AAMA THERMAL PERFORMANCE REPORT. Rendered to: UNITED STATES ALUMINUM. SERIES/MODEL: 3150 Curtain Wall TYPE: Glazed Wall System

Similar documents
AAMA THERMAL PERFORMANCE REPORT. Rendered to: TUBELITE, INC. SERIES/MODEL: 200 Series Curtainwall (E2297) TYPE: Glazed Wall System

AAMA THERMAL PERFORMANCE REPORT (Revised) Rendered to: UNITED STATES ALUMINUM

AAMA THERMAL PERFORMANCE REPORT. Rendered to: TORO ALUMINUM. SERIES/MODEL: Commdoor 225 Awning (Project Out) TYPE: Projecting, Awning

AAMA THERMAL PERFORMANCE REPORT. Rendered to: US ALUMINUM INC., DIVISION OF CR LAURENCE CO., INC.

NFRC U-FACTOR, SHGC / VT, CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT. Rendered to: EARTHWISE GROUP, L.L.C. SERIES/MODEL: SS 145.

NFRC U-FACTOR, SHGC / VT, CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT. Rendered to: EARTHWISE GROUP, L.L.C.

NFRC U-FACTOR, SHGC / VT, CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT. Rendered to: EARTHWISE GROUP, L.L.C.

NFRC U-FACTOR, SHGC / VT, CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT. Rendered to: EARTHWISE GROUP, L.L.C.

CREEP PERFORMANCE TEST REPORT. Rendered to: TREX COMPANY LLC. Seclusions Composite Privacy Fence System TYPE: Composite Fence System

NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT. (Revised) Rendered to: SPECIALTY WHOLESALE SUPPLY

NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT. Rendered to: PARAMOUNT WINDOWS

NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT. Rendered to: CR LAURENCE CO., INC.

NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT. Rendered to: PARAMOUNT WINDOWS CORPORATION

PERFORMANCE TEST REPORT. Rendered to: AIR VENT, INC. SERIES/MODEL: Hip Ridge Vent PRODUCT TYPE: Ridge Vent

CALIBRATION REPORT. Rendered to: United States Aluminum Corp. LOCATION: Waxahachie, Texas

U-Factor, Solar Heat Gain Coefficient, Visible Transmittance and Condensation Resistance Calculation Report

TEST REPORT. Report No.: G Rendered to: VELUX America LLC Greenwood, South Carolina

U-Factor, Solar Heat Gain Coefficient, Visible Transmittance and Condensation Resistance Calculation Report

NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT. (Revised) Rendered to: EARTHWISE GROUP, L.L.C

AAMA/WDMA/CSA 101/I.S.2/A TEST REPORT. Rendered to: MASTER WINDOW SYSTEMS, INC.

ASTM E 1886 and ASTM E 1996 TEST REPORT. Report No.: A Rendered to: GLASSCRAFT DOOR COMPANY Houston, Texas

ASTM E 1886 and ASTM E 1996 TEST REPORT. Report No.: A Rendered to: GLASSCRAFT DOOR COMPANY Houston, Texas

ASTM E 1886 and ASTM E 1996 TEST REPORT. Report No.: A Rendered to: GLASSCRAFT DOOR COMPANY Houston, Texas

IMPACT TESTING ON SAFETY GLAZING MATERIAL. Rendered to:

TEST REPORT. Rendered to: HOMELAND VINYL PRODUCTS, INC. For: PVC Guardrail System Utilizing New Nylon/PVC Rail Mounting Bracket

TEST REPORT. Report No.: G Rendered to: SKYCO SKYLIGHTS Costa Mesa, California

COMPUTER SIMULATION U-FACTOR, SHGC, VT PERFORMANCE EVALUATION OF FIXED WINDOW 3000 SERIES LOW PROFILE FIXED. Dominion Doors & Windows Ltd.

COMPUTER SIMULATION U-FACTOR, SHGC, VT PERFORMANCE EVALUATION OF FIXED WINDOW 3000 SERIES CASEMENT WINDOW. Dominion Doors & Windows Ltd.

