Installation Instructions for JDB, JD, HJD, JDC, JW HJW, JWC Circuit Breakers and Molded Case Switches

Similar documents
Installation Instructions for KPS and KPH Circuit Breakers and Molded Case Switches

Installation Instructions for TMQV Circuit Breakers and Molded Case Switches

A WARNING. Installation Instructions for KD, HKD, KDC, CKD, CHKD Circuit Breakers I.L. 29C092C

I.L. 29C121A WARNING 1. INTRODUCTION. Maximum Freq. Maximum Dielectric Voltage Current Withstand (V) (A) Voltage (V)

Installation Instructions for R-Frame Circuit Breakers and Molded Case Switches

! WARNING I.L D WARNING GENERAL INFORMATION

Installation Instructions for NW, HNW, and NWC Circuit Breakers and N-frame Series C Molded Case Switches

Cutler-Hammer I.L. 29C160G WARNING NOTICE 1-0 INTRODUCTION. General Information

Q and M-Frame Circuit Breaker Instruction Leaflet for Installation and Operation for Thermal Magnetic Trip Units

Cutler-Hammer. Installation Instructions for Undervoltage Release Mechanism (Handle Reset) with LED for E 2 L and E 2 LM Mining Circuit Breakers

N-frame Circuit Breaker

Cutler-Hammer. Installation Instructions for the Digitrip OPTIM Pole Trip Unit Installation and Operation with L-Frame Series C Circuit Breakers

a WARNING Allen-Bradley Parts K-Frame Circuit Breaker Instruction Leaflet for Alarm Switch and Alarm /Auxiliary Switch Combination Bul.

Installation Instructions for Series C F-Frame 310+ Electronic Circuit Breaker Types FDE, HFDE, FDCE

Installation Instructions for the 14" Walking Beam Interlock for L-Frame and MDL-Frame Series C Circuit Breakers and Molded Case Switches

Cutler-Hammer. Installation Instructions for the ND OPTIM 550 PowerNet and/or Zone Interlock Accessories (ICK 550N, ZGK550N, ZGPK550N) I.L.

Q and M-Frame Circuit Breakers Instruciton Leaflet for Alarm Switch and Auxiliary Switch Combinaiton

Installation Instructions for Type SM Safety Handle Mechanism for L-Frame Series C Circuit Breakers and Molded Case Switches

I.L. 29C184A File WARNING

Installation Instructions for Series C F-Frame 310+ Electronic Circuit Breaker Types FDE, HFDE, FDCE

L-Frame LD F. Circuit Breaker/ Frame Ampere Rating. Trip Unit Rating/ Plug Ampere Rating LD T5 7 W

O & M Manual for the EATON Generator Ready Loadcenter

Westinghouse Molded Case Circuit Breakers Engine Generator FG Amperes

Table Line and Load Terminals. Terminal Body Material. Wire Type. Aluminum Copper Aluminum. English English English.

Cutler-Hammer Molded Case Circuit Breakers Amperes. January 2001 Vol. 1, Ref. No. [0477] G-Frame

Cutler-Hammer I.B. ATS-RT03. Instructions for Cutler-Hammer Residential Automatic Transfer Switch

Table Types LD, HLD and LDC Thermal-Magnetic Circuit Breakers with Interchangeable Trip Units

Cutler-Hammer. January 2001

Cutler-Hammer. Molded Case Circuit Breakers Amperes January J-Frame

Cutler-Hammer. Molded Case Circuit Breakers Amperes. -" Product Selection M-Frame

WARNING. Instructions for Combination Bypass Isolation and Transfer Switches Amps I.L A FILE APPLICATION SAFETY PRACTICES

Instructions for A200, A210, A250 size 6, two- or three-pole non-reversing or reversing motor controllers

Switchboards Instant Service

Table Type FD Thermal-Magnetic Circuit Breakers with Non-interchangeable Trip Units

Interrupting Capacity (Symmetrical Amperes) Volts ac (50/60 Hz) Y/ ,000 25,000. Frame Only E2L3600F

Cutler-Hammer I.B. ATS-RM05. Instructions for Cutler-Hammer Residential Automatic Transfer Switch

