AD592/592-10K Non-Room Units with a Junction Box, Weatherproof (WP) or Weather Tight (EU) Enclosure

Similar documents
AD592/592-10K Non-Room Sensors in BAPI-Box, BAPI-Box 2 or BAPI-Box 4 BA/592-x-(BB, BB2, BB4) Temperature Sensor Instructions & Operation

Temperature Transmitters

Duct Averaging Transmitters BA/T#-A Temperature Transmitter Installation & Operations

Submersible Averaging Duct Transmitters BA/T#SA Temperature Transmitter Installation & Operations

VOC Duct and Rough Service Sensor

BAPI-Stat 4 Room Humidity Sensor (BA/ B4 -H200 Series)

CO 2 Room Sensor in the BAPI-Stat 3 Enclosure with Common Ground Configuration

BAPI-Stat Quantum Temperature Sensor with Display and Slider Setpoint

CO 2 Room Sensor in the BAPI-Stat Quantum Prime Style Enclosure

BAPI-Stat 3 Room Sensor

BAPI-Stat Quantum Temperature Sensor with Display, Button Setpoint, Fan or System Mode Control

VOC Room Sensor in the BAPI-Stat 3 Enclosure with Differential Ground Configuration

C7170A,B Encapsulated Temperature Sensor

TS Series TS Series

Low Pressure Sensor. Overview. Specifications. Installation and Operation

T Series Temperature Sensors with Linitemp Product Overview

TS Temperature Sensor and Transducers. Product Bulletin. Wide range of mounting types and signal outputs

Installation Instructions

Installation Instructions

MODEL 8682 SUREFLOW ADAPTIVE OFFSET CONTROLLER

TE-6300 Series Temperature Sensors Catalog Page

Immersion Temperature Sensors

BAPI-Com, Two Wire Multifunction Sensor with Setpoint Slider (BA/BS4SCOM) Temperature/Humidity Sensor

BAPI-Com, Two Wire Multifunction Sensor BA/BS4SCOM Temperature/Humidity Sensor Installation and Operating Instructions

Immersion Wells and Compression Fittings FOR TEMPERATURE CONTROLLERS

Combined Ventilation Controller RVWS-T-224HA

MicroTech III Water Source Heat Pump Wall-Mounted Room Temperature Sensors

MODELS DSH/KSH/DSV/KSV R-410A LOW-AMBIENT KIT

Immersion Wells and Compression Fittings FOR TEMPERATURE CONTROLLERS

Compact Low Pressure Sensor

Quarter Master Chief Series 92 Actuator

PRESSURE SENSOR INSTRUCTIONS

ACCUVALVE MODEL AVC6000 SUBMITTAL MATERIALS MODEL CODE. AccuValve Model AVC6000 AVC6 - - DWG. NO: REVISION: REV. DATE:

SEN and SEN Outdoor Air Temperature Sensors

Andover Controls Duct and Immersion Temperature Sensors provide accurate measurement of air

SB 2000 PUSH TO SEARCH NEXT STAG E. Aerotech, Inc. FORM: QM 1320

TE-6300 Series Temperature Sensors

Barbara, Here is the list of items. I numbered the attachments to match with the numbers below.

746 Wrist Strap Tester Installation, Operation and Maintenance

Reproduction or other use of this Manual, without the express written consent of Vulcan, is prohibited.

Quarter Master Series 94 Actuator

1100 Series Piston Type Differential Pressure Gauges

TE-6300 Series Temperature Sensors

Application Note. Monitoring Bearing Temperature with ProPAC

TEGAM HTRHSERIES. High Temperature, Relative Humidity/ Temperature Probe Transmitter

Condensed Version of Operator s Manual For The VI/VP700 Series Flowmeter and VI800 Series Flowmeter

Torque min. 35 in-lb, for control of air dampers

Northwest RV Supply Manual Compliments of Printed From TROUBLESHOOTING

OPTIONS BLANK = No Options B = BACnet MS/TP D = Internal Transmitter Display (Ref Note 4)

Temperature Sensors. Description. Specification

Page 1 of 1 ALTERNATORS. Overview. Intek TM V-Twin Cylinder OHV Engine Service Manual Version 1.0. Copyright 1999 by Briggs and Stratton Corporation

Installation Instructions Mineral Insulated (M.I.)

