Bray/ VAAS Slurry Series Knife Gate Valve 760/762/765/766/767/768 Series Operation and Maintenance Manual

Similar documents
SERIES 90/91 R PNEUMATIC ACTUATOR OPERATION AND MAINTENANCE MANUAL. The High Performance Company

Bray/McCannalok High Performance Butterfly Valve Operation and Maintenance Manual

McCannalok HIGH PERFORMANCE BUTTERFLY VALVE OPERATION AND MAINTENANCE MANUAL. The High Performance Company

Series 70 24V On/Off Electric Actuator Operation and Maintenance Manual

YOUR GLOBAL FLOW CONTROL PARTNER. BRAY/MCCANNALOK EN High Performance Butterfly Valve Operation and Maintenance Manual

PFA LINED BALL VALVES Installation, Operation and Maintenance Manual

Your Global Flow Control Partner. Series 70 24V On/Off Electric Actuator Operation and Maintenance Manual

SERIES 73 ELECTRIC ACTUATOR OPERATION AND MAINTENANCE MANUAL. The High Performance Company

INSTALLATION - MAINTENANCE MANUAL Severe Service Series M4 Ball Valve

GT-200 GATE VALVES PN16, Screwed end

Bray/Mckannalok Butterfly Valve Series 40/41/42/43/44/45 Installation Manual Technical Bulletin No Date: May 2004/Page 1 of 6

MK Series - High Performance Butterfly Valves Operation and Maintenance Instructions

KEYSTONE. Butterfly valves Figure 9 Installation & Maintenance Instructions. Please read these instructions carefully

Installation, Operation, and Maintenance Manual

Standard Valves Series Globe Valves Series Angle Valves Series Way-Valves

KEYSTONE SERIES 320 BUTTERFLY VALVES INSTALLATION AND MAINTENANCE INSTRUCTIONS

Your Global Flow Control Partner. Series 92/93 Pneumatic Actuators. Technical Manual

Butterfly valves Figure 56 Installation & Maintenance Instructions

ONYX VALVE CO MODEL CAR, CAP-PFO Installation & Maintenance

DeZURIK " BAW AWWA BUTTERFLY VALVES WITH EPOXY-RETAINED SEAT

Keystone Butterfly valves ParaSeal Installation and maintenance instructions

EC4 SERIES CRYOGENIC VALVES 1/4 2 Sizes

Installation, Operation, and Maintenance Manual Full Port Y-Pattern, Bolted Bonnet, Globe and Check Valves

Operation and Maintenance Instructions for Bettis GVO-C Series GVO-CLP-SR Pneumatic Actuators

INSTRUCTION MANUAL. for BUTTERFLY VALVES

I-795/906. Series 795 and 906 Installation-Ready Knife Gate Valves WARNING INSTALLATION AND MAINTENANCE INSTRUCTIONS

PNEUMATIC SLIDING VALVE

NYL Resilient Seated Butterfly Valves Operation and Maintenance Instructions

HYDRAULIC PUMP. INSTALLATION, OPERATION, & MAINTENANCE MANUAL MAINTENANCE MANUAL #: MM-HP Rev. A Page 1 of 12

INTERNAL CHEMICAL HYDRAULIC VALVE

HIGH PRESSURE CONTROL VALVE PISTON BALANCED

ACHL Series Pump. Operation and Maintenance Manual Air Driven, Hand Operated High Pressure Liquid Pump

2001 SERIES CRYOGENIC BAR STOCK BODY VALVES

MERIDIAN, 2 or 3 PIECE, TRUNNION MOUNTED BALL VALVES

ONYX VALVE CO MODEL DAO-PFO Installation & Maintenance

USER INSTRUCTIONS. Kämmer SmallFlow / / SP Low and Micro Flow Valves. Installation Operation Maintenance

ONYX VALVE CO MODEL DAC-PFO Installation & Maintenance

QUICK CLEAN CHEMICAL HYDRAULIC VALVES

USER INSTRUCTIONS. Kämmer SmallFlow - Series / Low and Micro Flow Valves. Installation Operation Maintenance. Experience In Motion

Installation and operating manual Quick closing valve (Bellow sealed) LK product no:

DO NOT INSTALL, OPERATE, OR MAINTAIN AN ATI PRODUCT UNLESS TRAINED AND QUALIFIED IN PRODUCT AND ACCESSORY INSTALLATION, OPERATION AND MAINTENANCE.

