Model ESV Uninterruptible Power System 1.5 KVA/KW KVA/KW Single Phase

Similar documents
EON Model EL3 Three Phase Centralized Emergency Lighting Inverter. General Specification 10KW 33KW Systems

EON Model EL3 Three Phase Centralized Emergency Lighting Inverter. General Specification 40KW 55KW Systems

Fortress 1 Outdoor Emergency Central Lighting Inverter (CLI) Technical Specifications

Illuminator Series CR NEMA 3R

Power Lynx 3 Uninterruptible Power System (UPS) Technical Specifications

Cobra 3 Stand-By Emergency Central Lighting Inverter (CLI) Technical Specifications

Defender Mini Online Emergency Central Lighting Inverter (CLI) Technical Specifications

Illuminator Series CM. GUIDE SPECIFICATIONS And TECHNICAL DESCRIPTION. 500W, 1000W, 1500W and 2000W Single-Phase Emergency Power System

Fortress 3 Harsh. Harsh Environment. Emergency Central Lighting Inverter (CLI) Technical Specifications

Model ES VA to VA SINGLE PHASE UNINTERRUPTIBLE POWER SYSTEM

APC Smart-UPS. GUIDE SPECIFICATIONS FOR 1000VA & 2000VA Smart-UPS 230VAC Uninterruptible Power Supply

TECHNICAL SPECIFICATION FOR A 10 TO 50 KVA THREE PHASE, UNINTERRUPTIBLE POWER SYSTEM WaveRider III

Technical data sheet VH UL. Digital Energy Uninterruptible Power Supply. GE Digital Energy Power Quality

MINUTEMAN UPS Endeavor Series Product Specifications 5,000VA 10,000VA Single-Phase Uninterruptible Power Supply 1.0 GENERAL

n Lower energy costs and carbon footprint n Cooler operation extends internal component life n High input power factor of 0.99

Aurora Single Phase Emergency Lighting Inverters

3. MAJOR SYSTEM COMPONENTS Emergency Lighting Power System shall consist of the following major subsystems:

Special Specification 6058 Battery Back-Up System for Signal Cabinets

Liebert GXT & 10000VA RT208 Rack-Tower models, Dual Inverter GUIDE SPECIFICATIONS 1.0 GENERAL

DPP/3DPP. Digital ProcessPower UPS INDUSTRIAL PWM UNINTERRUPTIBLE POWER SUPPLY SYSTEM SINGLE PHASE THREE PHASE

Product Specifications

TOSHIBA G , 750kVA

MINUTEMAN POWER TECHNOLOGIES Endeavor LCD Series Product Specifications 1000VA 3000VA Single-phase Uninterruptible Power Supply 1.

MKN-DSP SERIES - THREE PHASE

SmartOnline SUT Series 3-Phase 208/120V 220/127V 30kVA 30kW On-Line Double- Conversion UPS, Tower, Extended Run, SNMP Option

Liebert GXT & 6000VA RT230 Rack-Tower models GUIDE SPECIFICATIONS 1.0 GENERAL

SmartOnline SUT Series 3-Phase 208/120V 220/127V 20kVA 20kW On-Line Double- Conversion UPS, Tower, Extended Run, SNMP Option

APC Smart-UPS RT. GUIDE SPECIFICATIONS FOR 2400VA and 3000VA Smart-UPS RT 100 and 120VAC Uninterruptible Power Supply

Liebert GXT VA RT230 Rack-Tower model GUIDE SPECIFICATIONS 1.0 GENERAL

SmartOnline SVTX Series 3-Phase 380/400/415V 20kVA 18kW On-Line Double-Conversion UPS, Tower, Extended Run, SNMP Option

n Lower energy costs and carbon footprint n Cooler operation extends internal component life n High input power factor of 0.99

TLE Series UPS 400/500 kw With eboost Technology

GUIDE SPECIFICATIONS 15-45kVA and 15-90kVA Scalable Three-Phase Uninterruptible Power System 1.0 GENERAL

G V Series UNINTERRUPTIBLE POWER SYSTEMS. Phone: Fax: Web:

TLE Series UPS 160/200/225/250 kw with eboost Technology

Technical Data Sheets

TOWER MAXI T SINGLE CONVERSION ON LINE UPS SYSTEMS

EMEX. Central Battery Systems Emergency Lighting

SECTION DC POWER SUPPLY/BATTERY CHARGER

POWER WAVE 1 SINGLE-PHASE, (3 TO 20 KVA) & (3 TO 17 KW) UL924 CENTRAL LIGHTING INVERTER

Crucial Power Products

Series. On-line, Single-phase Parallel Redundant UPS System. 6 and 10 kva Rack Mount. Your Tailored Power Solutions Provider TM

.3 Section Waste Management and Disposal.

