SIMPLEX, SINGLE PHASE PUMP CONTROL PANEL Model SPC-PANEL Pump Controls for 2 HP Grinder Pumps

Similar documents
MODEL SPC-PANEL. Pump Controls for 2 HP Grinder Pumps

SPC-PANEL Simplex, Single Phase Pump Control Panel

Pump Installation and Service Manual HRS Hydromatic Retractable System

RETROFIT SYSTEMS INSTALLATION AND SERVICE MANUAL. Engineered for quick and easy replacement of existing progressive cavity grinder systems.

PUMP VAULT S.T.E.P. SYSTEM

HYDR-O-RAIL SYSTEM. Pump Installation and Service Manual

SEPTIC TANK PUMP VAULT FILTER SYSTEM PUMP VAULT INSTALLATION AND SERVICE MANUAL

ME3H/ME3F SERIES. Automatic and manual models. Single phase power only 115 or 230 volt.

NOVUS 3000 STANDARD ELECTRICAL CONTROLS INSTALLATION AND SERVICE MANUAL

HV200 SERIES GRINDER PUMPS INSTALLATION AND SERVICE MANUAL

MODELS WGL20, WGL20H and WGL20F

SUBMERSIBLE SEWAGE PUMPS

MODELS HPGFX/HPGHX & HPGFHX/HPGHHX

S4HVX Shown. (Class I, Division 1, Groups C & D): FM

NOTE! To the installer: Please make sure you provide this manual to the owner of the equipment or to the responsible party who maintains the system.

MODEL S4F SUBMERSIBLE SOLIDS HANDLING PUMP INSTALLATION AND SERVICE MANUAL

MODEL HPGX200. (Class I, Division 1, Groups C & D): FM HAZARDOUS LOCATION SUBMERSIBLE GRINDER PUMP

(Class I, Division 1, Groups C & D): FM

INSTALLATION AND SERVICE INSTRUCTIONS AND REPAIR PARTS LIST FOR MODELS K4RP & K4VP SUBMERSIBLE SOLIDS-HANDLING SEWAGE PUMPS

SHEF30 Submersible Sump/ Effluent Pump

MODEL MRG20 GRINDER PUMP INSTALLATION AND SERVICE MANUAL. 2 HP Grinder Pump for Residential Applications.

V2 SERIES GRINDER PUMPS INSTALLATION AND SERVICE MANUAL

MODELS HPGF/HPGFH, HPGH/HPGHH

MODEL HPGX200. (Class I, Division 1, Groups C & D): FM HAZARDOUS LOCATION SUBMERSIBLE GRINDER PUMP

HVR200 SERIES GRINDER PUMPS INSTALLATION AND SERVICE MANUAL

NOTE! To the installer: Please make sure you provide this manual to the owner of the equipment or to the responsible party who maintains the system.

MODELS CX10 and CX20 INDUSTRIAL PUMPS INSTRUCTIONS AND SERVICE MANUAL

W/D/V-A1. Submersible Sump Pump. Pump Installation and Service Manual W-A1 V-A1 D-A1

MODELS 4V, 4R, 4VH, 6VH, 4VC and 6VC

SUBMERSIBLE GRINDER PUMP Models HPGF/HPGFH; HPGH/HPGHH

SKHS Series Submersible High Head Sewage Ejector Available Horsepower: 1/2, 1, 1-1/2, 2

Pump Installation and Service Manual SP40 Submersible Sewage Ejector Pump

HYDROMATIC. G1X200/G1LX200 Explosion Proof Submersible Grinder Pumps (Class I, Division 1, Groups C & D): FM. Pump Installation and Service Manual

MODELS S3S(D)/S4S(D) and SB3S(D)/SB4S(D)

Ion Technologies SHR-HR Submersible Sewage Pump Single Seal, Single Phase, & Three Phase Power

A+ Battery Backup Power Supply For use with Hydromatic model B-A1/BV-A1

Pump Installation and Service Manual SK75/100 Submersible Sewage Ejector Pumps

METAL-TO-METAL RAIL SYSTEM

SUBMERSIBLE SOLIDS HANDLING PUMP Models S4T, S8L, S8LA, and S12L

MODELS 125M/B, 150M/B and 200M/B

MODELS: C4S(X)P, H3H(X)P, H4H(X)P, S4M(X)P, S4P(X)P, S4HV(X)P and S4MV(X)P (Class I, Division 1, Groups C & D): FM SUBMERSIBLE SOLIDS HANDLING PUMP