ONYX VALVE CO MODEL DAO-ADA Installation & Maintenance

ONYX VALVE CO MODEL DAO-PFC Installation & Maintenance

Installation and Operation Manual

Model DF233 Control Valve

Operating & Maintenance Manual For Steam Conditioning Valve

OpTK. Product Instruction Manual. Spring Cylinder Rotary Actuators INTRODUCTION SAFETY INFORMATION INSTALLATION. Leading Technologies For Control

Fisher 657 Diaphragm Actuator Sizes and 87

IOM Manual. IOM Manual. Series 76/77.

John Crane Type 5620 and 5620PR Dual O-Ring Cartridge Seal Assembly and Installation Instructions

Valtek Spring Cylinder Linear Actuators

Double Acting & Spring Return. SERIES 92/93 Rack & Pinion PNEUMATIC ACTUATOR. The High Performance Company

Keystone Series GR resilient seated butterfly valves GRW/GRL Installation and operation manual

Series 820 AWWA Butterfly Valves

Installation, Operation, and Maintenance Manual

Railroad Ball Valves Series 5REB3

Installation, Operation, and Maintenance Instructions for Bettis RGS F-Series Spring-Return (SR) Actuators

Binks MODELS & AGITATOR DRIVE UNITS

Installation, Operation and Maintenance Manual RGS Rev. 0 November Bettis RGS F-Series Spring-Return Actuators

ONYX VALVE CO MODEL CER with JORDAN ACTUATOR Installation & Maintenance

OPERATING AND MAINTENANCE MANUAL

Sentinel 250 Fire Hydrant

PRESSURE REGULATOR BACK PRESSURE TO ATMOSPHERE WITH OUTSIDE SUPPLY

VSI, LLC SERIES 2100 RESILIENT SEATED BUTTERFLY VALVES INSTALLATION, OPERATION AND MAINTENANCE MANUAL

Mounting and Operating Instructions EB 8053 EN. Series 250 Type and Type Pneumatic Control Valves

Valtek VL-HC Spring Cylinder Linear Actuators

Installation, Operation and Maintenance Manual

LOW PRESSURE BALANCED VALVE DIAPHRAGM BALANCED

KENNEDY VALVE RESILIENT WEDGE GATE VALVE MAINTENANCE MANUAL

Baumann 24000C Carbon Steel Little Scotty Control Valve Instructions

Model DF269 Control Valve

Scope. Applicability. Caution. I & M CV3000 Series. Storage. Installation & Maintenance Instructions for Marwin CV3000 Series Three Piece Ball Valves

INSTRUCTION MANUAL. Anchor Darling 1878 Swing Check Valves. Installation Operation Maintenance. Sizes 1/2 through 2 FCD ADENIM

DeZURIK KGC-MD KNIFE GATE VALVES

METERING VALVE 2" STEM GUIDED

KENNEDY VALVE Plant and Industrial Group 1021 East Water Street Elmira, New York Telephone (607) Fax (607)

KEYSTONE SERIES GRF RESILIENT SEATED BUTTERFLY VALVES INSTALLATION AND OPERATION MANUAL

Brake System H TX, H2.0TXS [B475]; H TX [B466] Safety Precautions Maintenance and Repair

INSTALLATION, OPERATION, MAINTENANCE MANUAL FOR MANUALLY OPERATED STOP CHECK VALVE

KEYSTONE. Check valves Figure 85/86 Installation & Maintenance Instructions. Figure 85. Figure 86.

