications

NSB OPzV Batteries. Tubular Gel Technology. NSB OPzV Battery Application Manual. northstarbattery.com

Tel.X Ni-Cd batteries for telecom networks Technical manual

EUROBAT EUROBAT GUIDE FOR MOTIVE POWER VRLA BATTERIES

XLR Energy Storage Module

Duracell Battery Glossary

LIFE CYCLE COSTING FOR BATTERIES IN STANDBY APPLICATIONS

GLOSSARY: TECHNICAL BATTERY TERMS

IEEE IAS Atlanta Chapter

Specification Approval Sheet

VRLA Batteries. Battery Installation And Start up Guide

Deep Cycle Battery Safety. First. Battery Handling, Maintenance & Test Procedures

DataSafe HX Top Terminated Batteries 6 and 12 Volt HX

SVTX AGM VRLA batteries

Specification Approval Sheet

FEATURES & BENEFITS. 10 year design 25 C

Energy Storage. Lithium Batteries

Proper Torque Values for Connection Hardware. 90 to 100 in-lbs

CYCLON SELECTION GUIDE

Sonnenschein Lithium HC (High Current)

APPLICATION MANUAL. Genesis NP and NPX Series. Publication No: US-NP-AM-002 June 2006

6 & 12 Volt Monobloc GEL Range

Sealed Lead-Acid Batteries

TROJAN BATTERY COMPANY Renewable Energy Warranty Claim Form

SECTION

Nickel Zinc Battery Evaluation at Crane

Haze Battery Company Ltd

Reference Number PDS 18 - (RIC Standard: EP SP)

The Benefits of Cell Balancing

Form: SES Issued: ECO

HAZE 6/12 Volt. STATIONARY 6/12 Volt BATTERIES. HAZE Battery Co. INSTALLATION and OPERATING INSTRUCTIONS. Supplied Worldwide by :

Technical Manual EIGHTH EDITION

Dismantling the Myths of the Ionic Charge Profiles

Transcription:

Application Manual and Product Information for NSB Series NorthStar Battery Company

Table of Contents Table of Figures... 3 Introduction... 4 NSB Series Benefits... 5 NSB Approvals and Certifications... 6 ISO Certifications... 7 NSB Product Specifications... 8 Leak Free Terminations... 10 Open Circuit Voltage and State of Charge... 10 Charging... 12 Ambient Temperature and Battery Performance... 15 Cycle Life... 16 Low Voltage Disconnect... 16 Optimizing Battery Life and Performance... 17 Contact Information... 19 Appendix A - Battery/System Sizing Examples... 20 Appendix B Product Performance Specifications... 22 NorthStar Battery Company 2

Table of Figures Figure 1: Effect of temperature on OCV and SOC...11 Figure 2: Charge voltage compensation for NSB batteries...13 Figure 3: Effect of ambient temperature on float life...15 Figure 4: Effect of DOD and discharge rate on cycle life...16 Figure 5: Recommended EODV as a function of discharge rate...17 NorthStar Battery Company 3

Introduction T and cyclic capability. he NSB series of premium high density valve-regulated lead acid (VRLA) batteries from NorthStar Battery has been specifically designed to offer ten to fifteen years trouble free service in standby emergency power (float) applications as well as delivering high power This document has been written with two goals in mind. The first is to provide comprehensive technical information on the full range of batteries from NorthStar Battery Company. Using this information the reader will be able to select the right battery for a particular application. Step-by-step examples in the Appendix illustrate the battery sizing process. The second goal of this manual is to outline factors that affect battery life and performance. An understanding of these factors is critical to getting the most out of these premium batteries. NorthStar Battery Company 4