TLE Series UPS 750/1000 kw With eboost Technology

gimagination at work Technical data sheet Uninterruptible Power Supply LP Series 6 & 10 kva GE Digital Energy

POWER+ PREMIUM CBS. BS-EN Emergency electrical installations Electric power systems Emergency lighting Escape lighting

SmartOnline S3MX Series 3-Phase 380/400/415V 60kVA 54kW On-Line Double-Conversion UPS

Sola/Hevi-Duty S3K Series Mini-Tower UPS

STATIC UNINTERRUPTIBLE POWER SUPPLY GUIDE SPECIFICATION Eaton 93PM kw UPS

TECHNICAL DATA SHEET KVA UPS Systemss

Technical data sheets

Liebert GXT & 10000VA RT208 Rack-Tower models, Dual Inverter GUIDE SPECIFICATIONS

AT EVO SERIES BATTERY CHARGER

Sola 3000 Guide Specifications

SmartOnline SUT Series 3-Phase 208/120V 220/127V 40kVA 40kW On-Line Double- Conversion UPS, Tower, Extended Run, SNMP Option

TECHNICAL GUIDE SPECIFICATIONS

G9000 UNINTERRUPTIBLE POWER SYSTEMS

Liebert GXT & 6000VA RT208 Rack-Tower models, Dual Inverter GUIDE SPECIFICATIONS 1.0 GENERAL

3 Uninterruptible Power Systems

ATevo SERIES BATTERY CHARGER

GLX. Series. 1kW to 16kW Central System

On-line, Single Phase, Double Conversion UPS

Series. Full Three Year Warranty. On-line, Single-phase Parallel Redundant UPS System. 6 and 10 kva Tower. Your Tailored Power Solutions Provider TM

G9000 UNINTERRUPTIBLE POWER SYSTEMS

SmartOnline 120V 2.2kVA 1.8kW Double-Conversion UPS, 2U, Extended Run, Network Card Slot, LCD, USB, DB9

Liebert PowerSure PSI UPS

Standard 1000VA, 2000VA & 3000VA Universal Tower/Rack Mount LB Extended Models 900VA, 1700VA & 2500VA

Technical Data Sheets

U N I T Y / Three-Phase Uninterruptible Power Systems UT380 and UT Hz

Specification Guide. for RMAX. Direct Replacement. AC Low Voltage. Power Circuit Breakers

AT30 SERIES BATTERY CHARGER

SECTION MOTOR CONTROL

Uninterruptible Power Systems

WARREN COUNTY, N.Y. M/E REFERENCE A. Submit manufacturer's product data on all motors and adjustable speed drives.

Phase Modular Finally the benefits of Modular ups are for all

Technical Data Sheets

Technical Data Sheets

SECTION [ ] [16611] SOLID STATE UNINTERRUPTIBLE POWER SUPPLY

EFFEKTA Power Supplies

D Series: UPS UPTO - 300KVA - Three / Three Phase

GUIDE SPECIFICATION THREE PHASE UNINTERRUPTIBLE POWER SUPPLY

Series 120/120VAC Universal Tower/Rack Mount

UPS Sentry HPS. power supply sources - isolation transformers and generators over less sophisticated power systems.

