I I e k ill L ill. INDUSTRIAL DIGITAL EARTH LEAKAGE CIRCUIT BREAKER and 3 PHASE ROTATION TESTER BESANTEK BST-ELC01 INSTRUCTION MANUAL

Similar documents
3 PHASE TESTER & MOTOR ROTATION TESTER

MARTINDALE MARTINDALE IN2001/IN2003 INSULATION & CONTINUITY TESTERS INSTRUCTION MANUAL IN2001/IN2003 INSULATION & CONTINUITY TESTERS

IN1001/IN1003 ANALOGUE INSULATION & CONTINUITY TESTERS INSTRUCTION MANUAL IN1001/IN1003 ANALOGUE INSULATION & CONTINUITY TESTERS INSTRUCTION MANUAL

Digital Low Resistance Ohm Meter

Metrohm E3640 FLASH TESTER INSTRUCTION MANUAL. Martindale Electric Co Ltd.

ANALOGUE INSULATION-CONTINUITY and VOLTAGE METER

Chek-A-Cell TM. Instruction Manual Rev A 8/12

Instruction Manual. Model 307A Analog Insulation & Continuity Meter

1 This instrument must only be used by a competent and trained person and operated in strict accordance with the instructions.

USER MANUAL. 10KV Digital High Voltage Insulation Tester. Model MG500. Additional User Manual Translations available at

MANUAL PCE-IT111

INSPECTOR LINE LOAD SIMULATOR INSTRUCTION MANUAL TASCO, INC.

BATTERY OPERATED DIGITAL MILLI-OHMMETER

KEWTECH. KT56 digital multi function tester. Instruction manual

Instruction Manual. 99 Washington Street Melrose, MA Fax TestEquipmentDepot.com. Model 308A Digital Insulation & Continuity Meter

Instruction Manual. Model 310 Digital Milli-Ohm Meter

HIGH VOLTAGE PROXIMITY DETECTOR

OPERATING INSTRUCTION

HIGH VOLTAGE PROVING UNIT

Non-Contact Phase Rotation Tester

Test Equipment Depot Washington Street Melrose, MA TestEquipmentDepot.com INSTRUCTION MANUAL PSMR1

TRIPLETT. Model 310 Type C Type 9

OPERATING INSTRUCTION

Users Manual. Phase Rotation Indicator

DC-AC Power Inverter SAM Manual. Please read this manual before installing your inverter

Instruction Manual PC104/PC105 3-PHASE SOCKET TESTER. Check out what else you can get from Martindale:

MAX. AC 600V HOLD V M H.V. LIVE CIRCUIT DIGITAL INSULATION TESTER DO NOT OPERATE IF LIT POWER DATA HOLD TEST ON / OFF 250V 500V 1000V OFF CAT.

INSP-3 Wiring Inspection Tester

PRM-4. Phase Sequence and Motor Rotation Tester. Users Manual. For detailed specifications and ordering info go to

The function of this Dynamic Active Probe has divided into three preferences on the screen main Menus:

User's Manual. High Voltage Megohmmeter. Analog Insulation Tester plus AC Voltage and Continuity Tests. Model

1.Safe testing IMPORTANT:

Non-Contact Phase Rotation Tester

Model 616 Rotating Disk Electrode Instruction Manual

INSTRUCTION MANUAL ANALOGUE INSULATION TESTER KEW 3131M KYORITSU ELECTRICAL INSTRUMENTS WORKS,LTD., TOKYO JAPAN

User's Manual. Earth Ground Resistance Tester. Model Introduction

Phase Sequence Tester

Table of Contents Title Page No.

DIGITAL RCD(ELCB) TESTER

AC POWER SOURCE PURE SINE WAVE DC-AC INVERTERS OWNER S MANUAL

RS-3 PRO RS-1007 PRO. CAT IV Analog Clamp meter Series. Users Manual. For detailed specifications and ordering info go to

KD1E Range Potential Indicators

TRIPLETT. Model 310 Type C Type 9. Test Equipment Depot Washington Street, Melrose, MA TestEquipmentDepot.

