DESIGN GUIDELINES FANS PAGE 1 of 7

Similar documents
Roof Upblast and Sidewall Exhaust

Roof Upblast and Sidewall Exhaust

CENTRIFUGAL WALL EXHAUSTERS Models VWDK and VWBK

Fixed Pitch Vane Axial Fan

CENTRIFUGAL UPBLAST ROOF EXHAUSTERS Models VUDK and VUBK

The Industrial Choice. Model SCDD Direct Drive. Model SCBD Belt Driven SQUARE INLINE FANS. Direct Drive & Belt Driven Model SCDD / SCBD

Centrifugal Filtered Supply Roof Blowers

CENTRIFUGAL UPBLAST ROOF EXHAUSTERS Model VQBL

Tube Axial Fan Page Specifications & Dimension Data Performance Data

CENTRIFUGAL UPBLAST ROOF EXHAUSTERS Model VRBK

BELT DRIVEN CENTRIFUGAL ROOFTOP FILTERED SUPPLY FAN

EXHAUST FANS CUD & CUB UPBLAST FANS

SECTION HVAC POWER VENTILATORS

MODEL TUB TUBEAXIAL UPBLAST PROPELLER ROOF EXHAUSTER

Centrifugal Utility Fans - SFD/SFB

Centrifugal Exhaust Fans Series C. Roof Upblast and Sidewall

MODEL TUB TUBEAXIAL UPBLAST PROPELLER ROOF EXHAUSTER

The Industrial Choice. Model BD40C UPBLAST AXIAL ROOF VENTILATORS. Macheta Airfoil Design. Model BD40C

.3 Section Vibration Isolation and Seismic Control..2 ANSI/AMCA 210/ASHRAE 51 Laboratory Methods of Testing Fans for Rating.

Propeller Upblast Roof Fans

SECTION AXIAL HVAC FANS

Centrifugal Inline Fans Models SQ-M and BSQ-M. Direct and Belt Drive

MODEL CTB TUBULAR CENTRIFUGAL INLINE BELT DRIVEN FAN

Propeller Hooded Roof Fans

Centrifugal Upblast Power Roof Ventilators

Utility Sets Standard Design Features Standard design features common to all Class I and Class II fans

Tube Axial Inline Fans

SECTION CENTRIFUGAL HVAC FANS

Tubular Centrifugal Inline Fans Page Introduction... 2 Construction Features... 3 Specification and Dimension Data TCN-D (Inline Fan- Direct

SQUARE INLINE CENTRIFUGAL FANS

Tamper Proof Downblast Centrifugal Exhaust Ventilators Page

UPBLAST AXIAL ROOF VENTILATORS

First Inline fan in the industry to be UL/cUL Listed Power Ventilator for Smoke Control Systems

Mixed-Flow Blowers Page Specifications and Dimension Data Performance Data Sound Data

High Performance Axial Fans

TUBEAXIAL PAINT SPRAY BOOTH EXHAUST FANS

Air Moving Solutions. VENTILATING SETs BCV BCVU5 BCVU2 BCVSH BAV FCV

Twin City Fan & Blower

Industry best 5 year fan housing warranty, 1 year motor warranty

Tubular Centrifugal Fans

Inline Fans [ 14 ] * UL is optional and must be specified.

The Industrial Choice. Model BSHD Direct Drive LOW PROFILE HOODED PROPELLER ROOF VENTILATORS. Models BSHD / BSHB

Centrifugal Ventilators Direct-Drive Upblast Centrifugal Roof & Wall Ventilators

UTILITY BLOWERS. Models: BIUB / BIUBR / BIUBSH BAUB / DFC / FCUB. The Industrial Choice.

