SDM72 Start on Demand Modules

Similar documents
REVISED ATM72 Auto Transfer Module

PSM72H Push-Button Start Module

EPM72 Engine Protection Module

BVF300 'Special' Battery Voltage Monitor

SUM340 SUMMATION BOARD

DEEP SEA ELECTRONICS PLC

GCU-10. Automatic Engine Control Unit Operators Manual

DEEP SEA ELECTRONICS PLC

702 AUTOMATIC START MODULE OPERATING INSTRUCTIONS

MODEL 520 REMOTE START ENGINE MANAGEMENT SYSTEM

DEEP SEA ELECTRONICS PLC

GL1200T Cut & Seal. (GL1200 Seal only)

DEEP SEA ELECTRONICS PLC

ECU-02 Ver2.1 Automatic Engine Control Unit Operators Manual

HGM1780. Automatic Genset Controller USER MANUAL. Smartgen Technology

DEEP SEA ELECTRONICS PLC

AUTOSTART 705S V1.00 AUTOSTART 710S / 720S / 730S V1.04 Programming Reference and Check Sheets

Crompton Controls. This is. Installation and Maintenance Instructions. S10 & Smooth-BRAKE DC Injection Brake Modules. Tel: +44 (0)

MX431 Generator Automatic Voltage Regulator Operation Manual

GL1200T Cut & Seal. (GL1200 Seal only)

DKG-114 MANUAL AND REMOTE START UNIT

KV4-300 mk2. KV5-200 mk2. KV5-100T mk2. KV3-250 mk2

GENSET CONTROL MODULE A121H / A241H. User selectable time delays for engine start and engine stop (cool down).

OPERATING AND MAINTENANCE MANUAL. Primary Current Injection Test Set. 750ADM-H mk2

5220 AUTOMATIC MAINS FAILURE MODULE OPERATING MANUAL

Dycon D2430 EN54-4 Fire Alarm Power Supply Series

Deep Sea Electronics Plc

K25000 & KD25000 Series

HGM72 Automatic Generator Module OPERATING MANUAL Smartgen Electronic

GENSET CONTROL MODULE LEVEL 1 A121CM / A241CM. Special logic to re-establish cranking following a false start.

Installation and Maintenance Instructions. World Leader in Modular Torque Limiters. PTM-4 Load Monitor

GENSET CONTROL MODULE A121A / A241A

HGM1780 AUTOMATIC GENERATOR MODULE CONTENT 1. SUMMARY PERFORMANCE AND CHARACTERISTICS SPECIFICATION OPERATION...

PRODUCT / TEST MANUAL 2L9K2 BATTERY EARTH FAULT RELAY

DEEP SEA ELECTRONICS PLC

HGM7100N SERIES (HGM7110N/7120N) GENSET CONTROLLER USER MANUAL

AA4006 Speed Sensitive Trip Unit. User Manual

MD10. Engine Controller. Installation and User Manual for the MD10 Engine Controller. Full Version

Approved Standards. Motor Contactor. Main contactor. Accessoires. 21 Motor Contactor J7KN

Application Engineering

USER MANUAL FOR GC500 GENSET CONTROLLER SEDEMAC ABSTRACT

SDS Enclosed Star-Delta Starter User Guide

Standby Amper VOLTAGE

Te 803 Electronic Controller. Service, Operation & Technical Information Manual

HGM72 Automatic Generator Module OPERATING MANUAL Smartgen Electronic

60 Series Engine Controls

Open Chassis Star-Delta Starter User Guide

James Hamilton Electrical Pty Ltd (Inc in Qld) A.C.N trading as. Power Drive Systems. Generator Control Specialists

Application Engineering

ACSI MODEL 1406BB-04-AO POWER SUPPLY INSTALLATION INSTRUCTIONS

HGM6320T AUTOMATIC GENERATOR CONTROLLER USER MANUAL

Electrical Energy and Power Ratings

Deep Sea Electronics Plc

INDUSTRIAL CHARGER AUTOMATIC BATTERY CHARGER SERIES 150 KUSSMAUL ELECTRONICS CO., INC. MODEL # XX YEAR WARRANTY INSTRUCTION MANUAL