NSB Series Benefits I n addition to the benefits offered by its valve regulated technology the NSB battery offers a long list of features that serve to increase the reliability and overall performance of your system. Specifically designed for indoor/outdoor telecom cabinet applications 10 year float life @ 25ºC (77ºF) or 15 year float life @ 20ºC (68ºF) Long cycle life capability up to 500 cycles to 80% DOD at C/3 rate Rapid recharge capability 2 year shelf life High power output makes the NSB series ideal for UPS systems 3 step terminal seal ensuring leak-free operation Wide operating temperature range of 40ºC to 60ºC (Continuous operation at or above 55 C requires an optional metal jacket) Industrial standard footprints assure mechanical interchangeability Non-halogenated flame retardant (UL94-V0) PC/ABS case and cover High conductivity female M8 terminals (female M6 on the NSB40) High charge acceptance Can be installed in any orientation (inverted is not recommended) NorthStar Battery Company 5

NSB Approvals and Certifications N SB products have been designed to meet the following international telecommunication requirements: Telcordia SR-4228 (formerly Bellcore TR-NWT-000766) VRLA Battery String Certification Levels Based on Requirements For Safety and Performance British Standard BS 6290: Part 4: 1997 Lead-acid stationary cells and batteries. Part 4 Specification for classifying valve regulated types Bellcore GR-63-Core, Issue 1, Compliance Test Program Requirement includes seismic zone 4 operation Telkom Specification SP-AP0016 Network Stationary Batteries DOT 49CFR173.159(d) (i) and (ii) Non-hazardous shipping Eurobatt Design life >15-years @ 20 C UL Approval All NSB products meet the UL requirements for flame retardancy, UL V-0, and proper venting operation NorthStar Battery Company 6

ISO Certifications I n addition NorthStar Battery Company has been fully tested and approved to ISO9001 and 14001 standards making it one of the most environmentally friendly lead-acid battery manufacturing facilities in the world today. NorthStar Battery Company 7

NSB Product Specifications Industrial Range NSB40 NSB70 NSB75 NSB90 NSB125 Height 176mm 6.93 176mm 6.93 200mm 7.87 213mm 8.39 274mm 10.81 Length 197mm 7.76 331mm 13.03 261mm 10.27 341mm 13.42 344mm 13.57 Width 165mm 6.50 165mm 6.50 173mm 6.80 173mm 6.80 173mm 6.80 Weight 16.0kg 35.3lbs 27.3kg 60.0lbs 27.3kg 60.0lbs 37.8kg 83.1lbs 54.0 kg 119lbs Terminal M6 x 1.25 M8 x 1.25 M8 x 1.25 M8 x 1.25 M8 x 1.25 C/10 Cap 40Ah 67Ah 67Ah 96Ah 125 Ah Impedance (1kHz) Admittance* (23Hz) Short-circuit Current 4.5mΩ 2.7mΩ 2.6mΩ 2.0mΩ 2.0mΩ 1,000Ω -1 1,700Ω -1 1,700Ω -1 2,000Ω -1 2,400Ω -1 2,000A 3,200A 3,200A 4,300A 5,000 A NorthStar Battery Company 8

Front Terminal Range NSB60FT NSB90FT NSB100FT NSB110FT NSB170FT Height 263mm 10.35 255mm 10.04 287mm 11.30 227mm 8.94 320mm 12.60 Length 287mm 11.30 396mm 15.59 396mm 15.59 560mm 22.05 560mm 22.05 Width 108mm 4.25 108mm 4.25 108mm 4.25 125mm 4.92 125mm 4.92 Weight 21.0kg 46.2lbs 32.0kg 70.6lbs 35.6kg 78.5lbs 41.4kg 91.3lbs 59.5kg 131.2lbs C/8 Cap 60Ah 90Ah 100Ah 110Ah 170Ah Impedance (1kHz) Admittance* (23Hz) Short-circuit Current 4.1mΩ 2.9mΩ 2.5mΩ 2.2mΩ 1.5mΩ 1,300Ω -1 1,700Ω -1 1,900Ω -1 2,000Ω -1 2,500Ω -1 2,000A 3,000A 3,500A 4,000A 5,000A * Admittance is an electrical term that quantifies the AC conductance of a circuit (or indeed an electrochemical system) to an imposed AC signal; it is dependent upon frequency and is the reciprocal of impedance so that its units are ohms -1 or Siemens. The term conductance rather than admittance is often used when applied to several commercially available battery testers. NorthStar Battery Company 9

