CombiTemp Temperature Measuring System Housing DIN-B Standard or Ex ia safety DIN-B Ex n safety Ø80 mm stainless steel Transmitters FlexTop 2201 FlexTop 2211 FlexTop 2221 FlexTop 2231 Displays The process connections shown are examples. FlexView BattTemp Description CombiTemp comprises a series of basic elements which can be combined to various temperature sensors and transmitters. Being a building block system CombiTemp offers a great fl exibility in respect to modifi cation, service and maintenance. The basic components in the system are: Housing: DIN-formB or Ø80mm stainless steel Process connection: Refer to the data sheet FlexTop transmitters: 2201, 2211, 2221, 2231 FlexView 4...20 ma LC-display BattTemp, Battery operated Pt100 LC-display The parts can be assembled by the user or delivered assembled and calibrated, if relevant. However, an Ex ia or Ex n approved product will always be assembled at the factory. Please refer to the relevant data sheets and installation manuals for each product: Product Data Sheet Manual CombiTemp 2000-1 This manual FlexTop2201 2201-1 2201-8906 FlexTop2211 2211-1 2211-8900 FlexTop2221 2221-1 2221-8900 FlexTop2231 2231-1 2231-8900 FlexView 9401-1 9401-8904 BattTemp 2400-1 2400-8900 All documentation can be found at This Ex-approved product is manufactured by: Baumer A/S Jacob Knudsens Vej 14 DK-8230 Aabyhoej Denmark Page 1
Technical Data, General Environmental conditions Media temperature, std. -50...400 C Surface sensor -40...150 C Ambient temperature -40...160 C (or max. temperature range for display/transmitter) Humidity < 100% RH, condensing (or max. humidity for display/transmitter) Protection class DIN housing IP 65 ø80 mm housing IP 65 + IP 66 Vibrations GL, test 2 (sensor tubes < 200 mm only) Disposal of product and packing According to national laws or by returning to Baumer Safety Instructions This instrument is built and tested ac cord ing to the current EU-directives and packed in technically safe con di tion. In order to main tain this condition and to ensure safe op er a tion, the user must follow the hints and warnings given in this instruction. During the installation the valid national rules have to be observed. Ignoring the warnings may lead to severe per son al injury or substantial damage to property. The product must be op er at ed by trained staff. Correct and safe operation of this equipment is de pend ent on proper transport, storage, installation and op er a tion. All electrical wiring must conform to local stand ards. In order to prevent stray elec tri cal radiation, we rec om mend twisted and shielded input cables, as also to keep power sup ply cables separated from the input cables. The con nec tion must be made ac cord ing to the connecting di a grams. Before switching on the power supply take care that other equip ment is not af fect ed. Ensure that the supply voltage and the conditions in the environment comply with the spec i fi ca tion of the de vice. Before switching off the supply voltage check the possible effects on other equipment and the processing system. WARNING For electrical installation and com mis sion ing of explosion protected devices, the data given in the con form i ty cer tifi cate as also the local reg u la tions for installation of elec tri cal apparatus within explosion protect ed areas must be considered. The intrinsically safe versions can be mounted in the explosion hazarded area according to its spec i fi ca tion only con nect ed to a certifi ed intrinsically safe supply loop with the corre spond ing electrical values. Sensor tube and connection Material Acid-proof, stainless steel (AISI 316L/W.1.4404) Media pressure Max. 16 bar Time constant t 0.5 See table below Mechanical tolerances ISO 2768-m Sensor element Sensor type Pt100, Class A or B Pt1000, Class B Accuracy DIN/EN/IEC 60751 1/1 DIN B: ±(0.3 + 0.005 x t) C 1/3 DIN B: +1/3 x (0.3 + 0.005 x t) C 1/6 DIN B: +1/6 x (0.3 + 0.005 x t) C 1/1 DIN A: +(0.15 + 0.002 x t) C Ex-Application - Configuration Valid for FlexTop 2201 / 2211 / 2221 and FlexView: None of the two types of FlexProgrammer