IQS300 Series Quasi-Sine Inverter. Installation & Operation Manual

INSTRUCTION MANUAL CM95/ CM100 TRUE RMS FLEXIBLE CLAMP METER. 1. SAFETY INFORMATION: Always read before proceeding. REMEMBER: SAFETY IS NO ACCIDENT

Battery Back-up BBM Owner's Manual. Please read this manual BEFORE installing your inverter

For technical questions and replacement parts, please call

User Guide. Model Insulation Tester / Megohmmeter. Introduction

INSTRUCTION MANUAL PORTABLE APPLIANCE TESTER

Model AS-RC3260 TV Cart. Rolling Cart for Audio Mount System & Flat Panel TVs

Switching DC Power Supply

Instruction Manual VT4 VOLTAGE TESTER. Check out what else you can get from Martindale:

Triple Output High Resolution Power Supply. User Manual

CLEAN POWER TM CPS Series Operator s Manual

Model AS-FM64 Wall Mount. Full Motion Television Wall Mount

Helios. 24 Light 240 Volt Controller. PRODUCT # Instruction Manual.

PD-20 HIGH VOLTAGE PROBE INSTRUCTION MANUAL

Distributor. Kewtech Corporation Limited 76 St. Catherine s Grove Lincoln LN5 8NA KEWTECH

NaviTrackTM Transmitter

Calibration Manual. Detachable Jaw True-rms Clamp Meter

PHASERS. Operating and Instruction Manual. a n d A C C E S S O R I E S

RU BMS Power Supply and Battery Management System Owners Guide

KMP Insulation-Continuity Tester. Users Manual

INSTRUCTION MANUAL FOR THE THERMOCOUPLE ATTACHMENT UNIT (TAU)

RENA AF371Feeder Operating Manual. Feeder. Operating Manual. Manual Part #: M AF371 Operations Rev

60 Watt Industrial LED Low Bay Light

Owner's Manual. 120 Watt DC-AC Inverter Pure Sine Wave PST-12S-12A. Please read this manual before using your inverter

Model T2642 Wall Mount. Television Wall Mount with Tilt Option

Vol-Con XL (61-086) Voltage/Continuity Tester and Vol-Test (61-085) Voltage Tester Instruction Manual WARNING

NEW 15KV HIGH VOLTAGE INSULATION RESISTANCE TESTER MODEL KM 7015 IN FEATURES : CAT IV 600V. Short Circuit Current 5mA.

ATD-5570 Deluxe Automotive Meter with RPM and Temperature Functions Owner s Manual Features:

OPERATING INSTRUCTIONS PLEASE READ CAREFULLY

Manufacturing & Service: Bierer & Associates Inc. Patent No. 6,885,180. ST Series Service Tester Phase Identifier Operating Instructions ST500PGN

Battery Back-up Model: BBM-1225

Digital/Analog Megohmmeter Model 1026

362 Clamp Meter. Users Manual

OBAE, OBAEXU, ON BOARD Battery Chargers

ME310B BATTERY POWERED CRIMP TOOL

MODEL 520 REMOTE START ENGINE MANAGEMENT SYSTEM

AFE8B BATTERY POWERED CRIMP TOOL

Nature Power Inverters. True Sinewave Inverter Modified Sinewave Inverter. Owner s Manual

Heavy-Duty Sawhorse. Owner s Manual

PIECAL 322 Automated Thermocouple Calibrator Operating Instructions. Product Description

TESTER SET SOCKET & VOLTAGE

Hydraulic Transmission Jacks

OPERATING INSTRUCTION

MARTINDALE INSTRUCTIONS ELITE FUSE FINDER KIT ELECTRIC. Trusted by professionals. 4.4 Storage Conditions

INSTRUCTION MANUAL CM69 TRMS AC EARTH LEAKAGE CLAMP METER. 1. SAFETY INFORMATION: Always read before proceeding. REMEMBER: SAFETY IS NO ACCIDENT

VTC610 Series Voltage Converter. Installation & Operation Manual

ROTARY HEAD DIGITAL STEM THERMOMETER

Angle Grinder Holder

PHASE ROTATION INDICATOR with OPEN PHASE CHECKER

QPET, QPETXU Battery Chargers

MAINFRAME HOT RUNNER TEMPERATURE CONTROL SYSTEMS. Instruction Manual

TRIPLETT. Series. Type 3. Railroad Test Sets Instruction Manual /07

1662/1663/1664 FC. Electrical Installation Tester. Safety Information. Warnings

INSTALLATION & OWNER'S MANUAL

99 Washington Street Melrose, MA Fax TestEquipmentDepot.com. Instruction Manual. Model 1672 Triple Output Power Supply

IV. PROOF OF PURCHASE: A warranty claim must be accompanied by proof of the date of purchase.

Automatic taper of charge rate for superior battery life through good equalization of cells and low water use rate.