350/500 TUFFLINE ENTRANCES 1

2000T TERRACE DOOR. Features

350/500 Heavy Wall TM Entrances 1

260/360/560 INSULCLAD ENTRANCES

350/500 Tuffline TM Entrances 1

NFPA 285 TEST REPORT. Report No.: H Test Date: June 1, Rendered to: ARCONIC ARCHITECTURAL PRODUCTS Eastman, Georgia

8400 SERIES THERMAL PERFORMANCE CHART

190/350/500 STANDARD ENTRANCES

Weather Shield Thermal Performance Criteria

Notice of Product Certification Authorization

New Gateway 101/I.S.2/A440

CHAPTER 3 INTEGRITY WOOD ULTREX DOUBLE HUNG

RSL Energy Efficiency and STC Ratings. Energy efficiency and beauty at your doorway!

your vision, our windows

CONSTRUCTION CONSULTING LABORATORY, INTERNATIONAL

SIZE AND PERFORMANCE SUMMARY GLAZING PERFORMANCE GRILLE PROFILES AND PATTERNS SIZE TABLES DESIGN DATA DETAILED PRODUCT DESCRIPTION CROSS SECTIONS

WA67 Folding System - Aluminum Clad Over Wood

AAMA/WDMA/CSA 101/I.S.2/A NAFS North American Fenestration Standard/Specification for windows, doors, and skylights

Solarban 70XL and Solarban 70XLVT Coated Glass Technical Considerations and Guidelines

Performance Data and Comparisons

Manufacturer s Certification Ply Gem Replacement Windows

SUMMARY OF PROPOSED CHANGES,

Guide Specification SECTION VINYL WINDOWS

SINGLE SLIDING WINDOW 1000 SERIES 4-1/2" FRAME SINGLE SLIDER LIFT OUT

LUXURY SLIDING PATIO & SWINGING FRENCH DOORS

Commercial Glass Performance Guide

Residential Glass Performance Guide

Product Selection Guide Size and Performance Data...W-HG-2 Features and Options...W-HG-3 Combination Assemblies...W-HG-4 Glazing Performance...

Size and performance summary. Glazing performance. Grille profiles and patterns. Size tables. Design Data. Detailed Product Description

Ambassador ALUMINUM WINDOWS & DOORS FOR ALL SEASONS

HURRICANESHIELD IMPACT-RESISTANT GLASS SECTION DIRECTORY. Size and performance summary. Glazing performance. Grille profiles and patterns.

Pilkington Product Guide Technical Data

New $1500 Stimulus Plan Tax Credit

Lifestyle Series Casement

SRD Design CORPORATION. Fenestration Specialists!

3948 Townsfair Way, Suite 200 July 2013 Columbus, Ohio Toll Free Website

Residential skylight sizes 2008 edition

Architect Series Traditional

ALUMINUM. Yellow Dog Window. Windows & Doors. Visit our website at

Double Hung. Power Lift 28,000 Constant Force

Size and performance summary. Glazing performance. Grille profiles and patterns. Size tables. Design Data. Detailed Product Description

AAMA/WDMA/CSA 101/I.S.2/A440-08

SIZE AND PERFORMANCE SUMMARY GLAZING PERFORMANCE GRILLE PROFILES AND PATTERNS SIZE TABLES DESIGN DATA DETAILED PRODUCT DESCRIPTION CROSS SECTIONS

Contents. Preface 6. 1 Scope General Outside of scope Terminology Units of measurement 13 1.

Size and performance summary. Glazing performance. Grille profiles and patterns. Size tables. Design Data. Detailed Product Description

Energy Management Performance Data

Energy Management Performance Data

Energy Management Performance Data

ECOSTAR and MAXGREEN

REPORT NO. TR-P NC SAFETY COMPLIANCE TESTING FOR FMVSS 223 REAR IMPACT GUARDS 2007 TRANSFREIGHT TECHNOLOGY NHTSA NO.

General Information SECTION DIRECTORY

82" RO 81 1/4" FD 3/8" MIN JOINT 75 5/8" DLO 2 13/16" SERIES 8200 HORIZONTAL SLIDING WINDOW ELEVATION - BLOCK INSTALL 82" RO 81 1/4" FD

Modern Aluminum COLLECTION

Voluntary Specification for Determining Forced Entry Resistance of Side-Hinged Door Systems

continuous mounting flange intended for direct attachment to roofing substrate.