Leak Free Terminations N orthstar batteries are produced with rugged highly conductive brass terminals. To take advantage of the design and insure a long life low resistance connection, the battery terminals should be coated with NO-OXID or similar material. Stainless steel hardware, with a minimum of 6mm engagement, torqued to 6.0 Nm/53 in-lbs is recommended. In portable applications, or installations where periodic retorquing of terminals is limited, a spring washer is recommended. This will reduce the loosening effects of material creep, temperature expansion and vibration. Open Circuit Voltage and State of Charge T he following figure shows the relationship between the open circuit voltage (OCV) and the state of charge (SOC) as determined experimentally for the NSB range of VRLA batteries. NorthStar Battery Company 10

NSB Shelf Life OCV /Volts 13.0 12.9 12.8 12.7 12.6 12.5 12.4 12.3 12.2 12.1 12.0 11.9 11.8 11.7 11.6 11.5 11.4 25C, 1.4 mv/day, 0.09%/day 55C, 7.2 mv/day, 0.50%/day 71C, 19.6 mv/day, 1.2%/day 0 50 100 150 200 250 300 350 400 450 500 550 600 650 700 Duration /days 100% 94% 88% 81% 75% 69% 63% 56% 50% 44% 38% 31% 25% 19% 13% 6% 0% SOC Figure 1: Effect of temperature on OCV and SOC Measuring the open-circuit voltage is an excellent way of estimating the %SOC of NSB batteries, since the open-circuit voltage is a direct function of the concentration of electrolyte within the battery. As the concentration of electrolyte decreases so too does the %SOC. The relationship can be linearly approximated by the following equation: %SOC @ C/20 = OCV x 62.5 712.5 In order to be accurate the open-circuit voltage should not be measured within a minimum of 4-hours of being discharged or recharged. NorthStar Battery Company 11

Charging C harging is one of the most critical factors that determine the life expectancy of a valve regulated lead acid (VRLA) battery and the NSB series from NorthStar Battery is no exception. There are two broad categories of charging, constant current (CC) charging or constant voltage (CV) charging. Constant current (CC) charging As the name implies, in CC charging a current of constant magnitude is forced into the battery, regardless of the state of charge of the battery. While CC charging rapidly replaces the ampere-hours lost by the battery, it is very easy to dangerously overcharge the battery with this method of charge. This is the main reason why CC charging on a regular basis is not recommended for the NSB battery. Since a CC charge provides each battery in the series string with exactly the same amount of ampere-hours this charge technique is well suited to equalize a series string that comprises cells in various states of charge. As the battery charges, its terminal voltage increases. Since the CC charger is designed to provide the same current throughout the charge cycle, its voltage must increase in order to overcome the rising battery voltage and push a constant current into the battery. Constant voltage (CV) charging I n contrast to CC charging it is the charge voltage rather than the charge current that remains constant during the charge cycle. As the battery charges its terminal voltage increases, the charge current drops as the charger s output voltage remains constant. This automatic regulation of the charge current makes CV charging the preferred charge technique for VRLA batteries. NorthStar Battery Company 12

The charge voltage should be controlled to within ±1% of the values shown in Figure 2 below for optimum performance. Figure 2 also shows that the charge voltage should be compensated for temperature. The thermal compensation coefficient for float and cycling applications is ±4mV per cell per ºC variation from 25ºC. Note that the compensation coefficient is negative, meaning that the charge voltage must be decreased as the temperature goes up and vice versa. Applied Voltage / (V/cell) 2.60 2.58 2.56 2.54 2.52 2.50 2.48 2.46 2.44 2.42 2.40 2.38 2.36 2.34 2.32 2.30 2.28 2.26 2.24 2.22 2.20 2.18 2.16 Float 0 5 10 15 20 25 30 35 40 Temperature /C Cyclic Figure 2: Charge voltage compensation for NSB batteries NorthStar Battery Company 13