Poles 3 Starter Size NEMA 3 NON ALUMINUM LINE TERMINAL, LOAD TERMINAL

Amperes. F-Frame. Price U.S. $ Catalog Number. Price U.S. $ EDH2100 EDH2125 EDH2150 EDH2175 EDH2200 EDH2225

section-page Table 1. Transfer switching device ratings. Conditional short circuit current

' '!' D Model, 70 to 250 Amperes. W Model, 63 to 250 Amperes. www. ElectricalPartManuals. com

Installation Instructions for Interlocking Trip Indicator with Remote Reset for Magnum Low Voltage Circuit Breakers

MOLDED CASE CIRCUIT BREAKERS

Product Line Overview. The Most Logically Designed Contact Assembly

25.4. Molded Case Circuit Breakers. For Immediate Delivery or Tech Support call KMParts.com at (866) Contents

Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers

Technical Data and Specifications. Table UL 489/IEC Interrupting Capacity Ratings. cu I cs I cu I cs I cu I cs I cu I cs I cu I cs

SECTION PANELBOARDS

Cutler-Hammer. Molded Case Circuit Breakers Amperes. Product Selection January 2001 Vol. 1, Ref. No ) J-Frame

Instructions for using Functional Test Kit on Digitrip 520 and 1150 family of Power Circuit Breaker Trip Units and Series G and FD MCCB Trip Units

Instruction Bulletin NF Panelboard Dual Sub-Feed Circuit Breaker Adapter Kit Installation onto an NF Panelboard Class 1670

Florham Park, NJ USA Call (ASCO) for sales or service

Two-way cable interlock kit for Magnum drawout circuit breakers

Cutler-Hammer. January 2001

Instruction Booklet for the Installation, Operation and Maintenance of Type 5-15 kv VCP-WG Vacuum Circuit Breaker 4000A MiniMod

Digitrip Retrofit System for the Federal Pioneer 25-H(L)-2, 30-H(L)-2, 30-H(L)-3, and 30-3 Breakers

Quik-Spec Coordination Panelboard

design prefix 50 Hanover Road, Florham Park, New Jersey USA (ASCO), for service call (ASCO)

Digitrip Retrofit System for Allis-Chalmers LA-600 F Electrically Operated Fused Breakers

Q-Frame Main Circuit Breaker (225 A Maximum) and Adapter Kit Installation onto an NQ Panelboard Class 1640

Molded Case. Circuit Breakers. Molded Case Circuit Breakers Contents

O & M Manual for the RLC1 Automatic Transfer Switch

CR193 Vacuum Limitamp* Contactors

TVSS Installation for RLCM/CHGENLC, RLCU, and CHGEN ATSs

Series C, F-frame molded case circuit breaker, 15A, Two-pole, Thermal Magnetic Trip, FD Breaker

MAx-305 & MAx-318 Series MAx-405 Through MAx-419 Series Two-Position Actuators

CENTERLINE 2100 Motor Control Centers 600A, 800A, and 1200A Bolted Pressure Contact Switch

Owner s Manual. Series 165 Automatic Transfer Switches rated 100 and 200 amps, single phase, 240 V ac for automatic 2 wire start generators

Installation, Service and Parts List Series 56,800 for Class I & II, Division 2 Manual Adjust Brakes

Instruction Bulletin Dual Sub-Feed Circuit Breaker and Adapter Kit Installation onto an NQ Panelboard Class 1640

CCP2-FLR1-21_ flange-rod operating mechanism

Removal/installation instructions for Series NRX (IZMX) drawout levering (racking) mechanism

Installation Manual. E-design A Transfer Switches A

Series C, F-frame molded case circuit breaker, 125A, Three-pole, Thermal magnetic trip. Thermal magnetic

Cutler-Hammer. Molded Case Circuit Breakers Amperes F-Frame. January 2001

Engine Generator Circuit Breakers

Rocker Lever Assembly

Florham Park, NJ USA Call (ASCO) for sales or service

Digitrip Retrofit System for BBC LKD 8 Breakers

Catalog Number Identification with Elements Explained

Parts Manual. Transfer Switch. OTPCB (Spec A) 150/225/260 Amps. English Original Instructions (Issue 4)

