FAQ S. Main Switchboard Design Criteria. ENGINEERED SOLUTIONS FOR ALL YOUR SWITCHBOARD NEEDS

Similar documents
FAQ s. Are you AS/NZS Ready?

The University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 2

CPG.1 Gas insulated, single busbar cubicle range Up to 27 kv / 2000 A / 31.5 ka Up to 38 kv / 2000 A / 31.5 ka IEEE Standards

TECHNICAL SPECIFICATION OF 11KV SF6 / VCB METAL ENCLOSED, INDOOR (PANEL TYPE) / OUTDOOR RING MAIN UNIT (RMU). (IEC standard equipment)

SWITCHBOARDS (LV and MV)

Unified requirements for systems with voltages above 1 kv up to 15 kv

Step 1: Collection of required data

013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS

FAQ s. Designing metering switchboards as per Victorian service installation rules

Type SIMOPRIME A4, up to 24 kv, Air-Insulated Medium-Voltage Switchgear

NXPLUS C Single busbar. Maintenance-free for lifetime

33KV INDOOR SWITCHGEAR

NPS/003/010 - Technical Specification for 400V Assemblies (LVAC Boards) utilised in Major Substations

Switchgear Type 8BT1, up to 24 kv, air-insulated. Medium Voltage Switchgear Catalog HA 26.

Menu. Home About this portal Latest updates. Print Save Resource detail Citations. Table of Contents

Steve Summers Region Sales Manager

020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB)

MV Air Insulated Switchgear TAP17. Technical Data TGOOD

ype UP T Busplugs Low Voltage Switchboard Equipment

Benefits, typical uses

045 : 2000 CEB STANDARD

Circuit-Breaker Switchgear Type SIMOPRIME, up to 17.5 kv, Air-Insulated Medium-Voltage Switchgear.

8DJ. Maintenance-free for lifetime

5kV to 38kV, 630 Amp to 4000 Amp Indoor or Outdoor Application

AIR INSULATED EXTENDABLE SWITCHGEAR UP TO 12KV GUIDE

CGMCOSMOS Fully gas-insulated modular and compact (RMU) system Up to 24 kv

MEDIUM VOLTAGE CE-B METAL CLAD SWITCHBOARDS. CE-B-C-en-REV

ZX2.2 Gas-insulated medium voltage switchgear

Medium voltage products UniSec DY800 New 24 kv air-insulated medium voltage switchgear to e-distribuzione specifications

UniGear. Technical Guide

IT 28 ELECTRICAL INSPECTOR EXAMINATION ANSWER SCHEDULE. Question 1 Marks Reference Marking notes. (1 mark) ESR 57(3)(e)(ii)

GAMBICA INTERNAL ARC FAULT CAPABILITY OF ASSEMBLIES IN ACCORDANCE WITH IEC/TR A GAMBICA Technical Guide. * i. Edition 1 January 2017

Key elements of the AS3000 Wiring standards and some of the recent changes.

Investigation into UK socket-outlets incorporating USB charging points

MEDIUM VOLTAGE CE-B METAL CLAD SWITCHBOARDS. CE - B - C - en - REV

Gas Insulated Switchgear

MEDIUM VOLTAGE CE-B36 METAL CLAD SWITCHBOARDS. CE - B36 - C - en - REV

INTERNATIONAL STANDARD

023 : 2006 CEB STANDARD. 12kV & 36kV LOAD BREAK SWITCHES CEYLON ELECTRICITY BOARD SRI LANKA

SWITCHGEAR FOR SERVICE UP TO 36kV (CABLE AND OVERHEAD CONDUCTOR CONNECTED)

B kv T&D GAS INSULATED SWITCHGEAR

34-SDMS-01 SPECIFICATIONS FOR

Technical Specification of GECOL. Packaged Transformers

CPG.0 Single busbar gas-insulated cubicles

Electric Vehicle Charging Safety Guidelines Part 2: Selection and Installation Edition DRAFT

