Power Interchange System for Reuse of Regenerative Electric Power

Similar documents
Development of Emergency Train Travel Function Provided by Stationary Energy Storage System

Railway Systems. Class 385 for the International Market

POWER DISTRIBUTION SYSTEM ANALYSIS OF URBAN ELECTRIFIED RAILWAYS

Battery-powered Drive Systems: Latest Technologies and Outlook

Energy Storage for Traction Power Supply Systems

Special edition paper Measurement and Analysis of the Driving Energy of Shinkansen Rolling Stock

NORDAC 2014 Topic and no NORDAC

Steering Actuator for Autonomous Driving and Platooning *1

Energy Management for Regenerative Brakes on a DC Feeding System

Development of Motor-Assisted Hybrid Traction System

Nissin s Products for Electric Railway System

Core Components for Large-scale PV Generation Systems

A study of the power capacity of regenerative inverters in a DC electric railway system

The evaluation of endurance running tests of the fuel cells and battery hybrid test railway train

Island Smart Grid Model in Hawaii Incorporating EVs

Rolling Stock System Technologies Underpinning the Next Generation of Railways

High-voltage Direct Inverter Applied to Induced Draft Fan Motor at Takehara Thermal Power Station No. 3 of Electric Power Development Co., Ltd.

Featured Articles Utilization of AI in the Railway Sector Case Study of Energy Efficiency in Railway Operations

Next-generation SCADA and Control Technologies for Large-scale Use of Photovoltaic Generation on Electric Power Grid

POWER TRANSMISSION OF LOW FREQUENCY WIND FIRMS

Estimation of electrical losses in Network Rail Electrification Systems

Development of an energy efficient train traffic control system for saving electricity

K. Shiokawa & R. Takagi Department of Electrical Engineering, Kogakuin University, Japan. Abstract

Development of Large-capacity Indirect Hydrogen-cooled Turbine Generator and Latest Technologies Applied to After Sales Service

Autonomous Haulage System for Mining Rationalization

Special edition paper

Track test monitoring system using a multipurpose experimental train

Regenerative braking and the different traction systems

PVI1000 : Outdoor High-Efficiency Power Conditioners for Mega Solar Projects

Environmentally Conscious Green Mobility

Power System Stability Solutions for Low-carbon Society

Power management control in DC-electrified railways for the regenerative braking systems of electric trains

Next-generation Inverter Technology for Environmentally Conscious Vehicles

Application of energy storage systems for DC electric railways

The 1,400-MW Kii-Channel HVDC System

Development of the SANUPS P73K Power Conditioner with Peak Power Cut Function

The Smart Way. HVDC PLUS One Step Ahead. Answers for energy.

A study of the train performance simulation for Korean next Generation high-speed train. high-speed train.

Next Generation of UHVDC System. R. Montaño, D Wu, L. Arevalo, B. Jacobson ABB - HVDC Sweden

Improving Onboard DS-ATC Equipment Functions in Response to Shinkansen Service Expansion

Development of the gauge change EMU train system in Japan

Robust Control Technique for Grid-connected Power Conditioner

Development of Catenary and Batterypowered

FRENIC-Mega Series of High-performance Multi-function Inverters

Georgia Transmission Corporation Georgia Systems Operations Corporation

Integration of Large Wind Farms into Electric Grids

Train Group Control for Energy-Saving DC-Electric Railway Operation

CHAPTER 3 TRANSIENT STABILITY ENHANCEMENT IN A REAL TIME SYSTEM USING STATCOM

Fig.1 Sky-hook damper

Hitachi Electric Drive Solutions that Contribute to Global Environment

Construction of power supply system using electric vehicle for stable power delivery from PV generation

PASSENGER DEMAND WEST CHECKPOINT November 2018 Scheduled Departing Passengers & Seats

Development of Next-generation Switchgear Targeting High Reliability and Maintenance Savings

SVC Light For electrical transmission grids

A Study on the Measurement of Contact Force of Pantograph on High Speed Train

Research on Transient Stability of Large Scale Onshore Wind Power Transmission via LCC HVDC

