K10 Intrinsically Safe Electro-Pneumatic Positioner Operating Manual

Similar documents
V200 Series Positioners

Features. Flexibility

V200 Series Positioners

Moniteur INSTALLATION & OPERATING INSTRUCTIONS. SERIES 40 Positioners. Installation and Operating Instructions Series 40 Positioners.

V200 Positioner. V200 P Pneumatic Positioner. V200 E Electropneumatic Positioner. Housing Material: Cast aluminium with polyester coating

TECHNICAL BULLETIN. Logix 510si Series Digital Positioner. Experience In Motion FCD LGENTB /09

SS3 Linear / Rotary. Smart Valve Positioner. Smart performance with innovative and ever-strong coil drive even under harsh working environments

VALVE ACCESSORIES & CONTROLS V200 POSITIONER A POSITIONER THAT OFFERS IT ALL IN ONE COMPACT, SIMPLE, HOUSING

V200 Series Positioners

Valve Positioners Series 760P/E Valve Positioners

Type Installation, Operation and Maintenance Instructions. Ordering Information. Contents CA20 -

POSITIONERS and Controls for Complete Valve Automation

Electro-Pneumatic Linear Positioner Installation and Operation Instructions B GB

1.0 Features and Description

Control Valves Positioner

Control Valves Positioner

Installation and Operating Instructions Electro-Pneumatic Rotary Positioner SP-21. Description of Device. Part Number System

Valve Positioners Series 760P/E Valve Positioners

ABB MEASUREMENT & ANALYTICS DATA SHEET. AV1 and AV2 Characterizable pneumatic and electro-pneumatic positioners

Model 116 DPI Switch Installation and Operating Instructions

SR1V. Industrial Low Cost String Pot

Double Acting & Spring Return. SERIES 92/93 Rack & Pinion PNEUMATIC ACTUATOR. The High Performance Company

AP ATEX AIRPOWER POSITIONERS AP2000 FEATURES AP1000 & AP1200 FEATURES OPTIONS OPTIONS

Series AV1 / 2 / 4 Characterizable pneumatic positioners

CONTROLS. Bray Pneumatic Actuators & Accessories. Technical Manual. A Division of BRAY INTERNATIONAL, Inc.

Type 2000 Transducer Product Instructions

SMART VALVE POSITIONER 4 to 20 ma + HART Digital Communication. smar B87

TECHNICAL BULLETIN. Logix 520MD Series Digital Positioner. Experience In Motion FCD LGENTB /09

Spring Cylinder Rotary Actuator

5001TCP SPEED CONTROLLER

12 Series Linear Actuators. Operation & Maintenance Manual, Analog Positioner Installation

Apex 5000 Positioner

V200 POSITIONER. V200 FEEDBACK OPTION r14

PEAKTRONICS DMC-101 ADDITIONAL FEATURES. DC Motor Controller, 5A DMC-101

Corrosion Resistant Pneumatic Positioners Model 4700P and 4700E


Surepowr Series Sure 150

Series AV1 / 2 / 3 / 4 Characterizable pneumatic positioners

TECHNICAL BULLETIN. Logix 510si Series Digital Positioner. Experience In Motion FCD LGENTB /13

Valtek Position Pac GENERAL INFORMATION INSTALLATION INSTRUCTIONS OPERATION. Valtek Linear Actuators

LTX RF LEVEL SENSOR. Instruction Manual

SS2 Linear / Rotary Smart Valve Positioner

Fisher 546 Electro Pneumatic Transducer

CONTROLS INC. Position Indicators. Valve Positioners

SP-20 Input. Installation and Operating Instructions Electro-Pneumatic Linear Positioner. Description of Device. Part Number System

Installation Manual OPEN. For Corrosive Service. The ONYX integrates electronic sensors and pneumatic valving into a vapor tight enclosure.