CM52 Network Protector with Arc Flash Reduction Module

Parts Manual. Transfer Switch. OTPCC (Spec A) 300/400/600 Amps. English Original Instructions (Issue 4)

www. ElectricalPartManuals. com ltciil Cutler-Hammer A WARNING

Operator s Manual Series ADTS Automatic Delayed Transition Transfer Switches, amps

Lighthouse Power Pedestals,

IM K IM K. Instructions for Cutler-Hammer Jockey Pump Controllers

O & M Manual for the EGSU Automatic Transfer Switch with RTC-100 Control and Integral Loadcenter-100 Amp

SECTION ENCLOSED SWITCHES AND CIRCUIT BREAKERS

Digitrip Retrofit System for General Electric AKR/AKRU-6D/7D-30S Series Breakers

Operator s Manual Series ADTS Automatic Delayed Transition Transfer Switches 150 through 4000 amp. Rating Label. Nameplate A

600 D 220 E 230 J Hanover Road, Florham Park, New Jersey USA For sales or service call (ASCO)

Two-way cable interlock kit for Magnum fixed circuit breakers

Interchangeable Built-in Fixed thermal Adjustable thermal Magnetic Fixed Adjustable Adjustable Electronic RMS 7 LS LSI

Digitrip Retrofit System for Siemens-Allis RLX-1600 Breakers

Operation and Installation RDT-HFNA-0100B RDT-HFNC-0200A MPAC 300. Automatic Transfer Switches. Models: Electrical Controls: TP /07b

AUTOMATIC DUST COLLECTION FOR SMALL SHOPS INSTRUCTIONS GG500C MOTOR CONTACTOR WITH THERMAL PROTECTION 220VAC COIL

PowerWorx Power Distribution Products Select Series Circuit Breaker for ±24 or ±48 Vdc User Manual

MODEL HM A01

2.3. Molded Case Circuit Breakers. Series C. Accessories Selection Guide and Ordering Information

Mipco Connections for Refrigerated Containers. No One Does It Like Mipco. The Mipco. Advantage. Reliability. Safety. Easy Installation & Service

Transcription:

Installation Instructions for JDB, JD, HJD, JDC, JW HJW, JWC Circuit Breakers and Molded Case Switches WARNING DO NOT ATTEMPT TO INSTALL OR PERFORM MAINTENANCE ON EQUIPMENT WHILE IT IS ENER- GIZED. DEATH, SEVERE PERSONAL INJURY, OR SUBSTANTIAL PROPERTY DAMAGE CAN RESULT FROM CONTACT WITH ENERGIZED EQUIPMENT. ALWAYS VERIFY THAT NO VOLTAGE IS PRESENT BEFORE PROCEEDING WITH THE TASK, AND ALWAYS FOLLOW GENERALLY ACCEPTED SAFE- TY PROCEDURES. CUTLER-HAMMER IS NOT LIABLE FOR THE MISAP- PLICATION OR MISINSTALLATION OF ITS PROD- UCTS. The user is cautioned to observe all recommendations, warnings, and cautions relating to the safety of person- nel and equipment as well as all general and local health and safety laws, codes, and procedures. The recommendations and information contained herein are based on Cutler-Hammer experience and judgment, but should not be considered to be all-inclusive or covering every application or circumstance which may arise. If any questions arise, contact Cutler-Hammer for further information or instructions. 1. INTRODUCTION General Information The J-frame Series C circuit breaker (Figure 1-1) types JD, JDB, HJD, and JDC are 600 Vac maximum rated devices with inter changeable thermal-magnetic trip units rated 250A maximum continuous current. Circuit breaker types JW, HJW, and JWC are 660 Vac maximum rated devices using interchangeable adjustable thermal/adjustable magnetic or electronic trip units rated up to 250A continuous current. The type JDB noninterchangeable trip circuit breaker is rated 600 Vac maximum with a maximum continuous current rating of 250A. Refer to Table 1-1 for all available trip unit rat- Table 1-1 Available Trip Unit Ratings Circuit Breaker Types Trip Unit Types Thermal-Magnetic Amperes I n Fixed Adjustable Adjustable Thermal Thermal 1 Magnetic of I 2 n JDB 70 5 to 10 JD 90 HJD 100 JDC JW 125 100-125 HJW 150 125-160 JWC 175 200 160-200 225 250 200-250 Figure 1-1 J-Frame Model D Series C Circuit Breaker with JT Trip Unit Installed 1 2 Not UL listed. For adjustable thermal trip units, the magnetic setting is a multiple of the maximum thermal setting.

