Position Switch Kits Accessory Kits for EntelliGuard* Retrofill Circuit Breakers

Similar documents
Programmer Disconnect Accessory Manual for Retrofil CB

GE Industrial Solutions Retrofill Door Assemblies for AKD-5, AKD-6, AKD-8 and AKD-10

Finger Cluster Replacement Parts Primary Disconnects for EntelliGuard* Retrofill Circuit Breakers

EntelliGuard Power Circuit Breaker Accessories. Network Interlock for Ampere Circuit Breakers. Introduction. Operation

EntelliGuard R Retrofill Application Guide

Operation and Maintenance Manual

GE Industrial Solutions. User/Installation Manual for 4.76kV -15kV SecoBloc

DANGER. Instruction Bulletin WARNING. Shunt Trip Kit for Manual DS/DSL Circuit Breakers POWER ZONE III Low Voltage Switchgear Class 6035 INTRODUCTION

GE Industrial Solutions. DEH Installation and Maintenance Manual AKD-20 AR / Entellisys AR Exhaust Plenum System

Installation, Operation, and Maintenance Manual Retain for Future Use. EntelliGuard G Circuit Breaker

ProTrip Conversion Kits. For GE Types AK-15, AK-25, and AKU- 25 Low-Voltage Power Circuit Breakers INTRODUCTION. DEH Installation Instructions

SecoVac * Ground & Test Device

Enclosure for AMP1 Series Energy Meters with Swing Panel Kit

Zone Selective Interlock Module. For GE Circuit Breakers

Effective June 2016 New Issue

Instruction Bulletin Dual Sub-Feed Circuit Breaker and Adapter Kit Installation onto an NQ Panelboard Class 1640

CR193 Vacuum Limitamp* Contactors

Low Voltage Power & Insulated Case Circuit Breakers

Test Cabinet (Inspection Box) Instructions. for Testing Accessories on Manually and Electrically Operated EntelliGuard G Low Voltage Circuit Breakers

www. ElectricalPartManuals. com Section 13 Switchgear Low Voltage

Instructions for installation, operation, and maintenance of medium voltage VC-W MR2 (integral racking)

Specification Guide. for RMAX. Direct Replacement. AC Low Voltage. Power Circuit Breakers

Two-way cable interlock kit for Magnum drawout circuit breakers

Vacuum Circuit Breakers (Vehicle) Type MSV 5kV. Instructions Installation Operation Maintenance SGIM-9988

Removal/installation instructions for Series NRX (IZMX) drawout levering (racking) mechanism

Spectra Series Power Panelboards. General. Installation. Bolt-On Circuit Breaker Kits. DEH059 Installation Instructions

Vacuum Circuit Breakers (Vehicle) Type FSV 5kV to 15kV. Instructions Installation Operation Maintenance SGIM-9968

SecoVac * R Retrofill Vacuum Circuit Breaker

Series A Construction

505 Size 5 Series A Construction

Vacuum Circuit-Breakers, Type HVX kv, of cassette design, cassette with motor drive

Mechanism Operated Contacts

Quick Connection Panel (QCP) Installation Guide

Distribution Cable Harness For Spectra RMS Molded-Case Circuit Breakers with microentelliguard TM, MicroVersaTrip PM or MicroVersaTrip Plus Trip Units

Bulletin 1494M Fixed Depth Remote Operated Disconnect Switches Renewal Parts

Vacuum Circuit Breakers (Vehicle)

Installation and removal instructions for Series NRX RF fixed breaker three-way Type 32 cable interlock kit

Installation Instructions for TMQV Circuit Breakers and Molded Case Switches

3-way multi-family drawout cable interlock kit - type 32 - RF

Ampgard medium voltage motor control renewal parts

Instruction manual. Type 3AH35-MA vacuum circuit breaker magnetic-actuator operator module.