SINGLE-ACTING ACTUATORS FOR DOUBLE-ACTING & SERIES 65 POSITIONERS PNEUMATIC & ELECTRO-PNEUMATIC. The High Performance Company

CENTURA CE Series. Installation, Operation SR and Limit Maintenance Switch Method Instructions

Type Type 1001 Transducers. I/P & E/P Transducers

Surepowr Series 100 Installation Manual

5001TCP SPEED CONTROLLER

SPECIFICATIONS ATTENTION OPERATION DESCRIPTION

LIMIT SWITCHES & POSITION INDICATION

Quarter Master Series 94 Actuator

Installation and Operating Manual

FAIRCHILD T5200 SERIES ELECTRO-PNEUMATIC TRANSDUCER Installation, Operation and Maintenance Instructions

Valtek XL Series High Performance Positioner. for Control Valves

TZIM. Electropneumatic Analog Positioner 10/ EN

Quarter Master Chief Series 92 Actuator

BULLETIN NO.ELEC IM121/10A Replaces IM121/09A

APS & APIS ATEX AIRPOWER SWITCH BOXES FEATURES DESCRIPTION

T-1001 TYPE 1001 I/P & E/P TRANSDUCERS

Series 60. New Smart Positioner. Compact design Convenient & powerful function Enhanced reliability

AF-17 Electronic Positioner Installation, Operation and Maintenance Instructions

The EP5 electropneumatic positioner is

FAIRCHILD T8001 SERIES STANDARD RANGE MINIATURE TWO-WIRE, P/I PRESSURE TRANSDUCER. Installation, Operation and Maintenance Instructions

The Series I/P Current to Pressure Transducer

Installation, Operation and Maintenance Instructions Output Range Part Number Input psi bar Impedance Output Range

Operating Instructions. Angle Seat Control Valve. Type 7020

Series 10 Actuator. Installation, Operation and Maintenance Manual

SUREPOWR TM SERIES -SURE 24/25 FIELD INSTALLATION INSTRUCTIONS

12 Series Linear Electric Actuator Installation, Operation & Maintenance Manual

Actuators & Positioners Pneumatic Actuators Series UP1/2/3/4/5/6

Table of Contents. Proportional & Precision Regulator Instrumentation

Pattern Air Control Kit (PACK)

Your Global Flow Control Partner. Series 70 24V On/Off Electric Actuator Operation and Maintenance Manual

Automation Selection Guide

ESBE Series 60 Electronic Motor Actuator (Combined with ESBE 3&4-way rotary valves)

RCVC Red Circle Valve Controller VALVE CONTROLER

Fisher i2p 100 Electro Pneumatic Transducer

Control System Instrumentation

Actuators & Positioners Models UP1/2/3/4/5/6/7. Universal Pneumatic Rotary Actuators

RTX1000 SERIES ELECTRO-PNEUMATIC POSITIONER

Electric Actuated Ball Valves 2-way Stainless Steel, Full Port 1/4 to 2 inch NPT

P200 P/I Transducer. Installation, Operation, and Maintenance Instructions INTRODUCTION

Miniature I/P, E/P Transducer

Electric Actuated Ball Valves 2-way Stainless Steel, Full Port 1/4 to 2 inch NPT

Type 3761 Pneumatic or Electropneumatic Positioner for Rotary Actuators. Fig. 1 Type 3761 Positioner. Mounting and Operating Instructions EB 8386 EN

Electric Actuated Ball Valves 3-Piece Stainless Steel, Full Port 1/4 to 3 inch NPT

Series 70 24V On/Off Electric Actuator Operation and Maintenance Manual

Type 500X. Electropneumatic Transducer (I/P, E/P) Installation, Operation and Maintenance Instructions. Ordering Information.

VC-NR-100 SERIES STAINLESS STEEL, VERTICAL CANISTER PNEUMATIC ACTUATOR & SSBT SERIES CONTROL TOPS

Miniature I/P, E/P Transducer for Electronic Air Pressure Control

TECHNICAL BULLETIN. Logix 505si Series Digital Positioner. Experience In Motion FCD LGENTB /13

Tracer VMA with AutoReg

M9216 Series Electric Spring Return Actuators

Miniature I/P, E/P Transducer for Electronic Air Pressure Control

Section 55 Chapter 6

Figure 1: WPR2 Dimensions and Hardware

Electro-Pneumatic Positioner Series 830/831-WP/EX. Operation & Maintenance Manual

Transcription:

K0 Intrinsically Safe Electro-Pneumatic Positioner Operating Manual Pneumatic Connection Outlet Port Gauge Single Acting Actuator (Spring Return): For single acting actuators Outlet Port 2 is to be plugged. Outlet Port is to be piped to the actuator inlet port that acts against the spring. (Increasing signal causes pressure to increase in Outlet Port of the positioner). Supply Gauge CLOSED Double Acting Actuator (Double Return): For double acting actuators Outlet Port 2 is piped to drive the actuator towards the fail position. Outlet Port is piped to drive the actuator away from the fail position. (Increasing signal causes pressure to increase in Outlet Port of the positioner and pressure to decrease in Outlet Port 2 of the positioner). Note: Air supply to the positioner must be clean, dry, oil free instrument air per ISA-S7.3. Maximum supply pressure is 20 psi. All pneumatic connections are /4 NPT. Supply (Inlet Port) Outlet Port 4-20 ma Input (-) SUPPLY OUT OUT 2 Conduit Opening Outlet Port 2 4-20 ma Input (+) SW CCW CW Electrical Connection The electrical connection (4-20 ma Loop Input) to the K0 positioner is polarity sensitive. Connect the 4-20 ma Loop Input to terminal block J on the Connector Board as shown on the right (Positive lead to terminal point 3 and negative lead to terminal point 2). The wire size can range from 20 to 4 AWG. 0/8/04 Tech-362/D.W.O. 645 Page of 2

Position Sensor Initial Angle (Setting Mode) The K0 s Position Sensor, which measures the absolute position of the valve, has a limited operating angle for proper position measurement. The Position Sensor must remain within the operating angle in both the open and fail valve positions. This is accomplished by initially setting the Position Sensor angle while the valve is in the fail position. The K0 has a mode of operation to accomplish the setting of this initial angle using the following steps.. Apply loop current to the positioner and adjust to 2 ma. 2. Press & hold both the high and low buttons until the actuator is driven to span position. Release both buttons to remove air pressure from Outlet Port. Position Sensor Gear Switch (SW) Main Shaft Gear 3. If the valve fails clockwise and strokes counterclockwise, then set switch SW to the CCW position. If the valve fails counter-clockwise and strokes clockwise, then set switch SW to the CW position (see figure to right). SW CCW CW 4. With no buttons pressed and the actuator in the fail position, push the Main Shaft Gear (larger of the two) down until it disengages from its shaft locking position. 5. Rotate the Main Shaft Gear (both gears will turn), until only the green LED is flashing. Note: If the LED is already green, skip 5 and go to 6. 6. Pull up the Main Shaft Gear allowing it to reengage on the shaft locking it into position. 7. Press and hold the High Calibration button until the valve fully strokes away from the fail position while watching the LED s. The red or yellow LED s must not light as long as the High Cal button is being held down. If the red or yellow LED lights while the High Cal button is being held down, then the Position Sensor Orientation and Actuator air piping are out of phase. Correct the phase error by changing the position of SW and repeat this procedure starting from step 2. 8. Release the High Calibration button and watch the red LED. The red LED will flash until the valve reaches the fail position. 9. Press the Low Calibration button to exit the Position Sensor Setting Mode (if no buttons are pushed then this mode will time out automatically in about 2 minutes). 0/8/04 Tech-362/D.W.O. 645 Page 2 of 2