MODELS STXD & STXDe DIRECT DRIVE CENTRIFUGAL ROOF EXHAUSTERS

TURNING AIR INTO SOLUTIONS. LOW PROFILE UPBLAST PROPELLER ROOF VENTILATORS. LUD/LUB (Standard) LUBMO (Motor Out of Airstream) LUBSH (UL Smoke & Heat)

MODEL NBRTD BELT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTER

Square Inline Fans with Multi-Directional Discharge

Filtered Kitchen Supply Packaged Ventilator

2. Backward inclined / backward curved centrifugal wheel fans. 3. Axial / backward curved mixed flow impeller bifurcated fans.

an ISO 9001 Company Bulletin BCPF 100 NEW Design 70 PLUG FANS CHICAGO BLOWER CORPORATION GLENDALE HEIGHTS, ILLINOIS USA

Inline and Roof Mounted Fans

Model LIDA. DIRECT DRIVE TUBEAXIAL FANS Model LIDA DIRECT DRIVE TUBEAXIAL FANS SECTION 12. Application. Options/Accessories

MODELS UBB & UBX UPBLAST PROPELLER ROOF EXHAUSTERS BELT AND DIRECT DRIVE

The Industrial Choice. Vane Section For Model VTBD. Model TTABD TUBEAXIAL & VANEAXIAL FANS. Type "T" Belt Driven Model TTABD / VTBD

INDUSTRIES AMERICAN COOLAIR CORPORATION. Centrifugal Filtered Supply Roof Ventilators TYPE CFS - TYPE SIS

Vaneaxial Fans. Series 25 Series 53 Series 53C Series 54 Series 55 HARTZELL. Hartzell Fan, Inc., Piqua, Ohio

Centrifugal Spun Aluminum Products

Twin City Fan & Blower

MODEL UBSRD REMOTE DRIVE UPBLAST PROPELLER ROOF EXHAUSTER

CENTAXIAL TUBULAR CENTRIFUGAL FANS. BIA Airfoil Blade Design Direct Drive & Belt Driven Model CBD / CDD (Class I, II & III) Model CBD Belt Driven

INLINE CENTRIFUGAL DUCT FANS Direct and Belt Driven Models ZIDK and ZIBK

TURNING AIR INTO SOLUTIONS. UTILITY SETS DCV BCV BCVR BCVSH BAV DDF FCV

MODEL TXD DIRECT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTER

Centrifugal Roof Supply Fans Models RSF and RSFP. Forward Curved

forward curved inline duct blowers

MODEL LUBK (Belt Drive) UPBLAST PROPELLER ROOF EXHAUSTERS

Centrifugal Roof Supply Fans Models RSF and RSFP. Forward Curved

MODEL TDB TUBEAXIAL INLINE BELT DRIVEN DUCT FAN

MODELS HRSB & HRSD HOODED PROPELLER ROOF SUPPLY FANS

belt drive utility sets vent-pak series models vp-bi & fc january 2007 vp 1.07

Power Roof and Wall Ventilators

PRODUCT FEATURES. BEARING LIFE All bearings are designed for L50 life of 200,000 hours.

Industry best 5 year fan housing warranty, 1 year motor warranty

Type VA Vanax Fans. Models VA, VAD, & VAB

The Industrial Choice. Model VB Direct Drive. Model VBBD Belt Driven VANEAXIAL FANS. Direct Drive & Belt Driven Model VB / VBBD

MODEL TXD DIRECT DRIVE CENTRIFUGAL UPBLAST ROOF EXHAUSTER

BULLETIN 456. July 1997 VANEAXIAL FANS. Type W Direct Drive/Belt Driven. Model VW Direct Drive. Model VWBD Belt Driven

TURNING AIR INTO SOLUTIONS. DIRECT DRIVE EXHAUST & SUPPLY PANEL FANS. Model TCPE

Mixed Flow Inline Fan Model EQB

Safety disconnect. switch is optional. Belt drive with adjustable motor pulley provides flexibility to match operating requirements.

