ESC2301. Universal Electronic Governor Controller Operation Manual

Similar documents
EG3000. Generator Electronic Governor Controller Operation Manual

EG1069X. Generator Electronic Governor Controller Operation Manual

EG1065X. Compatible with Barber Colman* Dyn1-1065X series * Use for reference purpose only and not a genuine Barber Colman product.

EG3002. Electronic Engine Governor Controller User Manual

DYNA Power Control Manual For Plus 1, Plus 2, Plus 4 and Plus 6 Ft. Lb. Systems

ESD5500E Series Speed Control Unit

PRODUCT SERIES: DPG-2100

ESD5550 / 5570 Series Speed Control Units

ENGINE GOVERNING SYSTEMS

ESD5100 Series Speed Control Unit PART NUMBER ESD5120 ESD (127)

DYNA 8000 DYNA 8200 DYNA

Application Information

Product Manual (Revision E) Original Instructions. Min/Max Control Systems. Installation and Operation Manual

IGA225 Integrated Governor & Actuator

ESD-5550/5570 Series - Speed Control Unit

with discrete output (Overspeed) with auxiliary input (Synchronizer and Load Sharing)

Product Manual (Revision B) Original Instructions. EPG Electrically Powered Governor Models 501 and Installation and Operation Manual

ESD-5550/5570 Speed Control Unit. Manual

EDG6000 Electronic Digital Governor

INSTRUCTION MANUAL FOR VOLTAGE REGULATOR APR P/N

MD10. Engine Controller. Installation and User Manual for the MD10 Engine Controller. Full Version

EDG5500 Electronic Digital Governor With Quikset Display

10V. the rack of the oil pump must be on the

ESD-5500E Series - Speed Control Unit

Product Manual (Revision C) Original Instructions. EPG (Electric Powered Governor) with Position Feedback. Installation and Operation Manual

INSTRUCTION MANUAL FOR. VOLTAGE REGULATOR Model: APR Part Number:

2301A Load Sharing & Speed Control with Dual Dynamics. Product Manual (Revision NEW, 1990) Original Instructions

4024 EPG (Electrically Powered Governor) Product Manual (Revision B, 3/2008) Original Instructions

Application Information

Product Manual (Revision D, 5/2015) Original Instructions. 2301A Speed Control. Installation and Operation Manual

ENGINE GOVERNING SYSTEMS LSM672 LOAD SHARING MODULE. GOVERNORS AMERICA CORP. 720 Silver Street Agawam, MA , USA MEMBER

TRAC-3 TENSION READOUT AND CONTROL

PM300 VOLTAGE REGULATOR INSTRUCTION MANUAL

ES52. Auto Start Engine Controller. Full Version. Installation and User Manual for the ES52 Auto Start Engine Controller.

UNIVERSAL VOLTAGE REGULATOR Manufactured in the USA by

PED 5000 ELECTRIC ACTUATOR

UG-5.7, UG-8, UG10 Governor

ADVR-12. Hybrid Universal Analog Digital Voltage Regulator Operation Manual

Application Note. Controllers for Stanadyne Pumps Using DC Integrated Actuators. Calibration Instructions. Manual 36579

EPG Electrically Powered Governor. Installation and Troubleshooting Manual. Models 1712/1724 and 512/524 without Position Feedback

EEG6500 Enhanced Electronic Governor

CN0055 & CN0055B DC to DC NEGATIVE RESISTANCE SPEED CONTROL

AVR Hybrid Universal Analog Digital Voltage Regulator Operation Manual

GS10 Series MODELS: GS10 GS10-R NEMA 4X SCR MOTOR CONTROLS. User s Manual

Installation & Operation Manual

MX431 Generator Automatic Voltage Regulator Operation Manual

ECU. Speed Switch Manual. Contents. ECU is a registered trademark of Engineering Concepts Unlimited Inc.

ES52 Auto Start Engine Controller Installation and User Manual for the ES52 Auto Start Engine Controller.