CIVACON GROUND VERIFICATION RACK MONITOR SYSTEM and ASSOCIATED EQUIPMENT

General Electrical Information

N I S T traceable calibration equipment conforms to MIL-STD-45662A.

Pipe Freeze Protection Design/Install Guide

INSTALLATION INSTRUCTIONS WHITE / SINGLE COLOR 24V LED TAPE

Inlet Controller TC5-ITA USER'S MANUAL. M rev. 02 K rev. 00

CHAPTER 2. Current and Voltage

Signet 2760 DryLoc ph/orp Preamplifier

PowerLogic High Density Metering System 4-Meter Enclosure Installation Guide

* * Rev. 9 01/18 Product Manual

SITRANS AS 100. Instruction Manual September 2001 ITRANS AS 100

Mount directly to 1.05 jackshafts. (new ZG-120 bracket shown) EFB24-S N4, EFX24-S N4(H) EFB24-S, EFX24-S (p. 21)

LMCB24-SR LMCB24-SR-T. applications. Dimensions (All numbers in brackets are in millimeters.) 1/4 to 3/4 [6 to 20] 5/16 to 3/4 [8 to 26] 1.

Introducing NJK Precision Airflow Measuring Stations

E.S.P. Embedded Sensing Probes for Motor Brushes

I N C O R P O R A T E D

General Description. Product Specification. Document Digital Temperature Interlock

Table No. 1 provides a means of identifying the various alternator systems. Note: All output figures are rated at 3600 RPM. TABLE NO.

GE Measurement & Control

IP65 COOLEDGE TILE EXTERIOR R2 INSTALLATION MANUAL. Exterior TILE Jumper Cable. Exterior Cutout TILE. Cable Clamp. T-Cable.

Safety & Installation Instructions

Technical Installation Manual

LUDLUM MODEL 133 SERIES GAMMA DETECTOR

ThermoLite 110W-330W Solar Panel Installation Instructions

DFS Dynamic Fuel Systems Inc.

TS , -850 Series TS , -850 Series TS-57031, TS

Therm-L-Tec Building Systems LLC. Therm-L-Tech. Power Operated Retrofit Kit 230 VAC or 440/480 VAC 50/60 Hz Installation and Setup Manual

Minimum 18 in-lb Torque. Applications. TF Series At A Glance. TF Series Spring Return Direct Coupled Actuator. For damper areas up to 4.

Twin-Temp. Bimetal Thermometers with Thermocouple/RTD Output. For pricing info, call WIKA-USA or visit

Quick Install Lift AL065 Installation Guide & Owners Manual

Product Manual Manuel du Produit Manual del Producto

The Traveler Series: Adventurer

IP44 - IP66 Rated RCD, Power & Cable Management

From. McCROMETER, INC WEST STETSON AVENUE HEMET, CA Phone (951) Toll Free (800) Fax (951)

RK Standby Battery Operator s Manual

Versatile and Powerful

GMX24-SR. Proportional Control, Non-Spring Return, Direct Coupled, 24V, for 2 to 10 VDC and 4 to 20 ma

331-SV. User Manual THREE PHASE DUPLEX LIFT STATION CONTROL PANEL WITH STATIONVIEW CONTROLLER. Ashland, OH

Gold Series Thermal Dispersion Airflow Measurement Technology. Advantage. Installation, Operation and Maintenance Technical Manual GF1

M9106-AGx-2N0x Series Electric Non-spring Return Actuators

Installation Instructions CONSTANT WATT (CW) AND SELF-REGULATING (SR) PIPE TRACING CABLES

Single-Input Thermocouple. Thermometers Type J, K, T

Installation Instructions for SINGLE COLOR 12V or 24V LINEAR LED

LED REVEALS - INSTALLATION INSTRUCTIONS

Installation Instructions

Installation, Operations and Maintenance Guide

Temperature Controller. TC5+2V4SA Plus USER'S MANUAL

Pressure Transmitter. Informational & Installation Manual

Transcription:

592 Theory of Operation The 592 sensor is a two terminal integrated-circuit temperature sensor. The 592 provides an output current directly proportional to absolute temperature. When the temperature of the 592 sensor changes one-kelvin (one-degree Celsius), then the current through the 592 changes by 1uAmp. 77 Fahrenheit (25 Celsius) is 298.2 Kelvins and the output current from the 592 sensor is 298.2uAmp. Initial accuracy of the 592 temperature sensor is ± 8.1 Fahrenheit (± 4.5 Celsius) at 77 Fahrenheit (25 Celsius). Since most meters that field technicians use cannot accurately measure currents this low, BAPI recommends that a 10KΩ 0.1% resistor be placed between the sensor output and ground. The 10KΩ resistor changes the current into a voltage that varies 0.01 volts per one degree Celsius temperature change; the voltage at 77 F is 2.982 VDC. Resistors with other tolerances can be used, but you will have greater temperature uncertainty, see the 10KΩ uncertainty table; BAPI provides two styles of humidity probe with a 592 sensor, one with and one without the 10,000 ohm 0.1% resistor. The one with the resistor has three wires - red, black and white. The one without the resistor has two wires - red and black. 10KΩ uncertainty Table Tolerance Temperature uncertainty 0.1% ±8.64 F 1% ±13.47 F 5% ±34.93 F Fig. 1: 592 2-wire Fig. 2: 592 with 10K resistor Termination Table 2: 592 2-Wire Sensors 1. Install a 10KΩ 0.1% resistor from the controller's analog input to the controller's ground or common. 2. If you are using a separate DC power supply, connect the power supply's negative terminal to the controller's ground or common.. 3. Connect the 592 sensor's black wire to the controller's analog input. 4. Connect the 592 sensor's red wire to 5 to 30 VDC. Table 3: 592 3-Wire Sensors 1. All BAPI BA/592-10K, 3-wire, sensors have a built in 10KΩ 0.1% resistor. 2. If you are using a separate DC power supply, connect the power supply's negative terminal to the controller's ground or common.. 3. Connect the 592 sensor's black wire to the controller's ground or common. 4. Connect the 592 sensor's white wire to the controller's analog input. 5. Connect the 592 sensor's red wire to 5 to 30 VDC. 1

Temperature Measurement Offsetting All BA/592 sensors will have the following information provided on a label: Therm Reading The actual temperature reading according to a thermometer that is certified traceable to recognized standards by the National Institute of Standards and Technology (NIST). Sensor Reading The temperature reading according to the AD592 sensor. The output is dropped across a 10KΩ 0.1%, read in mv and converted to a Fahrenheit temperature. Offset The difference between the Thermometer Reading and the Sensor Reading To correct the Sensor Reading, simply add the offset value to the sensor reading so that it equals the thermometer reading. e.g. Therm Reading = 74.6, Sensor Reading = 73.0, Offset = +1.6 Correction: Add (+1.6) F to the sensor for an accurate reading: 73 + 1.6 = 74.6 F e.g. Therm Reading = 75.4, Sensor Reading = 77.2, Offset = -1.8 Correction: Add (-1.6) F to the sensor for an accurate reading: 77.2 + (-1.8) = 75.4 F Mounting for 592 Temperature Sensor Products The BAPI 592 temperature sensor becomes the basis for many products. Here are some examples with mounting instructions. Junction Box or No Box Units Indoors The junction box mount is intended for indoor mounting in equipment rooms, plenums or occupied spaces. The figures below show a typical junction box mounting in an air duct. BAPI recommends using #8 sheet metal screws that need 1/8-inch pilot holes to attach the sensor to the duct. After placing the sensing element in the duct, secure the mounting flange to the duct; center the blue plastic fitting holding the probe in the mounting hole. Make sure that the foam seals the hole; do not over tighten the screws. No box units use the same mounting holes as Junction Box units. Weatherproof Box Units Indoors Fig. 3 Junction Box (JB) duct Fig. 4 Junction Box (JB) or No Box (NB) mounting holes The weatherproof box is intended for outdoors or equipment rooms. Use the provided mounting tabs provided to mount the box as shown in the figure below. DO NOT drill screw holes through the back wall of the box, this destroys the integrity of the box and may void the warranty. The figures below show a typical weatherproof box mounting in an air duct. BAPI recommends using #8 sheet metal screws that need 1/8-inch pilot holes to attach the sensor to the duct. After placing the sensing element in the duct, secure the mounting tabs to the duct; center the blue plastic fitting holding the probe in the mounting hole. Be sure that the foam seals the hole; do not over tighten the screws. Place the foam gasket between the cover and the box before securing the cover in place with the screws provided. To keep water out of the box, be sure to coat the threads of the box plugs or conduit connectors with caulk before screwing them into the waterproof box. Fig. 5 Weatherproof (WP) mounting tabs Fig. 6 Weatherproof (WP) mounting holes Fig. 7 duct 2

