Type NR oil switch installation and operation instructions

Similar documents
COOPER POWER SERIES. Testing a motor capacitor on a voltage regulator procedure instructions. Voltage Regulators MN225064EN

High-voltage primary bushings installation instructions

Effective March 2015 Supersedes S August 2012

Effective June 2016 New Issue

COOPER POWER SERIES. K-Limiter back-up current-limiting fuse installation instructions. Fusing Equipment MN132010EN

COOPER POWER SERIES. 200 A loadbreak junction 15 and 25 kv class installation instructions. Loadbreak Connectors MN650015EN

COOPER POWER SERIES. UltraSIL polymer-insulated D-73P disconnect switches installation instructions. Switches MN008004EN

COOPER POWER SERIES. Current-Limiting Type NXC (C-Rated) Fuse Installation Instructions. Fusing Equipment MN132014EN

COOPER POWER SERIES. High-voltage primary bushings installation instructions. OEM Equipment MN800008EN

Effective November 2016 Supersedes September 1998 (S )

COOPER POWER SERIES. QD5 Quik-Drive tap-changer reversing neutral stationary contact asssembly kit A26 installation instructions

COOPER POWER. SERIES ELF Current-Limiting Dropout Fuse Installation Instructions. Fusing Equipment MN132028EN. Pull ring. Housing

COOPER POWER SERIES. 600 A 15, 25, and 35 kv Class Cleer Loadbreak Bushing Insert Installation Instructions. Loadbreak/Deadbreak Connectors MN650016EN

COOPER POWER SERIES. Pad-mounted Switchgear MN285019EN. Effective March 2017 Supersedes February 2007 (S )

COOPER POWER SERIES. Edison Modular Fuse (EMF) Installation Instructions. Fusing Equipment MN132031EN

COOPER POWER SERIES. ELSG Full-Range Current-Limiting Fuse Re-Fusing Instructions. Fusing Equipment MN132017EN

COOPER POWER. SERIES CMU Medium voltage power fuse installation instructions. Fusing Equipment MN132032EN

COOPER POWER SERIES. S.T.A.R. Hot line voltage indicator installation instructions. Fault Indicators MN320011EN. Indicator boot.

COOPER POWER SERIES. Screened Separable Connectors MN650023EN. Effective October 2016 Supersedes March 2012 (IS )

COOPER POWER SERIES. S.T.A.R. type LVR faulted circuit indicator installation instructions. Fault Indicators MN320005EN

COOPER POWER SERIES. HX-CB loadbreak fuse cutout installation instructions. Fusing Equipment MN132011EN

COOPER POWER SERIES. Screened Separable Connectors MN650024EN. Effective October 2016 Supersedes March 2012 (IS )

COOPER POWER SERIES. 200 A Fused Loadbreak Elbow Connector Replacement Fuse Installation Instructions. Fusing Equipment MN132021EN

COOPER POWER SERIES. RTE EL-BAY-O-NET FUSE Re-Fusing Instructions. Fusing Equipment MN132024EN

COOPER POWER SERIES. Expulsion fuse installation instructions. Capacitors MN230005EN. Effective November 2016 Supersedes November 2001 (S )

COOPER POWER SERIES. KA1169R Closing Coil Transfer-Switch Accessory Operation. Reclosers MN280069EN

COOPER POWER SERIES. Dielectric grease application to recloser cable instructions. Reclosers MN280070EN

Effective November 2016 Supersedes February 2012 (S )

COOPER POWER SERIES. KA662R tank-lifting windlass assembly and installation instructions. Recloser Mountings MN280071EN

COOPER POWER SERIES. 600 A 15/25 kv class T-OP II connector assembly installation instructions. Deadbreak Apparatus Connectors MN650048EN

COOPER POWER SERIES. Types 4H single-phase and 6H three-phase vacuum interrupter conversion kits. Reclosers MN280014EN

COOPER POWER SERIES. KA716L7001 adjustable control valve kit for Types L, E, 4E, V4E, and V4L reclosers installation and adjustment instructions

Effective May 2017 Supersedes January 2003 (S )

Effective May 2017 Supersedes December 2004 (S )

COOPER POWER SERIES. Electronic control battery testing, charging, and replacement instructions. Reclosers MN280074EN