Temp / C Minimum Float Voltage /VPC Nominal Float Voltage /VPC Maximum Float Voltage /VPC Minimum Cyclic Voltage /VPC Nominal Cyclic Voltage /VPC Maximum Cyclic Voltage /VPC 0 2.35 2.37 2.39 2.52 2.55 2.58 5 2.33 2.35 2.37 2.50 2.53 2.56 10 2.31 2.33 2.35 2.49 2.51 2.54 15 2.29 2.31 2.33 2.47 2.49 2.51 20 2.27 2.29 2.31 2.45 2.47 2.49 25 2.25 2.27 2.29 2.43 2.45 2.47 30 2.23 2.25 2.27 2.41 2.43 2.45 35 2.21 2.23 2.25 2.39 2.41 2.43 40 2.19 2.21 2.23 2.37 2.39 2.41 42 2.18 2.20 2.22 2.36 2.38 2.41 45 2.17 2.19 2.21 2.35 2.37 2.39 50 2.17 2.17 2.19 2.33 2.35 2.37 Figure 3: Charge voltage compensation for NSB batteries The low internal resistance of the NSB battery allows for very high charge acceptance. These batteries also do not require the charge current to be artificially limited, as long as constant voltage (CV) charging is used. This characteristic helps the battery reach a very high (>85%) state of charge (SOC) in less than one hour with a charge current of the order of 1C amps, where C is the rated capacity of the battery. Thus, 1C for a 100Ah battery would be 100 amps. NorthStar Battery Company 14

Ambient Temperature and Battery Performance H eat is the number one killer of batteries it accelerates the failure mechanisms such as corrosion and dry-out. A good rule of thumb to use is that for every 10ºC increase in ambient temperature the float life of the battery is cut in half. The NSB battery, which has a float life expectancy of 10 years at 25ºC, will only have a useful life of 5 years at 35ºC. Figure 3 shows the relationship between temperature and battery life. 16 Float life to 80% capacity / Years 14 12 10 8 6 4 2 0 20 25 30 35 40 45 50 55 60 Ambient temperature / ºC Figure 4: Effect of ambient temperature on float life Note: When mounted in a rack, it is recommended that all NorthStar products should have a space of approximately 10mm between the batteries to allow for heat convection. In addition, it is also recommended that the supporting shelf should have air circulation holes positioned directly below the gaps between the batteries. NorthStar Battery Company 15

Cycle Life battery. T he cycle life of a battery is dependent upon two discharge factors. The first factor is the depth of discharge while the second is the discharge rate. Figure 4 shows how these two factors can affect number the cycles you may expect from an optimally charged NSB 10000 C/1 C/3 C/10 Cycle Life 1000 100 20 30 40 50 60 70 80 90 100 % Depth Of Discharge Figure 5: Effect of DOD and discharge rate on cycle life Low Voltage Disconnect A nother key to optimizing battery performance is to ensure that it is not subjected to an overdischarged condition, particularly for any appreciable length of time. The only practical NorthStar Battery Company 16

way to prevent this condition from occurring is to employ a low voltage disconnect (LVD) in the load circuit that prevents the battery from discharging to a level below the designed end of discharge voltage (EODV) value. Although 10.02V is a typical EODV for a 12V battery, the following chart may be used to set the LVD. Discharge in amps EODV per 12V battery 0.05C 10 (C 10 /20) 10.5V 0.1C 10 (C 10 /10) 10.2V 0.2C 10 (C 10 /5) 10.02V 0.4C 10 (C 10 /2.5) 9.9V 1C 10 9.6V 2C 10 9.3V > 5C 10 9.0V Figure 6: Recommended EODV as a function of discharge rate Optimizing Battery Life and Performance T o obtain maximum performance from your battery and get the longest life out of it is simply a matter of providing the right environment for the battery. The following checklist is designed to help you optimize your battery s overall performance. The checklist assumes that the battery is properly sized for the application. Temperature NorthStar Battery Company 17

