Overhead Switching Devices

Similar documents
Single-Phase Underground Operating

Service Installation

Single-Phase Meter Components

B-03 ELECTRICIAN TRAINING SKILL DEVELOPMENT GUIDE

EE 741 Over-voltage and Overcurrent. Spring 2014

Medium Voltage Outdoor Apparatus Portfolio 2009

Electrical Equipment and Terminology

Transmission Switching

Circuit Concepts (Residential)

AutoLink Frequently Asked Questions

Power & High Voltage Joslyn Hi-Voltage Overhead Reclosers & Switches H-220. Series HVI Hi-Velocity Interrupter Attachment

PROTECTION OF THE BRANCH CIRCUIT

Oncor Electric Delivery Distributed Storage and Microgrid Demonstration Projects

ECET Distribution System Protection. Overcurrent Protection

Fusing Equipment. Kearney Fuse Links. general. Internal Construction. tin element

Electrical Safety. Electrical Safety Webinar. Electrical. Printing Industries Alliance Printing Industries Alliance 1

Sectionalizing. Rick Seeling. Pete Malamen. Introduction Philosophy. Three Phase Reclosers High-Side Protection Specific Applications

Pretest Module 29 High Voltage Unit 1

Switchgear and Distribution Systems for Engineers and Technicians

When power interruptions happen.

Transmission Switching

Chapter 6 Generator-Voltage System

Power Systems Trainer

S&C TripSaver II. Cutout-Mounted Recloser. For enhanced lateral circuit protection at 15 kv and 25 kv

Kearney fuse links. Technical Data General. Effective March 2014 Supersedes December 2013

PUB NLH 174 Island Interconnected System Supply Issues and Power Outages Page 1 of 4

MANUAL ELECTRIC FIRE PUMP CONTROLLERS METRON SERIES M450

COOPER POWER SERIES. UltraSIL polymer-insulated D-73P disconnect switches installation instructions. Switches MN008004EN

ENGINEERING SPECIFICATION

Longest Life Product for Electric Furnace Applications! 100,000 Operations No Routine Maintenance Required!

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation

Electrical Safety. Introduction

JUMPERS & SWITCHING TOOLS

ELECTRICAL. 60 Minutes

Copper Double Break Switch

Guideline for Parallel Grid Exit Point Connection 28/10/2010

Manufacturing & Service: Bierer & Associates Inc. Patent No. 6,885,180. ST Series Service Tester Phase Identifier Operating Instructions ST500PGN

Catalog 14A January 2013

3.0 Radial Distribution Systems

AVOIDING ELECTROCUTION HAZARDS

An average of one worker is electrocuted on the job every day There are four main types of electrical injuries:

UBC Technical Guidelines Section Edition Commissioning of Electrical Systems Page 1 of 5

CSP Circuit Breaker Three Phase

BREAK-SAFE Load Break & Pick-up Tool

2015 WDC Disturbance and Protection Standards Overview

S&C Loadbuster Disconnects

Michigan State University Construction Standards SECONDARY UNIT SUBSTATIONS PAGE

Pretest Module 24 Three-phase Service Entrance

Disconnect & ByPass Switches

WIRING DESIGN & PROTECTION REQUIREMENTS CHECKLIST

The X, Y, and Z of Circuit Breaker Control

Selective Coordination

9. Non-Residential Services (Commercial, Industrial, and Agricultural)

Joslyn Hi-Voltage. Overhead Reclosers & Switches. In this section...

DISCONNECT SWITCH REQUIREMENTS FOR DISTRIBUTED GENERATION CUSTOMERS

201 S. Anaheim Blvd. Page No Anaheim, CA RULE NO. 2 DESCRIPTION OF SERVICE

Solar Power Switchgear & Energy Storage Renewable Energy Systems

Kearney fuse links. Technical Data General. Effective December 2013 Supersedes November 2009

UNIT 3: GENErAL ELECTriCAL SySTEM DiAGNOSiS

Shippensburg University

2013 Grid of the Future Symposium. Utilizing Single Phase Operation Scheme on Untransposed 765kV lines for a Stability-Limited Plant

