SPECIFICATIONS OF Ni-Cd BATTERY BANK

Similar documents
ANNEXURE XI. (Ni Cd Battery Bank) TECHNICAL SPECIFICATIONS OF 125V STATION BATTERY BANK OF GTG I.

SPECIFICATIONS FOR 50 V, 600 AH LEAD ACID BATTERY

GUJARAT ENERGY TRANSMISSION CORPORATION LTD. TECHNICAL SPECIFICATIONS. 110 V, 100 Ah / 250 Ah & 220 V, 250 Ah / 350Ah TUBULAR LEAD ACID BATTERY SETS

Section V DC Nickel Cadmium Alkaline BATTERY

TECHNICAL SPECIFICATION FOR 30 V, 100 AH STATIONARY BATTERIES AND BATTERY CHARGING EQUIPMENT. (SPECIFICATION NO. MSEB/Dist/IV/2004.

SECTION 1 SCOPE, SPECIFIC TECHNICAL REQUIREMENT AND QUANTITIES

020: 2013 CEB SPECIFICATION MINIATURE CIRCUIT BREAKER (MCB)

CAMTECH/S/2005/LAC/2.0 1 LEAD ACID CELL

TECHNICAL SPECIFICATION FOR 11 KV CAPACITOR BANK

SPECIFICATION FOR REWIRABLE FUSES (KITKAT FUSES) 100A & 200A SPECIFICATION NO.: DIST/ A- KIT /

NCPP. Nickel Cadmium Pocket Plate Batteries. Single Cell Catalogue

CITY OF CHARLEVOIX REQUEST FOR BIDS WESTENBROEK SUBSTATION 48VDC BATTERY BANK

017: 1998 CEB STANDARD RING MAIN UNIT CEYLON ELECTRICITY BOARD SRI LANKA

SPECIFICATION FOR POWER BATTERIES

Material Description Quantity UOM

026-2 : 1996 CEB STANDARD

013 : 2009 CEB SPECIFICATION MOULDED CASE CIRCUIT BREAKERS

PURE LEAD PLUS UPS APPLICATIONS. Valve Regulated Lead Acid Battery Designed for UPS Standby Power Applications Watts per Cell

Switchgear Utility specific gravity nominal sulfuric acid. 10 years, full float service at 77 F (25 C)

KPM type Intended for medium discharge currents from 0.5 to 2 C

VentPro Reduced Maintenance Nickel Cadmium Batteries for Stationary Applications

NPS/003/002 Technical Specification for 30V Distribution Tripping Battery and Charger Systems

Standards are finally approved by the Standards High Council of Iranian Ministry of Petroleum.

Supply of 63 kva DIESEL GENERATOR SET WITH AMF

NCPP. Nickel Cadmium Pocket Plate Batteries. Single Cell Dimensional and Electrical Data

Technical Specification for 33 KV 200 AMPs,H.G,Fuse set.

Ni-Cd Batteries. Solutions for the toughest requirements

TECHNICAL SPECIFICATION FOR 11 KV AUTOMATIC CAPACITOR SWITCH

SUBSTATION EQUIPMENT - Page 1 of 8

Features and Benefits

LIBERTY SERIES 1000 VALVE REGULATED LEAD-CALCIUM BATTERY For standby applications Capacities from 25 to 600 Ampere-hours

Tender documents for supply, erection & commissioning of Plante Type Battery to 2x210 MW IB Thermal Power Station.

023 : 2006 CEB STANDARD. 12kV & 36kV LOAD BREAK SWITCHES CEYLON ELECTRICITY BOARD SRI LANKA

NCPP. Nickel Cadmium Pocket Plate Batteries. Block Cell Dimensional and Electrical Data

شركة كهرباء محافظة القدس المساهمة المحدودة

Technical Specifications

STANDARDIZATION ORGANIZATION FOR G.C.C (GSO) GSO 34/2007

INVITATION TO TENDER MR 84/2016. SUPPLY and Install 110V DC BATTERY BANKS and CHARGERS for Rarawai, Sabeto and Lautoka Switching Station

FLOAT CHARGER (40A) & BOOST CHARGER (35A) FOR NO BREAK POWER SUPPLY SYSTEM WITH REQUIREMENT FOR SCADA

GASTON GTF range battery manual

Valve Regulated Lead Acid (VRLA) Battery Series Designed for UPS Standby Power Applications FEATURES & BENEFITS

