Technical Description

Similar documents
EUROTHERM ONTROLS. Two phase thyristor power switches. Product data

For installation instructions refer to the mounting and dimensions details and the terminal layout drawings on page 5 of this manual.

MODEL 520 REMOTE START ENGINE MANAGEMENT SYSTEM

Functions provided by measuring relays in railway equipment

RE-PR3-E-86&105 3-Phase Panel Mount 86 and 105kW

Temperature Controllers

AUTOMATIC 12 WAY HEAT TREATMENT CONSOLE

Temperature Controllers

Burden Fuse Rating Resistor SAF / SAK6 1NM 10mm M8 12NM SAF / SAK10 2NM 16mm M8 12NM

ATevo SERIES BATTERY CHARGER

AT EVO SERIES BATTERY CHARGER

RU BMS Power Supply and Battery Management System Owners Guide

Control Relays Overview

Dycon D2430 EN54-4 Fire Alarm Power Supply Series

Q Range Watertight Single-Phase Electric Quarter-turn Actuators for part-turn valves and dampers

AT SERIES EVO BATTERY CHARGER

Application Engineering

Frost protection for pipes. 16 Technical handbook. Thermostat with line or ambient temperature sensor

5001TCP SPEED CONTROLLER

EVO AT SERIES BATTERY CHARGER

The Z Series. SCR Power controllers for resistance heating applications. Zero-Fired SCR Power Controllers AMPS VAC

V-SENSOR LOW AIR VELOCITY SENSOR

Current Switches and Transducers

HILLSTONE DC LOAD BANK

Tension Control Unit Type Product Manual EUROTHERM DRIVES. Copyright Eurotherm Drives Limited Printed in England HA Issue 3

5001TCP SPEED CONTROLLER

USER'S MANUAL MODEL DPD60001 MICROSTEP DRIVER PACK

Differential pressure sensor

Digital Pressure Regulator Sentronic PLUS Series 614

User Guide 4Q kW D.C.Motor Regenerative Speed Controller. Part Number: Issue Number: 3

PRODUCT / TEST MANUAL 2L9K2 BATTERY EARTH FAULT RELAY

CONTROLLER DIAGNOSTIC GUIDE

24V 3A EN54 Ancillary Power Supply

USER MANUAL GEBRUIKSAANWIJZING GEBRAUCHSANWEISUNG SKYLLA 24/100 3-PHASE CE

Installation and Maintenance Instructions. World Leader in Modular Torque Limiters. PTM-4 Load Monitor

DEEP SEA ELECTRONICS PLC

BLHV, BLHV-1. High Voltage Step Motor Driver. User s Guide. (714) fax: (714) website:

2.0 CONSTRUCTION 3.0 OPERATION. SA-1 Generator Differential Relay - Class 1E 2.5 TRIP CIRCUIT

EVO SERIES BATTERY CHARGER SERIES BATTERY CHARGER

A Caspian Technology Company all materials presented are trade mark and copyright protected by C.M.TECHNOLOGY Pty Ltd

99 Washington Street Melrose, MA Fax TestEquipmentDepot.com. Instruction Manual. Model 1672 Triple Output Power Supply

Harris IRT Enterprises Digital Resistance Tester Model XP

World Class Power Solutions. Rectifiers. For Stationary Battery Systems in Nuclear Power Plants

Industrial Chargers and

SERVICE MANUAL (DOMESTIC & INTERNATIONAL)

Pilot-Operated Proportional DC Valve Series D*1FH

Application Engineering

ATS22D88Q soft starter-ats22-control 220V-power 230V (22kW)/ V(45kW)

VT-SENSOR AIR VELOCITY AND TEMP

MODEL 540 USER MANUAL INCORPORATING MODEL 530 TEMPERATURE CONTROLLER

Type CDG 14 Extremely Inverse Time Overcurrent and Earth Fault Relay

DART Charger Product Description, Information and Specification

Power Supply EL

Phoenix Inverter

DEEP SEA ELECTRONICS PLC

AWT RANGE CONTROL AND MONITORING F ACILITIES. Publication E320E issue 10/02

Coleman Air Diversion Controller Model C40

3. OPERATION 2.1. RESTRAINT CIRCUIT 2.6. INDICATING CIRCUIT 2.2. OPERATING CIRCUIT 2.7. SURGE PROTECTION CIRCUIT 2.3.

HE-PSU(4.0) Power Supply & Battery Charger Installation, Commissioning & Operating Manual

fluid technology temperature sensors 1600 intelligent temperature sensor membrane keyboard, USB opto interface

4 x 0-10Vdc Channels Fused 24V o/p terminals for actuator power Direct or buffered output signals

CP-9301 CP Application. Features. Applicable Literature. Electronic Actuator Drives General Instructions

B BASIC HEAT TREATMENT CONSOLE

James Hamilton Electrical Pty Ltd (Inc in Qld) A.C.N trading as. Power Drive Systems. Generator Control Specialists

BATTERY CHARGERS.