FIXED PITCH PROPELLER FANS

Bulletin ACF 103 AIRFOIL CENTRIFUGAL FANS DESIGN 10A

MODELS HREB-C & HRED-C HOODED PROPELLER ROOF EXHAUST FANS

Centrifugal Spun Aluminum Products

TUBULAR CENTRIFUGAL INLINE FANS

Centrifugal Spun Aluminum Products

K SERIES SIDEWALL PROPELLER FANS

The Industrial Choice. PROPELLER WALL FANS DIRECT DRIVE & BELT DRIVEN. Models BSDDP / BSBP

Sidewall Propeller Fans Direct Drive. Exhaust / Supply

Bulletin VX05 VANEAXIAL FANS

K SERIES DIRECT DRIVE SIDEWALL PROPELLER FANS

PennBarry Fan Guide Specification. Laboratory Exhaust System: Model vplume

Turning Air Into Solutions. PLUG FANS TYPE BCPL

Industrial Material Handler Page Introduction... 2 Information Specifications MH Specifications... 6 MHR Specifications...

Twin City Fan & Blower

VANEAXIAL & TUBEAXIAL FANS

Industry best 5 year fan housing warranty, 1 year motor warranty

Climas y Proyectos Leyco, S.A. de C.V.

Twin City Fan & Blower

Transcription:

DESIGN GUIDELINES FANS PAGE 1 of 7 1.1. REFERENCE STANDARDS 1.1.1. Publications listed below (including amendments, addenda, revisions, supplements and errata) form a part of this specification to the extent referenced. Publications are reference in the text by designation only, latest revision applicable. 1.1.1.1. AMCA 99, "Standards Handbook" 1.1.1.2. ANSI/AMCA Standard 204 "Balance Quality and Vibration Levels for Fans" 1.1.1.3. ANSI/AMCA Standard 210 "Laboratory Methods of Testing Fans for Aerodynamic Performance Rating" 1.1.1.4. AMCA Publication 211, "Certified Ratings Programme - Product Rating Manual for Fan Air Performance" 1.1.1.5. AMCA Publication 311 "Certified Ratings Programme - Product Rating Manual For Fan Sound Performance" 1.1.1.6. AMBA - Method of Evaluating Load Ratings of Bearings ANSI-11 1.1.1.7. OSHA guideline 1910.212 - General requirements for Machine Guarding. 1.1.1.8. OSHA guideline 1910.219 - General requirements for guarding safe use of mechanical power transmission apparatus. (www.osha.gov) 1.1.1.9. UL Standard 705, "Power Ventilators" 1.2. ROOF CENTRIFUGAL EXHAUST FANS 1.2.1. Roof exhaust fans shall be centrifugal belt driven type. The fan wheel shall be centrifugal backward inclined, constructed of aluminum and shall include a wheel cone carefully matched to the inlet cone for precise running tolerances. Wheels shall be statically and dynamically balanced. The fan housing shall be constructed of heavy gauge aluminum with a rigid internal support structure. 1.2.2. Motors shall be heavy duty ball bearing type, carefully matched to the fan load, and furnished at the specified voltage, phase and enclosure. Motors and drives shall be mounted on vibration isolators, out of the airstream. Fresh air for motor cooling shall be drawn into the motor compartment from an area free of discharge contaminants. Motors shall be readily accessible for maintenance. 1.2.3. Drive frame assemblies shall be constructed of heavy gauge steel and mounted on vibration isolators. Precision ground and polished fan shafts shall be mounted in permanently sealed, lubricated pillow block ball bearings. Bearings shall be selected for a minimum (L10) life in excess of 100,000 hours at maximum cataloged operating speed. Drives shall be sized for a