PENTAGON PROTECTION USA

AAMA/WDMA/CSA 101/I.S.2/A440-08

U.S. ALUMINUM 3025 SERIES SLIDING DOORS

Euro Vista Pivot. Approved for use in Miami-Dade HVHZ Zones Florida Building Code Approved Product Approval FL FOLDING SLIDING STACKING PIVOT

May08 Rev C

Meeting Residential Energy Requirements with Wood-Frame Construction

ASTM B117 Testing Quality Control

Architect Series Traditional

Product Guide Specification

Pella 450 Series. Size and performance summary. Glazing performance. Grille profiles and patterns. Size tables. Design Data

Architect Series Designer Series Pella ProLine. Architect Series...AW-1 Designer Series...AW-2 Pella ProLine...AW-2

Euro Vista Pivot FPA HVHZ AMIA MI-DA DE H V HZ AFLO RIDA PRO D UC T

Voluntary Specification for Determining Forced Entry Resistance of Side-Hinged Door Systems

Size and performance summary. Glazing performance. Grille profiles and patterns. Size tables. Design Data. Detailed Product Description

InvestSmart Business Energy Upgrades Cool Roof and Window Film Equipment Catalog 01/01/2018

AIR-INS inc. 1320, boul. Lionel-Boulet, Varennes (Québec) J3X 1P7 Tél. : (450) Fax : (450)

Meeting ENERGY STAR Version 6.0

Transcription:

AAMA 507-07 THERMAL PERFORMANCE REPORT Rendered to: UNITED STATES ALUMINUM SERIES/MODEL: 3150 Curtain Wall TYPE: Glazed Wall System Report No: Report Date: 08/22/08 130 Derry Court York, PA 17406-8405 phone: 717-764-7700 fax: 717-764-4129 www.archtest.com

AAMA 507-07 THERMAL PERFORMANCE REPORT Rendered to: UNITED STATES ALUMINUM 200 Singleton Drive Waxahachie, Texas 75165 Project Summary: Simulation Specimen Description: Report No: Report Date: 08/22/08, Inc. (ATI) was contracted by United States Aluminum to provide U- Factor and Solar Heat Gain Coefficient thermal performance ratings on the 3150 Curtain Wall Glazed Wall System. The thermal performance ratings were determined in accordance with AAMA 507-07, Standard Practice for Determining the Thermal Performance Characteristics of Fenestration Systems Installed in Commercial Buildings. Reference Documents: AAMA 507-07, Standard Practice for Determining the Thermal Performance Characteristics of Fenestration Systems Installed in Commercial Buildings NFRC 100-2004, Procedure for Determining Fenestration Product U-Factors NFRC 200-2004, Procedure for Determining Fenestration Product Solar Heat Gain Coefficient and Visible Transmittance at Normal Incidence NFRC Technical Interpretation TI-2003-12, Curtain Wall Simulation Series/Model: 3150 Curtain Wall Type: Glazed Wall System Frame Material: Aluminum Thermally Improved Framing System Specimen Size: 2000mm wide by 2000mm high (78-3/4" by 78-3/4") Configuration: Two vision lites separated by one intermediate vertical Drawing Reference: U.S. Aluminum Drawing: 3150CW (Int Horiz 060 & Int Vert 048) 130 Derry Court York, PA 17406-8405 phone: 717-764-7700 fax: 717-764-4129 www.archtest.com

AAMA 507-07 Page 2 of 7 United States Aluminum 3150 Curtain Wall - Glazed Wall System System U-Factor vs. Percentage of Vision Area 1.30 1.25 1.20 1.15 1.10 1.05 1.00 0.95 0.90 COG U-Factor 0.85 0.80 0.75 0.70 0.65 0.60 0.55 System U-Factor (Btu/h ft 2 ºF) 0.48 0.46 0.44 0.42 0.38 0.36 0.34 0.32 0.28 0.26 0.24 0.22 0.20 0.50 0.45 0.35 0.25 95 90 85 80 75 0.20 70 Vision Area / Total Area (%)

AAMA 507-07 Page 3 of 7 United States Aluminum 3150 Curtain Wall - Glazed Wall System System SHGC vs. Percentage of Vision Area COG SHGC 0.75 0.70 0.65 0.60 0.55 0.50 0.45 0.35 0.25 0.20 0.15 0.10 0.05 95 90 85 80 75 0.80 0.75 0.70 0.65 0.60 0.55 0.50 0.45 0.35 0.25 0.20 0.15 0.10 0.05 0.00 70 System SHGC Vision Area / Total Area (%) System VT vs. Percentage of Vision Area COG VT 0.75 0.70 0.65 0.60 0.55 0.50 0.45 0.35 0.25 0.20 0.15 0.10 0.75 0.70 0.65 0.60 0.55 0.50 0.45 0.35 0.25 0.20 0.15 0.10 System VT 0.05 0.05 95 90 85 80 75 0.00 70 Vision Area / Total Area (%)