4.0 OPERATION Type ITH-T Relay

AT30 SERIES BATTERY CHARGER

The High Power Stack Horizon

TABLE OF CONTENTS. 8.3 Online Sensor Specifications. Series TS (Models TS1, TSP, TSH, TSL,TSF, TSB1, TSB2) According to Electromatic factory procedure

TRAC-3 TENSION READOUT AND CONTROL

Digital Room Thermostats with Touch Screen LCD

KAPower Starting Module (KSM) With Programmable Logic Controller (PLC)

System 350 P352AB Electronic Pressure Control Series

Mclennan Servo Supplies Ltd. Bipolar Stepper Motor Translator User Handbook PM546

INSTALLATION & OPERATING MANUAL RW SERIES WALL-MOUNT RECTIFIERS

FurnaceDoctor -DPT Dewpoint Analyzer. User Manual Version 008

BLD75-1. Bilevel Step Motor Driver. User s Guide. 910 East Orangefair Lane, Anaheim, CA

University of Houston Master Construction Specifications Insert Project Name SECTION ELECTRONIC VARIABLE SPEED DRIVES PART 1 - GENERAL

Electrical Energy and Power Ratings

Pluggable interface relays RT, PT and MT range

MX431 Generator Automatic Voltage Regulator Operation Manual

Functions The Series 19 incorporates the following functions: Indicator Pushbutton Illuminated pushbutton

DEEP SEA ELECTRONICS PLC

Blank-off. HVAC unit screws. Spacer for 1" filter ILL. 3. Screw

BATTERY OPERATED DIGITAL MILLI-OHMMETER

Power Supply EL

Time Electronics DC Voltage Calibrator. Technical Manual

R & D SPECIALTIES ROTROL I USER'S MANUAL

Features IN THIS CHAPTER

Model No. DFC-X Support DIRECT FIRED DIGITAL TEMPERATURE CONTROL INSTALLATION, OPERATION, AND MAINTENANCE MANUAL

PURE PHYSICS ELECTRICITY & MAGNETISM (PART I)

27.6 Vdc 1 Amp Switch Mode Power Supply for Fire EN54-4:1997 +A1 +A2

INSTALLATION, OPERATION & MAINTENANCE SERIES ABC11B-120-XX BATTERY CHARGERS

XMLRM01G1P25 Pressure sensors XMLR -1 bar - G 1/4-24VDC ma - PNP - M12

CDBR-B. Dynamic Braking Unit Instruction Manual. April 2009 Part Number: R1 Copyright 2009 Electromotive Systems

Solid State Electronic Pressure Switch with Integral LED Display Model PSD-10

Digital Thermometers Instruction Manual MODELS 868 and 869

DEEP SEA ELECTRONICS PLC

MODEL 422 Submersible Pump Controller

Illuminator Series CR NEMA 3R

Transcription:

Technical Description LUL, 73 Stock Refurbishment Heating, Ventilating & Air-conditioning Multi-stage Thermostat for Saloon 0.1 19-May-02 ISSUED FOR DISCUSSION FK DC Rev. Date Description By Check Copyright 2002 This document contains proprietary information which is protected by copyright. All rights reserved. This document or parts thereof may not be reproduced in any form without written permission of the publishers. The information in this document is subject to change without notice and should not be construed as a commitment by Tactical Controls Limited. shall not be liable for errors contained herein or for incidental or consequential damages in connection with the furnishing, performance or use of this material.