331-SV. User Manual THREE PHASE DUPLEX LIFT STATION CONTROL PANEL WITH STATIONVIEW CONTROLLER. Ashland, OH

MODELS 125M/B, 150M/B and 200M/B

(Class I, Division 1, Groups C & D): FM

Pump Installation and Service Manual JB-1 System Sewage Ejector Pump Package

SP40 Submersible Sewage Ejector Pump

GRINDER PUMP MODEL # Zoeller is a registered trademark of Zoeller Co. All Rights Reserved. Español p. 13

Pump Installation and Service Manual SHEF50/SHEF100 Submersible Effluent Pump

METAL-TO-METAL RAIL SYSTEM INSTALLATION AND SERVICE MANUAL

MODELS S4LX, S4BX, S4KX, S4QX, H4QX, S4LVX, S6AX, S6LX and S8FX

INSTRUCTIONS AND SERVICE MANUAL WITH PARTS LIST

SEWAGE PUMP MODEL # Zoeller is a registered trademark of Zoeller Co. All Rights Reserved. Español p. 14

S4HVX Submersible Pump with Explosion-Proof Motor End (Class I, Division 1, Groups C & D): FM For use with product built with USEM motor.

Installation and Service Manual OSP50/OSP50AB Submersible Effluent Pumps

Pump Installation and Service Manual SHEF50/SHEF100 Submersible Effluent Pump

MODELS WG/WGX20* GRINDER PUMP. *Used in Hazardous Locations Class I, Division 1, Groups C & D INSTALLATION AND SERVICE MANUAL

MODELS: C4S(X)P, H3H(X)P, H4H(X)P, S4M(X)P, S4P(X)P, S4HV(X)P and S4MV(X)P (Class I, Division 1, Groups C & D): FM SUBMERSIBLE SOLIDS HANDLING PUMP

PRE-PLUMBED SEWAGE SYSTEM

SUBMERSIBLE GRINDER PUMPS

Pump Installation and Service Manual SKV50 Submersible Sewage Ejector Pump

HPGB750/1000/1500. Submersible Grinder Pumps. Pump Installation and Service Manual

HAZARDOUS LOCATION SUBMERSIBLE GRINDER PUMP

S33 Sump Pump INSTRUCTIONS AND SERVICE MANUAL VERTICAL FLOAT SWITCH S33V1 & S33V1C AUTOMATIC S33P1 & S33PC-1 (CONTROL WITH SERIES PLUG) NOT SHOWN

Pump Installation and Service Manual SK60 Submersible Sewage Ejector Pump

WHR/WHRH and WHRE WASTE HANDLING SUMP PUMPS

Installation and Service Manual SK50 Submersible Sewage Ejector Pump

StormPro BA Series Sump Pump

PEDESTAL SUMP PUMP. MODEL # Español p. 11. Zoeller is a registered trademark of Zoeller Co. All Rights Reserved.

SUBMERSIBLE SOLIDS HANDLING PUMPS INSTALLATION AND SERVICE MANUAL

HYDROMATIC SPD50H/100H SUBMERSIBLE HIGH HEAD, DOUBLE SEAL EFFLUENT

SUBMERSIBLE BASIN MIXER

StormPro BCV400 Sewage Ejector Pump

GC-1. Roof and Gutter De-Icing Control Installation and Operating Instructions FOR EXTERIOR INSTALLATION ONLY

MODEL TL-PRO SYSTEM COMPLETE GRINDER PACKAGE OFFERING INSTALLATION AND SERVICE MANUAL. For use with HPG(X)200 and HPGR200 Hydromatic Grinder Pumps.

