IP800-Series FLOW SENSOR INSTRUCTIONS IP810 IP :2008 ISO CERTIFIED COMPANY IP800-SERIES FLOW SENSOR INSTRUCTIONS

Similar documents
IP800-Series FLOW SENSOR INSTRUCTIONS IP810 IP :2008 ISO CERTIFIED COMPANY IP80-SERIES FLOW SENSOR INSTRUCTIONS

IP80-Series FLOW SENSOR INSTRUCTIONS IP81 IP :2008 ISO CERTIFIED COMPANY IP80-SERIES FLOW SENSOR INSTRUCTIONS

TX80-Series FLOW SENSOR INSTRUCTIONS TX81 TX :2008 ISO CERTIFIED COMPANY TX80-SERIES FLOW SENSOR INSTRUCTIONS

IP800-Series. Insertion Paddlewheel Flow Sensor Instructions PROUDLY MADE IN THE USA

IP800-Series. Insertion Paddlewheel Flow Sensor Instructions PROUDLY MADE IN THE USA

TX800-Series FLOW SENSOR INSTRUCTIONS. TX81x TX82x 9 001:2008 ISO CERTIFIED COMPANY TX800-SERIES FLOW SENSOR INSTRUCTIONS

TX101/201 Insertion Turbine Instructions

S-Series. Low Flow Meter Instructions SPX SPT. Precision Flow Measurement An ONICON Brand PROUDLY MADE IN THE USA

TX100/200-SERIES INSERTION TURBINE INSTRUCTIONS TX101/201 TX115/215 ISO 9001:2008 CERTIFIED COMPANY

TX101/201 Insertion Turbine Instructions

EX80 Series EX81 EX82. E X 8 0 S E R I E S E l e c t r o m a g n e t i C F l o w s e n s o r i n s t r u c t i o n s. The Leader in Flow Meter Value.

TX 115/215 Hot-tap Insertion Turbine Instructions

SES. Stainless Single-Jet Meter Instructions PROUDLY MADE IN THE USA

TX100/200-SERIES INSERTION TURBINE. T X / S E R I E S I N S E R T I O N T U R B I N E instru c tions TX101/201 TX115/215

TX115/215 Hot-tap Insertion Turbine Instructions

SERIES TBS INSERTION TURBINE TBS-0XX TBS-1XX

ARCHIVED. EX80 Series. (Includes Dates 6/28/05 to 10/06) EX81 EX82

EX80-Series ELECTROMAGNETIC FLOW SENSOR INSTRUCTIONS EX81 EX82 EX :2008 ISO CERTIFIED COMPANY

PSF50 Paddle flow switch

EX100/200-Series INSERTION MAGNETIC FLOW METER INSTRUCTIONS EX110 EX210 EX150 EX :2008 ISO CERTIFIED COMPANY

SeaMetrics Flow Meters and Flow Computers

EX100/200 Series. Insertion Magnetic Flow Meter Instructions. EX11x EX21x. EX15x EX25x PROUDLY MADE IN THE USA

WMX-series MUNICIPAL/INDUSTRIAL MAGMETER INSTRUCTIONS

FIXED DEPTH INSERTION METER INSTRUCTIONS

SERIES FLMG MUNICIPAL/INDUSTRIAL MAGMETER INSTRUCTIONS

EX800-Series. Electromagnetic Flow Sensor Instructions PROUDLY MADE IN THE USA

LEVEL AND FLOW MEASUREMENT WS131 FLOW METER USER MANUAL.

M SERIES Multi-Jet Cold Water Meter

FLOWX3 F3.20 High Pressure Paddlewheel Flow Sensor MAIN FEATURES APPLICATIONS OPERATING PRINCIPLE

Insertion turbine INSTRUCTION SHEET. TECHNICAL PRODUCT

TURBINE METERS - WP Series

INSERTION flow sensor for continuous flow measurement

Paddle Wheel Turbine Flow Meters Installation, Operating & Maintenance Manual

G2 Industrial Grade Meters

FLS F6.60 MAGMETER FLOW SENSOR INSERTION FLOW SENSORS APPLICATIONS MAIN FEATURES

Paddle Wheel Turbine Flow Meters Installation, Operating & Maintenance Manual

WMP-Series PLASTIC-BODIED MAGMETER INSTRUCTIONS 9001:2008 ISO CERTIFIED COMPANY WMP-SERIES PLASTIC-BODIED MAGMETER INSTRUCTIONS. 3 inch.