FC/FCA 12, 24, 32 & 48 VOLT, 6 & 10 AMP BATTERY CHARGER OPERATION & MAINTENANCE GUIDE

RE-PR3-E-86&105 3-Phase Panel Mount 86 and 105kW

HGM1770 Automatic Generator Control Module OPERATING MANUAL Smartgen Electronic

SE-3SCR-LM MANUAL MOTOR LOAD MANAGER

1 Phase electronic contactor (SC 1)

Art. No. EC-315. Art. No. EC-330. Art. No. EC-340 SWITCH-MODE BATTTERY CHARGER CONTENTS IMPORTANT SAFETY PRECAUTIONS... 2

ASYN205B Central Synchronizing Controller

HGM6410/6420 AUTOMATIC GENERATOR MODULE WITH J1939 INTERFACE SOFTWARE MANUAL

Installation Manual for D154X Series Multi-Indicator, General Purpose Power Supplies

ICON 2 1. FEATURES AND CHARACTEIRICS

HGM1750 Genset Security Module USER MANUAL Smartgen Technology

320 to 327 M Series Low and Medium Voltage Motor Protection Relays

Timer Relays - Fixed & Adjustable

Phoenix Inverter

1 Safety instructions. 2 Intended use. 3 Product characteristics. 4 Operation. System Universal LED dimming insert Standard

CI-TI Contactors and Motor Starters Type CI 6-50

Dycon D1532SM. EN50131/PD6662 Grade 3, 12V 2A Power Supply. Technical Description Installation and Operating Manual DYCON POWER SOLUTIONS LTD

DEEP SEA ELECTRONICS PLC

InteliCharger V 20A Intelligent Automatic Battery Charger

INSTALLATION, OPERATION & MAINTENANCE SERIES ABC11B-120-XX BATTERY CHARGERS

SALDET SALES & SERVICE, INC. CLINTON TOWNSHIP, MICHIGAN

Battery Control Center - Diesel

HGM6320T AUTOMATIC GENERATOR CONTROLLER USER MANUAL

Standby Amper VOLTAGE

HE-PSU(4.0) Power Supply & Battery Charger Installation, Commissioning & Operating Manual

MANUAL ELECTRIC FIRE PUMP CONTROLLERS METRON SERIES M450

ES5 Security Theory/Regulations Answer Schedule

SECTION MOTOR CONTROL

KD LV Motor Protection Relay

Designed for ease of integration with automation systems

CI-TI Contactors and motor starters Types CI 61 - CI 98

4 x 0-10Vdc Channels Fused 24V o/p terminals for actuator power Direct or buffered output signals

GSC300. Auto Start Engine Controller. Installation and User Manual for the GSC300 Auto Start Engine Controller. Full Version

HGM501 Gen-set Controller USER MANUAL. Smartgen Technology

Burden Fuse Rating Resistor SAF / SAK6 1NM 10mm M8 12NM SAF / SAK10 2NM 16mm M8 12NM

CONTROLLER DIMENSIONS

ES52. Auto Start Engine Controller. Full Version. Installation and User Manual for the ES52 Auto Start Engine Controller.

Micro Controller based Motor Protection Relay & Motor Management System

Energy Division

SHORT-STOP. Electronic Motor Brake Type G. Instructions and Setup Manual

GSC300 Auto Start Engine Controller

HGM6000K Series Automatic Generator Module OPERATING MANUAL Smartgen Electronic

Installation Contactors RIC, RAC

GENSET CONTROL MODULE LEVEL 0 A120A. User selectable time delays for engine start and engine stop (cool down).