Calibrating The K0 Positioner Once the K0 and actuator have been connected and the initial angle has been set. Low and High Calibration can be performed on the K0. Low Calibration refers to the input current value that drives the valve into the fail position. High Calibration refers to the input current value that drives the valve into the Span Position. Calibration adjusts parameters internal to the K0 that are specific to the actuator, and input current values. The parameters that are adjusted are, the Gain of the K0 servo loop. the end position (Zero/Span) of the valve travel, and Drop-Off point (input current level at which the transducer is forced to the extreme position, to insure that the valve is fully open or closed). The calibration routine uses the input current value to set it s internal adjustment, so it is important that the input current does not change during the calibration routine. ** To Do a Low Calibration: (Zero Position). Set the Input Current level to the value that drives the valve into the fail position (typically 4 ma). 2. Start the Low Calibration routine by pressing and holding the LOW CAL button on the K0 until the Yellow LED flashes. 3. Observe the flashing Yellow LED on the K0 which denotes the various stages of the calibration routine: a.) Flashing time indicates Zero position set routine. b.) Flashing 2 times indicates Transducer Self Calibration routine. c.) Flashing 3 times indicates Gain setting routine. 4. When the Green LED begins to flash the Calibration is completed. If the Red LED flashes this is an indication that one of the Calibration routines could not be completed. The number of Red LED flashes indicates the calibration routine that failed. ** To Do a High Calibration: (Span Position). Set the Input Current level to the value that drives the valve into the span position (typically 20 ma). 2. Start the High Calibration routine by pressing and holding the HIGH CAL button on the K0 until the Yellow LED flashes. 3. Observe the flashing Yellow LED on the K0 which denotes the various stages of the calibration routine: a.) Flashing time indicates Span position set routine. b.) Flashing 2 times indicates Transducer Self Calibration routine. c.) Flashing 3 times indicates Gain setting routine. 4. When the Green LED begins to flash the Calibration is completed. If the Red LED flashes this is an indication that one of the Calibration routines could not be completed. The number of Red LED flashes indicates the calibration routine that failed. Calibration Complete: ** Note: For split range enter desired input values during low & high calibration. 0/8/04 Tech-362/D.W.O. 645 Page 3 of 2

Advanced Functions The K0 has the ability to change the calibration settings (Gain, Zero, Span, and Drop-Off) manually. This function was intended to make minor changes in the calibration values after doing the Low and High calibration. Some examples where this might be used are decreasing the Gain if the valve still shows some overshoot on rapid position changes, or increasing the High Drop-Off point so it will not be in effect at 20mA. Exercise caution if using the manual calibration, mis-adjustment of these settings on the K0 positioner can result in erratic behavior or failure of operation, and may require resetting the EEPROM before auto-calibration can be performed again. To Do a Manual Calibration Adjustment: Before performing a Manual Calibration Adjustment the positioner needs to be calibrated as described previously.. Apply Input Current to the K0. 2. Start the Manual Calibration routine by pressing and holding the Function (center) button on the K0 until the Green and Yellow LED flashes. 3. Observe the flashing Green and Yellow LED on the K0 which denotes the various stages of the manual calibration routine, pressing the Function (center) button again advances to the next stage: a.) Flashing 2 time indicates Manual Gain adjustment. b.) Flashing 3 times indicates Low Drop-Off adjustment. c.) Flashing 4 times indicates Zero position adjustment. d.) Flashing 5 times indicates High Drop-Off adjustment. e.) Flashing 6 times indicates Span position adjustment. 4. To alter any characteristics of the positioner follow the following steps: a.) Manual gain Increase the positioner gain by pressing and holding the High Cal button. Decrease the Positioner gain by pressing and holding the Low Cal button. The maximum adjustment has been achieved when the red LED lights. b.) Low Drop-Off Increase the ma input signal that the positioner drops output port pressure by pressing the High Cal button. Decrease the ma input signal that the positioner drops output port pressure by pressing the Low Cal button. 0/8/04 Tech-362/D.W.O. 645 Page 4 of 2

c.) Zero position [To adjust the zero position to a point other than the hard stop of the valve the Low calibration of the positioner must have been performed at a current slightly lower than the zero position current. (Ex. If the zero position current is 4.0 ma the Low Calibration as described in the previous section needs to be performed at 3.9 ma.)] Increase the zero position by pressing and holding the High Cal button. Decrease the zero position by pressing and holding the Low Cal button. Continue to increase or decrease the zero position by repeatedly pressing and holding the buttons. d.) High Drop-off Decrease the ma input signal that the positioner drops output port 2 pressure by pressing and holding the Low Cal button. Increase the ma Input signal that the positioner drops output port 2 pressure by pressing the High Cal button. e.) Span Position [To adjust the span position to a point other than the hard stop of the valve the High calibration of the positioner must have been performed at a current slightly higher than the span position current. (Ex. If the span position current is 20.0 ma the High calibration as described in the previous section needs to be performed at 20. ma.)] Decrease the span position by pressing and holding the Low Cal button. Increase the span position by pressing the High Cal button. 5. The Input Current can be changed during the test to observe the adjustment effects on the K0 behavior. 6. To save the adjustments and exit the Manual Calibration Mode the Function (center) button must be held for approximately 5 seconds (green and yellow flashing LED s will change to flash just green when adjustments are saved) This procedure to save and exit can be performed from any stage during the Manual Calibration. 7. Pressing the Function (Center) button during the High Drop-Off adjustment exits the Manual Calibration Mode without saving any adjustments made. 0/8/04 Tech-362/D.W.O. 645 Page 5 of 2