COOPER POWER SERIES. Types D and DV recloser installation instructions. Reclosers MN280030EN

COOPER POWER SERIES. 600 A 15 kv and 25 kv class BT-TAP connector system installation instructions. Deadbreak Apparatus Connectors MN650004EN

COOPER POWER SERIES. Mercury switch to microswitch retrofit kit KA349WE installation instructions. Reclosers MN280022EN

COOPER POWER SERIES. 600 A 15/25 kv class BOL-T and separable splice connector assembly installation instructions

COOPER POWER SERIES. KA146W5 single pole-mounting hanger; KA146W2 tank lifting windlass assembly and installation instructions. Reclosers MN280039EN

COOPER POWER SERIES. Quick Connect Assembly (QCA) Retrofit Kit, General Electric Installation Instructions. Voltage Regulators MN225075EN

COOPER POWER SERIES. 600 A 35 kv class BT-TAP connector system installation instructions. Deadbreak Apparatus Connectors MN650003EN

S Voltage Regulators GENERAL. Contents. Acceptance and Initial Inspection. Handling and Storage. Standards

COOPER POWER SERIES. Surge arrester interchangeable fuse cutout combination installation instructions. Surge Arresters MN235004EN

This Kit Is for Use with Types RE, RVE, WE, WVE, VWE, VWVE27, and VWVE38 Reclosers.

COOPER POWER SERIES. Fused loadbreak elbow connector installation instructions. Loadbreak Apparatus Connectors MN650014EN

S Voltage Regulators PRODUCT INFORMATION GENERAL. Contents. Acceptance and Initial Inspection. Handling and Storage

S Voltage Regulators GENERAL. PRODUCT INFORMATION Introduction. Contents. Acceptance and Initial Inspection. Handling and Storage.

S Fault Indicators. S.T.A.R. Type TPR Faulted Circuit Indicator Installation Instructions. Contents INSTALLATION PROCEDURES

COOPER POWER SERIES. Manually-Operated M-Force Switch Installation and Operation Instructions. Switches and Disconnects MN008003EN

S Voltage Regulators PRODUCT INFORMATION GENERAL. Contents. Acceptance and Initial Inspection. Handling and Storage.

COOPER POWER SERIES. Metal-enclosed capacitor banks installation instructions. Power Capacitors MN230010EN

COOPER POWER SERIES. Metal-enclosed, pad-mounted capacitor banks installation instructions. Power Capacitors MN230009EN

Figure 1. Kearney Type HX cutout.

COOPER POWER SERIES. Types VWE, VWVE27, VWVE38X, WE, WVE27, and WVE38X; threephase electronically controlled; installation and operation instructions

S Contents. Applicable to Serial Numbers A101 and above or beginning with CP57.

Factory Authorized Mechanism Enhancement (FAME)

TRINETICS CSD SERIES OIL SWITCH INSTALLATION INSTRUCTIONS

COOPER POWER SERIES. Externally fused block banks installation instructions. Capacitors MN230004EN

COOPER POWER SERIES. Instructions for oil-filled, single-phase overhead distribution transformers. Distribution Transformers MN201003EN

CCP2-FLR1-21_ flange-rod operating mechanism

3-way multi-family drawout cable interlock kit - type 32 - RF

Removal/installation instructions for Series NRX (IZMX) drawout levering (racking) mechanism

Instructions for VCP-W Simple Electrical Ground & Test Device (SEG&TD) with simplified interlock scheme - bottom terminal set version

Installation and removal instructions for Series NRX RF fixed breaker three-way Type 32 cable interlock kit

Installation Instructions for Interlocking Trip Indicator with Remote Reset for Magnum Low Voltage Circuit Breakers

KFE10010-E. Reclosers. Contents. Type KFVE and KFVME (27kV) Bus Bar Kit KRK710-1 Installation Instructions. Cooper Power Systems

Two-way cable interlock kit for Magnum fixed circuit breakers

Two-way cable interlock kit for Magnum drawout circuit breakers

O & M Manual for the EATON Generator Ready Loadcenter

COOPER POWER SERIES. VFI tester operating instructions. Underground Distribution Switchgear MN285001EN

Effective October 2016 Supersedes January 2014 (S )

Eaton s Cooper Power Systems

Reprogramming guide. Power Defense ICCB. Instructional Leaflet IL EN WARNING WARNING. Instructions apply to:

600 A 15 kv class Cleer loadbreak connector system

S Voltage Regulators. Contents. QD3 Quik-Drive Voltage Regulator Tap-Changer Manual. Figure 1B. QD3 Tap-changer. Figure 1A. QD3 Tap-changer.