CONTROL, PROTECTION AND VISUALIZATION ELECTRONIC MANUAL CEN- TRALITE FOR GENERATING SETS CMD2.0

1 Safety instructions. 2 Intended use. 3 Product characteristics. 4 Operation. LB management. Universal touch dimmer insert LED

Transcription:

Capricorn Controls DA04SDM72-2 Revised Design Page 1 of 6 SDM72 Start on Demand Modules Genset Controls - Timers - Monitors - Trips - Battery Charging - Spares & Accessories - Custom Products Application Start-on-Demand, also known as Auto-on-Demand, enables base load applications to only operate when a demand for power is present. This system is typically used in remote locations such as Farm Houses, Hunting Lodges and Pumping Stations. Although designed and described here for use with the RSM72 Remote-Start-Module, the SDM72 can easily interface with almost any Electric Start engine controller. Revised Design New Case, injection moulded to our own design. Two Tri-colour LED s provide additional status information Rear mounted fuse holder for Term.32 protection. Current and temperature protected relay driver output on Term.31 Operation Standby Mode Plant Run Plant on Load Plant off Load Plant Stop Manual Mode Plant stationary, the top LED is lit Green for standby, indicating that the DC Excitation voltage is connected to the dead AC Bus via term.32. Whenever a load with sufficiently low DC resistance, i.e. a 60W light bulb, central heating pump, refrigerator etc, is connected to the dead AC Bus, the top LED will change from Green to Amber indicating that a demand for power is present with the Excitation voltage still applied to the dead Bus. The bottom LED will light Green to indicate that the Run Relay is energised. The volt-free contacts of this relay are used to start the engine via the RSM72 Remote Start Module or other suitable Engine Controller. As the engine runs up to speed, the Excitation voltage is disconnected from the dead AC Bus prior to the contactor control relay energising. This will happen once the alternator has attained a pre-set voltage for approx. 3 sec. and once energised, this relay cannot de-energise if the alternator voltage falls. If low voltage protection is required then an external voltage monitor must be added. Load current is continually monitored via the CT100S current transformer and the set will continue to supply the load until the last load (i.e. 60W Bulb) is switched off. Whenever the load current falls below the Load Threshold, the top LED will be unlit, indicating that there is no longer a demand for power. If this remains the case for the duration of the Run On (on Load) Timer, the contactor control relay will de-energise; disconnecting the load. However, if a Load Demand is received during the Run-on time, this timer will be reset and the contactor will remain energised. Provided that a Load Demand is not received for the period of the Stop Delay, the Run Relay will de-energise, to stop the engine (Note: if a Load Demand is received during this Stop Time, the Load Contactor will re-energise). After the Run Relay has de-energised and subject to the loss of the AC voltage for a period of 5 sec (run-down timer) the SDM72 will revert to Standby Mode with the top LED lit green. The Manual input energises the Run relay, enabling the SDM72 to operate the contactor control relay when the engine is started manually from the RSM72. Auxiliary Demand As an example, a BVF300 Battery Voltage Monitor can be connected to term.30 of the SDM72 to provide Demand for power to start the set and / or to prevent it from stopping in order to keep the batteries charged see page 3. Designed & manufactured in England by Capricorn Controls Telephone: +44 (0) 1295 272360 Fax: +44 (0) 1295 264766 E-mail: sales@capricorncontrols.com