VRLA Batteries. Battery Installation And Start up Guide

045 : 2000 CEB STANDARD

PURE LEAD PLUS UPS APPLICATIONS Valve Regulated Lead Acid Battery Designed for UPS Standby Power Applications Watts per Cell

(High Pressure Boiler Plant) Tiruchirappalli , TAMIL NADU, INDIA MATERIALS MANAGEMENT / CAPITAL EQUIPMENT. Enquiry Date:

POWER-plus. Ni-Cd XHP. Capacity: 10 Ah to 250 Ah

34-SDMS-01 SPECIFICATIONS FOR

STR-1415 SPECIFICATION FOR BATTERY CHARGERS 220V, 30A FOR SUBSTATIONS ANNEXURES B

TECHNICAL SPECIFICATION

SPECIFICATION FOR VT D 70 CONTENTS

TECHNICAL SPECIFICATION FOR SHACKLE HARDWARE FITTINGS SUITABLE FOR TENSION STRING TO BE USED FOR 11KV LINE

FLOAT CHARGER & BOOST CHARGER F O R NO BREAK POWER SUPPLY SYSTEM (Float 100A & Boost 60 A with SCADA application)

Standby Products SD-SDH. series. Technical Features. Applications. Product Features

Tubular Flooded (OPzS) Batteries

SD / SDH. Applicable Standards. Applications and Key Benefits. FIAMM Manufacturing. - Technical Features

Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli , TAMIL NADU, INDIA CAPITAL EQUIPMENT / MATERIALS MANAGEMENT

SPECIFICATION FOR AUTOMATIC PRIMING AND OPERATING SYSTEM FOR CENTRIFUGAL PUMPS.

D.C. DISTRIBUTION BOARD

66 kv SF6 CIRCUIT BREAKER (SPRING OPERATED)

34-SDMS-02 SPECIFICATIONS FOR

POWER FOR TOMORROW. Motive Power. Network Power. Chargers. Bloc Batteries. Accessories. Service

33 KV STATIC SHUNT CAPACITOR WITH ALLIED EQUIPMENT

BHARAT HEAVY ELECTRICALS LIMITED Industrial Valves Plant Goindwal (AMRITSAR) Enquiry Date:

Vented fibre structure Nickel Cadmium batteries for stationary systems

TECHNICAL SPECIFICATIONS FOR 11KV AIR BREAK (A.B.) SWITCHES :

Ni-Cd Battery Product Specification

Supply, Installation and Commissioning of 1 No 50 Watt LED. based SPV SLS at Nadia District Library, Krishna Nagar, Nadia.

Technical Specification of 11KV 200Amp. (3-Pole/2-Pole) Air Break Switch Scope Description of the materials Standards Insulator make

FEATURES & benefits. Constant Power Discharge Ratings - Watts per 77 F (25 F) Operating Time (in minutes) to 1.

SPECIFICATIONS OF SINGLE GIRDER UNDER SLUNG E.O.T. CRANE CAPACITY: 5 MT

Bharat Heavy Electricals Limited (High Pressure Boiler Plant) Tiruchirappalli , TAMIL NADU. INDIA CAPITAL EQUIPMENT/ MATERIALS MANAGEMENT

TECHNICAL SPECIFICATIONS

PIBAS Ni-Cd cells can be assembled into many different configuration forms, for example:

SOMALI ENERGY TRANSFORMATION (SET) PROJECT

SPA AGM VRLA batteries

TECHNICAL SPECIFICATION FOR 11 KV AIR BREAK (A.B.) SWITCHES:

Scope of Supply of 11Kv Induction motor. The motor is being procured for cooling water pump. The scope of supply of motor is as given below:

NLC INDIA LIMITED (formerly Neyveli Lignite Corporation Limited) ('NAVARATNA'-Government of India Enterprise) MATERIALS MANAGEMENT COMPLEX

4.1 Type of the valve and materials of construction of body and trim shall be as specified in valve Data sheet.

ZAVOD AIT Nickel-Cadmium Cells and Batteries

Range. Alcad Single Cell Range. Powerful assurance for maximum operating reliability

AINO MICRO RANGE VRLA. Compact energy for increased security BATTERY SOLUTIONS. EverExceed power your applications

TECHNICAL SPECIFICATION FOR 11 KV DROP OUT (D.O.) FUSE with Polymeric Insulators:

UPS FEATURES & BENEFITS TECHNICAL DATA Valve Regulated Lead Acid Battery Designed for UPS Standby Power Applications.