Dip Switches Dip Switch # SW CCW CW Dip Switches shown in factory set positions Dip Switch #2 Dip switch # Off Position (Factory Setting) = Normal Acting (4 ma represents zero/fail position and 20 ma represents Span position). On Position = Reverse Acting (20 ma represents zero/fail position and 4 ma represents Span position). Dip switch #2 : NOT USED. Unit will operate with switch in either position. 0/8/04 Tech-362/D.W.O. 645 Page 6 of 2

Resetting the EEPROM Back to Factory Default Values The positioner has an internal Electrically Erasable Programmable Read Only Memory (EEPROM) that is used to store the calibration values. These values remain in the EEPROM memory even if power is removed from the positioner. During normal operation of the positioner the EEPROM will not have to be reset. The memory may become corrupted if power to the positioner is lost while the positioner is writing to the EEPROM. which only happens at the very end of the calibration cycle or at the end of the Position Sensor Initial Angle setup. This memory can be reset back to factory default values by holding down the HIgh Cal button while the positioner is being powered up. After the EEPROM is reset, the positioner will have to be calibrated again. Reversing the 4mA and 20mA Positions (Reverse Acting) Normally 4mA of input current represents the closed valve position and 20mA represents the open valve position. The positioner has the option to switch this so 20mA represents the closed valve position and 4mA represents the open valve position. The normal mode is chosen by setting the positioner DIP Switch position (the one closest to the LED s) to the OFF position (toward the LED s). The reverse acting mode is chosen by setting the positioner DIP switch position to the ON position (away from the LED s). The positioner should be calibrated again any time the switch position is changed. 0/8/04 Tech-362/D.W.O. 645 Page 7 of 2

Setting the Switches. Operate the actuator to one extreme. Choose the switch you would like to signal this position (upper or lower switch). Disengage the appropriate switch cam from the spline by pushing or pulling against the spring (push down for the upper switch, lift up for the lower switch). 2. Turn the cam until the switch is activated. Activation of the switch can be monitored using a continuity tester or equivalent means. 3. Release the cam allowing it to re-engage with the spline. 4. Operate the actuator to the opposite extreme and repeat steps through 3 for the other switch. TOP CAM PUSH DOWN TURN & RELEASE BOTTOM CAM LIFT UP TURN & RELEASE Wiring Schematic SWITCH # UPPER NC SWITCH #2 LOWER NO NC NO C C BROWN PURPLE YELLOW ORANGE BLUE RED 2 3 4 5 6 GND 0/8/04 Tech-362/D.W.O. 645 Page 8 of 2

Parts List K0 Parts Description Item # Qty Description Housing Ass y 2 Shaft Ass y 3 Electronic Ass y 7 4 5 Transmitter (optional) Manifold Ass y 6 Motor Ass y 6 SW CCW CW 2 7 Connector Board Ass y 8 Mechanical Switch Ass y (optional) 3 5 4 * 8 Optional Mechanical Switch Assembly * Void FM approval as Non-Incendive when ordered with 2-SPDT switch option. K0 product with optional switches is for use in general purpose applications only. 0/8/04 Tech-362/D.W.O. 645 Page 9 of 2