Transcription:

= = = = - - - BESANTEK - - BST-ELC1 INDUSTRIAL DIGITAL EARTH LEAKAGE CIRCUIT BREAKER and 3 PHASE ROTATION TESTER EARTH DIGITAL INDUST RIAL ELCB HAS OT ATl ONTE O C, 1:. : ==== === ;... P E R STE R ==! U -----L.. s, = MULTI VOLTAGE (22 to 317 Vae) t...e EARTH I R s r I I e k ill L ill AUTO POWER OFF /2.. L, I.\ L, L, MENU CURRENT ADJUST O@CRl!AS!" M i nimum INSTRUCTION MANUAL 99 Washington Street Melrose, MA 2176 Phone 781-665-14 Toll Free 1-8-517-8431 Visit us at www.testequipmentdepot.com

Index Page 1. Safety Rules... 1-2 2. Safety Checks... 2 3. Don't Touch... 2-3 4. General Description... 3-4 5. Brief Product Description... 4-5 6. Operating Instructions... 5-8 7. Front Panel Layout... 9 8. Keypad and Main Keys... 1 9. Principle of How It Work... 11-12 1. Preparation For Use... 11. Replacing The Batteries... 12 13 12. Specifications... 14-15 13. Limited Warranty... 15-16

BESANTEK -- - - - - - - - 1. Safety Rules CAUTION IA,. RISK OF ELECTRIC l: :l SHOCK This tester has been designed with your safety in mind. However, no design can completely protect against incorrect use. Electrical circuits can be dangerous and/or lethal when lack of caution or poor safety practices are used. Do not carry out field measurements on either the power system grounding, during periods of forecast lightning activity, in areas that encompass the station being measured or of the power network connected to the station being measured. In the event that lightning occurs, stop all testing and isolate any temporarily installed test spikes. Preparations for testing of power system grounding can leave personnel vulnerable to exposure caused by faults at or fed from the system under test, transferred potentials from remote test grounds, and inadvertent line energisations. While the probability of the occurrence of one of these events is low, personnel safety will, nevertheless, be enhanced by the following: When working near high tension systems rubber gloves and shoes should be worn. Work on clean, dry crushed rock or an insulating blanket. Avoid bare hand to hand contact between the tester and extended test leads. When using the tester with test leads, ensure that they are safe and properly authorized Disconnect the tester from any external circuit when changing the batteries. -1-

- - - -- BESANTEK -- - - - - CAUTION & READ THE MANUAL Follow the instructions in the Manual for every measurement. Read and understand the general instructions before attempting to use this tester. 2. Safety Check Before using the tester check the condition of the batteries. This is done by switching the tester ON. If the BAT OK led does not light up, the battery need replacing. Battery and fuse replacement are described later in this user's manual. When changing the battery, fuses, or removing the cover to access the internal circuitry, always disconnect the test leads. When replacing the fuse use only the type specified, 5 X 2mm, 1.A, fuse, and insert correctly into the fuse holder. Double check the switch setting, and lead connections before making measurements. 3. Don't Touch Don't touch exposed wiring, connections or other "Live" parts of an electrical circuit. If in doubt, check the circuit first for voltage before touching it. Do not use cracked of broken test leads. THIS INSTRUMENT SHOULD ONLY BE USED BY A COMPETENT, SUITABLY TRAINED PERSON. -2-

- - - -- BESANTEK -- - - - - REMEMBER SAFETY IS NO ACCIDENT & CAUTION RISK OF ELECTRIC SHOCK & CAUTION READ THE MANUAL 4. General Description This Test Instrument is a combined 3 Phases Presence and Rotation Indicator combined with a 3 Phases Industrial Earth Leakage Tester. When utilized as a 3 Phase Presence and Rotation Indicator, the instrument does not use the batteries and can still be utilized if the batteries are not present or if the batteries are too low. The 3 phase Presence and Rotation Indicator which is inside the meter, takes it's power from the circuit under test. The Earth Leakage can be utilized on a Single Phase (up to 31?Vac Line to Earth) or a 3 Phase Powered System (55V Line to Line or Phase to Phase) with a protective Earth conductor. The Earth Leakage requires batteries. When utilized on a single phase, ensure correct connection between Line and Earth before using the tester. When utilized on a 3 Phase Powered System, the instrument is then utilized as a 3 Phases Presence and Rotation Indicator and a Earth leakage tester (selecting which phase to Earth will be utilized for the ELCB test). When utilized on a 3 Phases Powered System, this instrument is a rotary field indication instrument which display all three phases by lighting up it's corresponding Lamp. It display the rotation (clockwise or anti-clockwise) on a LED. -3-