SECTION 9: ELECTRICAL POWER DISTRIBUTION. ESE 470 Energy Distribution Systems

16.13 Unit Substation to 15kV Construction Standards Page 1 of 7

BREAK-SAFE Load Break & Pick-up Tool

WUEKRO. Training & Didactic Systems. Protection Schemes DIN VDE 0100

ELECTRICAL METERING RESIDENTIAL

INSTALL CIRCUIT PROTECTIVE DEVICES

K-SEC 030. Fusing Equipment. Kearney Fuse Links GENERAL INTERNAL CONSTRUCTION SINGLE TIN ELEMENT

Improving distribution systems reliability with Cutoutmounted single phase Reclosers

1/6 through 5 HP Adjustable Speed, DC Motor Controllers

Eaton s Cooper Power Systems catalog Medium-voltage vacuum circuit breakers

Electrical Systems and Fault Finding

Workforce Development Learning Center Course Outline. Emergency Vehicle Driving FIP 3601

INTERCONNECTION STANDARDS FOR PARALLEL OPERATION OF SMALL-SIZE GENERATING FACILITIES KILOWATTS IN THE STATE OF NEW JERSEY

IAE-101: Electrical Fundamentals for Non-Electrical Personnel

A. Provide a complete system of overcurrent protective devises as indicated on the drawings, and as specified herein.

Elastimold Molded Reclosers, Switches & Switchgear. In this section... Elastimold. Molded Reclosers,

A. Submit manufacturer's literature and technical data before starting work.

Feasibility Study. Shaw Environmental, Inc. 12MW Landfill Gas Generation Interconnection. J.E.D. Solid Waste Management Facility. Holopaw Substation

Quick Start Guide TS 910 & TS 920

ichards MANUFACTURING COMPANY, SALES, INC. 517 LYONS AVENUE, IRVINGTON, NJ Phone Fax

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV)

S&C Loadbuster Disconnect Switches. Outdoor Distribution (14.4 kv through 34.5 kv)

Advanced Guide To Understanding Assembly Short-Circuit Current Rating WITH ENGINEERING SOLUTIONS AND OVERCURRENT PROTECTION DEVICES TO ENHANCE SCCR

SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV)

SUBSTATION VACUUM CIRCUIT BREAKER (38KV)

3.0 CHARACTERISTICS E Type CO-4 Step-Time Overcurrent Relay

Reviewed: DD Month University Code of Practice for Electrical Safety. PART B - Design and Construction of Electrical Equipment within the University

Type ICX Outdoor open type cutout

Transformer Protection

JEFFERSON COLLEGE COURSE SYLLABUS HRA101 ELECTRICITY FOR HVAC. 5 Credit Hours. Prepared by: William Kaune. Revised Date: March 17, 2014

ABB ! CAUTION. Type KRV Directional Overcurrent Relay E 1.0 APPLICATION 2.0 CONSTRUCTION AND OPERATION. Instruction Leaflet

Net Metering Interconnection Requirements

Question Set(2017) Switch Gear & protection(5 th SEm) 9. Explain the construction and operating principle with proper diagram:

May 13, 2008 Physics - Electricity & Magnetism. Title: Hot Dog Circuits Demonstration 1. Abstract:

COOPER POWER SERIES. Manually-Operated M-Force Switch Installation and Operation Instructions. Switches and Disconnects MN008003EN

BREAKER FAILURE PROTECTION

Electric Motor Controls BOMA Pre-Quiz

Installation and Construction Notes for EVSE4

PREVIEW ONLY - FULL COPY AVAILABLE TO CONSORTIUM MEMBERS. Escalator Specific Electrical Systems. Course 209 PARTICIPANT GUIDE

Transcription:

Overhead Switching Devices S T U D E N T M A N U A L March 31, 2005

2 STUDENT TRAINING MANUAL Prerequisites: Oil Circuit Recloser Operating Principles module Objectives: Given the Construction Standards manual, you will be able to describe the electrical system requirements for switching devices and their operation. Rationale: An electrical system is susceptible to many types of problems which may require isolating and switching. Proper switching helps the operator maintain and troubleshoot the system in a safe and efficient method. Learning Objectives Describe the function and operation of primary single-phase switching devices. Describe the function and operation of primary three-phase switching devices. Describe the function and operation of secondary switching devices. Demonstrate the procedure to operate a primary three-phase switching device. Learning Methods Self-learning + On-the-job Self-learning + On-the-job Self-learning + On-the-job On-the-Job Demonstration and Practice EVALUATION METHODS Written test Written test Written test On-the-Job Evaluation

OVERHEAD SWITCHING DEVICES 3 STUDENT RESOURCES Learning Steps Construction Standards manual 1. Read the Learning Guide. 2. Follow the steps outlined in the Learning Guide. 3. Clarify any questions or concerns you may have. 4. Complete the Practice and Feedback. 5. Complete the Evaluation.