SUBMERSIBLE SUMP PUMPS

MODELS 4VC(X * ), 6VC(X * ), 4VE(X * ) AND 4RC(X * ) SUBMERSIBLE SOLIDS HANDLING PUMPS. *Used in Hazardous Locations Class I, Division 1, Groups C & D

INSTALLATION AND SERVICE MANUAL MSKV50 Submersible Sewage Ejector Pump

INSTALLATION AND SERVICE INSTRUCTIONS KER KEEN PUMP - e/one Replacement

Air Curtain. Installation, Operating and Maintenance Instructions

Your Premier Pump Choice!

471 US Hwy 250 East, Ashland, Ohio PH: FX:

For use with Hydromatic grinder pumps: HPG200, HPGR200 and HPD200 (shown on cover).

SUBMERSIBLE SUMP PUMPS

MODELS H3H, H4H, S4M, S4P, S4HRC and S4MRC SUBMERSIBLE SOLIDS HANDLING PUMPS INSTALLATION AND SERVICE MANUAL

Installation and Service Manual JB-1 System Sewage Ejector Pump Package

Accu-Meter Oil Pump. Instruction Manual. Model #2114. Cincinnati, OH USA. Part No Revised June 1996

HYDROMATIC SKHS SERIES SUBMERSIBLE NON-CLOG, SEWAGE EJECTOR

Aqua Ultraviolet Sunami Series Pumps 1/3HP, 3/4HP, 3HP, 4HP, 5HP

HYDROMATIC SK75/100 SUBMERSIBLE SEWAGE EJECTOR

Ion Technologies WC33 Submersible Sump Pump

INSTALLATION MANUAL & START UP Control Panel

TALCO FIRE SYSTEMS. LSF Start-Up Instructions. 1) IMPORTANT: Inspect the unit for damage. Report any damage to the freight carrier immediately.

4" ENVIRONMENTAL E-SERIES PUMPS OWNER'S MANUAL. DANGER warns about hazards that will cause. WARNING warns about hazards that can cause

HYDROMATIC HE8/HE12/HE20/HE25/ HE30/HE35/HE50 HIGH HEAD FILTERED EFFLUENT

ESE Series Cast Iron Sewage Pumps

MYERS INSTALLATION AND SERVICE MANUAL CENTRI-THRIFT CENTRIFUGAL PUMPS. Models 125M/B, 150M/B and 200M/B

TPAK Series COOLANT PUMP

AUTOMATIC SUBMERSIBLE UTILITY PUMP

HAZARDOUS LOCATION SUBMERSIBLE PUMP Model S4NVX (Class I, Division 1, Group C & D): FM

Intelligent Flap Controller

Transcription:

Installation and Service Manual SIMPLEX, SINGLE PHASE PUMP CONTROL PANEL Model SPC-PANEL Pump Controls for 2 HP Grinder Pumps NOTE! To the installer: Please make sure you provide this manual to the owner of the equip ment or to the responsible party who maintains the system. 04/10 Item # E-03-352 Part # 5625-352-1