The Modeling and Simulation of DC Traction Power Supply Network for Urban Rail Transit Based on Simulink

Method to tie feeding cables for energy conservation

Impact of Plug-in Electric Vehicles on the Supply Grid

Development and Demonstration of Redox Flow Battery System

Implementation of a Grid Connected Solar Inverter with Maximum Power Point Tracking

OCS Inspection System for High-Speed Railways

FAULT ANALYSIS OF AN ISLANDED MICRO-GRID WITH DOUBLY FED INDUCTION GENERATOR BASED WIND TURBINE

Development of the Single Phase PV Inverter SANUPS P61A

Examining the load peaks in high-speed railway transport

Rural electrification using overhead HVDC transmission lines

Smart Grid System from Japan to India

POWER FACTOR CORRECTION OF FAST DYNAMICS INDUSTRIAL LOADS

Large-scale Photovoltaic Power Generation Systems

SIMINE DRAG. Innovative solutions for maximum productivity and reliability. Mining Technologies

Static frequency converter couples US paper mill s 25-Hz and 60-Hz electricity grids

Analysis and assessment of the electrification of urban transport based on real-life mobility data

Analysis on Steering Gain and Vehicle Handling Performance with Variable Gear-ratio Steering System(VGS)

Development of Higher-voltage Direct Current Power Feeding System for ICT Equipment

Development and Performance Evaluation of High-reliability Turbine Generator

Abstract In this paper, we developed a lateral damper to improve the running safety of railway vehicles

Electrification and Power Supply. Andrea Nardinocchi Technological Design Department Italferr S.p.A., Rome, Italy

Optimal Design of Hybrid Energy System with PV/ Wind Turbine/ Storage: A Case Study

Development of a High Efficiency Induction Motor and the Estimation of Energy Conservation Effect

Special edition paper

Common Bus and Line Regeneration

Reliable, economical and safe siemens.com/rail-electrification

Surabaya Seminar Ferdinand Sibarani, Surabaya, 30 th October Power Quality

Redflow Telco Application Whitepaper

Study of composition draft on automatic changeover system in neutral section railway catenary system for highspeed train line

Rescue operations on dedicated high speed railway lines

Voltage Sag Mitigation in IEEE 6 Bus System by using STATCOM and UPFC

INSTALLATION OF CAPACITOR BANK IN 132/11 KV SUBSTATION FOR PARING DOWN OF LOAD CURRENT

OPF for an HVDC feeder solution for railway power supply systems

Examples of Electric Drive Solutions and Applied Technologies

Development of Compact & High Efficiency Polymer Electrolyte Fuel Cell System for Enclosed Spaces

Impact of Increasing Electric Mobility on a Distribution Grid at the Medium Voltage Level. Julia Vopava

Defect Monitoring In Railway Wheel and Axle

Electric Vehicles Coordinated vs Uncoordinated Charging Impacts on Distribution Systems Performance

A STUDY ON ENERGY MANAGEMENT SYSTEM FOR STABLE OPERATION OF ISOLATED MICROGRID

Shinkansen- Japanese High Speed Railway Network Shinkansen- Japoński System Kolei Dużych Prędkości. Hitachi Rail Europe

Development of Rolling Stock Inverters Using SiC

Approved by This document is the property of Network Rail... Date: It shall not be reproduced in whole Phil Collins Head of Asset Management (E&P)

The Circuit and Control Technology in the Power Conditioner and Converter for Wind Turbine Systems

FEATURE ARTICLE. Advanced Function Analyzers: Real-time Measurement of Particulate Matter Using Flame Ionization Detectors. Hirokazu Fukushima

Transcription:

Latest Developments for Safe and Reliable Railways Power Interchange System for Reuse of Regenerative Electric Power In AC power feeding systems, the sections of track feed by each are separated by dead sections, with excess regenerative electric power from the rolling stock on each AC feeder section being fed back into the power system. In order to reuse this excess regenerative electric power on other feeder sections, Hitachi has been commercializing the SP-RPC power interchange system for installation at sectioning posts. Long-term monitoring data from installation of the system on conventional railway lines has shown that the amount of electric power transferred has exceeded initial expectations. Accordingly, Hitachi is now extending its deployment to Shinkansen systems also. Katsushige Aoki Kensaku Kikuchi Minoru Seya Tetsuya Kato 1. Introduction Normally, the regenerative electric power produced by rolling stock running on a section of track being fed with alternating current (AC) power (a feeder section ) is not able to be reused anywhere other than loads on that same section of track. This means that, even when power from one particular section of track is being fed back into the power system, the electric power used to supply other feeder sections still needs to be purchased. One method proposed for overcoming this problem is a sectioning post - railway power conditioner (SP-RPC) system for reducing total electricity purchases from the grid that works by using RPCs designed for installation at SPs (where power feeding equipment is housed) to supply regenerative electric power generated under regenerative braking by rolling stock on one feeder section to loads on other feeder sections. It is particularly difficult to reuse generated power on other trains in the case of railway lines on which all rolling stock are fitted with regenerative braking but where there are only a small number of stations in each feeder section and a comparatively low frequency of trains running at the same time. It is hypothesized that SP-RPC systems will be proved useful on railway lines like this that are fed by AC power (1). 2. Overview and Benefits of SP-RPC System 2. 1 Installation of SP-RPC on Conventional Lines of East Japan Railway Company Approximately three years of operational experience has been gained since the first SP-RPC was installed at an SP for a conventional line operating on AC Hitachi Review Vol. 67, No. 7 834 835 71.

power. This section describes the installation and the benefits of it. An SP-RPC was manufactured for the 22-kV AC feeder at the Ushiku SP on the Joban Line of East Japan Railway Company. The system commenced operation in 2015. While the already had an RPC system for handling imbalances between the main phase and teaser phase of Scott transformers, the SP-RPC for the Ushiku SP on the Joban Line was the first time that an SP-RPC had been used for power transfer on an AC feeder section. Figure 1 shows a block diagram of the system for the Ushiku SP on the Joban Line, Table 1 lists the SP-RPC specifications, and Figure 2 shows photographs of the equipment. As shown in Figure 1, the SP-RPC is installed at the Ushiku SP and converters are connected in back-to-back (BTB) configuration across the dead section to supply the single-phase 22-kV feeder systems for the and sides respectively. Both s are equipped with an arithmetic unit that calculates the amount of electric power consumed and regenerated at the three-phase point. Each of these units has is been given a function for transmitting information about the power at the three-phase point to the control unit of the SP-RPC at the Ushiku SP. The SP-RPC operates to transfer power from the three-phase point of the or that has excess regenerative electric power to the feeder system of the other. Because regenerative electric power is repeatedly generated in large amounts over short time periods, Figure 1 SP-RPC System Overview The system is installed in an SP located between s and works by transferring excess regenerative electric power from one to the feeder system of the other from the three-phase points for the two s. Three-phase point Arithmetic unit Regenerative electric power prior to RPC installation Ushiku SP RPC designed for installation in SP Controller Power transfer with RPC installed Arithmetic unit Traction power before RPC installed Three-phase point Dead section Regenerative power Train generating regenerative power Traction power Train drawing traction power SP: sectioning post RPC: railway power conditioner Table 1 SP-RPC System Summary Specifications The table lists the specification for the SP-RPC supplied to the Ushiku SP of East Japan Railway Company. with adjacent s is one of the features of the SP-RPC, and this can be performed using metal (wire), optical, or other links depending on the railway operator. Rated voltage Rated capacity Rated frequency Parameter Value Remarks 22 kv RPC mode 1.3 MW 2 One-minute overload rating: 5.3 MW (10 minute interval) SVC mode 1.3 MVr 2 Power device and configuration PWM pulse, DC voltage Cooling Calculation 50 Hz IGBT, single-phase/three-level/three-way 3 15 pulses, DC 6,000 V Circulating water and air cooling High-speed sampling Digital calculation of active and reactive power DSL Range: 10 to 20 km Dedicated metal (wire) link SVC: static var compensator PWM: pulse width modulation DC: direct current IGBT: insulated-gate bipolar transistor DSL: digital subscriber line 72.