Page 2 Thread-Forming Screws ings. Model D circuit breakers are listed in accordance with Underwriters Laboratories, Inc. Standard UL489 and satisfy the (P1) requirements of the International Electrotechnical Commission Recommendations No. IEC 157-1 Model W circuit breakers satisfy the requirements of IEC 947-2. Molded case switches are listed in accordance with UL 489. This instruction leaflet (IL) gives procedures for installation and field testing of J-frame Series C circuit breakers. For this publication, the term circuit breaker shall also include the molded case switch. 2. INSTALLATION Pan Head Screws Figure 2-1 Cover Mounting Hardware The installation procedure consists of inspecting the circuit breaker and, as applicable, installing the trip unit, accessories, interphase barriers and terminals; mounting the circuit breaker; connecting the line and load conductors; torquing terminals; and attaching terminal shields. Circuit breaker frames, trip units, accessories, mounting hardware, and unmounted terminals may be supplied in separate packages. To install the circuit breaker, perform the following steps. On/ Off/ JDB circuit breakers are factory sealed for reverse feed applications under UL489. UL requires that internal accessories be installed at the factory in this type of circuit breaker. For hardware conversion kits and handle mechanisms required to replace existing Cutler-Hammer circuit breakers. If required, internal accessory installation in any type of circuit breaker should be done before the circuit breaker is mounted and connected. Refer to individual accessory instruction leaflets. Circuit breaker mounting hardware is supplied separately. Screw,.190-32 x 3.13 Inch, Pan Head, Cross-Recessed. Screw, No. 8 x 1.88 Inch, Pan Head, Cross-Recessed, Thread Forming. Screw, No. 6 x 1.50 Inch, Pan Head, Cross-Recessed, Thread Forming (used with 4 Pole Only) Note: Hatched lines show additional pole and screws for 4-pole circuit breaker. Figure 2-2 Cover Screw Installation Positions 2-1. Make sure that the circuit breaker frame is suitable for the intended installation by comparing nameplate data with existing ratings and system requirements. Inspect the circuit breaker for completeness, and check for damage before mounting. Uninstalled cover mounting hardware is supplied in a plastic bag with the circuit breaker frame. (See Figure 2-1) 2-2. Remove installed cover screws and cover.

Page 3 Terminal Connectors TA250KB Terminal Collar before installation of the conductors, the terminal mounting screw can be checked or retightened through the terminal when the conductor screw is removed. When using terminal (Catalog No. T250KB), secure the terminal to the circuit breaker using screw and nut. Torque to 7-9 lb.-in (0.8-1.0 N.m). Collar WARNING Flat-Head Screw Nut T250KB Terminal Socket Screw THE VOLTAGES IN ENERGIZED EQUIPMENT CAN CAUSE DEATH OR SEVERE PERSONAL INJURY. BEFORE MOUNTING THE CIRCUIT BREAKER IN AN ELECTRICAL SYSTEM, MAKE SURE THERE IS NO VOLTAGE PRESENT WHERE WORK IS TO BE PER- FORMED. SPECIAL ATTENTION SHOULD BE PAID TO REVERSE FEED APPLICATIONS TO ENSURE NO VOLTAGE IS PRESENT. Figure 2-3 Terminal Installation The circuit breaker handle must be in the tripped or OFF position to remove the cover. Instructions for installing the trip unit accessories are supplied with the devices. 2-3. If not already installed, mount trip unit and accessories (if required) in circuit breaker frame. CAUTION WHEN REMOVED AND REINSTALLED, THREAD- FORMING SCREWS WILL TRY TO REFORM THE THREADS IN THE BASE. CARE SHOULD BE TAKEN EVERY TIME A THREAD-FORMING SCREW IS USED TO ENSURE THE SCREW STARTS IN THE ORIGINAL THREADS. DAMAGED THREADS CAN RESULT IN IMPROPER CIRCUIT BREAKER COVER RETENTION. 2-4. Install cover, and secure with pan-head screws followed by threadforming screws, as shown in Figure 2-2. Torque cover screws to 18-23 lb-in (2-2.6 N.m.). 2-5. If not already installed, mount terminals as shown in Figure 2-3. When using terminal (Catalog No. TA250KB), secure the terminal to the circuit breaker using a 1/8-inch socket wrench and torque to 6-8 lb.-ft (8-11 N.m). After mounting the circuit breaker and Depending on the equipment configuration, the circuit breaker can be mounted using different styles of hardware. The following steps describe how to mount the circuit breaker using standard hardware. When special hardware is needed (for example, with the electrical operator), the instruction leaflet describing the accessory also describes the special mounting arrangements. 2-6. To mount the circuit breaker, perform the following steps: a. For individual surface mounting, drill mounting panel using the drilling plan shown in Figure 2-4. For panelboard mounting, only load end support mounting holes are required. For deadfront cover applications, cut out cover to correct escutcheon dimensions. (See Figure 2-5) b. If circuit breaker includes factory- or field-installed internal accessories, make sure that accessory wiring can be reached when the circuit breaker is mounted. Labels with accessory connection schematic diagrams are provided on the side of the circuit breaker. A note should be made of the diagrams if the labels cannot be seen when the circuit breaker is mounted.