Page 2 DS LOW VOLTAGE POWER CIRCUIT BREAKERS Digitrip Trip Unit Inside Wiring Guide Outside Wiring Guide Shutter Drawout Unit Position Indicator Escut

Vacuum Circuit Breakers (Vehicle)

Instruction Bulletin NF Panelboard Dual Sub-Feed Circuit Breaker Adapter Kit Installation onto an NF Panelboard Class 1670

GE Industrial Solutions. Limitamp * AR. Arc Resistant Medium Voltage Motor Control. Installation Guide

Instruction Bulletin. DS/DSL and DSII/DSLII Low Voltage Power Circuit Breaker Replacement Parts Class 6035

GEH-6259 Installation Instructions Voltage Conditioner Assembly

Specification Guide. for RMVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers

L Frame - Assembly Guidelines

Digitrip Retrofit System for ITE K-3000, K-3000 S, K-4000 and K-4000 S Breakers

Vacuum Circuit Breakers (Vehicle)

Advance design OEM L-Frames, cell kits, & enclosures Metal-clad switchgear components OEM catalog & pricing

Company Switch Installation Instructions and User Manual

Vacuum Circuit Breakers (Vehicle)

WESTINGHOUSE / CUTLER HAMMER DS POWER BREAKERS

SecoVac * R Retrofill

Power/Vac Vacuum Replacement Breakers for GE Magne-Blast Type AM & AMH Breakers

Instruction manual. Type 3AH35-MA vacuum circuit breaker magnetic-actuator operator module.

Power Break II Switchboard

Two-way cable interlock kit for Magnum fixed circuit breakers

SWITCHGEAR OPERATING PERSONNEL SAFETY UPGRADE SOLUTIONS FOR AGED INSTALLED BASE

GE Industrial Solutions. EntellEon * Low-Voltage Power Panel. Simple. Responsive. Revolutionary.

ibusway for Data Center

Power Break Circuit Breakers

Type 2 Arc Resistant WL Low Voltage Metal-Enclosed Switchgear

Vacuum Circuit Breakers (Vehicle)

MicroVersaTrip Plus and MicroVersaTrip PM Conversion Kits For GE Types AK-25 and AKU-25 Low Voltage Power Circuit Breakers

Power delivery for industrial facilities

MANUAL ELECTRIC FIRE PUMP CONTROLLERS METRON SERIES M450

Vacuum Circuit Breakers (Vehicle) Type HKR 7.5kV to 15kV. Instructions Installation Operation Maintenance SGIM-9928C

Q-Frame Main Circuit Breaker (225 A Maximum) and Adapter Kit Installation onto an NQ Panelboard Class 1640

DEF 005. WavePro Power Circuit Breakers A Frames, Vac. Renewal Parts

8300 Series Installation Guidelines

AKD-20 Low-voltage Switchgear

Bussmann series Quik-Spec Power Module Switch elevator disconnect

Low Voltage WavePro TM and EntelliGuard TM Circuit Breakers Remote Racking Operator

The safest, most reliable Switchgear in the market today

Page 1 of 9 Knowledgebase Technote ID # Q /24/2006

Digitrip Retrofit System for Siemens-Allis RLX-1600 Breakers

When the ACB is CLOSED and in the connected position the draw-out handle cannot be inserted.

PROCEDURE FOR EVALUATION OF THE INTEGRITY OF THE FIXED PARTS

Low Voltage Power Circuit Breaker

S&C Type FVR Substation Circuit Breaker

CATALOGUE SPARE PARTS AND RETROFIT KITS FOR AIR CIRCUIT BREAKERS AND TRIP FREE SWITCHES

SecoVac * Vacuum Circuit Breaker

www. ElectricalPartManuals. com Digitrip Retrofit System for Allis-Chalmers LA-4000 F Fused Breakers IL 33-A1K-1 WARNING

Bussmann series Quik-Spec Coordination Panelboard

Dead Tank Outdoor Vacuum Circuit Breaker, Type VOX

COOPER POWER SERIES. QD5 Quik-Drive tap-changer reversing neutral stationary contact asssembly kit A26 installation instructions

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation

SUBSTATION VACUUM CIRCUIT BREAKER (38KV)

Digitrip Retrofit System for the ITE LG-3000 (Frameless) Circuit Breaker

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV)

SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV)

700 Type P & PK DC Relays Timer Units Latch Units Series A and B Construction. Renewal Parts

T- VACR Fixed (up to 40kA) T-VAC Draw out (up to 40kA)

GE CONSUMER & INDUSTRIAL

Cutler-Hammer. Instructions for Potential Transformer and Auxiliary Control Power Disconnecting Means for Use in Ampgard Lineups, 7.2 kv I.B.