TOSHIBA /20/25/30/50kVA Internal Battery GUIDE SPECIFICATION THREE PHASE UNINTERRUPTIBLE POWER SUPPLY

GUIDE SPECIFICATION THREE PHASE UNINTERRUPTIBLE POWER SUPPLY

Three Phase UPS Systems Range: 10 to 500kVA

STATIC UNINTERRUPTIBLE POWER SUPPLY GUIDE SPECIFICATION Eaton 93PM kw 208V UPS

Technical data sheets

Marketing Management Team of Europe

Liebert APM UPS. For a 30 to 150 kva / kw (50 or 60Hz) Modular Digital Uninterruptible Power Supply (UPS) System. V nd February 2010

200 kva* Noise level (Generator online) Fuel tank size (approx. 5.5 hours autonomy) 1400 liters 308 gallons /370 US gallons

Technical Data Sheets

EVO AT SERIES BATTERY CHARGER

EVO SERIES BATTERY CHARGER SERIES BATTERY CHARGER

AIR COOLED RECTIFIER SPECIFICATION S-50-A

Technical Data Sheets

Electric Power Marketing Spec Sheet Continuous Power Module CPM250

USER S MANUAL CONTENTS. Uninterruptible Power Supply 1. INTRODUCTION SAFTY INSTRUCTION SYSTEM DESCRIPTION... 4

Onfiniti. 1 Phase UPS

AT SERIES EVO BATTERY CHARGER

Transcription:

Model ESV Uninterruptible Power System 1.5 KVA/KW - 14.0 KVA/KW Single Phase 1.0 General General Specification This specification describes the features and design of an on-line, dual conversion, uninterruptible power supply (UPS) system. The Model ESV UPS is designed to assure maximum reliability, serviceability and performance. The system incorporates a microprocessor-based, DSP controlled, input power factor corrected, high-frequency IGBT PWM rectifier/charger, together with an IGBT PWM inverter and high speed fail-safe SCR automatic bypass transfer circuit. These components and battery backup work to provide immunity from all line disturbances and power interruptions, with no loss or break in AC output power. The Model ESV has a vertical space-saving front access enclosure design to provide extended battery runtime, facilitate centralized UPS installation, and accommodate vertical overhead cable landings for server racks and other critical equipment. A self-diagnostic monitoring alarm system with optional network remote communications continuously advises of system status and battery condition. The UPS includes a manual bypass switch for maintenance and periodic battery replacement. 2.0 Inverter Ratings Model ESV1500 ESV2200 ESV3000 ESV3500 ESV4200 ESV5000 ESV6000 ESV7000 ESV7500 ESV8500 ESV10000 ESV12500 ESV13500 ESV14000 Rating 1.5KVA / KW 2.2 KVA / KW 3.0 KVA / KW 3.5 KVA / KW 4.2 KVA / KW 5.0 KVA / KW 6.0 KVA / KW 7.0 KVA / KW 7.5 KVA / KW 8.5 KVA / KW 10.0 KVA / KW 12.5 KVA / KW 13.5 KVA / KW 14.0 KVA / KW 3.0 Standards The systems are designed in accordance with applicable portions of the following standards: 3.1 American National Standards Institute (ANSI C57.110). 3.2 Institute of Electrical and Electronic Engineers (IEEE 519-1992) (C62.41-1991). 3.3 National Electrical Manufacturers Association (NEMA PE-1). 3.4 National Electric Code (NEC 2005, Article 700). 3.5 Underwriters Laboratories (UL) (C-UL to CSA Standards). 3.6 Federal Communications Commission (FCC Part 15, Sec. J, Class A). 3.7 Federal Aviation Administration (FAA-G 201e). 3.8 Listed UL Standards UL 1778 Uninterruptible Power Systems, C-UL listed to CSA C22.2, No. 107.1- M01. Page 1 of 8