Page 4 2, 3 Pole Breakers 4-Pole Breakers 4.078 (103.58) 1.375 (34.37).688 (14.47).250-20 (M6-1.0) Tap (6 Holes) 2.750 (69.85) 1.375 (34.37).344R (8.74) 3.938 (100.02) 1.562 (39.67) 2.922 (74.22).781 (19.84) Circuit Breaker Handle CL CL Circuit Breaker Handle 7.250 (184.15).250-20 (M6-1.0) Tap (4 Holes).188R (4.77).781 3.50 (88.90).875 (22.22) Circuit Breaker Handle CL CL Circuit Breaker Handle CL Figure 2-4 Circuit Breaker Mounting Bolt Drilling Plans Figure 2-5 Circuit Breaker Escutcheon Dimensions c. Position circuit breaker on mounting surface. d. Install circuit breaker mounting screws and washers. Tighten screws firmly, but do not exceed 28 poundinches (3 N.m.). CAUTION WHEN ALUMINUM CONDUCTORS ARE USED, THE APPLICATION OF A SUITABLE JOINT COMPOUND IS RECOMMENDED TO REDUCE THE POSSIBILITY OF TERMINAL OVERHEATING. OVERHEATING CAN CAUSE NUISANCE TRIPPING AND DAMAGE TO THE CIRCUIT BREAKER. 2-7. Connect line and load conductors and accessory leads. 2-8. If required, install terminal shield on circuit breaker cover with mounting screws provided. 2-9. After the circuit breaker is installed, check all mounting hardware and terminal connecting hardware for correct torque loading. Torque values for line/load terminals are given in Table 2-1 and on the circuit breaker nameplate. 3. MANUAL OPERATION, AND THERMAL- MAGNETIC ADJUSTMENT Manual Operation Manual operation of the circuit breaker is controlled by the circuit breaker handle and the PUSH-TO-TRIP button in the trip unit. The circuit breaker handle has three positions, two of which are shown on the cover with raised lettering to indicate ON and OFF. On the sliding handle barrier, ON, OFF, and trip are also shown by a color-coded strip for each circuit breaker handle position: red for ON, white for tripped, and green for OFF. ON/OFF is also shown with the international symbols 1/0. (See Figure 3-1) Circuit Breaker Reset After an automatic or accessory initiated trip, or a manual Push-to-Trip operation, the circuit breaker is reset by moving the circuit breaker handle to the extreme OFF position. In the event of a thermal trip in a thermal magnetic type trip unit, the circuit breaker cannot be reset until the thermal element in the trip unit cools.