Contents 1. Introduction...3 2. Interface to external equipments...3 3. The four-stage thermostat unit...3 4. Contactors...4 4.1 Contactors switchings...4 4.2 Ventilation fan-speed switching...4 4.3 Safe switching...4 4.4 Contactor coil suppressor...4 5. Diagnostic test facility...4 6. Heater earth fault...5 6.1 Heater Earth Fault Test (HEF Test)...5 6.2 Heater Earth Fault Test (HEF Test)...5 6.3 Heater Earth Fault Alarm...6 7. Sensor...6 8. Logic signals...6 8.1 Static converter demand signal...6 9. Static converter...7 9.1 Static converter fault alarm...7 9.2 Static converter ON indicator...8 10. Test and calibration...8 11. Wiring...8 12. Technical specification...9 13. Standards...11 14. Ordering information...11 15. Supplier information...11 APPENDIX A DRAWINGS: Temperature control unit model PTS, drawing number PTS\FACIAL PTS and PTC housing dimensions, drawing number PTS\DWG\BOX PTS and PTC lid, drawing number PTS\DWG\LID PTS connections, drawing number PTS\DWG\CONNECT PTS system block diagram, drawing number PTS\SYS\SYSTEM PTS system connection, drawing number PTS\SYS\CONNECT PTS system dimensions, drawing number PTS\SYS\BP PTS system phenolic cover's fixings, drawing number PTS\SYS\COVER PTS system control panel, drawing number PTS\SYS\PB Converter fault alarm mounting bracket, drawing number PTS\SYS\PB2 Auto-transformer, drawing number PTS\SYS\TX Platinum resistance probe, drawing number PTS\SYS\SENSOR System components layout, drawing number PTS\SYS\LAY-C0MP APPENDIX B INTERNAL WIRING LIST APPENDIX C PART LIST APPENDIX D TEST PROCEDURES AND RECORDS APPENDIX E CALIBRATION EQUIPMENT 73TS-DES.WPS Page 2 19 May 2003

1. Introduction The function of the thermostat system Model PTS-SYS is to monitor the Saloon air temperature and provides the heating and ventilation according to a pre-set temperature. At the heart of the system is the four-stage thermostat, stage 1 switches an external heater contactor off, stages 2, 3 and 4 provide low, medium or high speeds for the five ventilation fans (See drawing number PTS\SYS\SYSTEM for system block diagram). In addition, the system provides temperature simulation via a key-switch and potentiometer; there are also test facility for the heater earth fault unit and alarm indications. Briefly, the thermostat system Model: PTS-SYS comprises of: 1. a four-stage thermostat unit, Tactical Model: PTS, 2. two auto-transformers, 3. three Siemens 3TH4031-5C-E4-Z relays with built in varistor suppressors, 4. one row of 21-ways M5 stud terminal, 5. a blocking diode for static converter demand signal, 6. a control panel consisting of: a key-switch, two-push button switches, and a potentiometer. These components are mounted on a metal plate and basin, for details of which, refer to drawing number PTS\SYS\LAY-COMP. PTS-SYS and the four- For simplicity, thereinafter, we would refer the thermostat system as: stage thermostat unit as: PTS (Piccadilly-Thermostat - Saloon) 2. Interface to external equipments The PTS-SYS interfaces to two external pieces of equipment: 1. the Heater Earth Fault unit (HEF) and 2. two emergency fans and five non-emergency fans 3. The four-stage thermostat unit The function of the four-stage thermostat unit, model PTS, is to monitor the saloon air temperature and switches external contactors according to a pre-set temperature. The outputs of the PTS consist of four 16A Schrack relays; each relay has a normally open contact and switches according to the following temperature. On rising temperature: at 17 C stage one - heater OFF at 21 C stage two - ventilation and emergency fans run at low speed at 24 C stage three - ventilation and emergency fans run at medium speed 73TS-DES.WPS Page 3 19 May 2003