DC Variable Speed Drive Panel

Tachometer, Ametek Electronic 54.21

SPECIFICATIONS ATTENTION OPERATION DESCRIPTION

MAGNAMAX DVR DIGITAL VOLTAGE REGULATOR

EEG6550 Enhanced Electronic Governor

CUMMINS SPEED CONTROLLER DATASHEET

SECTION 2.00 SPEED GOVERNING SYSTEM DESCRIPTION SPEED GOVERNING SYSTEM DESCRIPTION F18/H24 GOVERNOR

Troubleshooting Guide

USER'S MANUAL MODEL DPS32PG1 DRIVER PACK

500 Series Troubleshooting Guide for C520 Alternators

INSTRUCTION MANUAL MODEL PS VDC POWER SUPPLY

Tachometers and Tach/Hourmeters

Product Manual (Revision D, 3/2000) Original Instructions. UG-5.7, UG-8, UG10 Governor. Installation Manual

VA-715x Electric Valve Actuator

RODIX, INC. FC-40-PLC Plus Series Control Troubleshooting Guide for Circuit Board P/Ns and

Engine Controls & Actuation

715B CONTROL SERIES. Instruction Manual Line Voltage DC Brushless Motor Control CONTROLS. Phone (317) Fax (317)

17429X.00 SERIES MODELS:

CP-8301-xxx Series. Application. Features. Applicable Literature. 1 to 15 Vdc Input Electronic Actuator Drive General Instructions

EA16. Generator Automatic Voltage Regulator Operation Manual

Stewart-Warner Electronic Tachometer 54.07

PRODUCT INFORMATION BULLETIN

Fincor Series 2230 MKII/2240

5001TCP SPEED CONTROLLER

ELECTRONIC MANUAL VOLTAGE CONTROL Model: MVC 300. Part Number:

USER MANUAL MODELS NRG02-D240AC-4Q NRG02-D240AC-4Q-PCM NRG05-D240AC-4Q NRG05-D240AC-4Q-PCM NRG10-115AC-4Q NRG10-115AC-4Q-PCM

DPD72PG1 BILEVEL STEP MOTOR DRIVER PACK With RAMPING PULSE GENERATOR

Troubleshooting Guide

5001TCP SPEED CONTROLLER

Product Manual (Revision A, 8/2015) Original Instructions. ProAct II Digital Speed Control System. Technical Supplement

Operation and Installation Manual

POWER SUPPLY MODEL XP-800. TWO AC VARIABLE VOLTAGES; 0-120V and 7A, PLUS UP TO 10A. Instruction Manual. Elenco Electronics, Inc.

ATB Series - Integral Throttle Body Actuators

EA07. Generator Automatic Voltage Regulator Operation Manual

225 SERIES ELECTRIC ACTUATOR

oubleshooting Guide diesel - gasoline - LPG electric P.O. Box 1160 St. Joseph, MO Fax:

Reproduction or other use of this Manual, without the express written consent of Vulcan, is prohibited.

Servo and Proportional Valves

Tachometers and Tach/Hourmeters

Damper Actuator Installation

R81EAA-2 Economizer Circuit Board

DENISON HYDRAULICS Jupiter 500 Driver Card Series S

th Street, Surrey, B.C. Canada V3W 0A6 Telephone Fax July 2012

Series EA High Torque Actuators with Integrated Controller

Woodward PSG Governor

KT101 Series Governor System Installation Kit Cummins 4B(T) / 6B(T) With CAV/DPA Pump

Installation Instructions

Controlled Ferroresonant Ballast (CFB) Generation #3. Manual

MDC Series

DMC mA Positioner

Flowrite EA 599 Series SKD Electronic Valve Actuator 24 Vac Proportional Control

BLDC SPEED CONTROL INSTRUCTION MANUAL Line voltage Brushless DC control

Transcription:

ESC2301 Universal Electronic Governor Controller Operation Manual *Replaces most Woodward, Barber Colman & Cummins Speed Controls Features Smoke Limit Control, Idle Speed Control, 12V or 24V input Suitable for Built-in or Non-Built-in and PT Pump Type Actuator * Use for reference purposes only - not a OEM product. Trademarks are property of respective owners.