Pipe fi ttings MUST be installed by a certifi ed welder only. Signet will not assume liability of any kind for improper fi tting installations.

INSERTION flowmeter with paddle wheel, ELEMENT design

RPFS. ROTA PULSE FLOW SENSOR (Slip Insertion Paddlewheel) DATASHEET FEATURES

ROTA PULSE FLOW SENSOR Slip Insertion Paddlewheel (with inductive coil pulse output & built in op-amp circuit)

Pipe fittings MUST be installed by a certified welder only. +GF+ SIGNET will not assume liability of any kind for improper fitting installations.

FPD1001 thru FPD1003, FPD1102 and FPD1103, FPD1201 thru FPD1203 (includes -R Option) Positive Displacement Flowmeters

Liquid Turbine Flow Meter OwnerÊs Manual

RPFS. ManuFlo Page 1 MANU ELECTRONICS PTY LTD Flow Measurement Products 41 Carter Road, Brookvale NSW 2100

RUN ACCUM. TOTAL STOP BAT LOW HIGH

digital flow meters BW Digi-Meter F-1000

EM101 LOW FLOW MAGNETIC FLOWMETER INSTRUCTIONS

Flow Meter & Control Catalog

Distributed by: M&M Control Service, Inc MICRO-FLO MICRO-FLO

TR-QS Wafer-Style Turbine Flow Meters Installation, Operating & Maintenance Manual

Hydro-Flow 2200 Fixed Insertion Vortex Flow Meter

MODEL 1100 TURBINE FLOW METER

BI-DIRECTIONAL INSERTION FLOW TRANSDUCER

Before first operating the equipment read the whole of these instructions. Safety may be impaired if they are not followed.

BI-DIRECTIONAL INSERTION METER

EM 101 EM EM EM GENERAL INFORMATION. SPECIFICATIONS MATERIALS Wetted Materials - FLOW RANGE

OVAL GEAR FLOWMETER ELECTRONIC MODEL 006/009 (¼ )

Flow Meters & Instruments. Insertion Paddle Wheel & Magnetic Flow Meters Flow & Anaytical Instruments. Technical Catalogue

OVAL GEAR FLOWMETER ELECTRONIC MODEL 019 / ¾

TABLE OF CONTENTS GENERAL INFORMATION

Series TTMP PVC Electronic Totalizing Meter

Paddle-wheel flow controller for On/Off control

Sanitary Turbine Flow Meter - TA3 Installation, Operating & Maintenance Manual

INLINE Flow sensor for hazardous area II 1 G/D - II 2 D - II 3 GD - I M1

DIGIFLO ELECTRONIC FLOWMETER

Signet 2517 Brass Paddlewheel Flow Sensor * *

WATER METERS OCTAVE ULTRASONIC WATER METER INSTALLATION & USER GUIDE

User's Guide FPR300/310 SERIES. Shop online at. Low-Flow Meter. omega.com For latest product manuals: omegamanual.

Industrial Meter Catalog

Hydro-Flow Model 2200 Installation and Operation Guide B

F-2000 MODEL RT INSTRUCTION MANUAL. Blue-White. Industries, Ltd.

Hydro-Flow Model 2200 Fixed Insertion Vortex Flowmeter Installation and Operation Manual

AG2000 IRRIGATION MAGMETER INSTRUCTIONS

Condensed Version of Operator s Manual For The VL600 Series Flowmeters

Paddle-wheel flow controller with optical principle for On/Off control

Index Flow Sensors FLOWX3 F3.00 Paddlewheel Flow Sensor page 2 FLOWX3 F111 Hot Tap Flow Sensor page 18 FLOWX3 F3.60M Insertion Magmeter page 24 FLOWX3

Model TUR-200D Turbine Flowmeter

FPD1001B thru FPD1003B, FPD1102B and FPD1103B, FPD1201B thru FPD1203B SERIES LOW FLOW Positive Displacement Flowmeters

F-4600 INLINE ULTRASONIC FLOW METER Installation and Operation Guide

F111.X Flow Sensor for Hot Tap Installation INSTRUCTION MANUAL. 1. Introduction Safety Instructions Unpacking Description.