Thank you for purchasing your Hydromatic control panel. To help ensure years of trouble-free op er a tion, please read the following manual carefully. Before Operation: Read the following in struc tions care ful ly. Reasonable care and safe meth ods should be practiced. Check local codes and requirements before installation. Attention: This manual contains important information for the safe use of this product. Read this manual completely before using this product and refer to it often for con tin ued safe product use. DO NOT THROW AWAY OR LOSE THIS MAN U AL. Keep it in a safe place so that you may refer to it when needed. Unpacking Panel: Remove panel from carton. When un pack ing unit, check for con cealed damage. Claims for damage must be made at the receiving end through the delivery carrier. Dam age cannot be processed from the factory. WARNING: Before handling these Hydromatic pumps and controls, always disconnect the power first. Do not smoke or use sparkable electrical devices or flames in a septic (gaseous) or possible septic sump. 2 General Information Panel Installation Electrical Connections: The contractor must conform to the latest requirements of the National Electrical Code. All conduit and ca bles shall be in accordance with NEC code NFPA #70. To maintain UL type 4X and CSA ENCL 4 rating, use UL type 4 and CSA weatherproof con duit hubs when connecting to this enclosure. Prior to conducting any in stal la tion, repair or service with re gard to the control panel, refer to the schematic ap pro pri ate for that panel. The sche mat ic will provide guidance with regard to the terminal block con nec tions. CAUTION: Nonmetallic enclosures do not provide grounding conduit con nec tions. Use grounding bush ing and jumper wires. Make the Following Electrical Connections: a. Connect the pump leads to the control panel. When connecting the pump leads it is very critical that the prop er sequence be maintained. On single phase pumps, the color coded pump leads black, white, red, must be connected to the appropriate terminals as directed by the control schematic. b. Connect the pump heat sensor and seal failure leads (if available on the pump) to the appropriate ter mi nal blocks in the control panel. If the heat sensor lead from the pump is wired as indicated, re move jumpers as defined by the schematic. c. Connect all the float control leads to the appropriate panel terminal blocks. Con trac tor must be very careful in locating the floats at the proper elevations. The maximum distance from the control panel and the floats is the lesser of l00 feet, or the maximum distance recommended for the pump. d. Before connecting power to the control panel, make sure all the control switches (e.g. H-O-A switch) and protective devices (e.g. breakers) are in the Off position. Now connect power to the circuit breaker as directed by the schematic. e. Power must be the correct voltage for the pump model. Power must have neutral to supply 120 volts to the control circuit. f. Control panel must be grounded properly per NEC and/or local codes. To facilitate this, a ground lug is provided on the control panel. Panel Operations WARNING: Before handling these Hydromatic pumps and controls, always disconnect the power first. Do not smoke or use sparkable electrical devices or flames in a septic (gaseous) or possible septic sump. Check List: 1. Check junction box for moisture. 2. Check wiring of pump black, white, red power wires. 3. Check wiring of heat sensor and seal failure wires if supplied.

4. Energize control panel. (Turn on power to panel.) 5. Check overload relay and verify reset mode (if overload is supplied). 6. WARNING! Live voltage can kill! Check voltage to the panel and to the con trol circuit using a voltmeter. 7. Check float operation and response to control panel to the float operation. For sequence of operation, refer to design specification. 8. Check full load current with amp probe and compare it with the nameplate rat ing. (Clamp amp probe around black pump wire.) 9. With pump running, check discharge to verify the pump is running. Check for flow. 10.Check operation of start relay, per procedure in Item #3 on page 4. 11.Make sure H-O-A switch is left in the Auto position after start-up is com plet ed. 12.Make sure all conduits from wet well to panel are sealed below panel. Septic gases will damage components in panel. Pump Start-up: Refer to pump Installation and Service Manual. Panel Maintenance WARNING: Before handling these Hydromatic pumps and controls, always disconnect the power first. Do not smoke or use sparkable electrical devices or flames in a septic (gaseous) or possible septic sump. 1. Pump does not run in Hand position. a. Check pump circuit breaker and control fuse for trip ping or blown condition. b. Check incoming power voltage and control circuit voltage. c. Check overload relay to see if it is tripped. Reset relay if tripped. d. With the power off, check motor heat sensor continuity. e. Check wiring of pump to control panel. It should agree with the schematic. f. Check contactor coil resistance. It should be 50 to 200 ohms. 2. Pump does not run in Auto position. a. Check items (a.) through (d.) per Item #1. b. Floats may be miswired to control panel. Check float type (N.O. or N.C.) and hook up by referring to the schematic. If the start and stop floats are hooked in reverse, pump will short cycle and will not pump the level down. c. Is the water level in the system high enough to activate floats? d1. With the power off, remove Off float and On float wires and replace with two jumpers made from insulated wire. d2.turn power on (with H-O-A switch in Auto position). If pump runs, the prob lem is in one of the floats. d3.if the problem is in a float, turn power off, remove jumper and reconnect the upper float. Turn power on and see if pump will run in Auto. This will help identify which float is the problem. Turn power off before removing any jumper or reconnecting any float. 3. Pump runs, but run light does not energize. a. Remove light bulb and check with ohmmeter. b. Check wiring for run light in panel. 4. Pump runs but does not pump down the wet well. a. Impeller may be dragging in volute due to solids. High am per age draw would identify this. b. Refer to the pump manual for other possibilities such as closed discharge gate valve, etc. 5. Severe humming/chattering of contactors and control relays. a. There may be low voltage. Check voltage to the panel and to the control circuit using a voltmeter. This low voltage condition may even cause se vere chattering and burn-out of relays. Contactors require a minimum of 85% of full vol tage to pull in without chatter. If the problem is a recurring one, measure voltage with re cord er on a 24 hour basis. b. Contactor may have dust around magnet of coil struc ture. Dry or clean as re quired. c. Make sure the floats are located away from any turbulence. 3