1. SPECIFICATIONS 1.1 Electronic Specifications Operating Voltage 12 or 24 VDC ±20% Output Current 0.5 ~ 15 A Run Speed Adjustment range Speed adjustment Potentiometer (30 turn) 4 Segment Dip Switch Adjustable From 600 ~ 9500 Hz. Idle Speed Adjustment Range Run Speed 30 ~ 85% Ramp Time 3 ~ 20 Sec Remote Speed Pot Ext. Remote speed pot terminal 6, 7, 8 (ILS) and 6, 7, 9 connect a 5KΩ potentiometer ±5% adjustment range. Temp. Stability <0.01% Run Speed Stability ± 0.25 % at steady state MPU input signal 1 ~ 120VAC RMS Droop 4% Adjustment Run Speed, Idle Speed, Ramp Time, Droop, Integration, Gain Mechanical Vibration 1G @ 18 ~ 30 Hz, 2.5G @ 48 ~ 70 Hz Relative Humidity < 95% Operating Temperature -40 ~ 85 Storage Temperature -40 ~ 85 Dimensions 147mm L * 114mm W * 50mm H Weight 690g ± 2% 2 Function Descriptions The ESC2301 provides both an adjustable Idle Speed and ramp, for controlling engine smoke, vibration and warm-up. 2.1 Controller Together, the ESC2301 Controller, Actuator and MPU (Magnetic Pickup) form the electronic engine governor assembly. The ESC2301 receives the signal from the MPU and, depending on the engine RPM, the actuator controls the fuel intake on the engine. The ESC2301 receives its power from the engine batteries or an AC to DC power supply rated from 12 or 24 VDC ±20% matching the Actuator voltage. The average operating current is around 2.5 to 3.5 amps, but it may reach 15 Amps during engine start or sudden load changes. 2.2 Installation Descriptions 1. Protect the ESC2301 by installing it inside the engine instrument control panel. 2. Mount the Actuator close to the engine fuel system. See actuator manufacture instructions. 3. Always choose a point on the actuator control arm in which it can rotate freely, providing minimum and maximum fuel (But do not bottom out the actuator; leave 2 to 3 degrees before the off and on position). 4. Use a Non-Linear link on Gas engines to get low Gain at light loads and high Gain at heavy loads and a linear link on diesel ejection pumps. 2 ESC2301

5.Mount the magnetic pickup on the flywheel bell housing to count the teeth on the ring gear. The teeth are converted to an electrical pulse by the MPU. These pulses are cross referenced with the original setting on the ESC2301. Any difference is used by the actuator to change engine RPM to maintain the same pulse count. 3. CONNECTION T e r m i n a l 1, 2 DC Power Input 2, 3 IDLE Terminal 4, 5 For ACT, Max @ 15A 6, 7, 8 6, 7, 9 Remote speed control. Connect 5KΩ potentiometer approx. ±5 % a d j u s t m e n t r a n g e. 10, 11 MPU input, Ground Terminal No. 10 1. Terminal 1 & 2 used for DC power input. Terminal 1 for Positive (+) and Terminal 2 for Negative ( ) input -Voltage can be 12/24VDC ±20%. 2. Terminal 2 & 3 are the IDLE SW. Terminal when 2 & 3 open normal Run Speed, When Terminal 2 & 3 shorted engine in Idle. 3. Terminal 4 & 5 is the output terminal for the actuator, providing a maximum of 15A. 4. Terminal 6 and 7-8 and terminal 6 and 7-9 are two sets of remote speed control. Referring to figure 4, connect a 5KΩ potentiometer, and turn the knob to central position. Let engine run on Run Speed to adjust to the rated engine speed, the adjustable range is ±5%. Users can also series a resistor to the potentiometer variable point to either terminal 8 or 9 to narrow the adjustable range. The wirings used to connect to terminal 6, 7-8 and 6, 7-9 must use the 3-wire shielded cable. The drain shield wire is to be connected to terminal 10 and the other end of the drain shield wire must cut off and taped. 5. Terminal 10 and 11 is the MPU signal input terminal. The wiring used to connect to the terminals must use a 2-wire shield cable. The drain shield wire is to be connected to Terminal 10 and the other end of the drain shield wire must cut off and taped. 4. OPERATION 4.1 Idle Speed and Smoke Limiting Adjustment The ESC2301 has two settings used for smoke limiting : 1. Idle Speed The setting of the lowest engine operating speed. Before firing the engine, adjust the Idle Speed to the maximum, and Ramp Time to the minimum. Adjust Run Speed to minimum and let Terminal 2 & 3 be Open Circuit. Start engine. The engine speed may rev to Run Speed right away. Slowly adjust Run Speed to the rated generator RPM. Short Terminal 2 & 3 the engine speed should drop, slowly set Idle Speed to a comfortable engine idle. Stop engine and adjust Ramp. Time to it center setting then restart engine. At this time, the engine speed will stay in Idle and slowly Ramp up to normal engine speed. Adjust to preferred Ramp speed. Refer to Figure 1. When operating at normal RPM closing the IDLE SW, d e c r e a s e s e n g i n e R P M b a c k t o i d l e R P M according to preset Ramp Time. To ensure positive engine starts every time follow step (4) and turn the Idle Speed potentiometer an additional 3 to 5%. 2. Ramp Time. On hot engines, a specific fuel limit setting will control start-up smoke, but not completely. A hot engine does not need the same fuel limits to start as a cold starting engine. Ramp Time can be set from 3 up to 20 seconds. The Ramp Time is the length of time from Idle to the rated Run Speed. 6. Harness used to connect to Terminal 1, 2, 4 and 5 must use the 2.0mm twist pair harness. Figure 1 ESC2301 3