To test the tripping time or the tripping current of a Eathr Leakage Circuit Breaker, make sure to connect the earth wire. This instrument represents the quickest and easiest way for servicing, repairing and electrical maintenance of 3 phase system with earth leakage. With this equipment, you can, before connecting Load to Supply: On the supply side; Quickly verify the presence of the three Phases on a 3 Phases Power System. Confirm the Phase Rotation on a Powered 3 Phase System. Test the Tripping (disconnection) current and time of the protections. 5. Brief Product Description This 3 Phases Rotation and Earth Leakage Tester has 4 test leads which connects to the 4 mm female sockets on the tester. These Test leads are color coded. R(L1) = Red which connects to R on the tester. S(L2) = White which connects to S on the tester. T(L3) = Blue which connects to T on the tester. T(L3) = Blue which connects to T on the tester. Earth = Green which connects to Earth on the tester. On the other side of the test leads are the probes, also color coded. The Phase Presence Indicator has three neon lamps which are the Phase Presence indicators; Neon Lamp for Individual Phase Presence Indication = R(L1) Neon Lamp for Individual Phase Presence Indication = S(L2) Neon Lamp for Individual Phase Presence Indication = T(L3) Please note that any of these Neon lamp will only start to light up if more than 1Vac is present between any 2 phases. -4-

The Phase Rotation Indicator has; A LED to display clockwise rotary direction L1L2L3. A LED to display counter clockwise L2L1L3. The Earth Leakage Tester comprise of the Phase Selector, which permit the selection to connect Phase 1 ( L1 or R ) to the earth Leakage tester, or Phase 2 ( L2 or S), or phase 3 (L3 or T). The Industrial Earth Leakage Tester injects a fault current between one of the phase and earth. When utilized to test on a single phase system, the 3 Phase Presence and rotation features and indications must be disregarded. The Selector Switch must be on the R position, and the R(L1) phase is connected to the Phase(Line), the green socket to Earth. Neutral wire is not utilized in the testing of the Earth leakage Circuit Breaker. 6. Operating Instructions Determination of the rotary field direction and phase presence On a 3 Phase System, the sequence of the 3 phases determine the rotation of a 3 phase motor connected to that system. The correct 3 Phase Sequence R(L1), S(L2), T(L3) results in a clockwise rotation of the connected motor. Connect the Test Leads to the sockets of the Instrument, respecting the correct color. Red to R(L1), White to S(L2), Blue to T(L3). Clip the test probes to the three mains phases, R(L1), S(L2), T(L3). When connecting to a voltage superior to 1V AC, the corresponding neon lamp will start to glow, indicating the presence of the voltage on it's corresponding lead (L1, L2, L3 lamps). -5-

- - - - - BESANTEK - - - - - If the LED (Right arrow) L 1-L2-L3 is illuminated, clockwise rotary field is present. If the LED(Left arrow) L2-L 1-L3 is illuminated, a counter clockwise rotary field is present. Determination of the disconnection sensitivity of the Earth Leakage Circuit Breaker Connect the Earth lead from the tester to the Earth connection on the system. Using the rotary switch, select which phase you want to test from, connect the phases. Determination of the disconnection sensitivity of the Earth Leakage Circuit Breaker Connect the Earth lead from the tester to the Earth connection on the system. Using the rotary switch, select which phase you want to test from, connect the phases. Turn Instrument "ON" by pressing the "TEST-ON" button. The L.C.D. display will come to the following Screen. ---- 1 * - Instantaneous -Time Delay Push Select to change Selection to Instantaneous, then Press "TEST " to accept. Dial Starting Current. 123mA Dial the Starting Current of the Instantaneous Test using the Current Adjust Knob. Positive Start Edge -6-