at 27 C stage four - ventilation and emergency fans run at high speed On falling temperature: at 16 C stage one - heater ON at 20 C stage two - ventilation and emergency fans OFF at 23 C stage three - ventilation and emergency fans run at low speed at 26 C stage four - ventilation and emergency fans run at medium speed 4. Contactors 4.1 Contactor switching The PTS has a four-stage relay outputs. These are used for: 1. stage 1 is used to switch a heater contactor with 115Vac 850Hz coil (the heater contactor is not part of the PTS-SYS). 2. stages 2, 3 and 4 are used to drive three Siemens 3TH4 contactors, with a 60Vdc coil; varistor suppressors are built into the contactor's coils. 4.2 Ventilation fan-speed switching Stages 2, 3 and 4 of the PTS outputs are used to drive three Siemens 3TH4 contactors for the purpose of switching the ventilation fan-speeds. The contactors switch three voltage tappings on the auto-transformers 135, 160 and 240Vac to give low, medium and high speeds respectively (see drawing number 83TS\SYS\CONNECT). 4.3 Safe switching A feature of the design is the inherent "safe switching" and this could be explained with reference to the System Block Diagram. These contactors switching arrangement and design ensures that should a contactor contact "weld-on" occurs, no damage or over-heating to the system would result, that is, it is not possible to short-circuit the auto-transformer winding. 4.4 Contactor coil suppressor The Siemens contactors, 3TH4031-5C-E4-Z 60Vdc coil, has a built-in varistor suppressor to the contactor's coil. Test conducted on the contactor's suppressor shows that it has a clamping voltage of 70Vdc. 5. Diagnostic test facility Built into the thermostat system, PTS-SYS, is the facility for providing simulated sensor temperature inputs to the PTS. This is achieved by: 1) a Craigg Derricott, rotary key-switch, for switching between sensor simulation and normal operations. 73TS-DES.WPS Page 4 19 May 2003

2) a potentiometer for sensor simulation. When the key-switch is switched to the normal mode (key removable), the unit senses the saloon temperature via the external sensor. When the key-switch is switched to the test mode, the potentiometer is switched to the thermostat unit sensor input and could be used to simulate a change in the saloon temperature. The potentiometer could simulate the temperature variation from 16 C to 27 C thereby enable the checking of the contactor switchings of the four-stage outputs; visual indications of outputs are given by four LED indicators on the thermostat unit. It must be borne in mind that for the sensor simulation to become operational, the Platinum Resistance Thermometer (PT100) must be properly connected - that is TC1 and TC2 are the shorted terminals at the sensor probe end. However, if the sensor is not connected, the test still could be simulated by simply shorting the TC1 and TC2 on the M5 stud terminal rail. During test mode, the key is not removable and that the key prevents the door of the compartment which houses the PTS-SYS, from closing. This prevents the key from accidentally left in the test position. 6. Heater earth fault 6.1 Heater Earth Fault Test (HEF Test) Simulation of Heater Earth Fault is made by depressing the normally open, green "HEF Test" button, located at the front panel of the system. When this button is depressed, it simulates an earth fault current by introducing a current imbalance in the Heater Earth Fault unit. An external resistor (Re) is connected between the thermostat system terminal number `92N' and the supply ground; Re is not part of the thermostat system (see PTS system connections, drawing number 83TS\SYS\CONNECT). The value of the resistor Re depends on the sensitivity of the HEF. When the "HEF Test" button is depressed, the `Heater Earth Fault' alarm (red) illuminates. 6.2 Heater Earth Fault Reset (HEF Reset) A normally closed "HEF Reset" push-button (red) is connected in series with the -52Vdc supply to the Heater Earth Fault unit (HEF) and externally connected to the M5 stud terminal number 92B (see PTS system connections, drawing number 83TS\SYS\CONNECT). When the "HEF Test" push-button (green) is depressed, it simulates an earth fault and the "HEF Fault" alarm indicator illuminates and could be reset by the "HEF Reset" button (red). When pressed, the red button disconnects the -52Vdc supply to the HEF, in doing so, it resets the HEF Fault alarm indicator- provided that the HEF Fault no longer present. 73TS-DES.WPS Page 5 19 May 2003

Note that the HEF unit is not part of the thermostat system, but it does require to interface with the PTS-SYS via the M5 stud terminal number 92B. 6.3 Heater Earth Fault alarm (HEF Alarm) The Heater Earth Fault alarm is a red LED indicator resides inside the thermostat unit. When an alarm occurs, a -52Vdc appears at the M5 stud terminal number 91D and the HEF Alarm indicator illuminates. When the thermostat system is fully connected to the locomotive; the HEF Alarm indicator could be tested by pushing the "HEF Test" button, as described under the section 6.1. 7. Sensor A platinum resistance thermometer sensor PT100 to BS1904 class A, with error not greater than +/-0.15 C, 3-wire connection, is connected to the PTS-SYS M5 stud terminal numbers TC1, TC2, TC3 and EE (see drawing number PTS\SYS\SENSOR for detail); EE is the screened cable of the sensor. The sensor is colour coded, TC1 and TC2 are red, TC3 is white and EE is green. A three core, 1mm square, screened cable to RSE\STD\024 type 8 is used. The sensor is supplied with 600mm of this cable. See Platinum Resistance Probe, drawing number PTS\SYS\SENSOR for further details. 8. Logic signals 8.1 Static converter demand signal Whenever the thermostat system output switches to fan cooling, this occurs when the temperature exceeds 21 C, low-speed fan cooling is called for; contactor RL3 is energised and generates a -52Vdc voltage via RL3 and diode D1, as shown in drawing number PTS\SYS\CONNECT. Note that the above condition could be simulated by using the diagnostic test facility as described in section 5. To test the diode, you may connect an external Siemens 3TH4 60V coil (A1 as marked on the contactor) to the terminal number 87 on the M5 stud terminal and the other end of the coil (A2) to the E terminal. The 3TH4 contactor should energised together with the RL3 contactor of the PTS-SYS system, when the temperature exceeds 21 C. The diode D1 acts as a blocking diode; there could be several similar diodes connected to a common Static Converter Demand signal line and any one of these diodes (cathode end) could be switched to the -52Vdc supply rail - in simple logic term, these diodes form the logic inputs to an `OR' CIRCUIT. 9. Static converter 73TS-DES.WPS Page 6 19 May 2003