Mounting for 592 Temperature Sensor Products continued... IP66 EU Enclosure Indoors The Weather Tight (EU) enclosure is made from ABS plastic for indoor applications and a UV light stabilized plastic for outdoor applications or indoor applications exposed to direct sun light. The figures below show an EU enclosure mounting in an air duct. BAPI recommends using #8 sheet metal screws that need 1/8-inch pilot holes. After placing the sensing element in the duct, secure the mounting feet to the duct; center the blue plastic fitting holding the probe in the mounting hole. Do not over tighten the screws but be sure that the foam insulation makes an airtight seal. Tighten the lid to two clicks when you are finished Fig. 8 Weather Tight (EU) enclosure duct making terminations. Fig. 9 Weather Tight (EU) enclosure mounting holes Weather Tight (EU) and Enclosures Outdoors Do not mount in direct sunlight, preferably mount on the north side of the building. Install with the sensor probe pointed down. For best correlation with the local weather bureau s temperature, position the end of the probe between four feet and six and one-half feet above the ground. Drill a hole through your mounting surface as shown in the figures below. Mount the unit to the surface with a wiring knock out centered over the wiring hole. Pull the wiring into the unit and terminate using sealant filled connectors. Best practice is to caulk the wiring hole after the wiring is installed. Be sure that the foam on the back of the unit makes a good weather tight seal. Use the mounting tabs provided to mount the weatherproof box as shown in the figure below. DO NOT drill screw holes through the back wall of the box, this destroys the integrity of the box and may void the warranty. Note: Air temperature units are shown. Temperature and humidity units are available in double gang weatherproof boxes only. To keep water out of the box, be sure to coat the threads of the box plugs or conduit connectors with caulk before screwing them into the waterproof box. Fig. 13: enclosure mounting tabs Fig. 10: Weather Tight (EU) enclosure Fig. 11 Weather Tight (EU) enclosure mounting holes Fig. 12 Outdoor Air Weatherproof (WP) Fig. 14: enclosure mounting holes 3

Mounting for 592 Temperature Sensor Products continued... Immersion Sensor Place the thermowell into the pipe nipple using Teflon tape and/or pipe dope. Tighten securely but do not over torque. Insert the immersion sensor into the well with the blue plastic fitting screwing into the opening on the well. Tighten the immersion sensor snugly by hand without too much torque. Make sure that the tip of the immersion sensor is in contact with the bottom of the well. The unit is designed so that the temperature probe moves slightly into the junction box as the sensor hits the bottom of the well. The figure shows a junction box, but weatherproof boxes and IP66 rated enclosures may be used as well. Fig. 15 T1K transmitter mounted to a Weatherproof box cover and Weatherproof box with an immersion probe Fig. 16 Cross section of immersion unit Spring-Loaded Strap Unit The spring-loaded strap sensor is used when a large section of insulation cannot be removed from a pipe. The spring-loaded strap sensor accommodates insulation of up to two inches thick. Cut a 1-1/4 inch diameter hole in the insulation and remove the insulation from the hole down to the bare pipe. Be sure to remove all insulation and debris from the hole. Place the copper pad on the end of the spring-mounted foam into the hole; make sure it makes good physical contact with the pipe. Tighten the straps until the strap-mounting bracket contacts the insulation. The springloaded strap on sensor is sized for pipe diameters of 5 to 12.5 inches, including the insulation. Fig. 17 Spring-Loaded Strap Clamp On Strap Unit Place the clamp-on sensor on bare pipe, or a section of pipe with the insulation removed. Make sure that the copper pad on the foam is in good physical contact with the pipe. Snug the straps so that the assembly does not rotate around the pipe when moderate pressure is applied to the junction box. Do not over tighten. You may place pipe insulation over the whole assembly. The clamp-on strap sensor is sized for bare pipes of 2 to 4.5 inches in diameter. Add another pipe clamp if needed. Fig. 18 Clamp-On Strap 4