confi guring unit must be connected to the FlexView within the hazardous area. Confi guring procedure: a) Disconnect mains from the 4...20 ma loop circuit. b) Disconnect the product from the circuitry within the hazardous area. c) Bring the product to the safe area. d) Connect the FlexProgrammer and perform the confi guring session. e) Re-install the product in the hazardous area. f) Connect the power supply to the circuit. Valid for FlexTop 2221 only: Confi guration of the FlexTop2221 can be made within the hazardous area by means of a handheld HART confi gurator, providing the precautions and guidelines described in the product s manual are observed. Valid for FlexTop 2231 only: Confi guration of the FlexTop2231 can be made within the hazardous area by means of a Profi bus PA confi gurator, providing the precautions and guidelines described in the product s manual are observed. WARNING This product contains no replaceable parts. In case of malfunction the product must be shipped to Baumer for repair. WARNING Products with painted and/or plastic surfaces (e.g. display) imply a risk of electrostatic charging. To prevent electrostatic hazard - do only clean with a moist cloth. After mounting the device - do check that the housing has a ground potential. Page 2
Dimensional Drawings - Mounting Details [mm] 76 71 85 7.5 12.5 11 Male Nipple G1/2A Male Nipple G1/2A Male Nipple G1/2A mounted on DIN B housing mounted on ø80 mm housing Sensor inserts Calculation of insert length: When ordering an insert the length must be calculated from the formula: Housing shaft {8} Total body length Sensor length (L) DIN housing with G1/2A male nipple connection and sensor insert Insert length = Sensor length + total body length + housing shaft (Total body length can be calculated from the dimensional drawings on pages 6 and 7) Example. Insert for a G1/2A male nipple sensor in a DIN housing, 100 mm sensor tube, normal response sensor tip: Housing shaft = 11.5 mm Total body length = 27.5 + 12.5 = 40 mm (see page 6) Sensor length = 100 mm This insert must be ordered with a 151.5 mm sensor tube. Note {8} Housing shaft DIN housing: 11.5 mm ø80 housing: 6.5 mm Time Constant τ 0.5 Sensor type Liquids Air Dimension Response Insert 0.4 m/sec. 3 m/sec. 0 m/sec. ø6 mm tube fast < 1.5 sec. < 21.4 sec. < 135.6 sec. ø8 mm tube fast < 1.5 sec. < 33.6 sec. < 181.0 sec. ø10 mm tube fast < 1.5 sec. < 46.8 sec. < 238.9 sec. ø12 mm tube fast < 1.5 sec. < 59.9 sec. < 311.4 sec. ø6 mm tube normal < 6.1 sec. < 27.2 sec. < 137.8 sec. ø8 mm tube normal < 7.6 sec. < 47.7 sec. < 200.9 sec. ø10 mm tube normal < 11.1 sec. < 57.8 sec. < 270.6 sec. ø12 mm tube normal < 16.2 sec. < 70.8 sec. < 319.8 sec. ø8 mm tube normal 5.6 mm < 13.6 sec. < 51.1 sec. < 253.1 sec. ø10 mm tube normal 5.6 mm < 28.1 sec. < 67.0 sec. < 271.1 sec. ø12 mm tube normal 5.6 mm < 31.3 sec. < 82.3 sec. < 289.3 sec. Surface sensor, fl ush mounted < 1.0 sec. Page 3
Technical Data, Ex ia IIC T4/T5, ATEX II 1G Approval Product Identification The label at the product will show the type no. like this: 814x xxxx xxxx xx4 xxxx + xxxx xxxx + xx xx-xxx CombiTemp no. + FlexTop no. + FlexView/BattTemp no. The complete confi guration will be referred to as CombiTemp. A CombiTemp with a type no. with the upmentioned structure is Ex ia IIC T4/T5, ATEX II 1G approved in accordance with the current EU-directives. Ex- data for the below listed configurations Ø80 housing: FlexTop 2201 / 2211 / 2221 / FlexView DIN-B housing: FlexTop 2201 / 2211 / 2221 Internal inductivity L i < 11 µh Internal capacity C i < 36 nf Barrier data U < 28 Vdc ; I < 0.1 A ; P < 0.7 W Temperature class T4: -20 < T amb < 70 C T5: -20 < T amb < 60 C guidelines for zone 0 or 1, and a certifi ed, intrinsically safe zener barrier or isolation barrier with the listed maximum values must be used. Ex- data for the below listed configurations Ø80 housing: FlexTop 2231 DIN-B housing: FlexTop 2231 Internal inductivity L i < 10 µh Internal capacity C i < 2 nf Coupler/link FISCO standard; U < 17.5 Vdc ; I < 215 ma ; P < 2 W Zener barrier U < 20 Vdc ; I < 0.1 A ; P < 