Page 5 Handle Position Indicator Color Red White Green ON TRIP OFF (Reset) Adjustment Buttons On/ ON TRIP OFF (Reset) Off/ Figure 3-2 Trip Unit Magnetic Trip Adjustment Buttons International Symbols ON OFF Thermal-Magnetic Trip Unit Adjustment Button (3 Places) Figure 3-1 Circuit Breaker Manual Controls Push-To-Trip Button Table 2-1 Terminal Types Terminal Terminal Screw AWG Metric Wire Torque Cat. No. Material Head Wire Wire Type Value Body Type Range Range lb-in (N.m.) T250KB Stainless Socket 4-350 MCM 25-185 Cu Only 180 (20) Steel TA250KB Aluminum Socket 4-350 MCM 25-185 Cu/AI 275 (31) No circuit breaker should be reclosed until the cause of trip is known and the situation rectified. PUSH-TO-TRIP Button The PUSH-TO-TRIP button checks the circuit breaker tripping function and is used to periodically exercise the operating mechanism in thermal-magnetic trip units. The button is designed to be operated by a small screwdriver. Thermal-Magnetic Trip Unit Adjustment The magnetic element of each pole of the trip unit can be adjusted by rotating the adjustment buttons on the front face of the trip unit with a screwdriver. The buttons have several settings, as indicated on the nameplate, with values in multiples of the trip unit ampere rating (I n ). (See Figure 3-2) To adjust the setting, rotate each button clockwise until arrow on button points to desired setting. 4. INSPECTION AND FIELD TESTING Series C molded case circuit breakers are designed to provide years of almost maintenance-free operation. The following procedure describes how to inspect and test a circuit breaker in service. Inspection Circuit breakers in service should be inspected periodically. The inspection should include the following checks (4-1 through 4-8): WARNING THE VOLTAGES IN ENERGIZED EQUIPMENT CAN CAUSE DEATH OR SEVERE PERSONAL INJURY. BEFORE INSPECTING THE CIRCUIT BREAKER IN AN ELECTRICAL SYSTEM, MAKE SURE THERE IS NO VOLTAGE PRESENT WHERE WORK IS TO BE PERFORMED. SPECIAL ATTENTION SHOULD BE PAID TO REVERSE FEED APPLICATIONS TO ENSURE NO VOLTAGE IS PRESENT.

Page 6 CAUTION MAKE SURE THAT CLEANING AGENTS OR SOL- VENTS USED TO CLEAN THE CIRCUIT BREAKER ARE SUITABLE FOR THE JOB. SOME COMMER- CIAL CLEANING AGENTS WILL DAMAGE THE NAMEPLATES OR MOLDED PARTS. 4-1. Remove dust, dirt, soot, grease, or moisture from the surface of the circuit breaker using a lint-free dry cloth, brush, or vacuum cleaner. Do not blow debris into circuit breaker. If contamination is found, look for the source and eliminate the problem. 4-2. Switch circuit breaker to ON and OFF several times to be sure that the mechanical linkages are free and do not bind. If mechanical linkages are not free, replace circuit breaker. 4-3. With the circuit breaker in the ON position, press the PUSH TO-TRIP button to mechanically trip the circuit breaker. Trip, reset, and switch circuit breaker ON several times. If mechanism does not reset each time the circuit breaker is tripped, replace the circuit breaker. 4-4. Check base, cover, and operating handle for cracks, chipping, and discoloration. Circuit breakers should be replaced if cracks or severe discoloration is found. 4-5. Check terminals and connectors for looseness or signs of overheating. Overheating will show as discoloration, melting, or blistering of conductor insulation, or as pitting or melting of conductor surfaces due to arcing. If there is no evidence of overheating or looseness, do not disturb or tighten the connections. If there is evidence of overheating, terminations should be cleaned or replaced. Before reenergizing the circuit breaker, all terminations and cable should be refurbished to the condition when originally installed. 4-6. Check circuit breaker mounting hardware, Tighten if necessary. 4-7. Check area where circuit breaker is installed for any safety hazards, including personal safety and fire hazards. Exposure to certain types of chemicals can cause deterioration of electrical connections. 4-8. The operation of circuit breakers with electronic trip units can be field-tested periodically using the Seltronic test kit. Field Testing Any field testing should be done in accordance with applicable NEMA Standard.

Page 7

Page 8 Eaton Electrical, Inc. 1000 Cherrington parkway Moon Township, PA 15108-4312 USA Tel: 1-800-525-2000 www.eatonelectrical.com 2010 Eaton corporation All Rights Reserved Printed USA/TQC Style 6632C43H08 Printed in U.S.A. /TQC Effective January 2010