Page 2 of 6 CONNECTIONS Always ensure that the correct wire sizes are used and that all terminals are tightened correctly. Terminal Description Input / Output Connect To ------ 21 B+ +Ve Supply Input RSM72, Term.17 (Auto Mode +Ve O/P) 22 B- - Ve Supply Input Battery -Ve 23 Run Relay N/C contact Volt Free Contact * (not normally required with RSM72 ) 24 Run Relay C/O contact Volt Free Contact * RSM72, Term.17 (Auto +Ve O/P) 25 Run Relay N/O contact Volt Free Contact * RSM72, Term.18 (Run, +Ve I/P) 26 MANUAL Manual Input +Ve Input RSM72, Term.11 (Manual, +Ve O/P) 27 INT Interlock - Ve Input RSM72, Term.14 (Alarm O/P) 28 Lamp Test +Ve Lamp Test Supply +Ve Input External Lamp Test input 29 Alt. On Load Alternator On Load Status - Ve Input Standby Contactor (n/o Aux. contacts) 30 Aux. Demand Auxilliary Demand + Ve Input i.e. BVF300 Batt. Volts Monitor 31 Relay External Relay - Ve Output *** 3-phase application - see page 4 32 Load Sense DC Excitation / Start Sensing + Ve In / Out ** see pages 3 & 4 33 C.T. CT100S AC current Input see page 3 34 C.T. (secondary) AC current Input see page 3 35 N/O Contacts * Standby Contactor Coil SCR 36 Standby Control Relay N/O Contacts * see pages 3 & 4 37 ALT. (L) Alternator Voltage Sensing A.C. Input Main Alternator (280VRMS max) 38 ALT. (N) Alternator Voltage Sensing A.C. Input Main Alternator NOTE : * De-rate to 14% for Inductive Loads (i.e. 16A resistive = 2.2A holding current to allow for 7X inrush). ** DC Excitation is protected by an internal fuse see below. *** Current limited and temperature protected relay driver. CT100S This special current transformer is supplied with the SDM72. It is suitable for all load currents (subject to the output cable diameter). However, if the SDM72 is to be used with a large or multi-set system we recommend that the CT100S is connected to an auxiliary load rather than the main load. WARNING: Relay Contacts Although the on board relays are quite capable of directly switching small solenoids and contactor coils, we would recommend that slave relays are always used as a matter of course unless the Inrush & holding currents are known and are within the specification of the SDM72 contacts. In line with other manufacturers, we quote contact rating current for a resistive load. However, if the load is inductive (relay, solenoid, contactor coil or unknown ) the quoted current must always be de-rated to 14%. Example: a quoted rating of 16A 2.2A continuous current to allow for a 'seven times' inrush, when the inductive load is energised. WARNING: Safety Circuit Although several levels of protection are provided, please ensure that the DC Sensing voltage on term.32 is NEVER connected to a live (AC) Bus. Such action may permanently damage this module and possibly other equipment as Voltages dangerous to human life will be connected to the DC control circuits. WARNING: Voltages dangerous to human life Voltages dangerous to human life may be present at some of the terminal connections of this unit. Ensure that all AC and DC supplies are isolated before attempting any connection / disconnection. REAR VIEW Pull out to access the 100mA QB 20mm Fuse that protects Term.32. A spare fuse is also located here. DESIGN CHANGES INCLUDE > Solid Back panel with Fuse Holder > Connectors are now mounted vertically E. & O. E. The Proven Solution to Power Controls DA04SDM1-2

Capricorn Controls DA04SDM72-2 Revised Design Page 3 of 6 LOAD L N A Typical Single Phase System Single phase application shown for clarity Battery Ve SDM72 Start on Demand RSM72 Remote Start C1 31 Relay B+ 21 32 Sense B- 22 16 Aux LOP 1 12 Meter + HET 2 CT100S Twisted pair 33 CT n/c 23 34 CT c/o 24 13 PreHeat Starter 3 17 Auto+ B+ 4 C1 35 n/o 25 36 Man 26 18 Start + Fuel 5 11 Man + B-- 6 37 Alt. Int. 27 14 Alarm Exc 7 Metering 38 Alt. LT 28 AOL 29 Aux. Demand 30 19 LT+ CF 8 15 SW+ AC 9 AC 10 (Optional) L N ALTERNATOR B+ BVF300 B -- Battery Voltage Monitor C1 Battery Ve Battery +Ve SYSTEM DESIGN RULES Refer to the RSM72 Data & Application Note for generic Engine wiring, instructions & constraints. Refer to the BVF300 Data & Application Note if this part is to be used. Ensure that both the Alternator Neutral and the Battery Negative are bonded to Earth. Ensure that all metering is connected to the Alternator side of the Contactor NEVER push the contactor closed Terminal 32 is now fused internally. Fuse carrier complete with spare fuse is at rear of module. Load Contactor C1 requires two auxiliary contacts (1 x n/o + 1 x n/c) Load Contactor C1 will require 3 poles in a 3 phase application. DO NOT SWITCH THE NEUTRAL. If a switched or isolated neutral is required, please contact the Sales Desk for further information. See overleaf for: output metering (i.e. kwh) & / or 3-Phase application Designed & manufactured in England by Capricorn Controls Telephone: +44 (0) 1295 272360 Fax: +44 (0) 1295 264766 E-mail: sales@capricorncontrols.com