2 Volt AGM Range. Haze Battery Company Ltd

MANUAL 4. The Norms set for discharge of its Function

Reference Number PDS 18 - (RIC Standard: EP SP)

33KV INDOOR SWITCHGEAR

SPECIAL SPECIFICATION 6576 Solar Panel Power Supply System

Tubular Flooded (OPzS) Batteries

VRPP. Nickel Cadmium Valve regulated Pocket Plate Batteries. Dimensional and Electrical Data

SPECIFICATION FOR HARDWARE FITTINGS SUITABLE FOR TENSION STRING TO BE USED FOR 11KV/22KV LINE

SPECIFICATION FOR BATTERY & BATTERY CHARGER (D.C. SYSTEM)

LDP MP. Ni-Cd single cells. LD P - M P ranges Capacity: 10 Ah to 70 Ah L2.4. Benefits

NICKEL-CADMIUM POCKET TYPE ALKALINE STORAGE BATTERY

HARYANA VIDYUT PRASARAN NIGAM LTD.

Technical Specification

XHP. Low maintenance high performance batteries

31-SDMS-01 REV. 03 SPECIFICATIONS FOR

Dakshin Gujarat Vij Company Limited

Transcription:

SPECIFICATIONS OF Ni-Cd BATTERY BANK ANNEXURE-Z Supply, Installation and commissioning of Ni-cd battery bank for high rate of discharge type KPH 125V 210 AH consisting of 103 number of cells. Detail technical specification is given below 1. IS/IEC CONFORMITY: Bank shall be supplied as per IS 10918 & IEC 623 with latest amendments. 2. SITE CONDITIONS: (a) Climate: Wet & Tropical (b) Temperature Range: 1.1 to +55 degree Celsius. (c) Electrical Ground Resistivity: 30-40 Ohm Meter. (d) Relative Air Humidity: 100% Max (e) Site above MSL: Less than 1000 meters. (f) The atmosphere in the factory shall be laden with Urea dust. The air may contain Ammonia Vapors. 3. FEATURES: (a) The cells shall be vented type, assembled and end plastic container with covers. Covers shall be fitted with spray proof vent plugs. (b) All cell terminals shall be of adequate current carrying capacity. Cell terminal post shall be equipped with connector bolts. Cell terminal posts, Bolts and associated hardwares shall be electrolyte resisting material. (c) Electrolyte level indication lines for minimum and maximum levels shall be marked on maintenance access side of each jar or container. (d) Each battery shall be rated for specified ampere hours at five hours rate of discharge to end voltage of 1.00 volts per cell. (e) Nickel plated copper intercell connectors shall be used for connecting up adjacent cells and rows. Bolts, nuts and washers shall be nickel-plated steel/stainless steel. All terminals and cell inter-connectors shall be fully insulated or have insulation shrouds (f) Each cell shall be contained in close top container preferably transparent and unbreakable and shall incorporate positive and negative

plates and separators in position. Wooden separators shall not be acceptable. The cells shall be provided with inter cell connectors, Nut bolts along with two flat and one spring washer. Connector must be suitable to take full current and should be designed to withstand short circuit current also. Inter row, Inter Tier Connector and take off terminals shall be designed for rated current and shall also be able to withstand Short circuit current.. (g) The battery units shall be complete with all necessary components such as lids, plugs, separators and and buffers, inter cell connectors, cell insulators. (g) The required quantity of electrolyte plus 10% extra quantity complying relevant standards IS 10918 shall be supplied in suitable non returnable containers along with battery. 4. ACCESSORIES FOR MAINTENANCE You will supply the following accessories for maintenance along with main battery bank: (a) Syringe type hydrometer suitable for specific gravity readings 04 No s (b) Thermometer with specific gravity correction scale 02 No s (c) Cell Testing Voltmeter (3-0-3) complete with leads 02 No s (d) Insulated Spanners (For each type of battery) 02 sets (e) Rubber Syringe 02 No s (f) Funnel 02 No s (g) Jug 02 No s (h) Apron 02Nos (i) Rubber Gloves 02 sets (j) Teak Wood Stand For Hydrometers 02 Nos. 5. SPARES You will supply the following spares along with main battery bank: (a) Inter cell connectors- 10 No s (b) Vent plugs- 10 No s (c) Nuts & Bolts& Washers (2 flat and 1 Spring washer)- 10 Nos. 6. SPACE AVAILABLE FOR BATTERY STAND:

The battery bank being supplied by you has to be arranged in step type, three row stand with following limiting dimensions: Length: 2860mm, Width: 650mm, Height: 350mm approx.supply of battery stand shall be in party scope. 8. TEST 1.The Bidder shall have to submit along with offer, as pre-requisites, the complete Type test Reports of similar or higher rating battery bank, carried out within 5 years from the due date of Tender, from CPRI/NABL accredited/govt. recognized Test House failing which their offer may not be technically acceptable. 2. Guaranteed Test Particulars annexure 2 shall be duly filled and submitted along with offer. 2. Routine Test & Acceptance test certificates as per IS 10918 shall be furnished by the party along with the supply of material 3. Capacity test of the supplied battery bank shall be carried out by the party as per IS 10918.. 9. BUYBACK OF USED/UNSERVICEABLE BATTERIES Manufacturer shall buyback used/unserviceable batteries of similar rating from the substations where batteries are replaced. The bidder should quote their rates for buyback of old battery bank. 10. DOCUMENTS Documents, Test Certificates, Drawing etc. along with operational and maintenance Manuals, complete charging, initial charging, discharging procedure shall be supplied along with battery banks/ dispatch documents as per Annexure III.

TECHNICAL PARTICULARS TO BE FILLED BY PARTY Sr. No. 125 Volts, 210AH, 103 Cells Ni-Cd Battery Bank To be filled by party 1. Manufacturer Name 2. Country Of Manufacturer 3. Type Of Battery 4. Reference Standards For Construction and performance 5. No. of cells 6. Nominal Voltage Of Battery 7. Finishing rate of Charge (A) 8. Voltage per cell at the end of charge at the finishing rate 9. Voltage of each cell on complete discharge at 10 hour rate 10. Open circuit voltage of each cell on full charge (volts) 11. Internal Resistance Per cell (milli ohm per cell) 12. Minimum voltage per cell at which it can be operated at 20hour rate of discharge 13. Requirement of First Charge (Ampere Hour) 14. Discharge Capacity in Ampere Hour a) 5 Hour rate to 1.14 volts per cell b) 3 Hour rate to 1.10 volt per cell c) 1 Hour rate to 1.06 volt per cell d) 30 minutes discharge rate to 1 volt per cell e) 15 minutes discharge rate to 0.85 volt per cell f) 5 minutes discharge rate to 0.65 volt per cell

g) 1 minute discharge rate to 0.65 volt per cell 15. Guarantee efficiency on 10 hour rate in terms of watt hour 16. Type of positive plate per cell 17. No. of positive plates per cell 18. Type of negative plate per cell 19. No. of negative plates per cell 20. Size of positive plates (mm) 21. Size of negative plates (mm) 22. Fully charge specific gravity of electrolyte 23. Slow Charging Rate (A) 24. Quick Charging Rate (A) 25. Float Charging Voltage per cell (V/cell) 26. Size and material of connectors and method of connection between cells a) Inter cell (mm) b) Inter row c) Inter stand d) Take off e) Stud/Bolts, Nut and Washer 27. Type of Separators 28. Thickness of Separator (mm) 29. Material and Size of Container (mm) 30. Clearance between the bottom of plates and containers (mm) 31. Battery mild steel supporting rack dimensions(mm) 32. Amount and specific gravity of Electrolyte per cell required for first filling (litres/cell)

33. Weight of complete cell with Electrolyte(KG) 34. Type of Venting 35. Self Life 36. Expected Life a) For cyclic use(in terms of no. of charge/discharge) b) For use under float (trickle charge) 37. Operating Temperature Range 38. Type of cell arrangement

Documents to be submitted in different stage of Tender Sr No. DOCUMENTATION With the Quotation for approval After Order No. of Copies Final No. of Copies 1. General arrangement drawing showing the arrangement of the battery 2. Illustrative and descriptive technical literature 3. Installation, operation and Maintenance Manual 1 3 1 3 1 3 4. Type Test Certificate 1 3 5. Routine Test & Acceptance Test Certificates --- 3 6. Guarantee Certificate --- 2 8. Technical Particulars 1 3 NOTE: All final documents shall be furnished in superior quality files.