Instruction Booklet for the Installation, Operation and Maintenance of Type 5-15 kv VCP-WG Vacuum Circuit Breaker 4000A MiniMod

ELB ELB

Installation Instructions for KPS and KPH Circuit Breakers and Molded Case Switches

600 A 28 kv class Cleer loadbreak connector system

S Fault Interrupters. Type CI; Three-Phase Installation and Operation Instructions. Service Information

COOPER POWER SERIES. Type MOST Fluid-Insulated Switchgear; Installation, Operation, and Maintenance Instructions

Low voltage bushings for pad-mounted distribution transformers Technical information guide

600 A 35 kv class BT-TAP deadbreak connector

II DISTRIBUTION & SUBSTATION TYPE C

GWI Rev. 1 October 2007 Supersedes Rev. 0 Dated February 2004

Raychem CSJA Safety Instructions. Safety Instructions. Customer Service. Kit Contents. Installation Instructions

Hubbell has a policy of continuous product improvement. Please visit hubbellpowersystems.com to confirm current design specifications.

Installation Instructions for R-Frame G-Series (RG) 310+ Trip Unit

TVSS Installation for RLCM/CHGENLC, RLCU, and CHGEN ATSs

www. ElectricalPartManuals. com Instructions for Field Testing of Ground Fault Systems Utilizing Cutler-Hammer Magnum DS Circuit Breakers

Edison modular fuse, vault application products

38 kv Bay-O-Net Cartridge and Fuse Assemblies Certified Test Report

Instruction Booklet IB E. Contents

COOPER POWER SERIES. Type PST Model-9 automatic source transfer switchgear with ist control installation, operation, and maintenance instructions

M-Force three-phase switch

COOPER POWER SERIES. RVAC Fluid-insulated Vacuum Switchgear; Installation, Operation, and Maintenance Instructions. Switchgear MN285005EN

Installation Instructions For Motor Control Center (MCC) Units

ELB ES. Product Installation Instructions

Vacuum Circuit Breaker (Vehicle)

Transcription:

Oil Switches Effective October 2013 Supersedes S260-20-1, March 2002 S230-60-1 Type NR oil switch installation and operation instructions

DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITY The information, recommendations, descriptions and safety notations in this document are based on Eaton Corporation s ( Eaton ) experience and judgment and may not cover all contingencies. If further information is required, an Eaton sales office should be consulted. Sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eaton selling policies or other contractual agreement between Eaton and the purchaser. THERE ARE NO UNDERSTANDINGS, AGREEMENTS, WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY, OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES. ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON. THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES. In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability or otherwise for any special, indirect, incidental or consequential damage or loss whatsoever, including but not limited to damage or loss of use of equipment, plant or power system, cost of capital, loss of power, additional expenses in the use of existing power facilities, or claims against the purchaser or user by its customers resulting from the use of the information, recommendations and descriptions contained herein. The information contained in this manual is subject to change without notice. ii Type NR oil switch installation and operation instructions S230-60-1 October 2013 www.cooperpower.com

Contents safety information Safety Information...iv product information Introduction... 1 Acceptance and Initial Inspection.... 1 Handling... 1 Storage... 1 Ratings and specifications Ratings and Specifications... 2 Installation Procedure Check-Out Procedure... 3 Main Wiring... 3 Control Wiring.... 3 Three-Wire Control... 4 Wiring Diagram.... 4 Switch operation Electrical Operation...5 Manual Operation...5 dimensions and weights Dimensions and Weights..... 6 Maintenance information Maintenance Requirements... 7 Maintenance Manual... 7 Frequency of Maintenance.... 7 Replacement Parts... 7 Factory Authorized Service Centers.... 7 Type NR oil switch Installation and operation instructions S230-60-1 October 2013 www.cooperpower.com iii