Page 4 of 6 OUTPUT METERING L ALT Contactor Coil kwh Meter (example) L LOAD N N Term.35 Term.32 Single Phase shown for clarity 3 PHASE APPLICATION n/c auxiliary on main Contactor C1 Term.32 Load Sense Term.31 (Relay -Ve) Small DC contactor 5A A/S Fuses x 3 to protect contacts Term.21 (Batt +Ve) L1 L2 L3 To Load Terminals ORDERING INFORMATION Model No. AC Volts Alternator CT Minimum ----------------- Delay Timers --------------- L - N Available Type Load Run-On Stop Safety SDM72A/230 200 240 180V CT100S 60W 30s 30m 10s 5s SDM72A/115 100 120 90V CT100S 30W 30s 30m 10s 5s SDM72C -------------------------------------------- designed to order ----------------------------------------------------------------- SPECIAL BUILDS SDM72 - / - - / X0? An 'X' number indicates non-standard product which may have been designed and manufactured to suit a specific customer. Many such part numbers will not appear in our price list and may only be available to the original customer. When re-ordering, please quote the full part number together with the 'Serial Number' of the original unit. CUSTOMISED PRODUCTS If you have a specific requirement that is not listed above; please contact our Sales Desk for a quotation. A standard product can normally be customised within a matter of days. E. & O. E. The Proven Solution to Power Controls DA04SDM1-2

Capricorn Controls DA04SDM72-2 Revised Design Page 5 of 6 Always check the obvious first ---- FAULT FINDING ----- SDM72 BASED SYSTEMS System correctly wired All AC metering and control circuits are powered from the Alternator side of the Load Contactor Correct SDM72 type fitted and Run-On timer set to suit the specific application Current Transformer (i.e. CT100S) correctly positioned so it is only monitoring the Load current All connections use suitably rated cables to comply with all appropriate regulations. All terminal screws are correctly tightened. The battery negative and AC Neutral are bonded together and to earth Battery is of the correct voltage and capacity, charged and in good condition with connections clean and correctly tightened. The SDM72 module MUST be fitted in a control panel with adequate protection from -- temperature, moisture & vibration. WARNING - Incorrect wiring may permanently damage the module i.e. - 1/ Do not connect any DC inputs or outputs to a DC Supply in excess of the rated value. 2/ Do not connect any DC terminals or CT inputs to the Alternator line voltage. 3/ Do not connect terminals 37 & 38 to an Alternator line voltage in excess of the rated value. Unit Dead - set will not start Using a DC voltmeter, check for correct battery supply on term.21(b+) [with respect to term.22(b-)] if the RSM72 is in Auto mode or term.26(man) if it is in Man mode. Alternatively, connect term.21 (or 26) to term.19 (lamp test) and observe if ALL LED s light. Load applied to Dead Bus but Load Demand not lit and Genset doesn t start The DC resistance of the applied load is not low enough to trigger the sensing circuitry (i.e. fluorescent lighting). It may be necessary to connect an incandescent bulb in parallel with it. Load Demand - but Genset doesn t start Terminals 23, 24, 25 are incorrectly wired or disconnected by external circuitry. Check that the RSM72 is in Auto mode and is operating correctly. Genset starts - but will not take the Load Alternator Available Led NOT lit - Alternator voltage below threshold of SDM72 (typically 180V on 230V system) - Alternator voltage not connected to terminals 37 & 38 Alternator Available Led lit - Incorrect wiring to the contactor - Terminal 27 (INT) connected to battery Ve or earth Alternator on Load but status led not lit Terminal 29 must connect to battery Ve via volt-free n/o auxiliary contacts on the Load Contactor. Load removed - but contactor will not de-energise Load Demand Led NOT lit - Run On (on Load) timer (typically 30s 30m) is set to high Load Demand Led lit - RSM72 switched to Manual mode - BVF300 (if fitted) providing a Low Battery input to term.30 ( Auxiliary Load Led lit) - metering & / or control circuitry connected to the Load side of the contactor Loss of Demand Load contactor de-energises but set does not stop Terminals 23, 24, 25 are incorrectly wired or connected by external circuitry. Check that the RSM72 is in Auto mode and is operating correctly. Loss of Demand Load contactor de-energises set stops but starts again after a short delay (a) A load remains connected which is below the current threshold but has sufficiently low DC resistance to trigger the Sensing circuitry each time the SDM72 reverts to Standby mode. Ensure that any AC metering and control circuitry is connected to the Alternator side of the contactor. (b) Typically, a Refrigerator or Freezer unit can cause this problem where the thermostat is set too low and therefore calling for power again soon after the set has stopped. Ensure that the thermostat is set correctly and that the appliance is positioned in a cool place. Increasing the Run-on time may also help. Designed & manufactured in England by Capricorn Controls Telephone: +44 (0) 1295 272360 Fax: +44 (0) 1295 264766 E-mail: sales@capricorncontrols.com