4 STUDENT TRAINING MANUAL Lesson 1: Primary Single-Phase Overhead Switching Devices Learning Objective:Describe the function and operation of primary single-phase switching devices. Learning Method:Self-learning + On-the-job Evaluation Method:Written test Introduction Sectionalizers Primary single-phase overhead switching devices are frequently used to isolate and connect electrical apparatus and/or electrical lines. Two basic types of switching devices are:

OVERHEAD SWITCHING DEVICES 5 Sectionalizers are an oil type switch designed to work in conjunction with oil circuit reclosers (OCR) to isolate faults on distribution lines. They are usually installed on single-phase tap-off lines fed from the three-phase system. When a fault occurs on the load side of the sectionalizer, the OCR will operate. The sectionalizer counts the number of OCR operations and, after two operations, the sectionalizer will lock out under a no current flow condition. This system design allows the OCR to energize the line up to the sectionalizer location on the third operation, thereby reducing the outage to affect only the customers on the load side of the sectionalizer and isolating the fault.! CAUTION Although Type Form 1-GH sectionalizers can not be used to pick up load, Type GN-3 sectionalizers can. Identify each before operating. Disconnects Disconnects are designed as a non-load break and non-load pickup switching device. Two types of disconnects are: solid blade bypass blade These switching devices are available in high amperage ratings, which makes them useful in areas where high amperage conditions exist.

6 STUDENT TRAINING MANUAL Solid Blade A solid blade allows the operator to isolate and energize sections of electrical apparatus, as well as power lines, under no load conditions, while maintaining the ability for high current flow in the power lines and electrical apparatus.

OVERHEAD SWITCHING DEVICES 7

8 STUDENT TRAINING MANUAL Bypass Blades A 3-blade bypass switch is basically three solid blades connected such that it allows the flow of electrical energy to be maintained in the power line while diverting the flow of electrical energy from apparatus such as OCRs and regulators. This allows maintenance and exchange of electrical apparatus while maintaining the electrical supply in the power

OVERHEAD SWITCHING DEVICES 9 lines.! CAUTION When operating bypass switches with porcelain insulators (brown or gray), two operators must be utilized. One supports the switch with a hotstick, while the other performs the switching operation. Because some bypass switch insulators have been known to break during switching, these types of bypass switches should be replaced with the polymer type.! CAUTION Always ensure the blade is locked in the closed position with the use of a tug test.

10 STUDENT TRAINING MANUAL Lesson 2: Three-Phase Overhead Primary Switching Devices Learning Objective:Describe the function and operation of primary three-phase switching devices. Learning Method:Self-learning + On-the-job Evaluation Method:Written test Introduction A three-phase overhead primary switching device has three individual switches mechanically connected together to operate simultaneously by a single handle. These devices, usually referred to as GOPT (gang operated pole top) switches, allow an operator to isolate and energize three-phase power lines. Two types of GOPT switching devices are: non-load break load break

OVERHEAD SWITCHING DEVICES 11 Non-load Break Switch Non-load break switches are used to isolate and energize power lines and electrical apparatus (transformers) under no load conditions. Nonload simply means that no form of energy is present.

12 STUDENT TRAINING MANUAL Load Break Switch Figure 1. Three-Phase Load Break GOPT Switch Load break switches are designed to energize and isolate loaded circuits and transformers up to their manufacturer s rating (current and power factor) as required for either radial or parallel operations. Load break switches are available with a variety of arc interrupting devices such as: arcing horns and whips arc stranglers

OVERHEAD SWITCHING DEVICES 13 arc interrupters STOP DANGER Always wear the proper protection (appropriate class of rubber gloves) when operating overhead threephase (GOPT) switches.! CAUTION Always check the switch blades to ensure they are completely open or completely closed.! CAUTION Ensure the switch handle is locked after switching is complete.

