24V 3A EN54 Ancillary Power Supply

Similar documents
Dycon D2430 EN54-4 Fire Alarm Power Supply Series

Dycon D1532SM. EN50131/PD6662 Grade 3, 12V 2A Power Supply. Technical Description Installation and Operating Manual DYCON POWER SOLUTIONS LTD

K25000 & KD25000 Series

PREMIER POWER PACK INSTRUCTION MANUAL EN54-4 POWER SUPPLY UNIT INSTRUCTION MANUAL. GLT.MAN-138 Issue: /05/2016 N.R.P.J.

27.6 Vdc 1 Amp Switch Mode Power Supply for Fire EN54-4:1997 +A1 +A2

PSU EN54-4 Power Supplies

HE-PSU(4.0) Power Supply & Battery Charger Installation, Commissioning & Operating Manual

Elmdene International Ltd

RE-PR3-E-86&105 3-Phase Panel Mount 86 and 105kW

The 4HR-UPS 220V ac output is provided via a Pure Sine Wave inverter, allowing it to be backed up by 2x 12V standby batteries.

Metrohm E3640 FLASH TESTER INSTRUCTION MANUAL. Martindale Electric Co Ltd.

Sentry Battery Charger. Installation and Operations Manual Section 75

Cellwatch Electrical Installation

RE-PR1-F 1-Phase Din-Rail Mount 1.5, 3 & 6kW

Central Battery Systems Loadstar AC/DC Systems

USER MANUAL. 10 January Certification of constancy of performance CNBOP No CPR-0454 Certificate of admittance CNBOP No.

Switching DC Power Supply

5 IN 1 JUMP START OPERATION & MAINTENANCE INSTRUCTIONS MODEL NO: JS5IN1 PART NO: LS0810

Product Data Sheet. Damper Interface. Features

Free Fall Fire Valve Range & Accessories

TC2-ES MANUAL Page 1 OPERATING INSTRUCTIONS USER INFORMATION TC2-ES POWER SUPPLY

KEWTECH. KT56 digital multi function tester. Instruction manual

KV4-300 mk2. KV5-200 mk2. KV5-100T mk2. KV3-250 mk2

& HIGH CURRENT DC POWER SUPPLIES INSTRUCTION MANUAL

MAX. AC 600V HOLD V M H.V. LIVE CIRCUIT DIGITAL INSULATION TESTER DO NOT OPERATE IF LIT POWER DATA HOLD TEST ON / OFF 250V 500V 1000V OFF CAT.

Sentinel 150 series Automatic switch mode battery chargers Installation, Operation and Maintenance

HT Dielectric Withstand Tester Volts AC Output 25mA Leakage Option

BellMega BM-510. Operation Manual Ver: 1.0 Rev: 1

OPERATING INSTRUCTION

Guardian Battery Charger Series. Installation and Operations Manual Section 75

MARTINDALE INSTRUCTIONS ELITE FUSE FINDER KIT ELECTRIC. Trusted by professionals. 4.4 Storage Conditions

SB 2000 PUSH TO SEARCH NEXT STAG E. Aerotech, Inc. FORM: QM 1320

POWER FOR TOMORROW. Motive Power. Network Power. Chargers. Bloc Batteries. Accessories. Service

TECHNICAL MANUAL. Inverter / Charger Combi. Combi SW 12V 1600VA Réf : PF Combi SW 24V 3800VA Réf : PF NOT_COMBI_SW-00

KD1E Range Potential Indicators

Installation Instructions

Installation Instructions

INSTALLATION & OPERATING MANUAL RW SERIES WALL-MOUNT RECTIFIERS

HILLSTONE DC LOAD BANK

POWERLINE 2000 Energy Management System TM

OPERATING AND MAINTENANCE MANUAL. Primary Current Injection Test Set. 750ADM-H mk2

1 This instrument must only be used by a competent and trained person and operated in strict accordance with the instructions.