Page 6 of 6 CONSTRUCTION SPECIFICATION Through panel mounting, 72mm sq. DIN standard case injection moulded to our own design. To aid assembly, a securing sleeve is employed rather than individual spring clips. Reverse screen printed Lexan front panel Printed circuit boards are varnished as standard TEMPERATURE TERMINATIONS - 10 C to +55 C Operating - 25 C to +70 C Storage Industry Standard two piece connectors INDICATORS Three single and two dual colour, high intensity light emmitting diodes (Led s)... Standby (Green), Load Demand (Red) Auxiliary Demand (Red) Alternator Available (Red) Alternator on Load (Red) Run Plant (Green), Plant Fail (Red) DC EXCITATION START LEVEL LOAD THRESHOLD DELAY TIMERS SUPPLY VOLTAGE CONTACT RATINGS Dimensions 72 72 A 10mA constant current source produces approx. + 10Vdc at term.32, wrt Batt Ve, when the Standby Led is lit & no Load is applied. Total sense resistance between Term.32 and Batt-Ve should be <= 1K Ohm (terminal voltage <5.0VDC) to initiate a Load Demand. No user adjustment is provided. Minimum load = 180mA to maintain the load demand. No user adjustment is provided. Start Delay = fixed 1 sec Warm-Up Delay = fixed 3 sec Run-on (on Load) Time = 30s - - 30mins, user adjustable, set at minimum. Stop Time = fixed 10 sec Run Down (Saftey) Delay = fixed 5 sec 12/24V single range supply. Burden in Standby mode = 105 ma at 13.8VDC Run Relay = volt-free change-over contacts rated at 16A, resistive load. Contactor Control Relay = 5A / 230VAC, resistive load. Note: contacts are not volt-free! 156 Notes: 1. Not to Scale 2. All dimensions in mm 3. Cut-Out = 68 x 68 4. New case injection moulded to our design. 5. Allow 10mm clearance on each side for sleeve housing CAPRICORN CONTROLS LIMITED INDUSTRIAL ELECTRONIC ENGINEERS SPECIALIST CONTROLS FOR ENGINE APPLICATIONS Thorpe Close, Banbury, Oxon., OX16 4SW. England Tel: +44 (0) 1295 272360 Fax: +44 (0) 1295 264766 E-mail: sales@capricorn-controls.com Web: www.capricorn-controls.com Keystart, Remote Start, Start-on-Demand, Mains Failure, Mutual Standby & Multi-set Controllers. Annunciators and Lamp Modules. Voltage, Current, Frequency, Speed, and Temperature Monitors. Timers. Transport Refrigeration Spares. Batteries, Battery Chargers and Power Supplies. Spares and Accessories. Customised Products and Bespoke Designs. E. & O. E. The Proven Solution to Power Controls DA04SDM1-2