SIGNET Vortex Flow Sensors ENGLISH

INDUSTRIAL METER CATALOG version seven

Pipe fi ttings MUST be installed by a certifi ed welder only. Signet will not assume liability of any kind for improper fi tting installations.

Liquid Turbine Flowmeter

MODEL 106F TEFLON LIQUID FLOW SENSOR

Model 1100 Turbine Flow Meter

DOR Insertion Paddle Wheel Flowmeter

Signet 7000/7001 Vortex Flow Sensors * *

MFM220 & MFM220DC Plastic-Bodied Magmeter

Paddle-wheel flow controller for On/Off control

FPD1000-HP SERIES HIGH PRESSURE Positive Displacement Flowmeters

Electronic Dynamo Regulator INSTRUCTION MANUAL. COPYRIGHT 2014 CLOVER SYSTEMS All Rights Reserved

TURBINE HOUSING. Owner s Manual Includes Aluminum, Brass and Stainless Steel Housings and ANSI Flange Fittings

A Member of the. Integrated Metering Technologies

INSTRUCTION MANUAL 272-5X5 ANALOG TRANSMITTER (210 SERIES FLOW METERS) 272-5X7 ANALOG TRANSMITTER (220/240 SERIES FLOW METERS)

Inductive conductivity meter

G2 SERIES INDUSTRIAL GRADE METERS

Operating Instruction for Plastic Vortex Flow Transmitter. Model: UV

Installation & Operation Manual

Transcription:

-SERIES FLOW SENSOR INSTRUCTIONS -Series FLOW SENSOR INSTRUCTIONS IP810 IP820 9001:2008 ISO CERTIFIED COMPANY

TABLE OF CONTENTS General Information Features, Specifications...Page 3 Installation Insertion Depth, Distorted Flows, Fitting Installation, Meter Installation, Positioning the Meter...Page 4 Straight Pipe Recommendations...Page 5 Full Pipe Recommendations... Page 6 Connection Diagrams FT415/FT420/AO55, Connecting to PLC's... Page 7 Operation Minimum Flow, Flow Range Table, Calibration ( K-Factor ), Field Calibration...Page 8 Maintenance Rotor Replacement, Signal Troubleshooting, Sensor Replacement... Page 9 Parts Explosion Parts List...Page 10 Troubleshooting Problems, Probable Causes, To Check, To Repair...Page 11 TABLES AND DIAGRAMS Specifications, Features...Page 3 Distorted Flows, Positioning the Meter...Page 4 Straight Pipe Recommendations...Page 5 Full Pipe Recommendations...Page 6 Connections Diagrams...Page 7 Flow Range Table, K-Factor Number on Tee Fitting, K-Factor Chart, Pressure vs. Temp Chart...Page 8 Rotor and Sensor Replacement...Page 9 Parts Explosion, Parts List...Page 10 Troubleshooting...Page 11 Page 2