USER MANUAL GEBRUIKSAANWIJZING GEBRAUCHSANWEISUNG SKYLLA 24/100 3-PHASE CE

V1606 3U RACK ENCLOSURE

GLM SERIES CONTROL Users Manual Rev:

Rental Industry Safety Tester Safe Check 5s

PowerOhm Installation Manual for BM R Series Braking Modules

NON MAINTAINED TWIN SPOTLIGHT WALL MOUNT LED EMERGENCY LIGHT

MKey9-series Safety Interlock Switch with Guard Locking

HWP Protection Board

OPERATION & MAINTENANCE INSTRUCTIONS

Powerware Vdc Extended Battery Cabinet User s Guide.

OPERATIONS AND APPLICATIONS MANUAL MODEL NUMBER PM6. 6 KV DC HIGH POTENTIAL TESTER WITH MEGOHMMETER Version 2.0

TOWER MAXI T SINGLE CONVERSION ON LINE UPS SYSTEMS

OPERATION & MAINTENANCE INSTRUCTIONS

Installing Power Components

DEEP SEA ELECTRONICS PLC

OPERATION & MAINTENANCE INSTRUCTIONS

EMEX Power. EMEX Power. Modular AC/AC Central Battery System. EMEX Power

MODEL ELC-12/40-CVM-D BATTERY CHARGER

OWNER S MANUAL Please read this manual before operating your power supply

Manifold QF. Contents. Description. Installation & Setup Guide. Safety 3. Introduction 3. Installation Standards 4. Specifications 5.

Instruction Manual. Model 307A Analog Insulation & Continuity Meter

EC400 Power Control System

INSTALLATION, OPERATION & MAINTENANCE INSTRATIONS

RELAY BOX PRODUCT MANUAL IMPORTANT

MODEL 520 REMOTE START ENGINE MANAGEMENT SYSTEM

EMERGENCY ONE-LED TM SOLO TM NON MAINTAINED LED LAMP AND DRIVER KIT

ANALOGUE INSULATION-CONTINUITY and VOLTAGE METER

EMPAC Metal enclosed capacitor bank for wind applications

Model DS1000/DT20 System

Vehicle battery BATTERY WARNING SYMBOLS BATTERY CARE

Compact Sine Inverter

ACSI MODEL 1406BB-04-AO POWER SUPPLY INSTALLATION INSTRUCTIONS

PowerOhm Installation Manual for BM R Series Braking Modules

model ps600 Address all communications and shipments to: FEDERAL SIGNAL CORPORATION

INTECH Micro 2300-RTD6

F3S-TGR-KHL1/-KHL3/-KHL3R

Installation, Operation and Maintenance Manual. EVC Controller (from February 2007)

Compact System NRGS 11-2 NRGS Original Installation Instructions English

EMERGENCY VEHICLE BATTERY MANAGER PS2024

Burden Fuse Rating Resistor SAF / SAK6 1NM 10mm M8 12NM SAF / SAK10 2NM 16mm M8 12NM

Unified requirements for systems with voltages above 1 kv up to 15 kv

Operators Guide: RoboSign Stop/Go Traffic Control System

LED AC DRIVERLESS FLOODLIGHTS WITH PIR FOR MODEL: FLAC10BPIR, FLAC20BPIR, FLAC30BPIR & FLAC50BPIR

Operators Guide: RoboSign Stop/Go Traffic Control System

IN1001/IN1003 ANALOGUE INSULATION & CONTINUITY TESTERS INSTRUCTION MANUAL IN1001/IN1003 ANALOGUE INSULATION & CONTINUITY TESTERS INSTRUCTION MANUAL

Art. No. EC-315. Art. No. EC-330. Art. No. EC-340 SWITCH-MODE BATTTERY CHARGER CONTENTS IMPORTANT SAFETY PRECAUTIONS... 2

PURE SINE WAVE DC TO AC POWER INVERTER

HGM501 Gen-set Controller USER MANUAL. Smartgen Technology

KD LV Motor Protection Relay

Installation and Maintenance Instructions. World Leader in Modular Torque Limiters. PTM-4 Load Monitor

RESIDUAL CURRENT CIRCUIT BREAKER

1.Safe testing IMPORTANT:

Contents. Overview. Safety Instructions. Before Installation. Installation. Operation. Maintenance. Replacement Parts. System Specifications 8 01

Why Electric Safety Standards

Car Battery Charger Instructions for Use

GL1200T Cut & Seal. (GL1200 Seal only)

HEAVY DUTY BATTERY BOOSTERS / CHARGER MODEL No. BC420N

Model 1693, 1694 Switching DC Power Supply

Transcription:

24V 3A EN54 Ancillary Power Supply Normal supply - green light on Fault condition - call Engineer Control relay - activated 3A Power Supply C-TEC Manufactured in England by C-Tec EN 54-4 : 1997 INSTALLATION INSTRUCTIONS Approved Document No. DFU0706100 Rev 1 THIS DOCUMENT MUST NOT BE LEFT ACCESSIBLE TO THE USER 24V 3A ANCILLARY POWER SUPPLY INSTALLATION INSTRUCTIONS APPROVED DOCUMENT No. DFU0706100 Rev 1 PAGE 1

IMPORTANT NOTES THIS SECTION MUST BE READ PRIOR TO THE INSTALLATION / MAINTENANCE OF THIS PRODUCT This equipment must only be installed and maintained by a suitably skilled and technically competent person. This equipment is a piece of Class 1 equipment and MUST BE EARTHED THIS POWER SUPPLY STORES VOLTAGES AT UP TO 400Vd.c. AND MAY BE LETHAL IF TOUCHED. DO NOT TOUCH THE POWER SUPPLY CIRCUIT BOARD WHILST THE RED LETHAL VOLTAGE PRESENT INDICATOR IS LIT. If the LED is not lit this does NOT mean it is safe to touch. Take great caution. The only sure and recommended way of handling this power supply unit is to physically remove the mains connector (after isolating) then wait until the red LED extinguishes. The LED is extinguished completely when the voltages present are less than 50Vd.c. Protective Cover: This cover complete with warning label protects the installer/programmer from accidental contact with circuit components that may be charged at up to 400Vd.c. This may be lethal. DO NOT ATTEMPT TO TOUCH OR PROBE ANY COMPONENT COVERED BY THIS LABEL OR ADJACENT TO IT. DO NOT connect mains to this unit until the installation is complete and all the circuit boards are correctly secured within the panel. The PSU earth strap must be fitted to the chassis earth point before connecting the mains supply. DO NOT OPERATE THE POWER SUPPLY OUT OF THE ENCLOSURE, or without the circuit board retained in the correct position. No responsibility can be accepted by the manufacturer or distributors of this power supply for any misinterpretation of an instruction or guidance note or for the compliance of the system as a whole. System design is beyond the scope of this document. An understanding of the system components and their use is assumed. Errors and omissions excepted. The manufacturers policy is one of continuous improvement and we reserve the right to alter product specifications at our discretion and without prior notice. PSU earth strap. DO NOT operate this equipment without this strap connected CHASSIS EARTH POINT DO NOT remove spade Incoming mains Note: Mains terminal block can be removed from PCB for ease of installation Output Fuse Fault LED The incoming mains cable earth must be connected to the terminal marked and not the chassis earth point. (The PSU earth strap connects the earth to the chassis). PCB Retaining Screw Battery Fault LED BATTERY BACK-UP LEADS LETHAL VOLTAGE PRESENT LED (illuminated red when potentially lethal voltages are present) SHADED SECTION INDICATES AREA OF PCB WHERE HAZARDOUS VOLTAGES ARE PRESENT 24V 3A ANCILLARY POWER SUPPLY INSTALLATION INSTRUCTIONS APPROVED DOCUMENT No. DFU0706100 Rev 1 PAGE 2