Figure 2 Example SP-RPC Installation The converter, control panel, operation panel, and arithmetic unit are installed indoors while the switchgear and converter transformers used to connect the converters to the power feeding system are located outside. Active power at point of Purified-water cooling system Active power at point of RPC control panel RPC operation panel s Outdoor cooling system 22-kV VCB transformer VCB: vacuum circuit breaker the transformer and cooling system capacities have been downsized by giving the system a rated capacity of 1.3 MW and a one-minute overload capacity of 5.3 MW (10-minute interval) (2). 2. 2 Electric Power Transfer Performance Table 2 lists measurements of the amount of electric power transferred between feeder systems by the RPC collected over a week-long period from April 19 to 25, 2015. The results show that the SP-RPC transferred a daily average of about 7.9 MWh, meaning that the benefit of using an RPC for reusing regenerative electric power is about 7.9 MWh/day. As this compares to an estimate of 7.3 MWh/day of power transfer arrived for by East Japan Railway Company prior to installation based on measurements of excess electric power, it demonstrates that the benefits of installing the system were enough to satisfy initial expectations (2). 3. Power Simulator for AC Power Feeding System Hitachi developed a simulator for AC power feeding as part of planning for utilizing excess regenerative electric power and installing an SP-RPC in the AC power feeding system described above. The two most common forms of AC power feeding are based on either the booster transformers (BTs) used on conventional lines and elsewhere or on the auto transformers (ATs) used for the Shinkansen. The simulator works for both types. The following section uses AT power feeding as an example to give an overview of the simulator and describe the results of comparative testing using the measured electric power from an actual railway line. This work was undertaken in September 2016 in collaboration with Kyushu Railway Company and was compared with the data on the supplied power and excess regenerative electric power at the Shin-Tosu Table 2 Measurements of Power Transfer by RPC over One Week The figures are actual data for SP-RPC operation at East Japan Railway Company. An average of about 7.9 MWh/day of electric power was transferred. Transferred electric power [kwh] Date (2015) 4/19 (Sun.) 4/20 (Mon.) 4/21 (Tue.) 4/22 (Wed.) 4/23 (Thur.) 4/24 (Fri.) 4/25 (Sat.) Average 3,092 3,281 3,423 3,271 3,252 3,166 2,961 3,207 5,222 4,529 4,500 4,635 4,637 4,504 4,724 4,679 Total 8,314 7,810 7,923 7,906 7,889 7,670 7,685 7,885 Hitachi Review Vol. 67, No. 7 836 837 73.