9.1 Static converter fault alarm (Conv. Fault) This is provided by a filament bulb GEC Alsthom red indicator, 22mm round. An aluminium clad, 470R, 25 watt resistor is connected in series with the 24V bulb. When an alarm occurs, a -52Vdc is connected to the bulb and resistor; the voltage across the bulb is 15Vdc, to give the bulb a longer operating life. The connection of this alarm signal is made via the M5 stud terminal number 92YL, as shown in drawing number 83TS\SYS\CONNECT. The Static converter fault alarm is fitted to the trailer vehicle only. Use a DVM to measure the voltage across 92YL terminal, this should measure -52Vdc when the static converter alarm occurs and the GEC red lamp should illuminate. 9.2 Static Converter ON indicator (Conv. ON) The static converter ON is a green LED indicator resides in the PTS unit; the LED derives its power from an isolated winding (5Vac) of the auto-transformer. The green LED illuminates when 240Vac is present. 10. Test and calibration The multi-stage thermostat unit, model PTS, could be tested and calibrated in situ. All that is required is the Test and Calibration unit, model TC1000. Briefly, the TC1000 unit is housed in a carrying-case. The unit consists of a LCD display, a 10-turns potentiometer and a Derricott switch. Connection of the unit to the system is made via two mating pairs of 5-way Litton bayonet plug-socket connectors. The TC1000 unit's LCD display could display three different temperatures: 1. The saloon sensor temperature (Derricott switch in sensor-position). 2. The test temperature (Derricott switch in test-position) 3. The reference temperature (Derricott switch in sensor-position and reference resistor connected) Note that the reference resistor is connected to an independent bayonet free-plug and mates with the sensor-socket of the TC1000. The reference resistor value is 108.18 ohm (21 C) and uses a high precision, high stability resistor (15 ppm/ C). 11. Wiring All external wiring to the unit, PTS-SYS, is made via the 21-way M5 stud terminals and follow the cable markers from inside the unit. Refer to drawing number 83TS\SYS\CONNECT for the terminal connections. All internal wiring is given under Appendix B of this document. 73TS-DES.WPS Page 7 19 May 2003

12 Technical specification This technical specification relates to the Electronic Four-Stage Thermostat temperature sensing unit, model PTS. It is the heart of the PTS-SYS, which is the subject of this Manual, hence its detailed specification is given here. POWER SUPPLY Voltage -32 to -63 Vdc; -52 Vdc nominal. Ripple Unaffected by 2 volt peak to peak. Input protection Reverse polarity protection. Surges and transients to BRB/RIA 12. Low battery cut-out The unit outputs are inhibited when the supply voltage reaches 32.5 ±0.5 Vdc during a falling voltage and become enabled at 36 ±1Vdc during a rising voltage. Current consumption 170mAdc maximum at -33Vdc (when outputs 2,3 and 4 are on). 70mAdc minimum at -33Vdc (when all outputs are off) 110mAdc maximum at -52Vdc (when outputs 2,3 and 4 are on) 45mAdc minimum at -52Vdc (when all outputs are off). 105mAdc maximum at -63Vdc (when outputs 2,3 and 4 are on). 40mAdc minimum at -63Vdc (when all outputs are off). SENSOR One PT100 sensor, to BS1904 class A; sensor error not greater than ±0.15 C; third wire compensation against error due to lead resistance. Lead resistance error Less than 0.05 C error for every 10 meter of sensor cabling; (for copper cable cores 1mm square). Screened cable Sensor cable wires must be screened and connected to system earth. Interchangeability The temperature probes are easily detachable and interchangeable with sensor error altered by not more than ±0.15 C. Time constant 20 to 40 seconds when the sensor is subject to an air stream of 2m/s. INDICATORS Indicators DC supply 240Vac Heat output Low-speed Medium-speed High-speed Heater fault 7 LEDs are provided for indicating the status of the supplies, alarms and outputs. LED1, green; illuminates when the dc voltage -52Vdc is present. LED2, green; illuminates when the static converter supply 240Vac voltage is present. LED3, orange; illuminates when heat is ON. LED4, yellow; illuminates when low-speed in ON. LED5, yellow; illuminates when medium-speed is ON. LED6, yellow; illuminates when high-speed in ON. LED7, red; illuminates if and when earth fault occurs. RELAY OUTPUT Relays The unit has four relay outputs, type: Schrack RP330024, single pole. Contact rating The relays are rated at 250Vac, 16A. 73TS-DES.WPS Page 8 19 May 2003