! SAFETY FOR LIFE Safety for life! SAFETY FOR LIFE Eaton s Cooper Power Systems products meet or exceed all applicable industry standards relating to product safety. We actively promote safe practices in the use and maintenance of our products through our service literature, instructional training programs, and the continuous efforts of all Eaton s Cooper Power Systems employees involved in product design, manufacture, marketing, and service. We strongly urge that you always follow all locally approved safety procedures and safety instructions when working around high voltage lines and equipment, and support our Safety For Life mission. Safety information The instructions in this manual are not intended as a substitute for proper training or adequate experience in the safe operation of the equipment described. Only competent technicians who are familiar with this equipment should install, operate, and service it. A competent technician has these qualifications: Is thoroughly familiar with these instructions. Is trained in industry-accepted high and low-voltage safe operating practices and procedures. Is trained and authorized to energize, de-energize, clear, and ground power distribution equipment. Is trained in the care and use of protective equipment such as flash clothing, safety glasses, face shield, hard hat, rubber gloves, clampstick, hotstick, etc. Following is important safety information. For safe installation and operation of this equipment, be sure to read and understand all cautions and warnings. Hazard Statement Definitions This manual may contain four types of hazard statements: DANGER Indicates a hazardous situation which, if not avoided, will result in death or serious injury. Indicates a hazardous situation which, if not avoided, could result In death or serious injury. CAUTION Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury. Caution: Indicates a hazardous situation which, if not avoided, could result in equipment damage only. Safety instructions Following are general caution and warning statements that apply to this equipment. Additional statements, related to specific tasks and procedures, are located throughout the manual. DANGER Hazardous voltage. Contact with hazardous voltage will cause death or severe personal injury. Follow all locally approved safety procedures when working around high- and low-voltage lines and equipment. G103.3 Before installing, operating, maintaining, or testing this equipment, carefully read and understand the contents of this manual. Improper operation, handling or maintenance can result in death, severe personal injury, and equipment damage. G101.0 This equipment is not intended to protect human life. Follow all locally approved procedures and safety practices when installing or operating this equipment. Failure to comply can result in death, severe personal injury and equipment damage. G102.1 Power distribution and transmission equipment must be properly selected for the intended application. It must be installed and serviced by competent personnel who have been trained and understand proper safety procedures. These instructions are written for such personnel and are not a substitute for adequate training and experience in safety procedures. Failure to properly select, install or maintain power distribution and transmission equipment can result in death, severe personal injury, and equipment damage. G122.3 iv Type NR oil switch Installation and operation instructions S230-60-1 October 2013 www.cooperpower.com

Product information Introduction Service Information S230-60-1 provides installation instructions, operation information and testing procedures for the Type NR oil switch. The information contained in this manual is organized into the following major categories; Safety Information, Product Information, Ratings and Specifications, Installation Procedure, Switch Operation, Dimensions and Weights, and Maintenance Information. Refer to the Table of Contents for page numbers. Read this manual first Read and understand the contents of this manual and follow all locally approved procedures and safety practices before installing or operating this equipment. Additional information These instructions cannot cover all details or vari ations in the equipment, procedures, or process described, nor provide directions for meeting every possible contingency during installation, operation, or maintenance. When additional information is desired to satisfy a problem not cov ered sufficiently for the user's purpose, please contact your Cooper Power Systems representative. Handling and storage If the switch is to be stored for an appreciable time before installation, provide a clean, dry storage area. Locate the switch so as to minimize the possibility of mechanical damage, particularly to the bushings. Description of operation The Type NR oil switch is a single-phase device for use on distribution circuits. Compact design makes this switch ideal for use on capacitor banks, especially pole-top installations. This switch is electrically operated and can be controlled by time switches, voltage- or current-sensitive control devices, or by single-pole, double-throw switches. An operating handle, which also serves as a contact position indicator, is provided for manually opening and closing the switch. Check switch ratings prior to installation The switch must be applied within its specified ratings. Check data plate ratings and compare with the system characteristics at the point of application, prior to installation. Tables 1 and 2 list the specifications and ratings for the Type NR oil switch. Quality standards ISO 9001 Certified Quality Management System Acceptance and initial inspection Each switch is completely assembled, inspected, tested and adjusted at the factory and is filled to the correct level with insulating oil. It is in good condition when accepted by the carrier for shipment. Upon receipt of a switch: 1. Inspect the switch thoroughly for damage and loss of parts or oil incurred during shipment. If damage or loss is discovered, file a claim with the carrier immediately. 2. Check for oil leakage and tighten all bolts that may have loosened during shipment, especially the bolts attaching the head to the tank. Type NR oil switch installation and operation instructions S230-60-1 October 2013 www.cooperpower.com 1