NC C NO POWER SUPPLY OVERVIEW This unit is a 185-265Va.c. 50-60Hz off line switched mode power supply which combines the functions of a power supply unit, battery charging unit and battery monitoring unit. It is intended for use with fire alarm systems for powering ancillary circuits. If used with a fire alarm system, we recommend you read BS 5839: Pt 1: 1988 Fire Detection and Alarm Systems for Buildings (Code of Practice for System Design, Installation and Servicing) available at your local reference library or from the BSI. It is designed to supply a maximum of 3A to a load (if a battery is fitted this reduces to 2.5A in order to charge the battery) and is continuously rated. It has the ability to switch the load on and off dependent upon input signals. The unit is internally fault monitored, and any fault can be signalled to other equipment. It has the ability to include battery back up, from 2Ahr to 10Ahr. Isolated input and output signals are available. OUTPUTS These are controlled via a 2 pole changeover relay (RLY2). When this relay is activated the output is triggered. Supply Output (CONN1) - 1st pole of RLY2 0V Output V Output NC Output NO Output F1 NO NC V 0V OUTPUT CONN1 FUSE 3AF D6 Output Fuse Fault LED The PSU has four supply output terminals:- 0V Zero volts V Continuous 24V NC 24V in a non-triggered state, open circuit in a triggered state NO Open circuit in a non-triggered state, 24V in a triggered state The Supply Outputs are protected by a common fuse (F1) and can supply a total maximum of 3A. Isolated Output (CONN5) - 2nd pole of RLY2 NO C NC ISO O/P CONN 5 This isolated set of contacts can switch up to 3A. When in a non-triggered state C is connected to NC, NO is open circuit When in a triggered state C is connected to NO, and NC is open circuit Fault Output (CONN4) NO NC C CONN4 FAULT C NC NO This is an isolated relay output rated at 1A and is configured for fail safe operation, i.e. it is normally energised when there is no fault condition. In this state C is connected to NC and NO is open circuit. In any fault condition (including the complete loss of power), the relay changes state, C is connected to NO and NC becomes open circuit. 24V 3A ANCILLARY POWER SUPPLY INSTALLATION INSTRUCTIONS APPROVED DOCUMENT No. DFU0706100 Rev 1 PAGE 3

INPUTS The PSU has three inputs and one control link:- Local Trig Trig Hold Off CONN2 CONN3 - - - HOLD TRIG LOCAL OFF TRIG PLK1 HOLD OFF DISABLE EXTERNAL & INTERNAL INDICATORS Three LED indicators are provided on the PSU front:- Local Trig (CONN2) This input is NOT isolated from the PSU and is intended for local control switching. When a short is applied to this input the unit will trigger. Trig (CONN3) This input is an isolated input. When a signal of between 5 and 30V is applied to it the unit will trigger. If any trigger inputs are applied then the PSU will be in an activated state. To be in a non-activated state the two trigger inputs must not be applied and either PLK1 fitted or a valid signal applied to Hold Off Hold Off (CONN3) This input is an isolated input which must be held between 5 and 30V to prevent the unit from triggering. To use this input remove the HOLD OFF DISABLE link (PLK1). If this input is not used ensure PLK1 is fitted. This input can be used for failsafe operation. If Hold Off is not applied and PLK1 is not fitted the unit will be in a triggered state. Normal supply green light on When lit, this indicates the mains supply is healthy. Fault Condition - call engineer When lit, this indicates that a fault has occurred. Normal supply - green light on Fault condition - call Engineer Control relay - activated Control Relay Activated When lit, this indicates the unit is in the triggered state. Three engineer LED indicators are also provided on the main board:- Output Fuse Fault LED Lethal Voltage Present LED Mains is present and voltages of up to 400V are present on the primary (hatched) area of the PCB. Output Fuse Fault LED The output fuse has ruptured. Battery Fault LED. The batteries are low, faulty or the battery fuse has ruptured. Battery Fault LED Lethal Volatge Present LED EARTHING AND CIRCULATING CURRENTS The output of this unit is floating with respect to earth. IMPORTANT: The mains input to the power supply MUST be earthed. If screened cables are used they should be earthed. Consideration should be given to the magnitude of possible fault and leakage currents that may flow in the earthing system, especially in multiple point earthing schemes. The 0V or 24V supply output of this unit should not be connected to other supplies. This could cause large 0V to 0V currents to flow between the units. 24V 3A ANCILLARY POWER SUPPLY INSTALLATION INSTRUCTIONS APPROVED DOCUMENT No. DFU0706100 Rev 1 PAGE 4