LNG Screw Down Non-Return Valve Installation, Operation and Maintenance Manual

OPERATING INSTRUCTIONS & SERVICE MANUAL BLUE MAX II HYDROSTATIC TEST PUMP

Mounting and Operating Instructions EB 8097 EN. Type and Type Pneumatic Control Valves

SERIES PC INSTRUCTION AND OPERATION MANUAL

Instruction Manual & Parts List For H/G323FXFSX-500_ & 800_ Pumps With Flowserve Type BX Cartridge Seal

KEYSTONE OPTISEAL F14/16-15/17 AND BREWSEAL BUTTERFLY VALVES INSTALLATION AND MAINTENANCE INSTRUCTIONS

Baumann Little Scotty Bronze Control Valve

Installation, Operation, and Maintenance Manual

ONYX VALVE CO MODEL DAC-ADA Installation & Maintenance

Split Body Valves with Bellows Seal Series Globe Valves Series Angle Valves Series Way-Valves

Keystone Figure 85/86 Check valves Installation and Maintenance Instructions

FWS1 and FWS2 Series Fifth Wheels

ASSEMBLY INSTRUCTIONS

WARNING Carefully Read These Instructions Before Use

ONYX VALVE CO MODEL CER and CEP Installation & Maintenance

INSTRUCTION MANUAL IM-422 For HTC/COUPLING ASSEMBLY HC-8088

DeZURIK KUL KNIFE GATE VALVES

MGM Brakes Service Manual

SERIES CLASS 300 FULL-BORE REACTOR DISCHARGE VALVES. Installation, Maintenance and Operating Instructions

Mounting and Operating Instructions EB 8135/8136 EN. Series V2001 Valves Type 3535 Three-way Valve for Heat Transfer Oil

Transcription:

Bray/ VAAS Knife Gate Valve 760/762/765/766/767/768 Series

Table of Contents Definition of Terms 1 Safety Instructions 1 Introduction 2 Unpacking 2 Storage 2 Installation 3 Commissioning 3 Cylinder-Operated Valves 3 Manual Valves 3 Valve Maintenance 4 Lubrication 4 Secondary Seal Replacement 4 Manual Valves 5 Cylinder-Operated Valves 5 Stroke Length Tables 6 Seat Replacement (Series 760, 762, and 767) 7 Seat Replacement (No Retainer - Series 765, 766 & 768) 8 Actuator Maintenance 8 Spare Parts 9 Troubleshooting 9 For information on this product and other Bray products please visit us at our web page - www.bray.com.

Definition of Terms - Safety Instructions READ AND FOLLOW THESE INSTRUCTIONS SAVE THESE INSTRUCTIONS DEFINITION OF TERMS Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury. Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. NOTICE Used without the safety alert symbol indicates a potential situation which, if not avoided, may result in an undesirable result or state, including property damage. HAZARD-FREE USE This device left the factory in proper condition to be safely installed and operated in a hazard-free manner. The notes and warnings in this document must be observed by the user if this safe condition is to be maintained and hazard-free operation of the device assured. Take all necessary precautions to prevent damage to the valve due to rough handling, impact, or improper storage. Do not use abrasive compounds to clean the valve, or scrape metal surfaces with any objects. The control systems in which the valve is installed must have proper safeguards to prevent injury to personnel, or damage to equipment, should failure of system components occur. QUALIFIED PERSONNEL A qualified person in terms of this document is one who is familiar with the installation, commissioning, and operation of the device and who has appropriate qualifications, such as: Is trained in the operation and maintenance of electrical equipment and systems in accordance with established safety practices Is trained or authorized to energize, de-energize, ground, tag, and lock electrical circuits and equipment in accordance with established safety practices Is trained in the proper use and care of personal protective equipment (PPE) in accordance with established safety practices Is trained in first aid In cases where the device is installed in a potentially explosive (hazardous) location is trained in the commissioning, operation, and maintenance of equipment in hazardous locations 1