Ratings and specifications Table 1. Electrical Data (Control) Description Rating Nominal operating voltage (50/60 Hz only) (Vac) 120 240 Operating voltage range (Vac) 95 130 190 260 Closing-motor current (amp) 1.9.7 Switch response time, opening (sec) 4.0 4.0 Switch response time, closing (sec) 0.5 0.5 Table 2. Voltage and Current Ratings Description Standard 15 kv with 17" Creepage 15 kv with 125 kv BIL 22 kv Maximum Design Voltage, kv 15.0 15.0 15.0 22.0 Nominal Operating Voltage, kv 2.4-14.4 2.4-14.4 2.4-14.4 20.0 Basic Insulation Level (BIL), kv 95 95 125 125 60 Hertz Withstand Voltage, kv Dry, One Minute Wet, Ten seconds 35 30 35 30 42 36 60 50 Continuous Current Rating, Amps 200 200 200 60 Load Interrupting Ability (Inductive), Symmetric Amps 75-100% power factor 50-75% power factor < 50% power factor 200 100 50A 200 100 100A 200 100 50A 60 60 60 Maximum Capacitive Current, Amps (parallel bank-max) 200 200 200* 60* High Frequency Transient Current, Amps 12000 12000 12000 12000 Transient Frequency, Hz 6000 6000 6000 6000 High Frequency Damping Factor.40-.55.40-.55.40-.55.40-.55 Momentary Rating, Amps asym. 9000 9000 9000 9000 Short Time Current Amps 1/2 second,sym. 1 second, sym. 6000 4500 6000 4500 6000 4500 6000 4500 Close and Latch Rating, Amps asym. 9000 9000 9000 9000 *The 125 kv BIL switch and the 22.0 kv switch are rated for single bank switching only. 2 Type NR oil switch installation and operation instructions S230-60-1 October 2013 www.cooperpower.com

Installation procedure Do not operate this equipment if energized parts are not immersed in dielectric fluid. Operation when parts are not properly immersed in dielectric fluid may result in internal flashovers that will damage the equipment and can cause death or severe personal injury. G104.4 caution This equipment relies on dielectric fluid to provide electrical insulation between components. The dielectric strength of the fluid must be checked on a regular basis, as part of the routine maintenance inspection, to ensure that it is at or above minimum dielectric requirements. Use of this equipment with dielectric fluid that does not meet minimum requirements can result in internal flashovers that will damage the equipment and can cause personal injury. G107.3 Check-out procedure 1. Untank the switch. When untanking the switch for inspection, remove the four bolts that secure the tank and head casting. Trip the switch and carefully lift the mechanism. 2. Check oil level. Before installing the switch, check for proper oil level. With the mechanism removed from the tank, the oil level should be even with the top of the tank liner. 3. Test oil dielectric strength. If the switch has been stored for some time or is being relocated, perform a dielectric test on the oil. Refer to Reference Data R280-90-1, Oil Specifications and Tests for test procedures and test values. Oil that does not meet specifications should be replaced. Approximately 1-1/2 gallons are required. 4. Replace head casting and mechanism in tank. A. Wipe clean the O-ring type gasket and the tank gasket seat. B. Place head and mechanism assembly into the tank. The head can be rotated to any position except where the actuator housing or manual operating handle interfere with the tank mounting bracket. C. Position the four head bolts, with fasteners under the tank lip, and tighten alternately (torque to 10-14 ft lbs). 5. Test mechanical operation. CLOSE and OPEN the switch contacts manually using the yellow operating handle. Confirm that the contacts have closed and opened by listening for the sound of operation or by a continuity check between the switch bushings. Leave the contacts in the open position. 6. Check data plate. Make sure that ratings on the data plate are correct for the planned installation. 7. Mount the switch. The switch can be direct pole mounted with a through-bolt. Mounting hardware is also available for substation and cross-arm pole mounting. Dimensions to determine mounting position and clearances are shown in Figures 5, 6 and 7. Main wiring 1. Ground the switch. Make the ground connection to the ground connector (located 3 from the bottom of the tank). 2. Make line connections. Connect the primary leads to the switch bushing terminals. The universal clamp type terminals accommodate No. 8 solid through 2/0 stranded conductor. Control wiring Connections Connections to the actuating mechanism are made at a terminal strip located in the actuator housing. Wiring access is through a 1-1/16 diameter opening in the bottom of the housing. Receptacles are supplied with 5-pin, 3-conductor or 6-pin, 6-conductor configurations as standard from the factory. The terminal strip is factory wired to an accessory receptacle mounted in the bottom of the housing. Wiring and receptacle combinations are available to accommodate various combinations of accessories. Mating plugs for the accessory receptacles must be ordered separately. Maximum cable and wire sizes accommodated by the plugs are tabulated in Table 3. Pin orientation diagrams for the accessory receptacles are shown in Figure 1. Table 3. Control Wiring Specifications Accessory Plug Catalog Number This equipment is not intended to protect human life. Follow all locally approved procedures and safety practices when installing or operating this equipment. Failure to comply can result in death, severe personal injury, and equipment damage. G102.1 Hazardous voltage. Solidly ground all equipment. Failure to comply can result in death, severe personal injury, and equipment damage. T223.2 Number of Pins Cable Range O.D. (in.) CCR010P1 5 0.437-0.562 12 CCR009P1 6 0.500-0.625 16 Maximum Wire Size AWG Type NR oil switch installation and operation instructions S230-60-1 October 2013 www.cooperpower.com 3