14 STUDENT TRAINING MANUAL Lesson 3: Secondary Switching Devices Learning Objective:Describe the function and operation of secondary switching devices. Learning Method:Self-learning + On-the-job Evaluation Method:Written test Introduction Secondary switching devices are used to isolate and energize secondary circuits, and can be found on farms, oilfields and on irrigation services. They are also used for street light systems. Two types of secondary switches are: current totalizing and thermal breakers secondary cabinet switches Reference For further information on breakers, refer to the Single Trip Overcurrent module Secondary Cabinet Switch A secondary cabinet switch provides a means of isolating and energizing secondary cables and electrical apparatus through the use of a load break and load pickup switch.

OVERHEAD SWITCHING DEVICES 15 Lesson 4: Procedure to Operate a Three-Phase Switching Device Learning Objective:Demonstrate the procedure to operate a primary three-phase switching device. Learning Method:On-the-Job Demonstration and Practice Evaluation Method:On-the-Job Evaluation

16 STUDENT TRAINING MANUAL Skills Practice 1. Isolate: 1. Inspect and wear Class 1 rubber gloves. 2. Unlock the switch handle. 3. Open the switch with a firm positive motion. 4. Check the blades. 5. Lock the handle in the open position. 2. Make alive: 1. Inspect and wear Class 1 rubber gloves. 2. Unlock the switch handle. 3. Close the switch with a firm positive motion. 4. Check the blades. 5. Lock the handle in the closed position.

OVERHEAD SWITCHING DEVICES 17 Summary To summarize this module, you have learned: The function and operation of primary single-phase switching devices. The function and operation of primary three-phase switching devices. The function and operation of secondary switching devices. Practice Feedback Review the lesson, ask any questions and complete the self-test. Evaluation When you are ready, complete the final test. You are expected to achieve 100%.

18 STUDENT TRAINING MANUAL Review Questions 1. Two types of primary overhead single-phase switching devices are: (a) Solid blade and bypass blades. (b) Sectionalizers and disconnects. (c) Hot line clamps and sectionalizers. (d) None of these T / F 2. A disconnect switch is used to open sections of power lines under no load conditions. 3. A bypass switch provides an operator with: (a) Three-phase switching capability. (b) Load breaking capability. (c) An ability to isolate electrical equipment. (d) None of these T / F 4. A sectionalizer cannot be used with an OCR. 5. Two types of disconnects are: (a) Solid blade and bypass blades. (b) Hot line clamps and sectionalizers. (c) Hot line clamps and bypass blade. (d) Riser and hot line clamp. T / F 6. Sectionalizers work in conjunction with oil circuit reclosers. T / F 7. Sectionalizers lock out under a no current flow condition. T / F 8. Sectionalizers work in conjunction with a cutout. T / F 9. A three-phase overhead switching device always has load breaking ability. 10. To energize and isolate three-phase overhead primary power lines with a primary current of 60 amps, an operator would use a:

OVERHEAD SWITCHING DEVICES 19 (a) (b) (c) (d) Disconnect. Sectionalizer. Three-phase GOPT load break switch. All of these T / F 11. Never use rubber gloves to operate a GOPT switch. 12. Load break switches are available with a variety of ARC interrupting devices such as: (a) Arcing horns and whips. (b) ARC stranglers. (c) ARC interrupters. (d) All of these 13. Two types of secondary switching devices are: (a) Breakers and solid blades. (b) Sectionalizers and secondary cabinet switches. (c) Bypass blades and sectionalizers. (d) Breakers and secondary cabinet switches. T / F 14. A secondary cabinet switch provides a means of isolating and energizing secondary cables and electrical apparatus through the use of load break and load pickup switch.

20 STUDENT TRAINING MANUAL Review Question Solutions 1. Sectionalizers and disconnects. 2. T 3. An ability to isolate electrical equipment. 4. F 5. Solid blade and bypass blades. 6. T 7. T 8. F 9. F 10. Three-phase GOPT load break switch. 11. F 12. All of these 13. Breakers and secondary cabinet switches. 14. T