Panel Maintenance d. Dry out the junction box (if furnished); moisture in the junction box may tend to cause relays to energize intermittently. 6. Nuisance tripping of overload on motor starters or circuit breakers. a. Check all reset buttons and tripped breakers. b. Check pump amp draw with amp probe and compare to nameplate amps on pump. c. The impeller may be locked up due to excessive debris or solids. d. Possible motor failure (fault on windings). e. Pump may be miswired to terminal blocks. 7. Short cycling pump. a. Check float controls. 8. Run light stays on. a. Selector switch may be in the Hand position. 9. Test for blown fuse. a. Check for continuity with a V-O-M set on ohm scale. Single Phase Pump Only: Connections and start components 1. Motor winding resistance readings. a. Disconnect all three motor leads. b. Using a volt-ohm meter, with the scale set on RX1, measure the resistance be tween the leads with the following chart. Typical Motor Resistance Winding Leads Reading Main Black to Lowest White Start Black to Next Red Lowest (Middle) Both White to Highest Red 2. Capacitor Check. a. Make sure the capacitors are discharged. Use extreme caution; severe shock hazard may exist with capacitors. b. Disconnect the capacitor leads and connect a volt-ohmmeter to the capacitor terminals. c. The meter should indicate low ohms when it is first connected, but as the capacitor becomes charged (by the meter), it will return to a reading of infinity (open circuit). NOTE: Set the meter on the RX10,000 scale to check the run capacitor. Set the meter on the RX1,000 scale to check the start capacitor. b. Turn power on and run pump in Hand position. After the pump starts, check the voltage from terminal 1 to terminal 2 on the start relay to be sure that the relay has operated. The voltage from terminal 1 to terminal 2 on the start relay must exceed 10 VAC. For some pumps the voltage may exceed 400 VAC. If after 5 seconds the voltage from terminal 1 to terminal 2 on the start relay does not exceed 10 VAC, stop the pump as damage to the start capacitor will occur in about 15 seconds. If the start relay is not operating, check the pump and the system voltage to be sure that they match. Check the power wiring to ensure that the pump is connected properly. Start the pump once more and check to see if the voltage from the terminal for the black wire to the white wire is within system tolerance. Call for help if you cannot resolve the problem. WARNING: Disconnect all power from the panel before making these checks. 4 3. Start relay check. a. With power off, check the start relay coil resistance. It should be 3000 to 7000 ohms.