0.75 W Temperature class T4: -30 < T amb < 85 C T5: -30 < T amb < 60 C guidelines for zone 0 or 1, and a certifi ed, intrinsically safe zener barrier or isolation barrier with the listed maximum values must be used. Ex- data for the below listed configuration Ø80 housing: BattTemp Temperature class Battery: Energizer Lithium FR6 L91 AA T4: -10 < T amb < 70 C T5: -10 < T amb < 50 C Battery: Duracell Alkaline MN1500 LR6 AA T3: -10 < T amb < 70 C T4: -10 < T amb < 60 C guidelines for zone 0 or 1. However, being a battery operated instrument the installation does not involve a barrier. CAUTION: Replacement of the battery must be done outside hazardous areas. The BattTemp is battery supplied and must not be connected to any external power supply, nor to a 4...20 ma loop circuit. When the BattTemp is installed in a hazardous area the battery clip must be mounted. Observe the polarity of the battery. BattTemp contains no repairable parts and must be replaced as a unit in case of malfunction. It has no need for preventive maintenance, except replacement of the battery. Confi guring by the push buttons is allowed within the hazardous area. Battery Battery clip Terminals for Pt100 sensor + Ex-Application Example RTD Zone 0/1 Safe area 230 Vac 3 4 2 - + 1 - + 4...20 ma 1 2 + - 24 VDC FlexTop 2211 FlexView Isolation Barrier Power Supply CombiTemp Page 4
Technical Data, Ex na II T4/T5, ATEX II 3G Approval Product Identification The label at the product will show the type no. like this: 814x xxxx xxxx xx5 xxxx + xxxx xxxx + xx xx-xxx CombiTemp no. + FlexTop no. + FlexView/BattTemp no. The complete confi guration will be referred to as CombiTemp. A CombiTemp with a type no. with the upmentioned structure is Ex na II T4/T5, ATEX II 3G approved in accordance with the current EU-directives. Ex- data for the below listed configurations Ø80 housing: FlexTop 2201 / 2211 / 2221 / 2231/FlexView DIN-B housing: FlexTop 2201 / 2211 / 2221 / 2231 Temperature class T4: -20 < T amb < 70 C T5: -20 < T amb < 60 C guidelines for zone 2 without a barrier. WARNING: Do not open when energised. Ex- data for the below listed configurations Ø80 housing: BattTemp Temperature class Battery: Energizer Lithium FR6 L91 AA T4: -10 < T amb < 70 C T5: -10 < T amb < 50 C Battery: Duracell Alkaline MN1500 LR6 AA T3: -10 < T amb < 70 C T4: -10 < T amb < 60 C Warning: Observe battery ambient temperature!!! guidelines for zone 2. CAUTION: Replacement of the battery must be done outside hazardous areas. The BattTemp is battery supplied and must not be connected to any external power supply, nor to a 4...20 ma loop circuit. When the BattTemp is installed in a hazardous area the battery clip must be mounted. Observe the polarity of the battery. BattTemp contains no repairable parts and must be replaced as a unit in case of malfunction. It has no need for preventive maintenance, except replacement of the battery. Confi guring by the push buttons is allowed within the hazardous area. Battery Battery clip Terminals for Pt100 sensor Electrical Connection Application we CombiTemp Gland Cable diameter Gland torque mm Nm Ø80 mm housing M16 3...9 8 DIN-B housing M20 8...13 6 CombiTemp Zone 2 RTD Safe area 230 Vac 3 4 Warning: If the CombiTemp is to be installed in ambient temperature exceeding 70 C a proper cable should be installed. 6 5 4 3 - + 2 1 4...20 ma - + 1 2 + - 24 VDC FlexView FlexTop 2211 Power supply Page 5
Mounting the ø80 mm Housing 35 Nm 2 Nm Page 6
Mounting the DIN-B Housing 2mm 2 Nm 35 Nm Page 7
4-wire Sensors Double Elements White White Red Red White White Red Red Application Photos Warning: One of the wires may not be connected in case of a 3-wire connection to the temperature transmitter ø80 mm housing with FlexView Cut through DIN - B housing ø80 mm housing with 2 glands Gland (blind plug at the rear) FlexTop 2201 temperature transmitter Cover not mounted Clamp connection G1/2A male nipple connection 3A connection at the rear Fast response sensor Normal response sensor Fast response sensor 5850-008-UK/2008-04-25/Rev. A1 This data sheet may only be reproduced in full. Page 8