GE Consumer & Industrial Power Protection. New. SecoGear kV Metal-clad Switchgear. GE imagination at work

ES5 Security Theory/Regulations Answer Schedule

UniPack compact secondary substations (CSS) upto 36 kv For safe, reliable and space saving power distribution solutions

34-SDMS-02 SPECIFICATIONS FOR

Outdoor live tank vacuum circuit breaker Type OVB-VBF for 24/36/40.5 kv applications

SubDrive Inline Constant pressure controller Additional information for Australia, NZ TOLL FREE HELP 1300 FRANKLIN

vertical fuse switch disconnectors

Electric Vehicle Charging Safety Guidelines Part 2: Selection and Installation

Gas-insulated medium-voltage switchgear. For the mining industry. Answers for energy.

ELECTRICIANS REGULATIONS EXAMINATION 25 June 2011

STANDARD SPECIFICATION FOR. LIGHTING AND DC DISTRIBUTION PANELS WITH MCBs DOCUMENT NO: 44LK-5100/E.02/011

SWITCHCRAFT. Switchcraft Europe GmbH SWITCHCRAFT

Exceeding the standards with MNS

Page 2 of 39 Report No. CTI PA Testing location:

with Vacuum Circuit Breaker HAF

E-12 Low-voltage Switchboard

SYSclad switchboard equipped with draw out type vacuum circuit breaker closed dooroperationoperation. SYSclad 12 17,5kV A.

EMC 24 SERIES METAL CLAD SWITCHGEAR. We engineer, we assure. Up to 24 kv - 25 ka With Withdrawable, Air-Insulated, Medium Voltage Distribution Panel

Descriptive bulletin. Medium voltage load interrupter switchgear Reliable, low maintenance and economical for distribution applications

Metal Clad VCBs ~ Mk1

017: 1998 CEB STANDARD RING MAIN UNIT CEYLON ELECTRICITY BOARD SRI LANKA

Low Voltage Main Distribution Board

SF 6 Gas Insulated Switchgear Type SDH314 / SDHa314 for 72.5 to 145 kv

SOUTH AFRICAN NATIONAL STANDARD

MEDIUM VOLTAGE PRODUCTS. Powerbloc Pre-assembled modules for building medium voltage switchgear

MESG 12 / 17.5 / 24 / 36 KV

SF6 GAS INSULATED METAL ENCLOSED SWITCHGEAR (GIS)

INTERNATIONAL STANDARD

the safe, reliable, and efficient choice for MV switchgear

Medium Voltage Distribution PIX. Air Insulated Switchgear up to 24 kv PARS TABLEAU

SF 6 Gas Insulated Switchgear Type SDH714 for 72.5 to 145 kv

Medium Voltage Metal-Enclosed Switches

General. Main electric circuits Fuses compartment Operating mechanisms Cables connection compartment

MEDIUM VOLTAGE AIR INSULATED ARC-RESISTANT LOAD BREAK AND DISCONNECT SWITCHES

UniSafe 36. Medium voltage, arc-proof, air-insulated, metal-clad switchboard

Our brand POWER DYNAMIC PASSION COMMITMENT CREATIVITY. A strong brand for strong products: 8PU Premium. MV Energy

0.5 s to 30 h (30 s, 3 min, 30 min, 3 h, 30 h)

Power/Vac Vacuum Replacement Breakers for GE Magne-Blast Type AM & AMH Breakers

INTER PLANT STANDARD STEEL INDUSTRY SPECIFICATION FOR STATIC EXCITATION CONVERTORS FOR SYNCHRONOUS MOTORS (FIRST REVISION)

B kv Gas-insulated Substations

MCset kv Medium voltage equipment

FUSES. Safety through quality

A. Three-phase, oil filled self-cooled, padmounted transformers are installed outdoors on pads in the EWEB distribution system.

e 2 ALPHA Medium Voltage Switchgear K Catalogue EN

This small footprint makes a BIG impact

abb SafeLink SF 6 Insulated Ring Main Unit Installation and Operating Instructions Switchgear Division Auckland, New Zealand SLMIO ver 2.