4.0 Input Specifications 4.1 Input Voltage: 120 or 277 VAC - on models 1.5 KVA and 2.2 KVA 120, 208/120, 240/120, or 277 VAC - on models 3.0 KVA and 3.5 KVA 120, 208/120, 220, 240/120, 277, 347, 480, or 600 VAC - on models 4.2 KVA and 5.0 KVA 208/120, 220, 240/120, 277, 347, 480, or 600 VAC - on models 6.0 KVA through 14.0 KVA 4.2 Operating Range: +12% to -15% without battery usage. 4.3 The unit incorporates the use of variable range logic in conjunction with the load percentage to extend the input range to +12% to -30% without battery usage while maintaining a regulated, usable output voltage. 4.4 Frequency Range: 57.5 Hz. to 62.5 Hz. 4.5 Power Factor: Self-correcting to >0.97 (approaching unity). 5.0 Output Specifications 5.1 Output Voltage: 120 VAC - on models 1.5 KVA and 2.2 KVA 120, 208/120, or 240/120 VAC - on models 3.0 KVA and 3.5 KVA 120, 208/120, 220/127, or 240/120 VAC - on models 4.2 KVA through 14.0 KVA 5.2 Sine Wave Voltage Output: Maximum 3% THD under linear load. 5.3 Output frequency: 60Hz, plus or minus 0.5 % under full range load while in the battery operation mode. 5.4 Harmonic Attenuation: Reflected load generated harmonics are attenuated at the input. 5.5 Overload Rating: 105% continuous, 125% for 10 seconds, and 1000% for 3 cycles when fed from AC power source on models 1.5 KVA/KW through 3.5 KVA/KW. 125% for 2 minutes, 150% for 30 seconds and 200% for 15 cycles when fed from AC power source on models 4.2 KVA/KW through 14.0 KVA/KW. 5.6 On Battery Overload Rating: 125% for 30 cycles, 150% for 3 cycles. 5.7 Voltage Regulation: ±2%. 6.0 Battery Specifications 6.1 Battery Time: Runtime is at full rated kilowatt output, and determined by the battery option selected. 6.2 Battery Type: Valve regulated, sealed lead calcium, maintenance free batteries. 6.3 Charger: Four stage, temperature compensated, 1% ripple filtered. 700 watts on models 1.5 KVA/KW through 5.0 KVA/KW, or 1400 watts on models 6.0 KVA/KW through 14.0 KVA/KW 6.4 DC Bus voltage: 120 VDC. Page 2 of 8

7.0 Performance 7.1 Normal Operation: The load is supplied with regulated power derived from the normal AC power input terminals through the rectifier charger and inverter. The rectifier charger is fully rated to charge the batteries and supply sufficient DC energy for the inverter when under full load. The battery is connected in parallel with the rectifier charger output. 7.2 Uninterrupted Emergency Operation: Upon the failure or unacceptable deviation of commercial AC power, energy will be supplied by the battery through the inverter and continue to supply power to the load without switching loss or disturbance. When power is restored at the AC input terminals of the system, the rectifier charger continues to supply power to the load through the inverter and simultaneously recharges the batteries. 7.3 Automatic Bypass Operation: The system includes a high speed automatic static bypass for fault clearing, instantaneous overload conditions and/or to connect the load to the normal utility source in the event of a system rectifier charger or inverter failure. 7.4 Secure Internal Maintenance Bypass / Isolation Switch: The system includes an integral, make-beforebreak maintenance bypass switch accessible via the front of the UPS enclosure through a hinged, key lockable door. The switch incorporates a push-to-turn function. Pushing the maintenance switch will invoke the static bypass prior to completing the switch transition to bypass. When in the bypass position, the maintenance bypass switch will provide complete isolation of the UPS output from external circuits. When the load is supplied from the normal AC input power source through the maintenance bypass switch, the AC input supply terminals will remain energized to permit UPS operational checking. A maintenance circuit breaker is provided as means of disconnecting the AC input source from the rectifier charger and inverter, allowing complete maintenance and replacement of circuit cards or components without disrupting power to the load. The maintenance circuit breaker provides the ability to turn the AC input power source off and on again to the rectifier charger and inverter to facilitate on-site trouble shooting while the UPS output remains isolated from the load. With the rectifier charger and inverter energized, the UPS system may be returned to normal mode operation by placing the secure maintenance bypass switch in its normal position via the push to turn function, without disrupting power to the load. This internal method of bypass maintains the UPS s input output voltage configuration. 7.5 Optional Break-Before-Make External Maintenance Bypass: On UPS systems where the nominal input and output voltages are the same and output distribution breakers are external from the UPS enclosure, an external, wall mounted, push to turn, break before make, wrap around maintenance bypass switch is available for field installation. When in bypass mode, the switch will bypass the UPS system and feed the load power directly from the AC input power source. The UPS system s main input breaker may then be opened, allowing the UPS to be fully serviced, including the complete maintenance and replacement of circuit cards or components. The bypass switch includes an auxiliary contact to indicate the position of the switch (normal or bypass) for remote monitoring purposes. The bypass switch is provided with a padlock attachment for lockout purposes during maintenance. 7.6 Optional Make-Before-Break External Maintenance Bypass: On UPS systems where the nominal input and output voltages are the same and output distribution breakers are external from the UPS enclosure, an external, wall mounted, push to turn, make before break, wrap around maintenance bypass switch is available for field installation. When in bypass mode, the switch will bypass the UPS system and feed the load power directly from the AC input power source. The UPS system s main input breaker may then be opened, allowing the UPS to be fully serviced, including the complete maintenance and replacement of circuit cards or components. The bypass switch includes an auxiliary contact to indicate the position of the switch (normal or bypass) for remote monitoring purposes. A second auxiliary contact must be wired to the inverter and will invoke the system s static bypass before the switch is turned to the bypass position. The bypass switch is provided with a padlock attachment for lockout purposes during maintenance. Page 3 of 8