DESIGN GUIDELINES FANS PAGE 2 of 7 minimum of 150 percent of driven horsepower. Pulleys shall be of the fully machined cast iron type, keyed and securely attached to the wheel and motor shafts. Motor pulleys shall be adjustable for final system balancing. 1.2.4. A disconnect switch shall be factory installed and wired from the fan motor to a junction box installed within the motor compartment. 1.2.5. A fan conduit chase shall be provided through the curb cap to the motor compartment for ease of installation. 1.2.6. All fans shall bear the AMCA Certified Ratings Seal for sound and air performance. 1.2.7. Each fan shall bear a permanently affixed manufacturer's nameplate containing the model number and individual serial number for future identification. 1.3. ROOF UPBLAST EXHAUST FANS 1.3.1. Roof exhaust fans shall be upblast centrifugal belt driven type. The fan wheel shall be centrifugal backward inclined, constructed of aluminum and shall include a wheel cone carefully matched to the inlet cone for precise running tolerances. Wheels shall be statically and dynamically balanced. The fan housing shall be constructed of heavy gauge aluminum with a rigid internal support structure. Windbands shall have a rolled bead for added strength and shall be joined to curbcaps with a leakproof, continuously welded seam. 1.3.2. Motors shall be heavy duty ball bearing type, carefully matched to the fan load, and furnished at the specified voltage, phase and enclosure. Motors and drives shall be mounted on vibration isolators, out of the airstream. Fresh air for motor cooling shall be drawn into the motor compartment from an area free of discharge contaminants. Motors shall be readily accessible for maintenance. Drive frame assemblies shall be constructed of heavy gauge steel and mounted on vibration isolators. 1.3.3. Precision ground and polished fan shafts shall be mounted in permanently sealed, lubricated pillow block ball bearings. Bearings shall be selected for a minimum (L10) life in excess of 100,000 hours at maximum cataloged operating speed. Drives shall be sized for a minimum of 150% of driven horsepower. Pulleys shall be of the fully machined cast iron type, keyed and securely attached to the wheel and motor shafts. 1.3.4. Motor pulleys shall be adjustable for final system balancing. A disconnect switch shall be factory installed and wired from the fan motor to a junction box installed within the motor compartment. 1.3.5. Each fan shall bear a permanently affixed manufacturer's nameplate containing the model number and individual serial number for future identification. 1.4. SIDEWALL CENTRIFUGAL EXHAUST FANS 1.4.1. Sidewall exhaust fans shall be of the centrifugal belt driven type.

DESIGN GUIDELINES FANS PAGE 3 of 7 1.4.2. Construction of the windband shall be of heavy gauge aluminum with a rolled bead on the outer edge for strength. The fan wheel and inlet cone shall be aluminum and of the high performance centrifugal blower type. The fan wheel shall be of the aluminum, nonoverloading, backward inclined type, statically and dynamically balanced. Blades, fins, inlet cones and back plates shall be securely fastened together into a rigid assembly. 1.4.3. Motors and drives shall be isolated from the exhaust airstream. Motors shall be of heavy duty type with permanently lubricated, sealed ball bearings. Air for cooling the motor shall be taken into the motor compartment by means of an air tube from a location free of discharge contaminants. The entire drive assembly and wheel, as a unit, shall be removable through the support structure without dismantling the fan housing. The wheel shaft shall be mounted in heavy duty, permanently lubricated, sealed ball bearing pillow blocks. Drives shall be sized for 165% of driven horsepower. Pulleys shall be of the machined cast iron type, keyed securely to the fan and motor shafts. Motor pulleys shall be of the adjustable type to allow for final system balancing. The entire drive assembly shall be mounted on vibration isolators to minimize noise transmission. 1.4.4. Fans shall be AMCA licensed for air and sound performance data. 1.5. SIDEWALL AXIAL EXHAUST FANS 1.5.1. Belt driven, axial type sidewall fans shall provide as follows: 1.5.2. Propellers shall be constructed with cast aluminum blades and hubs. Propellers shall be securely attached to fan shafts. All propellers shall be statically and dynamically balanced. 1.5.3. Motors shall be permanently lubricated, heavy duty type, carefully matched to the fan load and furnished at the specified voltage, phase, and enclosure. 1.5.4. Ground and polished steel fan shafts shall be mounted in permanently lubricated, sealed ball bearing pillow blocks. Bearings shall be selected for a minimum (L10) life in excess of 100,000 hours at maximum cataloged operating speeds. Drives shall be sized for a minimum of 150 percent of driven horsepower. Pulleys shall be of the fully machined cast iron type, keyed and securely attached to wheel and motor shafts. Motors sheaves shall be adjustable for system balancing. 1.5.5. Drive frame and panel assemblies shall be galvanized steel or painted steel. Drive frames shall be formed channels and fan panels shall have prepunched mounting holes, formed flanges, and a deep formed inlet venturi. Drive frames and panels shall be bolted construction or welded construction. 1.5.6. The axial exhaust fans shall bear the AMCA Certified Ratings Seals for both sound and air performance.