GENERAL INFORMATION The -Series are impeller (or paddlewheel ) insertion meters designed for use with a wide variety of liquids in pipe sizes 1/2" to 8". Sensors are available in brass, 316 stainless steel, PVC, and polypropylene. Bodies are machined from a solid rod for maximum precision. High-quality jewel bearings and nickelbound tungsten carbide shafts are used for extreme low friction and long life. Low-flow performance is good, although other flow meters are recommended where extremely low flows are being measured. The rotation of the rotor is detected by a non-drag Hall-effect sensor. Output is a current-sinking pulse (square wave), which can be sent long distances (up to 2,000 feet) without a transmitter. This signal can be connected directly to PLC's, counters, and computer cards, as well as a variety of controls and displays. FEATURES Cover or Optional Module Housing Screw (connect ground to one) Cable-Seal Strain Relief Lower Housing (optional) IP meters are ideal for chemical proportioning ap-plications. If no display is required, a simple divider such as the PD10 provides adjustable pump pacing. For rate and total display, the FT415 (battery powered) or FT420 (loop powered) flow indicator can be mounted directly on the -Series meter, or remotely on a wall or panel. The AO55 blind analog transmitter can be used to convert to a 4-20 ma output. IP meters are also compatible with the DL76 data logger and FT520 batch processor. The -Series require special fittings that ensure correct depth placement in the pipe. Fittings come in a variety of materials for compatibility with specific applications. Tee fittings are individually wet-calibrated at the factory and marked with the K-factor (pulses per gallon). Saddle fittings must be fieldinstalled on the pipe and do not come wet-calibrated. K-factors for saddles are based on factory-testing. Caution: Clip(s) must be installed before use. High Pressure Model Retaining Slot (for U-Clip) For easy installation at correct depth setting O-Ring Jewel Bearings for superior low-flow performance Rotor SPECIFICATIONS* Specifications subject to change Please consult our website for current data. Power Source Standard Micropowered (-04 Option) Supply Voltage/Current 6-40 Vdc/< 2 ma 3.5-16 Vdc/60 μa @ 3.5 Vdc Sensor Hall Effect sensor, 12 Vdc current sinking pulse Materials Sensor Body Brass, 316 Stainless Steel, PVC, or Polypro Rotor PVDF (Kynar) Shaft Nickel-bound tungsten carbide (zirconia ceramic optional) Bearings Ruby jewel O-Ring EPDM (Viton optional) Rotor Pickup GMR (Giant Magnetoresistive) Sensor Maximum Brass 316 Stainless Steel PVC or Polypro (See Pressure vs. Temp. Chart) Pressure 200 PSI (14 bar) 200 PSI (14 bar) 175 PSI (12 bar) @ 75 F High Pressure Not Available 400 psi (28 bar) Not Available Temperature 200 F (93 C) 200 F (93 C) 130 F (55 C) Flow Range 0.3-30 ft./sec Accuracy +/- 1.5% of full scale Signal Hall effect current sinking pulse Power 6-24 Vdc, 2 ma Maximum Current 20 ma Cable #22 AWG 3-con, 18 (6m); 2,000 (650m) maximum cable run Regulatory Mark (Standard Power Only) Page 3

INSTALLATION Insertion Depth. The -Series are fixed-depth meters that must be used with matched fittings appropriate to the application and pipe size. This ensures that the flow sensor is installed at the correct insertion depth to measure the average flow velocity of the stream. POSITIONING THE METER Okay, if no air in pipe Straight Pipe. Straight pipe of at least 10 diameters upstream and five diameters downstream of the meter is strongly recommended for proper accuracy. This is necessary because the shape of the velocity profile changes as the rate increases around an elbow; placing the meter too near the elbow causes a distorted reading. Additional straight run may be needed under specific adverse circumstances (see next page). BEST If you can t provide enough straight run to smooth out the velocity profile, some decrease in accuracy may result. This does not mean the meter s reading is meaningless, however. In some applications (e.g., control system, valve operation) a repeatable reading may be more important than a highly accurate one. DISTORTED FLOWS Okay, if no sediment in pipe. Distorted Flow Profile Faster Flow Causes Meter To Read High FLOW 10X Diameter Minimum (See Below) 5X Diameter Minimum (See Below) PVC Fittings. A PVC fitting is usually installed by solvent welding. PVC tees are supplied with some upstream straight pipe, less than the recommended straight pipe requirements. It is not advisable to connect directly to the end of these fittings with a flow disturbing device (valve, elbow), but rather add straight pipe to the end of these fittings to meet the straight pipe requirements for your application. Meter Installation. After the meter fitting is installed in the pipeline, the meter can be installed in the fitting. Press the meter into the fitting as far as it will go. Retain the meter in place by inserting the u-pin. The pin can be installed from either side. It may be necessary to rotate the probe back and forth slightly to start the pin into the slots on the probe. Slide the pin in as far as it will go. Fitting Installation. Stainless steel and brass fittings have female pipe threads, requiring the appropriate male threaded fittings. Saddle fittings require a hole to be cut in the pipe (recommended hole size is 1-3/4 ). Before cutting into the pipe, observe the drawing below to choose your meter orientation. Caution: Never remove the u-clip retainer when the pipe is under pressure. Always remove pressure from the pipe before you attempt to remove the meter. Removal under pressure may result in damage or serious injury. Page 4