4.2 Isochronous Adjustment Isochronous operation is obtained by setting Droop potentiometer fully counterclockwise. ESC2301is normally operated in the isochronous mode; i.e., engine RPM is constant (±0.25%), under steady state load conditions, up to the engine s maximum capability, regardless of load on the engine. Please refer to Figure 2. 4.4 Remote Speed POT Adjustment ESC2301 is equipped with 2 sets of Remote Speed Potentiometer adjustment. By adding a 5KΩ Potentiometer, user can adjust the engine speed from as far as 60 meters away from the engine. Please refer to Figure 4 for connection. To narrow the adjustment range, series a resistor on either Terminal 8 or 9 to reduce. Without the resistor the adjustment range is approximately 5%. 4.5 Gain, I (Integration), Adjustment Figure 2 4.3 Non-isokinetic Operation When operated under Non- isochronous (Paralleled), Droop is used to distribute the actual power from the generators. Please refer to Figure 3. Droop operation is obtained by setting the Droop potentiometer. Moving Droop Pot clockwise increases the Droop. The amount of Droop for a given setting depends on the magnetic pickup frequency and no load to full load actuator shaft rotation. Figure 3 A Droop potentiometer setting of 10 o clock will give about 4% Droop, no load to full load when the pickup frequency is 4260Hz and actuator shaft rotation is approximately 30 degrees from no load to full load. Lower pickup frequency or smaller shaft rotation results in less Droop for the system. 1. Shutdown engine and DC input turned off. 2. Potentiometer original setting. 3. Adjust INT., Gain and Ramp Time Potentiometer to minimum setting (Fully Counterclockwise) 4. Under Isochronous operation, set Droop potentiometer fully counterclockwise. 5. Set the MPU frequency range : Select the suitable frequency setting according to the highest engine frequency range Input Signal Frequency : SW - 1 O N SW - 2 O N SW - 3 O N SW - 4 O N RPM Flywheel teeth 60 sec Frequency Selection 600 ~ 1200Hz 1200 ~ 2500 Hz 2500 ~ 5000 Hz 5000 ~ 9500 Hz (If uncertain Set SW3-ON and the balance to OFF) 6. Idle Speed set to maximum, Run Speed set to minimum 7. Adjust Remote Speed POT to central (If used) 8. Start Engine At this time the engine should rev to Run Speed, (If engine speed exceeds its rated speed, Stop engine and immediately choose a lower frequency setting) slowly adjust Run Speed pot clockwise to the rated engine speed. For Idle Speed, Ramp Time And Idle Sw Setting, Reference To Paragraph 4.1 9. Slowly adjust Gain clockwise until the actuator begins to oscillate. 4 ESC2301

10.Slowly adjust Gain counterclockwise until it becomes stable. 11.Manually move the linkage. If the linkage oscillates 3 to 5 times and then stabilizes, then the setting is correct. 12.If engine speed overly increases or decreases when adding load or reducing load, please adjust the Gain VR clockwise a little. 13.If engine speed recovers too slowly, adjust INT. (Integration) clockwise, in the same time decrease the GAIN setting. Observe the actuator linkage. If the linkage is stable, manually adjust the linkage. If the linkage slowly oscillates, then the response time is inadequate. Adjust INT. counterclockwise until the response is improved. 5. DIMENSION AND TYPICAL WIRING DIAGRAM 14.Again manually adjust the linkage. If the linkage begins to oscillate 3 to 5 times and then stabilizes, then the setting is complete. Please reference from 4.2 and 4.3 for Droop setting. Note 1: If GAIN or INT. (Integration) is over adjusted, it causes the engine speed to oscillate. Repetitively increasing and decreasing the GAIN and INT. arrangement can help to obtain the best performance. Note 2:Due to different types of external and internal built-in type actuators, the adjustment of Gain is very important, together with INT. (Integration) adjustment. In PT pump type actuators, the movement is very limited, so Gain is set to the minimum using INT. (Integration) to adjust engine speed compensation. DROOP INT. GAIN RAMP-TIME SW POWER : DC12/24V SW1-ON 600~1200HZ SW2-ON 1200~2500HZ SW3-ON 2500~5000HZ SW4-ON 5000~9500HZ + IDLE 1 2 3 IDLE SPEED REMOTE SPEED POT RUN SPEED ~ ILS ACT 4 5 6 7 8 9 10 MPU 11 Idle switc Cable A Cable B + _ DC Power Actuator R Magnetic Pickup CCW 5K CW Wiring Drawing Figure 4 * Cable A, B - use a cable with a wrapped Mylar aluminum foil shield with a drain wire. * To connect the 5K potentiometer, refer to paragraph 3. Connections. 1. To connect the DC power supply and actuator use a 12 AWG / 2mm twist pair harness. 2. Connect the MPU to the ESC2301 using a 2-wire shielded cable. Anchor the drain shield wire to Terminal 10 and the other end cut and tape off. ESC2301 5