DESIGN GUIDELINES FANS PAGE 4 of 7 1.6. IN-LINE CENTRIFUGAL FANS 1.6.1. Duct mounted supply, exhaust or return fans shall be of centrifugal belt driven in-line type. The fan housing shall be of the square design constructed of heavy gauge galvanized steel and shall include square duct mounting collars. 1.6.2. Fan construction shall include two removable access panels located perpendicular to the motor mounting panel. The access panels must be of sufficient size to permit easy access to all interior components. 1.6.3. The fan wheel shall be centrifugal backward inclined, constructed of aluminum and shall include a wheel cone carefully matched to the inlet cone for precise running tolerances. Wheels shall be statically and dynamically balanced. 1.6.4. Motors shall be heavy duty ball bearing type, carefully matched to the fan load and furnished at the specified voltage, phase and enclosure. Motors and drives shall be mounted out of the airstream. 1.6.5. Precision ground and polished fan shafts shall be mounted in permanently sealed, lubricated pillow block ball bearings. Bearings shall be selected for a minimum (L10) life in excess of 100,000 hours at maximum cataloged operating speed. 1.6.6. Drives shall be sized for a minimum of 150% of driven horsepower. Pulleys shall be of the fully machined cast iron type, keyed and securely attached to the wheel and motor shafts. 1.6.7. Motor pulleys shall be adjustable for system balancing. A NEMA 1 disconnect switch shall be provided as standard, except with explosion resistant motors, where disconnects are optional. Factory wiring shall be provided from motor to the handy box. 1.6.8. All fans shall bear the AMCA Certified Ratings Seal for both sound and air performance. 1.6.9. Each fan shall bear a permanently affixed manufacturer's nameplate containing the model number and individual serial number for future identification. 1.7. SINGLE WIDTH, SINGLE INLET UTILITY TYPE FANS 1.7.1. Fan Housing And Outlet 1.7.1.1. Fan housing is to be aerodynamically designed with high-efficiency inlet, engineered to reduce incoming air turbulence. 1.7.1.2. The housings on all fan sizes shall be of continuously welded heavy gauge steel. All interior and exterior surface steel shall be coated with a minimum of 2-4 mils of Permatector (Polyester Urethane), electrostatically applied and baked. Finish color shall be gray. No uncoated metal fan parts will be allowed.