Instruction Manual LongArm ABL3 Remote Operator for Medium Voltage Allen-Bradley Centerline** Motor Control Center Units

Introduction. Installation. A Series Lighting Control Panelboards. DEH41081 Installation Instructions

Transcription:

GE Industrial Solutions Position Switch Kits Accessory Kits for EntelliGuard* Retrofill Circuit Breakers This position switch actuator, mounted on the cassette using simple hardware, is an actuator or actuator bracket. It makes a strong contact with the position switch assembly when the racked-in breaker provides mechanical pressure against the arm.

Table of Contents Related Publications... 2 Estimated Time to Complete Tasks... 2 General Description... 2 Ordering Info... 4 Compartment Switch Options... 4 AKD-5 AK25 Position Switch Actuator... 4 Description... 4 AK25 Cassette... 5 AKD-5 AK50 Position Switch Actuator... 6 Description... 6 Installation... 7 AKD-6 Position Switch Actuator... 8 Description... 8 Installation... 8 AKD-8/10 Position Switch Actuator... 8 Notes... 10 Page 1 of 11

Related Publications Publication Brochure Snapshot Installation Manual AKD8 Installation Manual AKD6 Installation Manual AKD5 Accessory: Door Interlock (Door Interlock Kit) Accessory Retrofill Doors Assembly Accessory: Position Switch Plate & Position Switch Assembly & Wiring (Position Switch Kit) Accessory: Neutral Rogowski CT Disconnect (Neutral Assemblies) Accessory: Programmer Disconnects Accessory: Finger Clusters (Cluster Assemblies) Accessory: Secondary Disconnects FAQ Application Guide Guideform Spec Spare/Renewal Parts Guide Publication Number DEA-532 DEE-543 DEH-41549 DEH-41548 DEH-41547 DEH-41529 DEH-41563 DEH-41531 DEH-41532 DEH-41533 DEH-41534 DEQ-171 DET-753 DET-754 DET-755 Estimated Time to Complete Tasks It takes about 15 minutes to install or replace the assembly. General Description For the retrofill, the following information is for either installing or replacing the mechanism for the position switch (not the position switch itself) on the retrofill circuit breaker; the position switch assembly is already mounted in the compartment; if not, it can be ordered as an option. The mechanical subassembly is a simple ancillary lever-and-tension device that pushes against the position switch arm when the retrofill breaker is racked in completely. This device, mounted on the cassette using simple hardware, is called the actuator or actuator bracket. Its purpose is to make a strong contact with the position switch when the racked-in breaker provides mechanical pressure against the arm. The mechanical force on the lever and tension mechanism then activates the position switch. The position switch, when activated, determines that the racked-in circuit breaker is connected. Figure 1 is an example of an installed position switch. It is activated mechanically when the breaker is racked in. Page 2 of 11

Figure 1. Position Switch, an Example The mechanical subassembly comes with mounting hardware, lever, and bracket. Depending on the switchgear, this simple device is mounted in different locations. Turn off all power to switchgear. Tagout and lockout main source, up-stream or main breaker. Failure to comply with these instructions will result in death or serious injury from severe burns caused by arc flashing that has exceedingly high temperatures. Always wear personal protection equipment according to OSHA standards and appropriate to the severity of potential burns. Ensure only qualified personnel install, operate, service, and maintain all electrical equipment. Note: It is strongly advised that the LVS (low voltage switchgear) be completely de-energized before you assemble and mount the position switch actuator. The compartment position switch assembly is not part of the retrofill kit. If the customer desires to install or replace a position switch assembly in the compartment, the customer can order it separately. Refer to Table 1. Page 3 of 11