INSTALLATION STRAIGHT PIPE RECOMMENDATIONS (X = diameter) 10X 5X Reduced Pipe Two Elbows In Plane 10X 5X Two Elbows, Out Of Plane 20X 5X 20X 5X Expanded Pipe 30X Spiral Flow Propeller Meter 50X Swirling Flow Partially Open Butterfly Valve Page 5

INSTALLATION FULL PIPE RECOMMENDATIONS Better Installation: Ensures full pipe Possible Problem: Allows air pockets to form at sensor Possible Problem: Post-valve cavitation can create air pocket Better Installation: Keeps pipe full at sensor Possible Problem: Air can be trapped Better Installation: Allows air to bleed off Caution: These flow sensors are not recommended for installation downstream of the boiler feedwater pump where installation fault may expose the flow sensor to boiler pressure and temperature. Maximum recommended temperature is 130 F (Plastic), 200 F (Metal). Page 6

CONNECTION DIAGRAMS All Controls (FT415/FT420/AO55)(Except FT520) Red (+) 6-24 Vdc White (signal) Black (-) Sensor Input + s - Figure 1 PLC's and other non Controls Input Designed for Current Sinking (NPN) Devices Red White Black +DC Voltage Signal Ground NPN Device Figure 2 Input Designed for Current Sourcing (PNP) Devices 2.2k Ohm Pull-up Resistor Red White Black +DC Voltage Signal Ground NPN Device Figure 3 Page 7

OPERATION Minimum Flow. As with any other flow sensor, there is a rate below which the -Series sensor cannot read. Check the flow rate table below for the minimum flow rate detectable by the sensor for a given pipe size. Flow Range (Gallons per Minute) ½" ¾" 1" 1½" 2" 3" 4" 6" 8" Min 0.28 0.5 0.8 1.9 3.1 6.9 12 27 46.8 Max 28 50 80 190 314 691 1190 2700 4680 Flow Range (Liters per Minute) ½" ¾" 1" 1½" 2" 3" 4" 6" 8" Min 1.06 1.89 3.03 7.19 11.73 26.11 45.42 102.21 117.16 If a saddle or weld-type itting has been ordered, use the K-factor calculator at the bottom to determine the K-factor. In PVC, however, it is possible to order a saddle preinstalled on a standard length of pipe, and the fitting can be wet-calibrated in this case. Field Calibration. It is possible to field-calibrate an - Series flow sensor to determine an accurate K-factor in the actual installation. The reason for doing this would be to compensate for an unusual condition, for instance, applications with higher viscosity fluid (IP meters are calibrated for water use) or which lack adequate straight pipe ahead of the meter. Max 105.99 189.27 302.83 719.22 1188.61 2615.72 4504.64 10220.61 17715.73 Calibration ( K-factor ). The K-factor represents the number of pulses per gallon the meter produces during a flow test. This number must be entered into your electronic control to make it read properly. If the -Series meter is ordered with a tee fitting, it is factory-calibrated in the fitting and the K-factor is indicated on the side (see below). PRESSURE VS. TEMPERATURE (PVC/Polypro) 200 150 P.S.I. 100 50 60 70 80 90 100 110 120 130 140 K: 53.6 MF81T-P200 10031295 Find Your K-Factor Here Page 8

