Measurement of induction motor characteristics

Similar documents
EXPERIMENT CALIBRATION OF 1PHASE ENERGY METER

DHANALAKSHMI COLLEGE OF ENGINEERING MANIMANGALAM. TAMBARAM, CHENNAI B.E. ELECTRICAL AND ELECTRONICS ENGINEERING

Question Number: 1. (a)

ELECTRICAL AND ELECTRONICS LABORATROY MANUAL

Power Quality. Power Factor Wiring and Service. Background. Introduction. bchydro.com

Powerframes - Power Electronics

Effect of prime mover speed on power factor of Grid Connected low capacity Induction Generator (GCIG)

Powerframes - Power Electronics

Armature Reaction and Saturation Effect

Principles of Doubly-Fed Induction Generators (DFIG)

Exercise 2-1. The Separately-Excited DC Motor N S EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Simplified equivalent circuit of a dc motor

DC CIRCUITS ELECTROMAGNETISM

Microcontroller Based Power Factor Correction Using SCR

Installation and Maintenance Instructions. World Leader in Modular Torque Limiters. PTM-4 Load Monitor

The Wound-Rotor Induction Motor Part III

AF09... AF30 3-pole Contactors up to 20 HP / 480 VAC

POWER FACTOR CORRECTION USING SHUNT COMPENSATION

Electrical Power Electric power electrical electric power Electric power electric electric

EKT112 Principles of Measurement and Instrumentation. Power Measurement

ELECTRICAL MAINTENANCE

The Wound-Rotor Induction Motor Part I

ELEN 236 DC Motors 1 DC Motors

Introduction. Upon completion of AC Motors you should be able to: Explain the concepts of force, inertia, speed, and torque

Dev Bhoomi Institute Of Technology LABORATORY Department of Electrical And Electronics Engg. Electro-mechanical Energy Conversion II

AF09... AF30 3-pole Contactors up to 25 HP / 600 VAC

ABB n.v Power Quality in LV installations

MODEL 422 Submersible Pump Controller

Exercise 6. Three-Phase AC Power Control EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Introduction to three-phase ac power control

ECET 211 Electric Machines & Controls Lecture 2-3 (Part 3 of 3) Symbols and Drawing for Electric Motor Control Systems

Electrical Power & Machines Range

The Wound-Rotor Induction Motor Part II

Lab 6: Wind Turbine Generators

Miniature circuit breaker Application guide

Study and Measure the Active and Reactive Power Developed By a Three Phase Induction Generator with Capacitive Load

Synchronous Generators I. Spring 2013

EE6351 ELECTRIC DRIVES AND CONTROL UNIT-1 INTRODUTION

HOKKIM. Control & Protection Relays. giving you control. Utilization: Power Factor Regulator : 14-STEP CYCLIC POWER FACTOR REGULATOR.

Department of Electrical and Computer Engineering

Iowa State University Electrical and Computer Engineering. E E 452. Electric Machines and Power Electronic Drives

2.1 Warnings & Agency Approvals Electrical Connections - Specifications Standard Wiring Configurations...2 4

ENSC387: Introduction to Electromechanical Sensors and Actuators LAB 5: DC MOTORS WARNING:

Application Notes. Calculating Mechanical Power Requirements. P rot = T x W

PSNH INTERCONNECTION REQUEST

Controls. THERMAL OVERLOAD RELAYS RW..D (up to 40A)

1-3 RAMP AND TORQUE BOOST EXERCISE OBJECTIVE

Power Quality Luis Vargas Research Engineer 9/18/2008

ELECTRICAL MACHINES-II LABORATORY MANUAL

Performance of DC Motor Supplied From Single Phase AC-DC Rectifier

Synchronous Generators I. EE 340 Spring 2011

Induction Generator: Excitation & Voltage Regulation

Final Written Examination.

Short form catalogue. Motor protection & control

ELECTROMAGNETIC INDUCTION. FARADAY'S LAW

Legal Name of the Customer (or, if an individual, individual's name): Name: Contact Person: Mailing Address: Physical Address: City: State: Zip Code:

APPARATUS AND MATERIAL REQUIRED Resistor, ammeter, (0-1.5A) voltmeter (0-5V ), battery, one way key, rheostat, sand paper, connecting wires.