Battery ambient temperature of 25ºC (77ºF) is ideal. A cooler temperature will extend battery life but may degrade capacity If battery temperature varies significantly from 25ºC (77ºF), compensating the battery charge voltage is necessary Charging Correct charge parameters are critical to battery longevity Charge method must be matched to the application; check with the Technical Support department if you are unsure about the parameters for your application Overdischarge Repeated over-discharge is harmful to the battery Use of a low voltage disconnect is recommended NorthStar Battery Company 18

Contact Information Mailing address: NorthStar Battery Company 4000 Continental Way Springfield, MO 65803 Tel: (417) 575-8200 Fax: (417) 575-8250 Email: info@northstarbattery.com Functional area Telephone number Customer Service (417) 575-8201 Technical and Quality (417) 575-8205 Sales and Marketing (417) 575-8203 NorthStar Battery Company 19

Appendix A - Battery/System Sizing Examples I n this section of the manual we will go through three examples to show how to select the correct battery size for your application. In the first example the constant current load is given in amperes and in the second case the battery load is a constant power in kilowatts. Finally, the third example is slightly more involved as inverter power factor and efficiency need to be accounted for. Example 1: Constant current battery load Load 180 amps Support time 45 minutes Battery voltage 240V EODV 1.75 VPC Calculation The first step is to calculate the number of batteries per series string. In this case there will be twenty batteries per series string (240V/12V per module = 20 modules) since each battery has a nominal terminal voltage of 12V. By looking up the discharge tables for an EODV of 1.75 VPC and a support time of 45 minutes, we find that no single battery is capable of delivering 180A for 45 minutes to 1.75 VPC. We next add a 240V string in parallel, so the load is halved to 90A per string. By going through the tables again we find that the NSB100FT will support 90.3A for 45 minutes; two parallel strings will support 180.6A for 45 minutes. Therefore the right battery for this load is two strings of NSB100FT, with each string comprising twenty batteries in series or forty batteries per system. NorthStar Battery Company 20

Example 2: Constant power battery load Load 50 kilowatts (50,000 watts) Support time 20 minutes Battery voltage 360V EODV 1.67 VPC Calculation Since the discharge tables give the constant power numbers in watts per cell (WPC) the first step is to calculate the number of cells per series string. In this case there will be 180 cells per series string (360V/2V per cell = 180 cells) since each cell has a nominal terminal voltage of 2V. The next step is to convert the load to a per cell basis. In this example the load is 278 WPC (50,000 watts / 180 cells = 278 WPC). We can now look up the discharge tables corresponding to a support time of 20 minutes and an EODV of 1.67 VPC. The smallest battery that can support this load is the NSB90, which is capable of delivering 338.3 WPC for 20 minutes to 1.67 VPC. Thus the system in this example will comprise 30 modules of the NSB90 battery. NorthStar Battery Company 21

Example 3: Constant kilovolt-ampere (KVA) battery load Load 50 KVA (50,000 VA) Inverter power factor 0.85 Inverter efficiency 90% Support time 20 minutes Battery voltage 360V EODV 1.67 VPC Calculation The first step is to convert the KVA into an equivalent KW by using the following formula: Kilowatt = (Kilovolt-ampere Power Factor) Efficiency Using this formula the above numbers translate into a kilowatt requirement of 47.2 kilowatts. The subsequent steps are identical to those outlined in the second sizing example given above. Appendix B Product Performance Specifications Refer to the NorthStar Battery Company Product Specification Sheets for Current, Capacity, and Power Performance Figures. NorthStar Battery Company 22