MAINTENANCE Caution: Never remove the u-clip retainer when the pipe is under pressure. Always remove pressure from the pipe before attempting to remove the meter. Removal under pressure may result in damage or serious injury. Rotor Replacement. It is unusual for a rotor to require replacement due to damage sustained in normal service. More commonly, the meter is dropped while it is out of the pipe. Another reason for rotor replacement is shaft wear after long service. Rotors are easily field-replaced. To install a rotor, follow these steps: 1. Unscrew the threaded bearing housings to expose the shaft ends. If bearings are being replaced, back them completely out. 2. Remove the rotor. Put the new rotor in its place. 3. Thread in one bearing housing part way, then the other. Take care to start the end of the shaft into the bearing hole before tightening further. 4. Screw in bearing housings until they bottom. Note: Do not use excessive force. 5. Check for free spin. Blowing lightly on the rotor should result in it spinning rapidly and coasting to a smooth stop. Sensor Replacement. It is very unusual for a sensor to require replacement in normal use. The primary cause of sensor failure is overvoltage (inadvertent connection of high voltage, for example) or incorrect polarity on hookup. The sensor is replaced by removing the strain relief, then threading out the sensor retainer plug. Remove the entire sensor capsule by pulling on the cable. The new sensor capsule can then be installed. Replace the retainer plug, and then replace and tighten the strain relief. Sensor Replacement 1) Loosen and unthread Strain Relief 2) Remove Sensor Retainer Plug by inserting a screwdriver blade into one side of the slot and turning 3) Remove the Sensor Capsule by pulling on the cable 4) Reverse the process to replace Signal Troubleshooting. The flow sensor has only one moving part, the rotor. If this is turning properly and there is no signal, the magnetic sensor is not operating properly. To check the signal, apply 12 Vdc power to the red (+) and black (-) leads. Set a multimeter to voltage reading. Put the positive multimeter lead on the red wire and the negative lead on the white wire. Slowly turn the rotor. Voltage reading should swing between -12 Volts and 0 Volts as the rotor turns. If it does not, the solid-state magnetic sensor is not working properly. Checking for continuity is not a useful test of these sensors. Page 9

PARTS EXPLOSION 4 OPTIONAL 7 8 1 2 3 7 9 10 5 6 11 12 14 15 13 -Series Parts List 1 Upper Housing 100662 2 Gasket 100411 16 MODEL SERIAL HPS MODEL SERIAL 3 Lower Housing 100502 4 Housing Screw Assembly 100414 5 Plug, Steel 100360 6 Plug, Plastic 100364 7 Strain Relief 101850 8 Sensor Retainer 100298 9 Sensor, Low Power 100419 10 Body * 11 O-Ring, EPDM 100264 12 Bearing Assembly (Qty 2 Included) 103315 13 14 Rotor (Nickel/Carbide Shaft) 100035 Rotor (Ceramic Shaft) 100036 Rotor Repair Kit (Kynar/Carbide) 100317 Rotor Repair Kit (Kynar/Ceramic 100043 15 Standard Fitting * 16 High Pressure Fitting * * Consult distributor Page 10

TROUBLESHOOTING Problem Probable Cause Try... No signal after installation Inaccurate metering Insufficient flow Bad connections to control electronics Incompatible control Damaged or missing rotor Failed magnetic sensor Not enough straight pipe between meter and severe flow disturbance Wrong K-Factor entered Magnetic sensor failing to pick up each blade Wrong time units on flow indicator Consult Flow Range Chart Reduce pipe size or use different sensor Check connections at control; Red (+), Black (-), White (signal) Use 6-24 Vdc power supply Add pull up resistor, if using currentsourcing device Remove flow sensor from fitting and check for free spinning; replace rotor See signal troubleshooting; replace magnetic sensor Move meter away from flow disturbance, or field-calibrate Check fitting for K-Factor, check indicator to see if it is entered properly ("Set K" on FT420, FT415, FT520) Remove flow sensor from pipe. If indicator is FT415, FT420, FT520, set K to 1.00, turn rotor slowly by hand, indicator should count each blade; replace sensor If using FT415 or FT420, check left side of display (sec, min, hr, day); change to desired unit Page 11 4/30/2015