Chapter 6 Generator-Voltage System

DISTRIBUTION SOLUTIONS. GSec Gas-insulated switching and isolating apparatus

4 Technical Application Papers

Medium Voltage Metal-Enclosed Switches

Vacuum Generator Circuit Breaker - A trend-setting power plant technology

E-15 Uninterruptible Power Systems (UPS)

All rights reserved. Neither this catalogue nor any part of it may be copied using any method or for any purposes. Most studies are legally protected.

AIR INSULATED METAL ENCLOSED SWITCHGEAR AND CONTROLGEAR

OTEC Transfer switch open transition

Transcription:

FAQ S Main Switchboard Design Criteria h ENGINEERED SOLUTIONS FOR ALL YOUR SWITCHBOARD NEEDS www.electricalswitchboards.com.au

Main switchboard Design criteria Q: What is the Australian standard for main switchboards? Current Australian standard is AS/NZS 3439.1: 2002, originating from IEC 60439. The new series of standard AS/NZS 61439 will supersede the current standard in 2021 as it was published in the second half of 2016. Q: What is meant by TTA? Type tested assembly (TTA) is a low voltage switchgear and controlgear assembly that is verified for its performance as per AS/NZS 3439.1. Q: What are the type tests that need to be carried out to verify compliance? Verification of temperature rise limits. Verification of the dielectric properties. Verification of the short-circuit withstand strength. Verification of the effectiveness of the protective circuit. Verification of clearances and creepage distances. Verification of mechanical operation. Verification of the degree of protection and internal separation. Q: Can you claim type tested assembly if the switchboard construction is different to the tested arrangement or have made modifications to suit different applications? No. If modifications are made to the components of the switchboard, new type tests have to be carried out, but only in so far as such modifications are likely to adversely affect the results of the 7 type tests listed above. FAQ S - Main Switchboard Design Criteria 3

Q: What is meant by PTTA? Partially type tested assembly (PTTA) is a low voltage switchgear and controlgear assembly, containing both type tested and non-type tested arrangements. In this construction non-type tested arrangements need to be derived (e.g., by calculation, etc.) from type tested arrangements. This switchboard construction is commonly used as it is not possible to cover all the possible configurations in your type tested arrangements and therefore customised switchboard arrangements derived from type tested arrangements are more practical in real world applications. Q: Do you need to perform any other tests even if you have type test certificates? Yes. Every switchboard must be routinely tested (4 tests) by the manufacturer (e.g., Dara Switchboards). Routine tests are intended to detect faults in materials and workmanship as follows: Inspection of the switchboard including inspection of wiring and, if necessary, electrical operation test The effectiveness of mechanical actuating elements, interlocks, locks, etc., shall be checked. The conductors and cables shall be checked for proper laying and the devices for proper mounting. A visual inspection is also necessary to ensure that the prescribed degree of protection, creepage distances and clearances are maintained. The connections, especially screwed and bolted connections, shall be checked for adequate contact, possibly by random tests. The conformity of the switchboard to the circuit and wiring diagrams, technical data,etc. Depending on the complexity of the switchboard, it may be necessary to inspect the wiring and to carry out an electrical functioning test. Dielectric test All electrical equipment on the switchboard shall be connected for the test, except currentconsuming apparatus like windings, measuring instruments, etc., that will be disconnected during the test. Test voltage is selected as per table 10 of AS/NZS 3439.1:2002. (e.g., for 690V applications the test voltage will be 2.5kV.) 4 Dara Switchboards