- - - - - BESANTEK - - - - - Select the Positive or Negative Start Edge using the Select Button. Connect Leads to Earth & Phase Connect Leads to Earth and Phase. Testing will start I Automatically when voltage is detected. V=317V I=127mA Test In Progress. The Voltage between leads was 317V before testing started and I=127mA V=317V 1=14mA Hold TRP TRP = Tripped, Display on Hold Tripped at 14mA, on - edge of signal. Determination of the disconnection time of the Earth Leakage Circuit Breaker Connect the Earth lead from the tester to the Earth connection on the system. Using the rotary switch, select which phase you want to test from, connect the phases. Turn Instrument "ON" by pressing the "TEST-ON" button. The L.C.D. display will come to the following Screen. -- * - Instantaneous - Time Delay Push Select to change Selection to Instantaneous, then Press "TEST" to accept. Dial Starting Current. 125mA I -7-

- - - - - BESANTEK - - - - - Dial the Testing Current of the Instantaneous Test using the Current Adjust Knob. Positive Start Edge Select the Positive or Negative Start Edge using the Select Button. Connect Leads to Earth & Phase Connect Leads to Earth and Phase. When voltage is detected, Testing will start Automatically. V=317V T=4.2s I=125mA Test In Progress since 4.2s. The Voltage between leads was 317V before testing started and Constant current is 125mA. V=317V + T=6.435s I=125mA Hold TRP TRP = Tripped, Display on Hold at 6.435s Tripped on + edge of signal. 99 Washington Street Melrose, MA 2176 Phone 781-665-14 Toll Free 1-8-517-8431 Visit us at www.testequipmentdepot.com -8-

::c z m -I z,, m s:: )> r m "' g '" <D I m -I,, C: "' m DIGITAL INDUSTRIAL ELCB PHASE ROTATION TESTER MULTI VOLTAGE (22 to 317 Vac) L-E I I AUTO POWER OFF [[OFF]) CURRENT ADJUST ' DECREASE IIICREASE \ ENTER 11 Minimum 'ves Maximum [I Q N ]) VOLTAGE APPLIED LOCATING ONTO ELCB TESTER PIN INDICATOR MAXNUll 55Vae Looi.. {317Vac l-e) SOHt line lyttem only zm 3>m -I ;;o o-< ;;oo " BATTERY! OK.,,, "'Oom :::r Os:: : m l> C, r- m ooo ::i no ::, " r- a!!l i "' ::, ;;o i;! ;;o 41 I I I m r m a ;;o -nr om ;;uo "'O "' :cc )> (i) ::c m--1 ;;o -I z... "11.., ::::J-""O II,) ::::J (I) r- 11,) '< C -

- - - - - BESANTEK - - - -- 8. Keypad and Main Keys select between types of tests Instantaneous (checking the tripping ) current or Time Delay (checking the tripping time) Turn the TESTER OFF MENU SELECT CURRENT ADJUST OFF DECREASE INCREASE ENTER YES Minimum Maximum ON Accept the selection Turn the TESTER ON Adjust the Starting Current (Instantaneous) or Adjust the ConstantCurrent (Time Delay) -1- BESANTEK Corporation, CANADA

9. Principle of How It Work The tester has two separate circuits: One is for the 3 Phase Presence and Rotation indicator, the other is for the Earth leakage Circuit Breaker Tester. The first circuit is the 3 Phase presence indicator, which is shown by the neon lamps and the three phase sequence indicator by leds. 3 Phase Presence and Rotation indicator: This circuit derive it's power from the system under test. This circuit does not require the user of battery and is self powered through resistors. 3 Phase Presence Indication circuit: This circuit uses neon lamps to indicate if a phase is present. These neon lamps are connected in series with a limiting resistor. Neon lamps will lights up when the voltage across any two phases is more than 1Vac. 3 Phase sequence indicator circuit: This circuit has an analog and a digital part. The analog signals are shaped then compared to a set of references. These results are digitally compared to give the results on the indicating LEDs. Earth leakage Circuit Breaker Tester At switch-on, the circuit is powered up. A low battery detection pickup circuit, with a Power On indicator LED is also present. This LED indicate that the batteries are ok and it will lights up when the batteries are ok. Should this led not lights up, replace the batteries. Once the Earth Leakage Circuit Breaker is turned-on, the first menu will indicate that the instrument is ready. -11-99 Washington Street Melrose, MA 2176 Phone 781-665-14 Toll Free 1-8-517-8431 Visit us at www.testequipmentdepot.com