Ordering Info Table 1. Retrofill Portion Position Switch Assemblies Ordering Information AK50 10106296G1 Position Switch Actuation Assembly AK50 / AKT50 AK25 10106269G1 Position Switch Actuation Assembly AK25 AKD6 10106480G1 Position Switch Actuation Assembly AKD6 (Later models No Sep. Order Req d) AKD8 Not Applicable No separate order required. AKD10 Not Applicable No separate order required. Compartment Switch Options Available as an option for mounting within the base of the cassette/substructure or compartment, the position switch provides six single-pole changeover contacts for local or remote electrical indication of the circuit breaker status: CONNECTED, TEST, and DISCONNECTED. The DISCONNECTED position is indicated only when the minimum isolating distances between contacts on both the main (primary disconnects) and auxiliary (secondary disconnects) have been achieved. This option is in addition to the mechanical indicators, which are fitted as standard components. When installed, the switch is IP2X-protected and includes wiring to a terminal block on the left side of the cassette. Table 2 displays the available normally-open and normally-closed switches. The ratings for position switches are shown in Table 3. Table 2. Position Switches Table 3. Position Switch Ratings (Common NO/NC Contact Configuration) Switch Configuration Catalog # Ratings One NO/NC switch per position GCPS1R AC 120 Vac 6 A 250 Vac 6 A Set of two NO/NC switches per position GCPS2R DC 125 Vac 0.5 A 250 Vac 0.25 A AKD-5 AK25 Position Switch Actuator Description The position-switch actuator assembly for the AK25 should be mounted on the bottom plate of the cassette assembly of the AK25 retrofill. The actual actuator assembly consists of two plates, one each on the top and bottom of the baseplate. The top plate of the actuator interfaces with the breaker when it is racked in and its motion is transferred to the bottom plate, which interfaces with the position switch lever on the legacy compartment. Completing the racking in of the EntelliGuard breaker into the cassette corresponds to the end-of-stroke of the position switch system in the compartment for AK25 in AKD-5 LVS. Figure 2 shows the exploded view of the AK25 retrofill position-switch actuator (actually a bracket assembly); Figure 3 displays the assembly from the bottom. Page 4 of 11

Figure 2. AKD-5 AK25 Retrofill Breaker, Actuator for Position Switch Assembly (Exploded View) Figure 3. AKD-5 AK25 Retrofill Breaker, Actuator for Position Switch Assembly (Bottom View) AK25 Cassette Note: While racking the EntelliGuard ACB breaker into the cassette, while actually racking in the breaker, the position indicator window begins to read connected. This position indicator means that the retrofit system has activated the existing position switch in the LVS. Installing the position switch actuator needs to be done before the cassette is racked into the compartment. Steps for installing the position switch actuator are as follows: 1. Place the retrofit EntelliGuard ACB cassette assembly for AK25 on an elevated surface, such as a table, to mount the position switch actuator assembly on to the base plate. Sufficient space should be available at the bottom of the cassette and the mounting table to provide easy access for inserting the 3-pin bracket from the bottom. 2. Unpack the position switch actuator components and mount them as shown in the exploded view in Figure 4. Page 5 of 11