AAMA 507-07 Page 4 of 7 United States Aluminum 3150 Curtain Wall - Glazed Wall System Size Specific U-Factor Matrix* Glazing Option Center of Glass U-Factor Overall U-Factor 1 0.48 0.53 2 0.46 0.51 3 0.44 0.50 4 0.42 0.48 5 0.46 6 0.38 0.44 7 0.36 0.43 8 0.34 0.41 9 0.32 0.39 10 0.37 11 0.28 0.35 12 0.26 0.34 13 0.24 0.32 14 0.22 15 0.20 0.28 Size Specific SHGC Matrix* Size Specific VT Matrix* Center of Glass SHGC Overall SHGC Center of Glass VT Overall VT 0.75 0.72 0.75 0.68 0.70 0.68 0.70 0.63 0.65 0.63 0.65 0.59 0.60 0.59 0.60 0.54 0.55 0.54 0.55 0.50 0.50 0.50 0.50 0.45 0.45 0.45 0.45 0.41 0.41 0.36 0.35 0.36 0.35 0.32 0.32 0.27 0.25 0.27 0.25 0.23 0.20 0.23 0.20 0.18 0.15 0.18 0.15 0.14 0.10 0.13 0.10 0.09 0.05 0.09 0.05 0.05 *Size Specific U-Factor, SHGC, and VT Matrices are based on the standard Glazed Wall System specimen size of 2000mm wide by 2000mm high (78-3/4" by 78-3/4"). This represents 90.6% Vision Area / Total Area.

AAMA 507-07 Page 5 of 7 0.2415 0.2596 0.2961 0.2778 0.3143 0.3325 0.3684 0.3505 0.3863 42 0.4398 0.4220 0.4929 0.4751 0.4574 0.2829 0.3182 06 0.3366 0.3543 0.3900 0.3724 77 0.4254 0.4607 0.4430 0.4784 0.5316 0.5138 0.4961 0.4830 0.4688 0.4973 0.5142 0.5444 0.5287 0.5589 0.5738 0.6036 0.5886 0.6187 0.6339 0.2460 0.2033 0.2460 0.6801 0.6646 0.6493 0.2734 0.2597 0.2188 0.2597 0.2505 0.2871 0.2734 0.2345 10 0.2663 09 0.2871 0.3291 0.3152 0.2823 0.3152 0.3141 0.3432 0.3290 0.2980 0.3571 0.3301 0.3571 0.3431 0.3854 0.3712 0.3463 0.3713 0.3787 0.3997 0.3854 0.3624 1.7416 0.7100 1.7415 0.4280 0.4431 0.4286 0.4115 0.4286 0.4140 0.3950 1.7430 1.7422 0.7221 1.7421 0.7569 1.7474 1.7430 0.7345 1.7485 0.7698 1.7485 1.7474 1.7595 1.7583 0.7830 1.7583 0.8097 1.7608 1.7594 0.7961 1.7622 0.8234 1.7623 1.7608 1.7654 1.7637 0.8374 1.7637 0.8661 1.7671 1.7654 0.8516 1.7723 0.9113 1.7723 1.7707 0.8959 1.7708 1.7692 58.4 54.1 55.2 56.3 57.3 50.0 51.0 52.0 53.1 45.8 46.8 47.9 48.9 Vision Area Data 43.7 44.8 0.4431 0.8811 1.7693 1.7670 0.4141 0.3997 NFRC 100-2004 78.74" by Vision Area 150.00" by 150.00" Frame U-Factor Edge U-Factor 70% Vision Area 23.45" by 23.45" Total Product U-Factor 78.74" 95% Option No. COG Temperature COG U-Factor 0.48 1 0.32 2 3 4 5 6 11 10 0.38 0.36 0.34 8 9 7 0.46 0.44 0.42 0.26 0.24 0.22 12 13 14 15 0.20 Cross Section 0.28 Frame Height

AAMA 507-07 Page 6 of 7 Detailed drawings, simulation data disks, and a copy of this report will be retained by ATI for a period of four years. The above results are the exclusive property of the client so named herein and are applicable to the sample simulated. This report does not constitute an opinion or endorsement by this laboratory. This report may not be reproduced except in full without the approval of ATI. For ARCHITECTURAL TESTING, INC.: SIMULATED BY: REVIEWED BY: Jason Mitzel Simulation Technician Michael J. Thoman Director - Simulations and Thermal Testing Simulator In Responsible Charge JAM:ksl Attachments (pages): Appendix A: Drawings and Bills of Material (3)

AAMA 507-07 Page 7 of 7 Revision Log Rev. # Date Page(s) Revision(s).01 R0 8/22/2008 All Original Report Issue

All drawings and Bills of Material used in simulating this product are enclosed in this Appendix. Appendix A