Wiring diagram Connection diagrams of switch actuators with various accessories wired for two- and three-wire control are shown in Figure 3. Green C Aux NC SW. NO Orange Blue Figure 1. Receptacle pin orientation. AC-White, DC-Black AC-Black, DC-Red SEL SW. Three-wire control The basic device for remote control of the Type NR oil switch is a single-pole, double-throw switch (three-wire control) supplied by the customer. Any manual switch, time switch, voltage-, current- or photo-electric controlled switch, or similar device can be used provided the control circuit is energized for a minimum of 4.5 seconds for each operation. A connection diagram for a standard three-wire control is shown in Figure 2. MOTOR NO NC C Red Black MOTOR AC-White, DC-Black AC-Black, DC-Red NO NC C SEL SW. Recaptacle (ACCY) KA121NR5 0 1 G 2 3 4 A B C D E Close Input Supply voltage Open Black Red Figure 3. Actuator wiring with various accessories connected. 0 1 G 2 3 4 NOTE: G=Ground 2=Close 3=Open Figure 2. Typical connection diagrams. 4 Type NR oil switch installation and operation instructions S230-60-1 October 2013 www.cooperpower.com

Three-wire control with holding switch If the controlling switch is energized for less than the required 4.5 seconds, a factory-installed holding switch accessory is required. However, the control circuit must be energized for at least one second for each operation to insure operation of the holding switch. A connection diagram for a three-wire control with a holding switch is shown in Figure 4. Switch operation Electrical operation The switch may be opened and closed electrically by applying rated control voltage to the proper terminals of the actuator terminal block. If the switch actuator does not respond to an electrical operating signal, it may be that the main switch contacts are not in synch with the electrical control. For example, if the switch is manually opened, an electrical OPEN signal must be transmitted to bring the control into synch with the switch contacts before an electrical CLOSE signal will close the switch. The converse is also true. Manual operation Never manually close this switch into a faulted line. The make-and-latch rating of the switch applies only when it is electrically operated. Closing a switch manually on a faulted line can result in death, severe personal injury, and equipment damage. G127.0 The switch may be manually opened by operating the yellow handle under the sleet hood. Figure 4. Three-wire control with holding switch. Type NR oil switch installation and operation instructions S230-60-1 October 2013 www.cooperpower.com 5