LENDI INSTITUTE OF ENGINEERING AND TECHNOLOGY

Contactors. Mini-contactors type LC1-SKGC for use in modular panels. Conforming to standards IEC/EN , IEC/EN , NF C , VDE 0660

Fachpraktikum Elektrische Maschinen. Experiments with a 400/ 690 V Squirrel Cage Induction Machine

To expose the students to the operation of D.C. machines and transformers and give them experimental skill.

Power Factor Correction

Motor Protection Fundamentals. Motor Protection - Agenda

ENGINE GOVERNING SYSTEMS LSM672 LOAD SHARING MODULE. GOVERNORS AMERICA CORP. 720 Silver Street Agawam, MA , USA MEMBER

BPS-v4 Technical Reference S-CAB 11 volt, 1 amp battery power supply

AE105 PRINCIPLES OF ELECTRICAL ENGINEERING JUNE 2014

EXPERIMENT 2 THREE PHASE INDUCTION MOTOR, PART 1

CUSTOMER / ACCOUNT INFORMATION Electric Utility Customer Information (As shown on utility bill)

American Traction Systems. DC Bus Capacitorss. Total. Dual Chopper Module. Dual. Inverter. 750kW. 750kW Generator Module. Module

Report on Usefulness of Data Collected and Plausibility of the Electric Car s Motor Zainab Hussein

Experiment 6: Induction

Planning and Commissioning Guideline for NORD IE4 Motors with NORD Frequency Inverters

Chapter 3.1: Electrical System

TECHNICAL TERMS AND ABBREVIATIONS

Technical Explanation for Inverters

Draft Guideline for the connection of smallscale inverter based distributed generation. EEA Asset Management Forum 22 June 2016 Dr Richard Strahan

Electrical Power Systems 2014/15

"Motors, Power, and Data Loggers Greg Jourdan-Wenatchee Valley College Tuesday, May 8, Sessions Session 1-8:30-9:25 a.m. Motors 101 Session

OPERATING AND MAINTENANCE MANUAL. Primary Current Injection Test Set. 750ADM-H mk2

Jeff Fehr, Senior Application Engineer. ACH550 Flux Optimization White Paper

Pretest Module 21 Units 1-4 AC Generators & Three-Phase Motors

UNIT 2. INTRODUCTION TO DC GENERATOR (Part 1) OBJECTIVES. General Objective

TABLE OF CONTENTS CHAPTER 1 ELECTRICAL THEORY About This Textbook...xi. Passing Your Exam...xiv. How to Use the National Electrical Code...

CI-TI Contactors and motor starters Types CI 61 - CI 98

COM Overcurrent Relay

AF / AF12Z pole Contactors AC / DC Operated - with Screw Terminals

ELECTRICAL FUNDAMENTALS

Renewable Energy Systems 14

Figure 1: Relative Directions as Defined for Faraday s Law

MOTORS, VOLTAGE, EFFICIENCY AND WIRING. A Deeper Understanding

AVR Hybrid Universal Analog Digital Voltage Regulator Operation Manual

AF09... AF38 4-pole Contactors AC / DC Operated - with Screw Terminals

Electrical Machines -II

Types of Motor Starters There are several types of motor starters. However, the two most basic types of these electrical devices are:

G PULLAIAH COLLEGE OF ENGINEERING & TECHNOLOGY DEPARTMENT OF ELECTRICAL & ELECTRONICS ENGINEERING

Faraday's Law of Induction

Full Voltage Starting (Number of Starts):

St.MARTIN S ENGINEERING COLLEGE Dhulapally, Secunderabad

2.0 CONSTRUCTION 3.0 OPERATION. SA-1 Generator Differential Relay - Class 1E 2.5 TRIP CIRCUIT

PQC-STATCON. PPHVC-Power Quality Solutions. Instantaneous and stepless power quality compensation for dynamic reactive power and unbalanced loads

Energy Systems Lab FALL Experiment No DC Machines

Figure 1. Type CWP-1 Ground Relay (Front View) Figure 2. Type CWP-1 Ground Relay (Rear View) E

Transcription:

Measurement of induction motor characteristics ES163 Electrical and Electronic Systems MR TJ KENNAUGH School of Engineering, University of Warwick 27/01/01

Summary The aim of the laboratory is to increase understanding of the use of simple 3-phase power systems and current, voltage, power, power factor and mechanical power. Also to develop and understanding of a small 3-phase induction motor. This was achieved by investigating the characteristics of the induction motor at the rated voltage under a range of loads until the motor stalled. It was found that the motor speed under normal operation does not vary much with load. It was also found, by plotting a graph that the efficiency of the motor is at a maximum at its rated load. The specifications on the motor s nameplate were found to be slightly different from the measured values. Speed was found to decrease as the applied torque was increased and the power factor was found to increase as the power output increased. A VA diagram was drawn for the motor at the rated load. The experiment showed roughly the expected results with a slight variation compared to the motor specifications. Page - 1

Table of Contents Summary...1 Table of Contents...2 Introduction...3 Theory...4 Apparatus and Methods...5 Observations and Results...7 Analysis and Discussion of Results...8 Table of Graphs...8 Conclusions...14 Bibliography...15 Appendices...15 Appendix A: Laboratory Instruction Sheets...15 Page - 2

Introduction A large proportion of energy used in industry is consumed by electrical drives. Many types of motor are available but the three-phase induction motor is by far the most common. Its basic capabilities are limited but may be extended using electronic controls. In order to specify a drive system the speed and torque (and hence power) required by the load must be matched by the capabilities of the drive. The basic characteristic of a drive is its torque-speed curve which is obtained experimentally on a dynamometer (a specially designed brake). The test system used in this exercise comprises a small motor connected to an electromagnetic dynamometer and a tachometer (an electrical speed-measuring device). The torque on the brake is measured by a strain gauge, and signals from this and from the tachometer are fed into a control box. This control box provides a manual adjustment of the braking torque and gives displays of speed and torque (measured) and mechanical power (calculated from speed & torque). The energy from the drive is dissipated as heat from the fins on the casing of the dynamometer. The experiment is designed to determine characteristics of a small induction motor and help develop knowledge of 3-phase supplies. See Laboratory instruction sheet (appendix A) Page - 3

Theory Voltage current and phase angle in single-phase systems The voltage varies sinusoidaly (e.g. v=240sin ωt) and the current varies in a similar way, I=10sin(ωt + Φ) the angle Φ may be zero, positive (current leading voltage) or negative (voltage leading current) depending on the circuit. Both current and voltage are usually expressed as root mean squared (rms) values, which are equal to the peak values divided by 2 In most practical situations the circuit is inductive and current lags the voltage. If the rms voltage across the load is V, the rms current through it is I and the phase angle between V and I is Φ, the power delivered to the load is VIcosΦ. Cos Φ is the power factor and by convention is positive when the current lags voltage. The product of V and I is known as volt-amps or VA ( apparent power ) and VIsinΦ is reactive volt amps or VAr ( reactive power ) Three phase systems Industrial power consumers are usually connected to a three-phase supply. In many circumstances this may be regarded as three interconnected single-phase supplies. The three voltages are displaced by 120º relative to each other and share one common conductor which is known as the neutral. If the three loads are similar the current in the neutral is zero. Basic three-phase systems may be analysed by considering one phase only. The phase voltage, V p, is the voltage between a line and neutral. The line voltage, V L, is the voltage between any to lines and is 3 V p. For further information see Appendix A: Laboratory Sheets. Page - 4