Dielectric test All electrical equipment on the switchboard shall be connected for the test, except currentconsuming apparatus like windings, measuring instruments, etc., that will be disconnected during the test. Test voltage is selected as per table 10 of AS/NZS 3439.1:2002. (e.g., for 690V applications the test voltage will be 2.5kV.) For the test either all circuits should be closed or the test voltage shall be applied for all parts successively. The test voltage shall be applied between the live parts and the conductive structural parts of the assembly. The test is considered to have been passed if there is no puncture or flashover. Checking of protective measures and of the electrical continuity of the protective circuits The protective measures with regard to protection against direct and indirect contact shall be checked. Screwed and bolted connections shall be checked for adequate contact, possibly by random tests. Verification of insulation resistance Insulation measurement using an insulation measuring device at a voltage of at least 500V must be carried out. In this case, the test is deemed satisfactory if the insulation resistance between circuits and exposed conductive parts is at least 1000 Ω/V for every circuit referred to the nominal voltage to earth of these circuits. By exception, items which, according to their specific requirements, are currentconsuming apparatus (e.g., windings, measuring instruments) at the application of the test voltage or are not designed for the full test voltage should be disconnected as appropriate. FAQ S - Main Switchboard Design Criteria 5

Q: How do you calculate the distribution busbar size of 10 circuits in the absence of actual currents of those circuits? In the absence of actual currents, the rated diversity factory is used to calculate the minimum busbar sizing. Below conventional values are used, as per table 1 of AS/NZS 3439.1:2002 Number of main circuits Rated diversity factor (RDF) 2 and 3 0.9 4 and 5 0.8 6 and 9 inclusive 0.7 10 ( and above ) 0.6 (e.g., if 10 x 100A MCCB s are fitted in a distribution chassis the diversity factor is 0.6,allowing a minimum busbar size of 600A.) Q: Is it mandatory to have a name plate on main switchboards? Yes. Each assembly should have one or more name plates with the below information: Manufacturer s name or trade mark. Serial number/drawing number. Relevant standard (e.g., AS/NZS 3439.1:2002). Type of current (and frequency, in the case ofa.c.) Rated operational voltages. Rated insulation voltages. Short-circuit withstand strength. Degree of protection. Type of system earthing. Weight. Form of internal separation. Date of manufacture. Rating Plate 6 Dara Switchboards

Q: What is the minimum clearance distance in a low voltage installation? Table 14 of AS/NZS 3439.1:2002 is referred to in obtaining this information. If you consider a maximum of 12kV rated impulse withstand voltage with a pollution degree of 4 (worst case) the clearance distance should be more than 14mm between phases, and between phases and neutral/earth. Q: What is the creepage distance in a low voltage installation? If the pollution degree is 1 or 2 (normally non-conductive pollution occurs, occasionally however, a temporary conductivity based on condensation may occur) the creepage distance should not be less than the associated clearance distance. This leaves the creepage distance also at 14mm. Q: What is the minimum IP rating allowed for indoor switchboards? IP2X. This is considering there is no need for protection against ingress of water. Q: Is a higher IP rating (eg. IP66) enclosure better for switchboards? This is not necessarily true unless the switchboard is installed in a location where there could be more damage to it by constant spray of water, presence of dust and gases that could increase the pollution degree inside a switchboard. Switchboards need to be properly ventilated to enable the switchgear to operate within its tested conditions (normally a 35-40 deg C maximum temperature) and the heat generated during the operation (through watt loss of conductors and switchgear) should have passage to escape. If the switchboards are constructed with a higher IP rating, the switchgear will need to be de-rated and the conductors up-sized to make the switchboard run cooler. You also need to consider using pressure release valves to enable the release of pressure build up during an arc. Due to these reasons switchboards are best performed when enclosed in properly ventilated enclosures, therefore dropping the IP rating to the minimum suitable level depending on the location and application. Q: Apart from a properly enclosed switchboard what is another important environment factor to consider for outdoor switchboards? When the switchboards are intended to be installed in a location with high humidity and temperature varying within wider limits, suitable arrangements (ventilation and/or internal heating, drain holes, etc.) must be made to prevent harmful condensation within the switchboards. FAQ S - Main Switchboard Design Criteria 7