OPTIONAL BATTERY BACKUP The PSU has the ability to charge, monitor and supply the load using 2Ahr to 10Ahr sealed lead acid (VRLA) batteries. If batteries are fitted link PLK2 (labelled LINK FOR BATTERY MONITORING ) should be fitted. If the unit is to be used without batteries link PLK2 should be removed to prevent a battery fault condition. If the mains supply fails the batteries will automatically supply the load. The batteries will start to discharge and their terminal voltage will fall. When the battery voltage level drops to 23V the unit will indicate a battery fault. When the battery voltage reaches 22V the unit will disconnect the batteries from the load. The size and capacity of batteries used will depend upon the stand-by-time required by the system. The battery back-up leads should be connected to 2x12V or 4x batteries connected in series and mounted as indicated in the diagrams shown (right). Shorting links are provided in the PSU accessory pack. Fuse F2 protects the battery and circuit from over current faults. If the battery back-up leads are connected the wrong way Fuse F2 will blow. IMPORTANT: Always dispose of used batteries according to the battery manufacturers instructions. Suggested positioning of batteries inside PSU cabinet or 12V or 12V Arrangement for 12V back-up batteries 12V 12V Black wire from PSU Red wire from PSU Arrangement for back-up batteries PL1 SYSTEM DESIGN Simple Overview MAINS SUPPLY Red wire from PSU Black wire from PSU CONTROL EQUIPMENT CONTROL WIRING FAULT RETURN 3A PSU LOAD Examples of System Arrangements The following diagrams demonstrate how to utilise the power supply s various features in different system scenarios. These are suggestions only and are not intended to be fully representative of actual installations. Load normally powered, trigger will disconnect power 0V Output V Output NC Output NO Output Local Trig Trig Hold Off Load Link PLK1 Fitted Control Unit Energise Trig input to turn off load. PLK1 is fitted so hold off is disabled. Note: this means the supply will not trigger if the control connection is lost. 24V 3A ANCILLARY POWER SUPPLY INSTALLATION INSTRUCTIONS APPROVED DOCUMENT No. DFU0706100 Rev 1 PAGE 5

Load normally off. Removal of hold off triggers unit and switches on load 0V Output V Output NC Output NO Output Local Trig Trig Hold Off Load Link PLK1 Not Fitted Control Unit Energise the Hold Off input to keep the load off. PLK1 is not fitted enabling Hold Off. Note: this means the supply will trigger if the control connection is lost and allows the unit to be used in a fail safe mode. Load normally off. Make local trigger to energise. 0V Output V Output NC Output NO Output Local Trig Trig Hold Off Load N/O Switch Link PLK1 Fitted Short Local Trig input to cause the unit to trigger and apply power to the load. PLK1 is fitted so hold off is disabled. Note: this means the supply will not trigger if the control connection is lost. Typical Fault Monitor Fault Output NO NC C End of Line Resistor Control Unit If a PSU fault occurs then the fault output will change state giving an open circuit fault to the control unit. The fault output controls the control unit s end of line resistor. INSTALLATION Mains Connection Please note: These guidelines are based on BS 5839: Pt1: 1988 and BS 7671 (Wiring Regulations). Other national standards of installation should be used where pertinent. It is important that mains is brought into the enclosure at the top right hand side as indicated in the diagram (right). The requirement for the mains supply to this equipment is fixed wiring, using three core cable (no less than 0.75mm2 and no more than 2.5mm2) or a suitable three conductor system, fed from an isolating switch fuse spur, fused at 3A. This should be secure from unauthorised operation and be marked DO NOT SWITCH OFF. Correctly terminate the incoming cables as shown in the diagram (right). If required, the 5mm connector block (CONN6) can be pulled from the PCB for ease of installation. Ensure that the incoming mains earth is connected directly to this connector block and NOT to the chassis earth point. (The PSU earth strap must be connected to the chassis earth point before operation). 24V 3A ANCILLARY POWER SUPPLY INSTALLATION INSTRUCTIONS APPROVED DOCUMENT No. DFU0706100 Rev 1 PAGE 6