Apparatus and Methods Apparatus Electrical power test panel (Feedback) equipped with: Three-phase supply control unit, ref. 60-100 ( The control unit ) Variable three-phase /dc supply 5A, ref. 60-125 ( The supply unit ) Single & three-phase measurement unit, ref. 68-100 ( The measuring unit ) Electrical machines test bed (Leroy Somer) equipped with Induction motor rated at 0.3kW 50Hz 1440rpm (Delta-connected: 220V 1.75A, Star-connected 380V 1.00A) Tachometer & powder brake dynamometer (Leroy Somer Modmeca), rated at 300W for 15min, 500W for 5min & equipped with overload trip. Dynamometer control box (Modmeca 3) 9 Connecting leads. Methods The single-phase circuit breaker with no-volt release on the control unit and the power switch on the measuring unit were switched on. The 3-phase energy meter was checked and the selector switch set to 4-wire it was then switched on and set to line voltages. The energy meter can be used to measure voltage, current, power, power factor, energy, frequency, and crest factor. (For further information see Appendix A: Laboratory instruction sheets.) The three-phase power circuit breaker on the supply panel was set to off, the variable output control knob to zero, and the output voltage selector to 1 (three-phase). The three phase outputs, L1, L2, L3, and N on the supply panel were connected to the respective inputs on the measuring unit. The three-phase circuit breaker with no-volt release on the control panel and the three-phase circuit breaker on the supply panel were switched on. The variable output control was set to about 25% and the line voltages were checked (on the energy analyser) and noted. The phase voltages and the line voltages were compared and it was noted that V L = 3 V p. The variable control was set back to zero and the three-phase power breaker switched off. The induction motor was connected in a star configuration and the three terminals L!, L2 and L3 on the right of the measuring unit were connected to U1, V1 and W1 on the motor. The three-phase power breaker was switched on and the variable output control was slowly increased until the motor started. The voltage was increased to the rated value of 380V line to line. It was noted that the speed of the motor while running was not greatly affected by the voltage. The dynamometer control box was set to manual control of torque and the manual control was set to zero. The speed range was set to 200.min and the power range to 300W. The unit was then switched on. Page - 5

Figure1 - Connections for load tests on induction motor Control Unit Variable 3Ø Supply Measuring unit Notes 1. Control unit is connected internally to supply unit 2. Dynamometer rating: 300W for 15min or 500W for 5min Induction Motor Dynamometer controller Dynamo & tachogenerator The values of torque, speed, mechanical power, voltage, current, power factor, and electrical power input were noted at this no load state. The load torque was increased in steps of 0.5Nm and values of torque, speed, mechanical power, voltage, current, power factor, and electrical power input were noted at each value. The torque was increased until the motor was running at the rated power of 300W. VA and VAr were measured at this point. The torque was again increased in steps of 0.5Nm and measurements taken until the motor stalled. Measurements were taken fast to prevent the motor overheating in this high load state. When the motor stalled the load torque was immediately set to zero and the motor allowed to run in a no-load state in order to cool down. Page - 6

Observations and Results Line to neutral voltages: Display shows voltage: 120V So: 3 69.7 = 120 Therefore: 120V is expected. L1 L2 L3 68.7V 69.8V 69.8V The speed is not greatly affected by the voltage. No Load State: Mechanical Power Electrical Torque Speed Voltage Current Power Factor power input 0.0Nm 1445min -1 1.2W 380V 581mA 0.33 127W Table of measured values (varying load torque): V (V) I (ma) PF P Elec P Mech (W) (W) n (min-¹) T (Nm) 380 581 0.33 127 1.2 1445 0.0 379 634 0.50 210 78.5 1430 0.5 379 701 0.61 280 140.6 1417 1.0 379 806 0.70 368 210.5 1399 1.5 379 938 0.77 473 288.3 1380 2.0 380 962 0.78 492 300.0 1372 2.1 380 1080 0.81 576 349.2 1350 2.5 380 1280 0.84 703 411.0 1313 3.0 380 1520 0.85 840 452.0 1272 3.5 380 1850 0.85 1120 491.0 1182 4.0 At rated power (300W): VAr = 397 VAr VA = 631VA Specification of motor on nameplate: V Hz min -1 kw cos φ A 220 50 1440 0.30 0.66 1.75! 380 50 1440 0.30 0.66 1.00 Page - 7