Basically, this instrument measure the voltage Line to Earth or between the selected phase to Earth. This is not the Line to Line voltage. The tester also has a computer controlled constant current source, from which the test fault current is taken from. This instrument reproduce a perfect 5Hz current sinewave, wich is independant from the shape of the voltage. 1. Preparation For Use Fuses : In doubt, check the fuses using a ohm meter. Please note that the Earth Leakage Tester will not indicate any voltage, should the fuses be blown. Should the fuse be blown, the Current Led will also not lit. Test Leads : Check the test leads for defects or cracks. Replace if cracked or damaged. Only replace with the same type. Cleaning : Use a damp cloth to clean the case. Do not use chemicals. Batteries : Checking the battery is automatically done, once the tester is switched "ON". Should the battery OK led not lit, replace the batteries. -12-

11. Replacing The Batteries Prior to battery replacement always disconnect the instrument from the circuit to which it's connected. Remove the test leads from the instrument. Remove the back cover to access the battery compartment. Remove all the bad batteries from the battery compartment and dispose properly of that batteries (see your local disposal facilities related to disposal of batteries). Only replace with 8 new batteries of the following type : 1.5 V, C type. Re-insert the (batteries) back cover onto the instrument and tighten the screw. Fuses Replacement Unscrew the front fuse cover and replace the faulty fuse with the same type, then screw the fuse cover back into place correctly -13-

12. Specifications ELECTRICAL Determination of the Phase Presence Nominal Voltage for Phase Presence Indication (the voltage required for the neon lamps L1, L2, L3 to lit up)... From 1Vac to 45Vac. Frequency Range... From 1Hz to 4Hz. Determination of the Phases Rotary Field Direction: Direction (the voltage required to have the direction LEDs L1-L2-L3 or L2-L1-L3 to indicates)... From 1 to 45Vac. Frequency Range... From 2Hz to 4Hz. Protection Over Load... 55V (between all terminals). Over Voltage... Class III - 45V towards ground. ENVIRONMENTAL Operating temperature Range : C to + 4 C Storage Temperature : -1 C to + 5 C Earth Leakage Current Settings 999mAac / 5-6Hz Current Selection Knob Phase Start Selection(*) and 18 Over-Temperature Protection(*) Yes Phase Polarity Trip Indicator(*) Yes Operating Voltage ( L-E ) 22Vac to 317Vac (*)Referenced to Earth Timer Resolution 1ms (Max Time = 99.99s) Timer Accuracy 1ms ±4ms Current Accuracy ±3% ±4mA Current Resolution 1mA Voltmeter Accuracy (5Hz) 5-35 Vac = ±3%±2V 35-55Vac = ±7%±3V Voltmeter Resolution 1V -14-

Batteries 1.5V "C" x 8 batteries Bat OK Led = Vbat >9V Maximum Current Specified at 317Vac / 5Hz CLEANING Clean the instrument case with an anti-static cleaner and wipe with dry cloth. 13. Limited Warranty We warrant the product manufactured by us to be free from defective material or factory workmanship and agree to repair or replace this product which, under normal use and service, disclose the defect to be the fault of our manufacturing, with no charge for parts and service. If we are unable to repair or replace this product, we will make a full refund of the purchase price. Consult the user's manual for proper instruction regarding use of this instrument. Our obligation under this warranty is limited to repairing, replacing or making refund of this test equipment which proves to be defective within twelve months from the date of original purchase. This warranty does not apply to any of our products which have been repaired or altered by unauthorized persons in any way so as, in our sole judgement, to injure their stability or reliability, or which have been subject to misuse, abuse, misapplication, negligence or accident or which have had the serial numbers altered, defaced or removed. Accessories, not of our manufacture used with this product, are not covered by this warranty. All warranties implied by law are hereby limited to a period of twelve months, and the provisions of the warranty are expressly in lieu of any other warranties expressed or implied. -15-

The purchaser agrees to assume all liability for any damages or bodily injury which may result from the use or misuse of the product by the purchaser, or it's user, his employees, or others, and the remedies provided for in this warranty are expressly in lieu of any other liability we may have including incidental or consequential damages. We reserve the right to discontinue models at any time, or change specification, price or design, without notice and without incurring any obligation. 99 Washington Street Melrose, MA 2176 Phone 781-665-14 Toll Free 1-8-517-8431 Visit us at www.testequipmentdepot.com -16-