Mounting for 592 Temperature Sensor Products continued... RPFEP and FEP Indoors Mount the or the Weather Tight (EU) enclosure as shown in the figures below. Mount with the wire connector down. Route the temperature probe to the spot where you wish to measure the temperature. Best practice is to tie down the wire every two feet. Make sure to caulk the upper screw in plug on the WP enclosure. Center mounting hole shown is only used if you are wiring through the mounting surface. Fig. 19 mounting tabs Fig. 20 Fig. 21 Weather Tight (EU) Fig. 22 mounting holes Fig. 23 Weather Tight (EU) mounting holes 5

Troubleshooting GENERAL TROUBLESHOOTING AND POSSIBLE SOLUTIONS - Determine that the input is set up correctly in the controller s and building automation software. - Check wiring for proper termination - Check for corrosion at either the controller or the sensor. Clean off the corrosion, re-strip the interconnecting wire and reapply the connection. In extreme cases, replace the controller, interconnecting wire and/or sensor. - Label the terminals that the interconnecting wires are connected to at the sensor end and the controller end. Disconnect the interconnecting wires from the controller and the sensor. With the interconnecting wires separated at both ends measure the resistance from wire-to-wire with a multimeter. The meter should read greater than 10 Meg-ohms, open or OL depending on the meter you have. Short the interconnecting wires together at one end. Go to the other end and measure the resistance from wire-to-wire with a multimeter. The meter should read less than 10 ohms (22 gauge or larger, 250 feet or less). If either test fails, replace the wire. 592 SENSOR TROUBLESHOOTING Note: The BAPI crimp-on sealant filled connectors have a convenient hole opposite the wire opening to insert a meter probe for measurements. 1) Measure the sensible temperature at the sensors location using an accurate temperature standard. 2) Set your meter to the Volts setting. 3) Measure from the controller ground (black sensor lead) to the 592 s power lead (red sensor lead) for +5 to +30 VDC. 4) Set your meter to the mv setting. a) For two wire units place a 10KΩ resistor between the sensors black lead and the return wire to the controller. Measure and record the voltage across the resistor. b) For three-wire units measure and record the voltage from the black lead to the white lead. 5) Using Table 4, if the sensor voltage is greater or less than 0.050VDC from the expected voltage measurement, call BAPI technical support. 6) If the sensor reads properly, verify that the controller is operating correctly. 7) If the sensor reads improperly, determine if the sensor is exposed to an external source different from the measured environment (conduit draft). Table 4: 592 Output Temperature 592 Semiconductor F C Output Current ua Output Voltage across 10KΩ 50 10 283.2 2.832 60 15.56 288.8 2.888 62 16.67 289.9 2.899 64 17.78 291 2.91 66 18.89 292.1 2.921 68 20 293.2 2.932 70 21.11 294.3 2.943 72 22.22 295.4 2.954 74 23.33 296.5 2.965 76 24.44 297.6 2.976 78 25.56 298.8 2.988 80 26.67 299.9 2.999 82 27.78 301 3.01 84 28.89 302.1 3.021 86 30 303.2 3.032 88 31.11 304.3 3.043 90 32.22 305.4 3.054 100 37.78 311 3.11 6