Analysis and Discussion of Results The following graphs are required: 1. Torque vs. Speed 2. Power Factor vs. Power Output 3. Percentage efficiency vs. Power Output For the third graph, valued for percentage efficiency are required. These may be calculated using the following formula: 100 mechanical power electrical power in For each value of load The results are shown in the table below: V (V) I (ma) PF P Elec P Mech %age n (min-¹) T (Nm) (W) (W) Efficiency 380 581 0.33 127 1.2 1445 0.0 0.9% 379 634 0.50 210 78.5 1430 0.5 37.4% 379 701 0.61 280 140.6 1417 1.0 50.2% 379 806 0.70 368 210.5 1399 1.5 57.2% 379 938 0.77 473 288.3 1380 2.0 61.0% 380 962 0.78 492 300.0 1372 2.1 61.0% 380 1080 0.81 576 349.2 1350 2.5 60.6% 380 1280 0.84 703 411.0 1313 3.0 58.5% 380 1520 0.85 840 452.0 1272 3.5 53.8% 380 1850 0.85 1120 491.0 1182 4.0 43.8% Table of Graphs Graph 1: Torque vs. Speed... Page 9 Graph 2: Power Factor vs. Power Output... Page 10 Graph 3: Percentage efficiency vs. Power Output... Page 11 Page - 8

Measurement of induction motor characteristics TJ KENNAUGH 0013679 Note the point showing the values at the rated power on each graph. VA Diagram Volt-Amps = VI (VA) Reactive Volt-Amps = VIsinφ (VAr) Power = VIcosφ (W) VA Diagram for motor at full load (300W) Motor measurements at full load (300W) Power Electrical Reactive Mechanical Volt- Torque Speed Voltage Current Factor power Volt- Power Amps input Amps 2.1Nm 1372min -1 300W 380V 962mA 0.78 492W 631VA 397VAr V = 3 L V p V p I 219V 0.962A Volt- Reactive Power Amps Volt-Amps 164.6WW 211.1VA 132.1VAr φ 39º Volt-Amps = 211.1VA Reactive Volt-Amps = 132.1VAr Power = 164.6W It has been noted from the Torque vs. Speed graph that until the motor stalls speed does not vary much with load. The rest of the torque speed curve (n = 0 to n = stall speed) is virtually impossible to measure as the motor does not operate below the stall speed. The efficiency of the motor at the rated load can be calculated using the following formula: 100 mechanical power electrical power in From the measured value this is calculated as 60.9% The power factor at the rated load was measured as 0.78 Specification of motor on nameplate: (To scale) Page - 12

V Hz min -1 kw cos φ A 220 50 1440 0.30 0.66 1.75! 380 1.00 Values measured at full load (300W Star connected) Power Electrical Reactive Mechanical Volt- Torque Speed Voltage Current Factor power Volt- Power Amps input Amps 2.1Nm 1372min -1 300W 380V 962mA 0.78 492W 631VA 397VAr The measured speed is close to the rated value as is the current. However the power factor is higher than the expected value. The test results do not exactly confirm the specification on the nameplate. From the nameplate the expected power can be worked out as 434W therefore expected efficiency should be 69% which is slightly higher than the measured value. From the graph of Power factor vs. power output is may be observed at small loads that the power factor and efficiency reduce dramatically. This is a disadvantage as if efficiency decreases then cost of electrical power will rise. A company will also be charged more for loads on the supply with a low power factor. Both of theses are undesirable in an industrial situation and therefore it is not viable to run the motor at small loads. As the motor is overloaded the efficiency reduces but the power factor rises and levels off. This is caused by the load reducing the speed of the motor which reduces the back emf produced in the coils, decreasing the resistance and drawing more current, without increasing motor speed. Page - 13

Conclusions The results show the characteristics of a small 3 phase induction motor connected in a star configuration. The efficiency of the motor was found to be a maximum at the rated power. The speed was found to decrease as the applied torque increased. The power factor was found to increase as the power output increased. It was found that the motor speed under normal operation does not vary much with load. It was found that at small loads operation is undesirable, with a low power factor and a low efficiency. The specifications on the motor s nameplate were found to be slightly different from the measured values. The efficiency of the motor at the rated load was found to be about 60% which was less than the 69% expected. The results for the investigation were in line with what would be expected. Page - 14

Bibliography Laboratory Sheet: ES163 Electrical and Electronic Systems: Measurement of induction motor characteristics (Attached) Lecture notes: ES163 Reference Edward Hughes (rev. I McKenzie Smith): Electrical Technology 7 th Edition, Longman 1995, Ch. 32 pp 542-547 & Ch. 41 pp 698-703 Appendices Appendix A: Laboratory Instruction Sheets 1. Instruction Sheet 2. Theory: Three phase power systems and safety devices 3. Feedback/Elcontrol Operation Page - 15