Technical Data Operating Specifications Input Current Voltage Drop Supply Air Pressure Resolution Linearity Hysteresis Repeatability Thermal Coefficient Output Flow Rates Air Consumption Operating Temp. Range Gain Air Connection Ports 4 to 20 ma (Analog) 9 volts (low) 5 to 45 psi (high) 40 to 20 psi 0.5% of span ±% of span 0.4% of span 0.4% of span 3%/00 C 8.0 scfm @ 25 psi (226.5 liter/min) 6.2 scfm @ 90 psi (458.7 liter/min).003 scfm @ 25 psi (.08 liter/min).008 scfm @ 90 psi (.23 liter/min) -40 C to 85 C (-40 F to 85 F) Electrically Adjustable /4 NPT Materials of Construction Area Classification & Approvals * Housing Cover Shaft Fasteners HiVue Manifold ModMount V3 Mechanical Switches Electrical Version Electrical Rating Engineered Resin (Nylon) Clear Engineered Resin (Nylon) Stainless Steel Stainless Steel Copolyester Anodized Aluminum Engineered Resin (Nylon) SPDT form C 5 Amps @ 25/250 VAC 0 Amps @ 24 VDC 0.5 Amps @ 25 VDC 0.25 Amps @ 250 VDC * FM APPROVED Enclosure Conduit Entries * Non-Incendive Class I, Div 2 Grps A,B,C,D Class II, Div 2 Grps F,G Class III, Div 2 x 3/4 NPT * Void FM approval as Non-Incendive when ordered with 2-SPDT switch option. K0 product with optional switches is for use in general purpose applications only. 0/8/04 Tech-362/D.W.O. 645 Page 0 of 2

Dimensions K0 POSITIONER 5.40 [37] 3/4" NPT 3.96 [0] 2.3 [59].38 [35] SQU.69 [8] 2.7 [69] 5/6-8 UNC TAP x.30 [8] DP, 4 PLC S 2.7 [69] CLOSED BEACON CLOSED M6 x TAP x.30 [8] DP, 4 PLC S.3 [29] 5.40 [37] 7.67 [95].69 [8].3 [29] 3.09 [78] 2.25 [57] SQU A 5.0 [27] A BOTTOM VIEW (VIEW SHOWN W/OUT MANIFOLD) 2.34 [59] DIA 2.94 [75].44 [] 4 PLC S.350 [8.9] 6.59 [67] CLOSED.39 [35] (OPPOSITE SIDE).25 [6] SUPPLY OUT.248 +.000 -.002 [ 6 +0.0-0.] FLAT.375 [0] DIA OUT 2.5 [4].56 [4].74 [44.2].30 [33].375 DIA [9.5 DIA] OPTIONAL NAMUR SHAFT.57 [3.9] +.000.57 -.002 FLAT [3.9 +.00 ] -.05 3.57 [9] /4" NPT OR /4" BSP 3 PLC S 2.8 [55].49 [38].24 [3].93 [24] SUPPLY OUT OUT 2.60 [5] 2.9 [56] Inches [mm] 3.29 [84] VIEW A-A (VIEW SHOWN W/OUT UNIT) 0/8/04 Tech-362/D.W.O. 645 Page of 2

Appendix A Electro-Pneumatic Positioner Transmitter Calibration Procedure. Calibrate the Positioner per the operating manual provided with the product. 2. Stroke the valve to the fully clockwise extreme. 3. Depress the main shaft gear disengaging it from its locking position, take extreme care Not to Turn the main shaft gear, as this will take the positioner out of calibration. 4. With the main shaft gear depressed turn the transmitter gear to the fully counter clockwise position, and note the reading (ma) of the transmitter. Next, turn the transmitter gear clockwise until the transmitter changes no more then 0.5 ma from previous reading. 5. Turn the clockwise ma adjustment screw to adjust the transmitter reading to the desired output for this valve position (typically this is 4 ma or 20 ma). 6. Stroke the valve to the fully counter clockwise extreme. 7. Turn the counter clockwise ma adjustment screw to adjust the transmitter reading to the desired output for this valve position. 8. Stroke the valve between the full clockwise and counter-clockwise positions checking and readjusting the (ma) output as necessary. Main Shaft SW CCW CW Main Shaft Gear CW ma Adjustment Screw for clockwise position { Transmitter Output Terminals & 2 (Not Polarity Dependent) CCW Transmitter Gear ma Adjustment Screw for counterclockwise position 0/8/04 Tech-362/D.W.O. 645 Page 2 of 2