PSU Location The PSU must be sited internally and must not be subject to conditions likely to affect its performance e.g. damp, saltair, water ingress, extremes of temperature, physical abuse etc. It is recommended that it is sited where it may be maintained easily and that the indicators may be clearly seen. Mounting the Enclosure The PSU is supplied with a hinged plastic lid, a metal back box and two separate PCBs. The relative location of these PCBs is indicated below: PL1 The PSU can be surface or semi-flush mounted (see FITTING THE ENCLOSURE section overleaf). To expose the base mounting holes, the base Power Supply PCB must first be removed. It is also recommended that the hinged lid is removed to prevent accidental damage during the fixing process. To remove the lid: - Take the unit out of its box and undo the two screws on the right hand side of the lid using the allen key provided. Hinge the lid 180 to the left (do not overbend the hinges). Disconnect the lid/base connecting cable (PL1) from the Indicator PCB. Care should be taken when detaching this connector to depress the telecoms-style locking tab to prevent damage (see diagram above). Carefully remove the four M4 retaining nuts which secure the hinges. To remove the base PCB: - Ensure power has been removed from the panel and that the PSU PCB is safe to handle (see IMPORTANT NOTES section on page two). Disconnect the connector cable from the cable clips on the base. Pull the PSU earth strap off the spade connector at the main chassis earth point. Carefully undo the PCB retaining screw located at the bottom left hand side of the PSU PCB using a crosshead screwdriver. Push the PCBs upwards and then pull forwards over the mounting pillars taking care not to damage any of the components. The panel lid and PSU PCB can now be removed from site to prevent accidental damage. Please note: The PSU PCB is static-sensitive and we strongly advise that the following anti-static handling precautions are observed when handling it. Operators should rid themselves of any personal electro-static charge by momentarily touching any of the earth studs on the unit s metal back box with all circuit boards and connections correctly in place. This should be done immediately prior to handling the sensitive components. If not in the vicinity of the back box, any other sound connection to safety earth may be touched. Static sensitive items may now be handled with care. Important: Always handle the PCB by it s sides and store it in a clean, dry place which is free from vibration, dust and excessive heat. Use a suitable antistatic enclosure to guard it against mechanical damage. Decide carefully how the wiring will be brought into the panel with reference to the diagram overleaf and remove the required knock-outs for cable entry. Always ensure if a knock-out is removed, the hole is filled with a good quality cable gland. Any unused knock-outs must be securely blanked off. 24V 3A ANCILLARY POWER SUPPLY INSTALLATION INSTRUCTIONS APPROVED DOCUMENT No. DFU0706100 Rev 1 PAGE 7