Dimensions and weights 5.62 5.62 2.75 2.75 13.88 13.88 #8 SOLID TO #2/0 STRD BUSHING TERMINAL CABLE RANGE GROUND CONNECTOR #10 SOLID TO #2 STRD 7.38 8.25 4.5 #8 SOLID TO #2/0 STRD BUSHING TERMINAL CABLE RANGE GROUND CONNECTOR #10 SOLID TO #2 STRD 7.88 8.25 4.5 12.00 SUPPORT LUG FOR 5/8 POLE BOLT 20.13 1.25 5.5 14.25 SUPPORT LUG FOR 5/8 POLE BOLT 1.25 5.5 22.38 8.0 2.0 10.75 1.25 4.75 2.0 10.75 1.25 1.5 8.0 4.75 Ø1.38 HOLE Ø7.12 Ø.44 HOLES (4) Ø1.06 OPENING FOR FACTORY-WIRED RECEPTACLE Ø1.38 HOLE Ø7.12 1.5 Ø.44 HOLES (4) Ø1.06 OPENING FOR FACTORY-WIRED RECEPTACLE Figure 5. Outline dimensions of 95 kv BIL Type NR oil switch with standard bushings, (15.0 kv Rating ONLY). Figure 6. Outline dimensions of 95 kv BIL Type NR oil switch with 17" creepage bushings, (15.0 kv Rating ONLY). 1.31 Table 4. Weight and Oil Capacity of Type NR Switch Net weight with oil 37 lbs. 5.62 Oil capacity 1-1/2 gal. 2.75 13.88 #8 SOLID TO #2/0 STRD BUSHING TERMINAL CABLE RANGE GROUND CONNECTOR #10 SOLID TO #2 STRD 8.25 12.63 1.2 4.5 14.5 13.3 SUPPORT LUG FOR 5/8 POLE BOLT 1.25 5.5 22.5 10.75 2.0 1.25 8.0 4.75 1.5 Ø1.38 HOLE Ø7.12 Ø.44 HOLES (4) Ø1.06 OPENING FOR FACTORY-WIRED RECEPTACLE Figure 7. Outline dimensions of 125 kv BIL Type NR oil switch (22.0 kv Rating standard bushings and 15.0 kv Rating optional bushings). 6 Type NR oil switch installation and operation instructions S230-60-1 October 2013 www.cooperpower.com

Maintenance information caution This equipment requires routine inspection and maintenance to ensure proper operation If it is not maintained, it can fail to operate properly. Improper operation can cause equipment damage and possible personal injury. G105.1 caution This equipment relies on dielectric fluid to provide electrical insulation between components. The dielectric strength of the fluid must be checked on a regular basis, as part of the routine maintenance inspection, to ensure that it is at or above minimum dielectric requirements. Use of this equipment with dielectric fluid that does not meet minimum requirements can result in internal flashovers that will damage the equipment and can cause personal injury. G107.3 Maintenance requirements All Type NR oil switches require routine inspection and maintenance to ensure proper operation. If the equipment is not adequately maintained, it may fail to operate properly. Frequency of maintenance Because this switch is applied under widely varying operating and climatic conditions, maintenance intervals are best determined by the user based on actual operating experience. Eaton's Cooper Power Systems recommends that the switch be inspected yearly and serviced as needed. In no case should the service interval, between periodic maintenance and inspection extend beyond 1200 operations. Replacement parts Replacement parts for the Type NR oil switch are available through the factory Service Department. To order replacement parts, refer to the applicable maintenance manual. Contact your Eaton's Cooper Power Systems sales representative for additional information and ordering procedures. Factory authorized service centers Factory authorized service centers are located throughout the continental United States to provide maintenance, repair, and testing services for Type NR oil switches. For further information, contact your Eaton's Cooper Power Systems representative. Maintenance manual Maintenance instructions for Type NR oil switch is provided in Service Information S230-60-8. Reference R280-90-1 provides information on oil specifications and tests. Type NR oil switch installation and operation instructions S230-60-1 October 2013 www.cooperpower.com 7

! SAFETY FOR LIFE Eaton 1000 Eaton Boulevard Cleveland, OH 44122 United States Eaton.com Eaton s Cooper Power Systems Business 2300 Badger Drive Waukesha, WI 53188 United States Cooperpower.com 2013 Eaton All Rights Reserved Printed in USA Publication No. S230-60-1 / October 2013 Eaton and Cooper Power Systems are valuable trademarks of Eaton, in the U.S. and other countries. You are not permitted to use these trademarks without the prior written consent of Eaton.