Pump Notes 5

STANDARD LIMITED WARRANTY HYDROMATIC warrants its products against defects in material and workmanship for a period of 12 months from the date of shipment from Hydromatic or 18 months from the manufacturing date, whichever occurs first - provided that such products are used compliance with the requirements of the Hydromatic catalog and technical manuals for use in pumping raw sewage, municipal wastewater or similar, abrasive free non-corrosive liquids. During the warranty period and subject to the conditions set forth, Hydromatic, at its discretion, will repair or replace to the original user, the parts which prove defective in materials and workmanship. Hydromatic reserves the right to change or improve its products or any portions thereof without being obligated to provide such a change or improvement for prior sold and/or shipped units. Start-up reports and electrical schematics may be required to support warranty claims. Warranty is effective only if Hydromatic authorized control panels are used. All seal fail and heat sensing devices must be hooked up, functional and monitored or this warranty will be void. Hydromatic will only cover the lower seal and labor thereof for all dual seal pumps. Under no circumstance will Hydromatic be responsible for the cost of field labor, travel expenses, rented equipment, removal/reinstallation costs or freight expenses to and from the factory or an authorized Hydromatic service facility. This limited warranty will not apply: (a) to defects or malfunctions resulting from failure to properly install, operate or maintain the unit in accordance with the printed instructions provided; (b) to failures resulting from abuse, accident or negligence; (c) to normal maintenance services and parts used in connection with such service; (d) to units which are not installed in accordance with applicable local codes, ordinances and good trade practices; (e) if the unit is moved from its original installation location; (f) if unit is used for purposes other than for what it is designed and manufactured; (g) to any unit which has been repaired or altered by anyone other than Hydromatic or an authorized Hydromatic service provider; (h) to any unit which has been repaired using non factory specified/oem parts. Warranty Exclusions: HYDROMATIC MAKES NO EXPRESS OR IMPLIED WARRANTIES WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF. HYDROMATIC SPECIFICALLY DISCLAIMS THE IMPLIED WARRANTIES OF MERCHANTABILITY AND FITNESS FOR ANY PARTICULAR PURPOSE. Liability Limitation: IN NO EVENT SHALL HYDROMATIC BE LIABLE OR RESPONSIBLE FOR CONSEQUENTIAL, INCIDENTAL OR SPECIAL DAMAGES RESULTING FROM OR RELATED IN ANY MANNER TO ANY HYDROMATIC PRODUCT OR PARTS THEREOF. PERSONAL INJURY AND/OR PROPERTY DAMAGE MAY RESULT FROM IMPROPER INSTALLATION. HYDROMATIC DISCLAIMS ALL LIABILITY, INCLUDING LIABILITY UNDER THIS WARRANTY, FOR IMPROPER INSTALLATION. HYDROMATIC RECOMMENDS INSTALLATION BY PROFESSIONALS. Some states do not permit some or all of the above warranty limitations or the exclusion or limitation of incidental or consequential damages and therefore such limitations may not apply to you. No warranties or representations at any time made by any representatives of Hydromatic shall vary or expand the provision hereof. Your Authorized Local Distributor USA 740 East 9th Street, Ashland, Ohio 44805 Tel: 419-289-3042 Fax: 419-281-4087 Warranty Rev 02/09 www.hydromatic.com CANADA 269 Trillium Drive, Kitchener, Ontario, Canada N2G 4W5 Tel: 519-896-2163 Fax: 519-896-6337

START-UP REPORT Distributor: Order No.: Installing Contractor: Phone: Sales Contact: Phone: Customer: Location: cut along dotted line 1. SYSTEM INFORMATION Size of Wet Well: Manufacturer: Discharge from Bottom of Basin: Discharge Location: Inlet from Bottom of Basin: Inlet Location: Type of Check Valves: Type of Piping: Does System Have Suction Gauges? Yes No Suction Pressure Reading: Does System Have Discharge Gauges? Yes No Discharge Pressure Reading: Liquid Being Pumped: Temperature (F ): Pct. of Solid (%): Is a Sketch or Photograph of System Available? Yes No If So, Please Attach. Any Additional Comments on System: 2. ELECTRICAL INFORMATION Control Panel Part Number: Panel Rated Amps: Manufacturer: Voltage: Phase: Heater Size: Location of Panel to Wet Well: Incoming Line Voltage: Actual? Voltage to Pumps: Actual? Type of Junction Box: Manufacturer of Junction Box: Are Floats Installed in Wet Well? Yes No Are Floats Set to Engineer s Specs? Yes No Are Floats Wired for Proper Sequencing? Yes No Are Heat Sensors Hooked Up? Yes No Is the Seal Leak Detection Hooked Up? Yes No Any Additional Comments on Electrical: 3. PUMP INFORMATION Type of Pump: Serial Number of Pump: Voltage of Pump: Phase: RPM: Amps: Impeller Size: C.O.S. TDH: GPM: Voltage Supplied from Panel: Actual? Actual Amperage (All Phases): Phase 1 Amps: Phase 2 Amps: Phase 3 Amps: Define the Rotation of the Pump: Clockwise Counterclockwise Method Used to Check Rotation: Viewed from the Top Viewed from the Bottom Any Additional Comments on Pumps: 4. ACKNOWLEDGE Acknowledge that all information is accurate and proper procedures have been followed. Customer: Date: Start-up Technician: Date: Send to Warranty Manager, 1101 Myers Parkway, Ashland, OH 44805 or Fax to 419-207-3344 or email to startupreport@hydromatic.com or submit online at http://forms.pentairliterature.com/startupform/startupform.asp?type=h