8.0 Environmental Specifications 8.1 Operating Temperature: 0 C (32 F) to 40 C (104 F). 8.2 Storage Temperature: -20 C to 50 C. 8.3 Relative Humidity: 95% non-condensing. 8.4 Elevation: 5,000 feet, 1,500 meters without de-rating. 8.5 Audible Noise Level: Not greater than 50 dba at 1 meter. 9.0 Enclosure Specifications 9.1 Description: Floor-mounted, NEMA 1 vertical front access cabinet with top-side conductor cable landings to facilitate centralized installation for server racks and/or other critical equipment. 9.2 Construction: The top and all sides of the enclosure are constructed from 14 gauge steel, and the base is constructed from 12 gauge steel. The enclosure steel is pre-treated and finished with a powder-coat paint to resist corrosion, marring or scratching. 9.3 Access: A hinged, key lockable front door is provided for access to all components and batteries. Side and back access are not required for system installation, operation, or service. 9.4 Breakers Location: A hinged, key lockable breaker panel door is provided for access to input and output circuit breakers. 9.5 Color: Graphite 10.0 Standard Display Monitor and Diagnostics 10.1 Display Panel System includes a local, front mounted, sealed, LED display panel to indicate system status and battery condition. Display automatically monitors input voltage normal, input voltage high, input voltage low, on bypass, % load, battery in use, battery full, battery low and check battery. 10.2 Automatic Self-Testing System provides a 30 second automatic battery test programmable for every 7, 30, or 90 days. 10.3 Manual Battery Testing System provides a push to test feature in the event that a manual battery test is required. 10.4 Audible Alarm The display panel includes an audible alarm with alarm silence for system on battery, low battery, check battery, over temperature warning, system fault, and inverter overloaded. 10.5 Control Functions The display panel includes a push button for UPS on, fail safe dual push buttons for UPS off, alarm silence push button, and push button for system battery testing. 10.6 Electrical Measurements (RS232) Electrical measurements include: Input voltage, output voltage, output current, output watts, output volt amperes, % load, battery voltage and DC charging current, and output frequency. Page 4 of 8

10.7 System Set Points (RS232) Systems include a provision to program the following via computer interface: The percentage point at which the display panel indicates the low battery alarm, sag point at which battery usage is to occur, surge point at which battery usage is to occur, and points at which automatic battery tests are to be performed (7 day intervals, 30 day intervals, or 90 day intervals). 10.8 System Log (RS232) Systems also include provisions to log power outages with date and time and system overloads with date and time. 11.0 Remote Communications 11.1 Communications Port (RS232) A communications port for remote monitoring access to electrical measurements, system set point programming and the system s log is furnished for computer interface. The communications port features Status / Alarm relay interface normally open contacts rated at 30VDC 2A. Contacts are provided for optional remote annunciator panel, automatic message dialer or TCP/IP adapter. Available contacts are: On Battery, Low Battery, Battery Test Activated, and General Alarm. 11.2 Relay Contact Terminal Strip Systems include a terminal strip with potential free, 500mA, 120 volt rated, relay contacts for system alarm monitoring. 11.2.1 The following normally open relay contact alarms are available via the terminal strip: On Battery, Low Battery, and General Alarm. 11.2.2 The following normally closed relay contact alarm is available via the terminal strip: Battery Test Active. 12.0 Optional Intellistat Monitor 12.1 Intellistat Monitor Panel Systems include a local, front mounted, sealed, touch screen, LCD display monitor panel with battery back-up memory. The Intellistat displays electrical parameters, system status and alarm conditions. 12.1.1 The monitor displays the following electrical parameters: Input Voltage Output Voltage Output Current Output Volt-Amperes Output Watts Output Power Factor Output Percent Load Output Frequency Battery Voltage Battery Charge Current 12.1.2 The monitor displays the following system status / alarm conditions: Input Voltage High/Low Output Voltage High/Low Output Volt-Amperes High - Overloaded Output Volt-Amperes Low Output Frequency High/Low Battery Voltage High/Low Battery Charger Current High General Alarm Page 5 of 8