Q: What are the temperature rise limits for components inside a switchboard? Temperature rise limits given in this standard are calculated for a mean ambient air temperature less than or equal to 35deg C, Therefore, this does not apply for outdoor switchboards where the ambient temperature reaches above 35deg C and the effect of solar irradiation on the switchboard operating temperature is unknown. Switchgear and controlgear: Temperature rise should be as per the manufacturer recommendations. Normally, switchgear is calibrated at 35-40 deg C operating temperature, a higher operating temperature would mean de-rating the circuit breakers as per the manufacturer data. You may also need to consider the maximum operating conditions in order to limit the temperature rise within the assembly. Terminals for external conductors A 70k rise is based on conventional tests Busbars and conductors Generally to be considered as complied with if the temperature rises do not exceed 70k for H.C copper busbars and 55k for H.C aluminium busbars. This is based on 105deg C and a 90deg C maximum temperature within an assembly. Q: What are the methods used in switchboards to protect the operator against electric shock? Protection by safety extra low voltage (SELV). Protection against direct contact. One or more protective measures may be selected to satisfy this requirement: Protection by insulation of live parts (e.g., PVC cable, Polythene pinhole free coating with a minimum thickness of 0.8mm, solid extruded PVD tubing of 1mm thickness, heat shrink sleeve with wall thickness of 0.45mm after shrinking, polycarbonate sheet of minimum 1.6mm thickness and non conductive powder coating of minimum 0.3mm thickness) Protection by barriers or enclosures All external surfaces of a switchboard must be minimum IP2X rated. All barriers firmly fitted. Barriers to be fitted with means that require a key or tool for removal. 8 Dara Switchboards

Protection against indirect contact All external surfaces of a switchboard must be minimum IP2X rated. All barriers firmly fitted. Barriers to be fitted with means that require a key or tool for removal. Q: What is the maximum length of unprotected cable that can be installed in a switchboard where a circuit breaker is fitted at the end of it? 3 metres. There are conditions that need to be met and are available in table 5 of AS/ NZS 3439.1:2002 (e.g., single insulated cables with an operating temperature above 90 deg C where there is no applied external pressure on them or sheathed, double insulation cable.) Q: What is the recommended minimum height from ground/platform for the terminals of a circuit breaker? 200mm as per section 7.6 of AS/NZS 3439.1. Q: What is the maximum height for the operating devices such as handles, push buttons etc., from the ground/floor? For floor-mounted switchboards, indicating instruments which need to be read by the operator should not be located higher than 2 m above the base of the switchboards. Applicable for operating devices, such as handles, push buttons, etc. Q: Is there a recommended distance from the ground to actuators of an emergency stop? Yes. The emergency stop buttons must be located between 0.8m to 1.6m. Q: Why are internal separation of assemblies used? Forms of internal separation are aimed at providing a base to: Protect the operator against contact with live parts belonging to adjacent functional units, busbars and terminals. Limit the probability of initiating an arc fault. Protect passage of solid foreign objects from one unit of assembly to another (achieved by using IP2X separation between each unit.) FAQ S - Main Switchboard Design Criteria 9