Figure 3 Block Diagram of Simulator The simulator can simulate both traction and regenerative electric power for the rolling stock and supplied and regenerative electric power at the s based on track conditions and operating conditions. Potential uses include planning for new construction or energy efficiency measures. Simulation conditions input Traffic management Signals Rolling stock Power feeding Train detection Position Overhead wire voltage Train movement instructions Train stop position Power demand Behavior across entire railway (energy efficiency, etc.) Table 3 Comparison of Simulated and Measured Amounts of Electric Power The comparison was performed for the Kyushu Shinkansen. The results indicate that amounts of supplied electric power and excess regenerative electric power can be predicted with an accuracy in the range of errors of 3.7 to 6.5%. (a) Shin-Tosu Measurement Simulation Error Supplied electric power 91.9 MWh 88.0 MWh 4.2% Excess regenerative electric power 15.1 MWh 16.1 MWh 6.5% (b) Shin-Gyokuto Measurement Simulation Error Supplied electric power 104.4 MWh 100.6 MWh 3.7% Excess regenerative electric power 10.8 MWh 10.1 MWh 6.2% and Shin-Gyokuto s collected to enable a study of actual rolling stock energy use on the Kyushu Shinkansen. 3. 1 Overview of AC Power Feeding Simulation When installing an SP-RPC system, it is important to estimate the current level of excess power by using simulation to analyze the drive and regenerative electric power of the AC power feeding system. For this analysis, Hitachi uses a railway network evaluation system that it developed itself. By supplying information such as speed limits and train schedules as inputs to the simulator along with actual track conditions, power feeding conditions, and rolling stock characteristics, it can analyze electric power under the actual conditions of rolling stock operation (see Figure 3). The following section describes an example comparison with simulation results that uses information provided by Kyushu Railway Company on the power supplied by the Shin-Tosu and Shin-Gyokuto s for the Kyushu Shinkansen. This analyzed the power supplied by the s, using the simulation to the two s and the region up to the adjacent switchgear locations. 3. 2 Comparison with Measurements A comparison was performed of measured data and a simulation based on the train schedule for the corresponding time. Table 3 lists the average values and simulation results for the amounts of supplied power and excess regenerative electric power at each. The simulation results had errors of 4.2% and 6.5% for total supplied power and excess regenerative electric power respectively at the Shin-Tosu, and 3.7% and 6.2% respectively at the Shin- Gyokuto. Although small errors arise due to factors such as train delays or the timing of out-of-service trains and input data such as train occupancy, the results are roughly equal, indicating the potential for using the 74.

Figure 4 Plan for Installation of SP-RPC for Kyushu Shinkansen The SP-RPC was installed at the Shin- Miyama SP located between the Shin-Tosu and Shin-Gyokuto s to reduce excess regenerative electric power at the two s. Shin-Tosu Shin-Gyokuto Shin-Nakagawa SP Shin-Miyama SP RPC Shin-Shiranui SP simulation to study ways of reducing energy consumption, such as by estimating the benefits of installing an SP-RPC (3). Company. The authors would like to express their deep gratitude for this. 4. Application to Shinkansen System Based on the supplied power measurements and simulator results for the Kyushu Shinkansen described above, Hitachi went on to prepare a detailed design for an SP-RPC to install at the Shin-Miyama SP. As shown in Figure 4, the Shin-Miyama SP is located between the Shin-Tosu and Shin-Gyokuto s that are mentioned above. It is used to reduce excess regenerative electric power and supplied power by the amounts indicated in Table 3 by monitoring these in the s and transferring power between them accordingly. References 1) M. Honda et al., Measuring Rolling Stock Regenerative Power on Joban Line and Its Effective Use, 2009 National Convention Record I.E.E. Japan. Industry Applications Society, Vol. 2009, No. 3, pp. III.275 III.278 (2009) in Japanese. 2) O. Sakuchi et al., Development of RPC (Railway Power Conditioner) for Sectioning Post in Joban-line, Papers of Technical Meeting on Electron Devices, IEE Japan, EDD-15-080, SPC-15-162 (2015) in Japanese. 3) T. Miyauchi et al., Development of AC AT-Feeding Simulation Model, Annual Meeting Record, I.E.E. Japan, 5-229, pp. 378 379 (2018) in Japanese. Authors Katsushige Aoki ground equipment for railway operators. 5. Conclusions This article has described the amount of power transfer achieved and the use of simulation for the installation of power interchange systems at SPs. Hitachi intends to continue contributing to the utilization of regenerative electric power through use of simulation and the installation of power interchange systems at SPs. Acknowledgments East Japan Railway Company provided advice and assistance with the installation of an SP-RPC at the Ushiku SP on the Joban Line and the supply of measurement data described in this article. Similarly, the measurement data for the Kyushu Shinkansen was obtained through cooperation with Kyushu Railway Kensaku Kikuchi ground equipment for railway operators. Minoru Seya ground equipment for railway operators. Tetsuya Kato ground equipment for railway operators. Society memberships: The Institute of Electrical Engineers of Japan. Hitachi Review Vol. 67, No. 7 838 839 75.