System on Battery Low Battery Warning Low Battery Shutdown DC Charger Failure / DC Open Inverter Over-temperature Warning Output Circuit Breaker Open REPO Shutdown System in Manual Bypass System in Static Bypass Battery Test Pass Battery Test Fail 12.1.3 The monitor displays the following operational conditions: System Normal Percent Battery Time Remaining Battery Test In Process 12.2 The monitor incorporates into its design, user programmable set points for the following: Status and Alarm Conditions User Programmable for all High/Low thresholds alarm set points. Automatic Testing User Programmable frequency of occurrence. 12.3 The monitor maintains a log that records all system alarms, events and battery system test results. The logs are made available through the LCD display of the monitor. The system log capacity is: Event and Alarm Log: 25 Alarms Battery System Test Log: 25 Battery Tests 12.4 The monitor features a manual, proprietary, password protected Push to Test feature. 12.5 The monitor features automatic battery testing that records test data: 12.5.1 It features a 30 second automatic battery test programmable for every 7, 30, or 90 days. 12.5.2 It reports the Time, Date, and a Pass/Fail indication via the local monitor panel and/or via E-mail, SNMP, MODBUS, BACnet, or Ethernet TCP/IP with an optional network adapter. This information is also available via fax, voice messaging and or web page generation via an optional multifunction communications modem. 12.6 The monitoring system includes a 9 pin status / alarm port and a terminal strip with potential free, 500mA, 120 volt rated contacts. 12.6.1 Alarms monitored from the Intellistat status/alarm port: On Battery Low Battery General Alarm System On Bypass 12.6.2 Status / Alarm port contact ratings: 24 VAC and/or 24 VDC, 500 ma. Page 6 of 8

12.6.3 The following alarms are monitored from the Intellistat terminal strip: On Battery Low Battery General Alarm System On Bypass Battery Test Pass Battery Test Fail 13.0 Reliability 13.1 MTBF Electronic / Electrical System: 100,000 hours. 13.2 MTTR: One hour. 14.0 Standard Equipment 14.1 Terminals for hard wired input and output. 14.2 Normally on, uninterrupted A.C. output bus. 14.3 Single control module design. 14.4 Static bypass switch. 14.5 Make before break secure bypass switch. 14.6 Front mounted diagnostic monitor panel. 14.7 Batteries. 14.8 Thermal magnetic A.C. input circuit breaker. 14.9 D.C. battery fuse and Anderson connector with interconnect cable. 14.10 Output distribution circuit breaker panel. 14.11 Copper conductor construction. 14.12 Functional steel cabinet enclosure with hinged, removable, lockable front door. 14.13 Graphite color powder coat finish. 15.0 Optional Equipment 15.1 Pre-installed, 20 amp output circuit breakers (Maximum of 20 pole positions.) 15.2 System output circuit breaker open or tripped alarm contacts. (Adds a pole position to each breaker.) 15.3 Automatic message dialer. 15.4 Remote annunciator panel. Page 7 of 8

15.5 Fax/Voice/Web multifunction communications modem. 15.6 Network device SNMP / Ethernet TCP/IP / MODBUS TCP adapter. 15.7 Network device MODBUS RS485 adapter. 15.8 Network device BACnet/IP or BACnet MS/TP adapter. 16.0 Warranty 16.1 All power components and system electronics are guaranteed to be free from defects in material and workmanship for a period of 2 years following shipment from the factory. 16.2 Batteries are warranted with a 2-year full replacement warranty, and an optional 3-year pro-rate with applicable maintenance contract. On site labor for warranty repair in the United States and Canada is covered for 90 days following shipment from the factory. 16.3 Extended warranty and maintenance contracts are available. 17.0 Serviceability Each UPS contains one front-accessible electronics module subassembly. Batteries are positioned and wired to facilitate rapid replacement. Page 8 of 8