Notes on cable terminations and cable selection It is vitally important that the cables are terminated correctly according to the cable manufacturers instructions. Cable glands must be fitted where cables enter the panel. Any holes made but subsequently not used MUST be sealed with a flame retardant gland or other such barrier. Excessive tails should not be left, especially within the power supply. The earth screen of the incoming cables MUST be adequately insulated and connected to the chassis earth point. See MAINS CONNECTION section (page 7) and IMPORTANT NOTES section (page 2) for earthing information) It is essential that the 230Va.c. cable comes into the enclosure via one of the inlets at the top right hand corner of the enclosure. The size and type of cable should be selected to accommodate the current required and the permissible voltage drop in the system. If the unit is to be used in a fire alarm system the consideration should be given to the cable recommendations in BS 5839: Pt1: 1988 Fitting the enclosure Using the four mounting holes, fix the base securely onto/into the wall. The mounting holes are suitable for use with No.8 roundhead or countersunk woodscrews. Assess the condition and construction of the wall and use a suitable screw fixing. Any dust or swarf created during the fixing process must be kept out of the power supply and great care must be taken not to damage any wiring or components. DIAGRAM TO SHOW SEMI-FLUSH MOUNTING OF POWER SUPPLY 60mm includes 'dimples' INTERNAL VIEW OF PSU BACK BOX (WITH PCB REMOVED) SHOWING MOUNTING HOLES, KNOCK-OUTS, EARTHING POINTS AND PCB MOUNTING PILLARS KNOCK-OUTS FOR OTHER CABLES KNOCK-OUTS FOR MAINS SUPPLY IMPORTANT: Incoming mains cable must be segregated from all other cables and should only enter the PSU through either of these two right hand knock outs. Cable glands must be used. MOUNTING HOLE CHASSIS EARTH POINT IMPORTANT: The PSU safety earth strap MUST be connected to this point. MOUNTING HOLE WALL DO NOT drill any additional holes for cable entry in the shaded area highlighed above as this is where the PCBs and back up batteries will be located. Connecting the Unit Connecting the unit s internal connections and PCBs is best undertaken immediately prior to commissioning We strongly recommend that all aspects of the installation are verified and logged by the installer. Re-fit the panel lid and PCB which were previously removed. Re-connect the lid/base connecting cable and ensure that the PCB retaining screw is firmly fastened down. The PCB must be securely fastened before operation. 24V 3A ANCILLARY POWER SUPPLY INSTALLATION INSTRUCTIONS APPROVED DOCUMENT No. DFU0706100 Rev 1 PAGE 8

TECHNICAL SPECIFICATION POWER SUPPLY SPECIFICATION Mains Supply Voltage 230Va.c. ±10% 50/60Hz Maximum continuous mains supply Current 680mA Output Supply Voltage 22 to 30Vd.c. Nominally 27V with mains supply present Total Output Current 3A (reduce to 2.5A if batteries are fitted) Supply monitored for failure Yes Battery charger monitored for failure Yes if enabled Batteries monitored for disconnection and failure Yes if enabled Charging temperature compensation Yes Quiescent current mains fail and triggered <50mA Quiescent current mains fail and not triggered <25mA Batteries 2 x 12V or 4 x 2-10Ahr sealed lead acid (VRLA) connected in series FUSES Battery Fuse 3A F 20 x 5 mm to IEC 127 (EN60127 Part 2). Output Fuse 3A F 20 x 5 mm to IEC 127 (EN60127 Part 2). Mains Fuse 1A HRC 20 x 5mm Ceramic to IEC 127 (EN60127 Part 2) For safety reasons and to avoid nuisance tripping, it is important that this type of fuse is used INPUTS & OUTPUTS IMPORTANT: DO NOT connect any inputs or outputs to mains potentials Hold Off Input 5 to 30V with an input current of 3 to 6mA.The input is polarity sensitive and polarity protected. This input is isolated to ±100V from any other area of the circuit. Trig Input 5 to 30V with an input current of 3 to 6mA.The input is polarity sensitive and polarity protected. This input is isolated to ±100V from any other area of the circuit. Local Trig Input Intended to be controlled via a voltage free switch or contacts capable of switching 6mA and with a maximum resistance of 1K ohm Local trigger should not be connected directly to any other equipment. Fault Output Change over relay; Contact rating of 1A at 24Vd.c. Isolated to ±100V Switched Supply Outputs First pole of RLY2 Total unit output 3A Isolated Output Second Pole of RLY2; Contact Rating of 3A at 30Vd.c. Isolated to ±100V CONNECTION BLOCK Plug on type connector Largest acceptable conductor size = 1.5mm Mains Input connector Largest acceptable conductor size = 2.5mm Battery connector Largest acceptable conductor size = 2.5mm FRONT PANEL LED INDICATORS 1 x Normal Supply (green) 1 x Fault condition (amber) 1 x Control relay activated (amber) APPROXIMATE DIMENSIONS Back Box 410 x 250 x 80mm; Lid 439 x 274 x 7mm. Weight 2.95Kg without batteries 24V 3A ANCILLARY POWER SUPPLY INSTALLATION INSTRUCTIONS APPROVED DOCUMENT No. DFU0706100 Rev 1 PAGE 9