Figure 4. AKD-5 AK25 Retrofill Breaker, Actuator for Position Switch Assembly (Top View) 3. Insert the 3-pin bracket from the bottom of the base of the cassette assembly, such that the two pins are within the longer slot and the single pin goes inside the smaller slot of the plate. 4. Place the L-bracket from the top of the cassette assembly, such that the pins from the bottom 3-pin plate get inserted into the top plate. 5. Secure the connection by fastening the nuts and washers provided in the actuator kit. 6. Mount the extension springs between the groove of the pin on this actuator assembly and the fixed pin provided on the cassette base plate. 7. Check that the position switch actuator on the cassette is now installed and ready to function as the breaker is being racked in the compartment. 8. Mount the cassette assembly on the rails of the AK25 cabinet in the AKD-5 and rack the cassette into the compartment of the AKD-5 LVS. AKD-5 AK50 Position Switch Actuator Description The position switch actuator assembly for the AK50 should be mounted on the bottom right side of the cassette assembly of the AK50 retrofill. The actuator assembly consists of a linkage system that interfaces with the racking shaft assembly at one end and the position switch actuator arm at the other. Completing the racking in of the EntelliGuard breaker in the cassette corresponds to the end-of-stroke of the position switch system in the compartment for AK50 in AKD-5 LVS. Figure 5, below, shows the AK50 position switch actuator assembly in an exploded view. The position switch actuator for the AK50 is a field-fit type of assembly and is assembled on the retrofill cassette before inserting the cassette into the compartment of the AKD-5. It needs to be ensured that the cassette is in the disconnected state. This can be verified by checking the racking position status in the window located at the right side window, located on the frame of the AK50 retrofil cassette, placed at the front. The position-switch actuator kit for the AKD5-AK50 retrofits needs to be installed on the bottom rear side of the right side sheet of the AK50 retrofit cassette. Page 6 of 11

This installation can be done by placing the cassette on a work table. The cassette should be placed such that there is enough overhang of the side where there s room to insert the position switch actuator components from underneath. Alternately, the installation can also be achieved by placing the cassette assembly on the retrofit AK50, that is, on the telescopic rails of the AKD5 compartment that is being retrofit. Installation 1. Once the access for installing the position switch actuator is achieved, slide the assembly up from the bottom of the cassette. When inserted, the plate is placed on the outside of the cassette side sheet and the movable flaps are on the inside. 2. Line up the holes on the cassette side sheet with the holes on the actuator assembly. 3. Fasten the three M6-bolts and 6-mm washers, provided with the actuator assembly, to the three holes on the cassette side sheet. Two holes are placed on the side and one hole on back of the cassette assembly. 4. Check that the position switch actuator on the cassette is now installed and ready for use as the breaker is being racked into the compartment. 5. Mount the cassette assembly on the rails of the AK50 cabinet in the AKD-5 and rack the cassette into the compartment of the AKD-5 LVS. Note: While racking the EntelliGuard ACB breaker into the cassette, as you rack in the breaker, the position indicator window reads connected. This position indicator means that the retrofit system has activated the existing position switch in the LVS. Figure 5. AKD-5 AK50 / AKT50, Actuator for Position Switch Assembly (Exploded View) Page 7 of 11

AKD-6 Position Switch Actuator Description Position switch actuator bracket can be installed on all versions of Retrofill EntelliGuard ACB for AKD6 LVS. Steps for installing are below: Retrofills use the legacy position switch already mounted in the cubicle. If a new position switch has to be installed, refer to legacy position switch installation manual. Installation 1. Unpack the position switch bracket. Each bracket is provided with a pair of M6X16mm Allen-type bolts and washers. 2. Place the bracket on the bottom right side of the AKD6 base. 2 locating holes are provided for mounting of the position switch bracket. 3. Fasten the 2 bolts to the locating holes after placing the washers so securely mount the bracket 4. The bracket is ready for use. Note: Individual hardware for the position switch actuator cannot be ordered separately. The item numbers given below are for reference only (Table 4). The assembly comes as a unit or a kit. Order the actuator assembly by part number. Table 4. AKD-6 Position Switch Actuator Components Level Item or Part Number Description Quantity 1 10105289P1 POSITION SWITCH BRKT, AKD6 1 1 10100950P4 WASHER M6 2 1 10100380P1 SERRATED BELLEVILLE WASHER M6 2 1 10100545P1 CAP HEAD SCREW M6X16 2 AKD-8 Position Switch Actuator Position switch actuator comes pre-installed on all versions of Retrofill EntelliGuard ACB. Therefore, no installation is required (Figure 6). Retrofills use the legacy position switch already mounted in the cubicle. If a new position switch has to be installed, refer to legacy position switch installation manual. Page 8 of 11

Figure 6. AKD-8/10 Actuator for Position Switch Assembly (Exploded Views) Page 9 of 11

Notes Page 10 of 11