Q: Will internal separation guarantee the integrity of the assembly (switchboard) in the event of an arcing fault? No. this will only limit the probability of an arcing fault, there are extra measures to be taken as per section 2.5.5 of AS/NZS 3000:2007 and annex ZC of AS/NZS 3439.1. Q: Why are there different methods of internal separation of switchboards, who decides which one to use? Internal separation is agreed upon by the manufacturer (e.g., Dara Switchboards) and user (e.g., BHP Billiton) as per section 7.7 of AS/NZS 3439.1. The following points are considered in deciding on the appropriate internal separation by the user, or in absence of specification by the switchboard manufacturer? Is the rated current of the switchboard less than 800A? If YES, you are free to select any form of separation (e.g., forms 1, 2a, 2b, 3a, 3b, 4a, 4b etc.) Is the rated current of the switchboard more than 800A? If YES, you are restricted to use one of the prescribed forms of separation as per section 2.5.5.2 of AS3000:2007 to reduce the probability of initiating an arcing fault (e.g., forms 3b, 3bi, 3bih, 4a, 4ah, 4aih, 4b, 4bi, 4bh and 4bih.) Can the assembly be isolated elsewhere before removing covers etc.? If the answer is YES, you may decide to use the lowest form of separation [form 1] without adding pressure to the switchboard price. Do you require additional integrity by having separation between functional units and busbars where the access of busbars in live conditions will result in the risk of contact with live busbars? If the answer is YES you will need to use, as a minimum, form 2 construction. Do you require access to functional units (e.g., circuit breakers) for limited maintenance (e.g., changing the settings) with adjacent circuits live? If the answer is YES you will need to use, as a minimum, form 3 construction and also provide separation between functional units. Do you require access to cable terminals (e.g., connecting cables to a spare circuit breaker in future while the switchboard is live) of a functional unit with adjacent live functional units? If the answer is YES you will need to use the maximum form of separation-form 4. 10 Dara Switchboards

Q: What are the measures to be taken in increasing security against the occurrence or the effect of internal arcing faults? By insulation of all live conductors. By the arrangement of busbars and functional units in a switchboard where there are vented compartments designed to promote rapid extinction of the arc and to prevent the arc or arc products affecting other parts of the switchboard. By the use of devices (e.g., fuses or circuit-breakers), designed to limit the magnitude and duration of the arcing current by interruption of the fault. Combinations of the above items, or other methods designed to either prevent the initiation of an arc, or to reduce the damage or risk of injury resulting from an arc, by sensing of the fault followed by interruption. Q: Can a successful internal arcing fault test guarantee to withstand all arcing faults that may occur in service? No. It is not possible to simulate all the conditions that can produce arcing faults in service and the arc does not always behave in a repeatable manner. Annex ZD of AS/NZS 3439.1:2002 covers the special tests to verify the increased security against the effects of internal arcing which may occur in service with all doors closed and all covers and internal barriers in place. DISCLAIMER: The information in this document is for general reference only. The contents of this document is provided without any express or implied warranty as to its completeness or accuracy. Dara Switchboards cannot accept liability for the content provided or included by reference. Dara Switchboards does not accept any liability for loss or damages incurred by any person or organisation as a result of dependence placed upon the content of this document or any other information/links included by reference. All contents provided herewith is on the basis that you or your organisation would make your own decision as to the accuracy of its content and would obtain proper professional advice on this subject before making any business decision or carrying out any electrical work. FAQ S - Main Switchboard Design Criteria 11

One Stop Shop For All Your Switchboard Requirements DARA SWITCHBOARDS (HEAD OFFICE) 5 faighstreet Mulgrave,VIC 3131 Australia info@dara-switchboards.com.au 1300 DARA SW (1300 327 279) DARA EXPRESS PRODUCTION PLANT (DEPP) 28 Remount Way Cranbourne West, VIC 3977 DARA MODULAR SWITCHBOARDS PRODUCTION PLANT (DMPP) 26 Remount Way Cranbourne West, VIC 3977 Member of ABOUT US At DaRa Switchboards, we recognize the importance of tight deadlines and quality electrical products. This is why we work to deliver our design services and manufactured electrical products in real time. DaRa Switchboards 3,000m 2 manufacturing facility contains everything we need to design and build you the perfect switchboard. The company provides more than 50 opportunities per year for young engineering and IT graduates to carry out their internship. The company s transformation is in using the latest technology in design and engineering switchboards to our clients special needs in mining, industrial, petrochemical, utility, solar and commercial sectors.