Mechanical life Electrical life Greater than 30 million operations. Greater than 1 million operations at 52Vdc, 0.5Adc. OUTPUT SWITCHING On rising temperature at 17 C heater OFF. at 21 C ventilation and emergency fans at low speed. at 24 C ventilation fans and emergency fans at medium speed. at 27 C ventilation fans and emergency fans at high speed. On falling temperature at 16 C heater ON. at 20 C ventilation and emergency fans are OFF. at 23 C ventilation and emergency fans at low speed. at 26 C ventilation and emergency fans at medium speed. Accuracy Hysteresis Maximum drift the switching repeatability is within ±0.3 C of each setpoint on rising temperature. The switching hysteresis on the rising or falling temperature of each stage is in the range 0.7 to 1 C. Maximum of 0.3 C drift in switching temperature, over the temperature range of 17 to 27 C and 1.5 C drift over -15 to 55 C. ENVIRONMENT operating temperature-15 C to +55 C. storage temperature -30 to +85 C. relative humidity 0 to 90%. IP rating IP65 MECHANICAL Connector 1 Litton CIR030-18-19P-F80-T12, 10-ways rear panel mounted connector with pin contacts. The free-end of the connector being a socket type, CIR060F-18-19S- F80-T12 plug. Connector 2 (sensor) Litton CIR030-16S-8S-F80-T12, 5-ways, rear panel mounted connector with socket contacts. The free-end of the connector being a pin contact type, CIR06F-6S- 8P-F80-T12 plug. Sensor probe PRT100 to BS1904 class A Dimensions and fixing holes refer to drawing number: PTS\SYS\LAYOUT Housing material: sheet steel 16SWG. finish: grey hammer powder coat. 73TS-DES.WPS Page 9 19 May 2003

13. Standards RSE/STD/031-PART 1: ISSUE B, GENERAL REQUIREMENTS FOR ELECTRONIC EQUIPMENT BRB/LU/RIA NO.13:1990, GENERAL SPECIFICATION FOR ELECTRONIC EQUIPMENT USED ON TRACTION AND ROLLING STOCK. BRB/LU/RIA NO.12:1984, GENERAL SPECIFICATION FOR PROTECTION OF TRACTION AND ROLLING STOCK ELECTRONIC EQUIPMENT FROM TRANSIENT AND SURGES IN DC CONTROL SYSTEM. BRB/LU/RIA NO.18:1990, GENERAL SPECIFICATION FOR INTERFERENCE TESTING FOR ELECTRONIC EQUIPMENT USED ON TRACTION AND ROLLING STOCK. BRB/LU/RIA NO.20:1988, EQUIPMENT FOR VIBRATION AND SHOCK TESTING OF EQUIPMENT FOR RAILWAY VEHICLES. 14. Ordering information Ordering code: 83TS/PTS-SYS You are welcome to order the unit by code or by description - 83/PTS-SYS; LUL, Piccadilly Line 83 Stock Refurbishment Heating, Ventilating, Air-conditioning and Fan Switching Multi-stage Thermostat System for Saloon. 15. Supplier information Unit 4 Parkland Business Centre Lancing Business Park Lancing, West Sussex BN15 8TR England Tel: (01903) 750800 Fax: (01903) 750678 73TS-DES.WPS Page 10 19 May 2003