DESIGN GUIDELINES FANS PAGE 5 of 7 1.7.1.3. Housing and bearing support shall be constructed of welded structural steel members to prevent vibration and rigidly support the shaft and bearings. 1.7.1.4. An OSHA compliant belt guard shall be included to completely cover the motor pulley and belt(s). 1.7.2. Fan Wheel 1.7.2.1. The fan wheel shall be of the non-overloading single width airfoil centrifugal type. Wheels shall be statically and dynamically balanced to balance grade G6.3 per ANSI S2.19. 1.7.2.2. Fan wheel shall be manufactured with continuously welded steel airfoils and coated with a minimum of 2-4 mils of Permatector (Polyester Urethane), electrostatically applied and baked. Finish color shall be industrial gray. 1.7.2.3. The wheel and fan inlet shall be carefully matched and shall have precise running tolerances for maximum performance and operating efficiency. 1.7.3. Fan Motors And Drive. 1.7.3.1. Motors to be NEMA T-frame, 1800 or 3600 RPM, Open Drip Proof (ODP) or Totally Enclosed Fan Cooled (TEFC) with a 1.15 service factor. 1.7.3.2. Drive belts and sheaves shall be sized for 150% of the fan operating brake horsepower, and shall be readily and easily accessible for service, if required. 1.7.3.3. Fan shaft to be turned and polished steel that is sized so the first critical speed is at least 25% over the maximum operating speed for each pressure class. 1.7.3.4. Fan shaft bearings shall be heavy-duty grease lubricated, self-aligning or roller pillow block type. Bearings shall be 100% tested for noise and vibration by the manufacturer. Bearings shall be 100% tested to insure the inner race diameter is within tolerance to prevent vibration. Bearings shall be selected for a basic rating fatigue life (L-10) of 80,000 hours. Bearings shall be fixed to the fan shaft using concentric mounting locking collars, which reduce vibration, increase service life, and improve serviceability. Bearings that use set screws shall not be allowed. 1.7.3.5. Bearings shall have Zerk fittings to allow for lubrication. 1.8. DOUBLE WIDTH, DOUBLE INLET FANS 1.8.1. Fan Housing And Outlet 1.8.1.1. Fan housing shall be doublewide to accommodate the backward inclined double width wheel.

DESIGN GUIDELINES FANS PAGE 6 of 7 1.8.1.2. Fan housing is to be aerodynamically designed with high-efficiency inlet, engineered to reduce incoming air turbulence. 1.8.1.3. The housings on all fan sizes shall be of continuously welded heavy gauge steel. All interior and exterior surface steel shall be coated with a minimum of 2-4 mils of Permatector (Polyester Urethane), electrostatically applied and baked. Finish color shall be gray. No uncoated metal fan parts will be allowed. 1.8.1.4. Housing and bearing support shall be constructed of welded structural steel members to prevent vibration and rigidly support the shaft and bearings. 1.8.1.5. An OSHA compliant belt guard shall be included to completely cover the motor pulley and belt(s). 1.8.2. Fan Wheel 1.8.2.1. The fan wheel shall be of the non-overloading Double Width Backward Inclined centrifugal type. Wheels shall be statically and dynamically balanced to balance grade G6.3 per ANSI S2.19. 1.8.2.2. Fan wheel shall be manufactured with continuously welded steel blades and coated with a minimum of 2-4 mils of Permatector (Polyester Urethane), electrostatically applied and baked. Finish color shall be industrial gray. 1.8.2.3. The wheel and fan inlet shall be carefully matched and shall have precise running tolerances for maximum performance and operating efficiency. 1.8.3. Fan Motors And Drive. 1.8.3.1. Motors to be NEMA T-frame, 1800 or 3600 RPM, Open Drip Proof (ODP) or Totally Enclosed Fan Cooled (TEFC) with a 1.15 service factor. 1.8.3.2. Drive belts and sheaves shall be sized for 150% of the fan operating brake horsepower, and shall be readily and easily accessible for service, if required. 1.8.3.3. Fan shaft to be turned and polished steel that is sized so the first critical speed is at least 25% over the maximum operating speed for each pressure class. 1.8.3.4. Fan shaft bearings shall be Air Handling Quality, bearings shall be heavy-duty grease lubricated, self-aligning or roller pillow block type. Bearings shall be 100% tested for noise and vibration by the manufacturer. Bearings shall be 100% tested to insure the inner race diameter is within tolerance to prevent vibration. Bearings shall be selected for a basic rating fatigue life (L-10) of 80,000 hours at maximum operating speed. Bearings shall be fixed to the fan shaft using concentric mounting locking collars, which reduce vibration, increase service life, and improve serviceability. Bearings that use set screws shall not be allowed.

DESIGN GUIDELINES FANS PAGE 7 of 7 1.8.3.5. Bearings shall have Zerk fittings to allow for lubrication.