5. TROUBLESHOOTING PROBLEM Actuator goes to full stroke when DC power is turned on (Engine is not operating) Governor is completely dead and actuator lever stays at minimum position when power is applied to governor. CORRECTIVE ACTION 1. Check magnetic pickup leads for proper shielded wire or open shield. Verify and correct wiring as necessary. Be sure there is no jumper between terminals 2 and 3. 2. Failsafe circuit in the controller may be damaged or defective. Replace with new controller. 3. With DC power OFF remove leads at actuator. Check continuity of conduction on each terminal to case. There should be no continuity of conduction between any terminal and case of ESC2301. If conduction is measured, please replace the controller. 4. If remote speed potentiometer has been connected to terminals 6, 7 and 9 of the controller, disconnect these leads. Turn DC power ON to the governor if the actuator is now normal. Proceed to corrective actions for the next problem. 1. Check battery voltage at terminals 1 and 2 on controller. Terminal 1 is positive. Check battery connections and contacts for turning power ON to the controller. 2. Check for proper linkage setup. Correct and free linkage. 3. Magnetic pickup signal absent or too low. Measure AC voltage across terminals 10 and 11 while cranking the engine. Voltage should be min. 1.0 VAC. NOTE: The voltmeter should have an impedance of 5000 ohms / volts or higher. Check pole tip gap over gear tooth. Should be 0.037 mm ~ / - 0.127 mm. 4. Measure the resistance of the magnetic pickup coil. This should be above 50 ohm. If there is an open or shorted coil, replace the magnetic pickup. 5. Measure the resistance of each pin to the metal case of the magnetic pickup. No continuity should be evident. 6. If there is continuity of conduction to the case, replace with new magnetic pickup. 7. Measure actuator coil resistance: If actuator coil is open or shorted to case, replace the actuator. If governor still does not operate, continue with steps below. 8. Measuring the resistance of each coil lead to the actuator case should indicate an open circuit on a low scale of the ohm meter. If continuity is defected, replace the actuator. 9. With DC to the governor ON and the engine OFF, measure the DC voltage from terminal 6(+) to terminal 2(-). This should be approx. 4VCD. If 4 VCD is not present, replace the controller. 10.Between terminal 7(+) and terminal 2(-), the voltage should be approx. 4.6 VDC. If 4.6VDC is not present, replace the controller. 6 ESC2301

PROBLEM Erratic governor operation Improper operation from remote speed potentiometer Slow, small amplitude hunting of speed or frequency Fast oscillation of governor linkage Engine will not start Actuator goes to full fuel during cranking CORRECTIVE ACTION 1. Measure DC voltage at 1 and 2 on controller terminal strip. Normal battery voltage should be indicated. If nominal voltage is present, wiring is correct. 2. Low battery voltage 20% below rated can cause erratic operation. Check battery and charging system. 3. RFI noise due to incorrect shielding. Correct wiring. 4. RFI noise fed through power supply leads. Connect power leads directly to the battery. 1. Investigate wiring to remote speed potentiometer for open or shorted circuits. Checking wiring. 2. If the leads at terminals 6 and 7 to the remote speed potentiometer are reversed, speed control by the remote speed potentiometer will be reversed. Correct wiring. 3. Lead wire to remote speed setting potentiometer should be 3-wire shielded cable. Verity that the drain shield wire is isolated from ground at the potentiometer. If terminal 6 lead to the remote speed potentiometer is open, engine speed will go high. Correct the wiring. 4. If lead 8 and 9 (wiper lead to remote potentiometer) is open, there will be no control by the remote speed potentiometer. Verify and correct wiring. 5. If lead 7 to the clockwise terminal of the remote speed potentiometer is open, speed will remain at the value set in ESC2301. Jammed or very loose linkage. Correct linkage. Verity calibration setting of the controller. Readjust setting as necessary. 1. Make sure fuel is available. Check fuel to engine. Check for correct wiring to the automatic shutdown circuits. 2. Air may be trapped in fuel line. Check fuel lines for leaks. 3. Try to operate engine manually. P.S. Performance and size specification can change without prior notification by the factory. ESC2301 7