The valve must only be installed, commissioned, operated, and repaired by qualified personnel. The device generates a large mechanical force during normal operation. All installation, commissioning, operation, and maintenance must be performed under strict observation of all applicable codes, standards, and safety regulations. Observe all applicable safety regulations for valves installed in potentially explosive (hazardous) locations. INTRODUCTION The Bray/ VAAS Series 760/762/765/766/767/768 provides repeatable bidirectional shutoff in a rugged, cast body. Additional information about valves including application data, engineering specifications, and actuator selection is available from your Bray distributor or sales representative. UNPACKING Ensure the box is not damaged externally. Remove the valve from the packaging and check for any damage to the valve and its components during transit. Valve size and brief material specification of body (markings such as SS or DI ) are marked on the valve body. Stainless steel nameplate (below) fixed on to the yoke of valve contains most of the relevant information on the valve including Bray/ VAAS work order number and unique serial number of the valve. These details should be quoted for all requirements of service and spares. SERIAL NUMBER SIZE MODEL FLG. DRILL BODY GATE STORAGE SEAT PACKING CWP MAX TEMP Wrap the valve with a polyethylene cover. Cover the ports for pneumatic actuator/accessories with plastic caps. Store these valves in the same packing indoors and without direct exposure to the environment. If the valve is to be stored for a long period of time before installation, it should be stored in a vertical position (preferable) and in a cool, clean area to prevent damaging effects on the packing. Gate should be off the seat to prevent compression set. 2

INSTALLATION Valves can be mounted with flow in both directions. Install the valve between flanges using fasteners. Support should be used for valves size 8 and over when installed in vertical pipe. Failure to do so can result in improper valve operation and/or valve failure. COMMISSIONING GUIDELINES Cylinder Operated Valves 1. Connect instrument quality air, preferably through an air filter/regulator of adequate size. The recommended air pressure is 80-120 psi (5-8 bar). Refer to the appropriate bulletin/drawing for port and cylinder size details. 2. Ensure the supply air is free from moisture, dirt, and other foreign particles. Drain the filter regulator before operating the actuator so that pipe rust and dirt if any in the air line will be removed before actuation. 3. If valves are supplied with electrical accessories like limit switch and solenoid valve, ensure wiring is done as per local electrical safety codes and regulations. Ensure correct electrical supply is given to electrical accessories for proper functioning and safety of the equipment. 4. Open the valve by energizing the solenoid valve/giving air supply to cylinder and operate the valve 2-3 times. Manual valves Open/Close the valve manually and observe valve operation. Wrong electrical supply to accessories will damage the equipment. Do not over tighten the gland nuts as this may cause excessive friction and premature damage to packing. 3

MAINTENANCE NOTICE Any modification or use of unauthorized parts voids any and all warranty considerations. Lubrication The manual valve stem should be lubricated at regular intervals for smooth operation of the valve. A lubrication nipple is provided on the collar. Cylinder operated valves do not require routine lubrication. NOTICE If the cylinder actuator is disassembled for repair, the cylinder wall and seals need to be lubricated with a lithium-based grease prior to reassembly. Manual Valve Stem Cylinder Actuator Secondary Seal Replacement (Applicable to Series 765, 766, 767, and 768) 1. Relieve the line pressure. 2. Fully close the valve. 3. Ensure the line is empty, and flush if necessary. 4

Manual Valves 1. Disconnect the stem from the gate by removing the clevis bolt and nuts 2. Rotate the Hand wheel counter clockwise by holding the stem from rotation, so that stem retracts fully from the gate. 3. If valves are supplied with bellows, ensure stem is not rotating, as rotation will damage the bellows. 4. Remove the secondary seal retainer bolts (6). 5. Remove the seal retainer (5), wiper (4) (if applicable) and old sec ondary seal (3) from the packing chamber, using a long thin tool to pry it out. 6. Insert the new secondary seal (3) into the packing chamber. 7. Re-attach the wiper (4), if applicable, and secondary seal retainer (5) onto the valve body. 8. Tighten the secondary seal retainer bolts (6). 9. Lower the stem by rotating the hand wheel clockwise while holding the stem and fasten the stem to the gate with nuts & bolts. 10. Adjust the gate positions from top of the body according to the following tables. With Seal Retainer Cylinder-Operated Valves 1. Switch off the electrical supply to the solenoid and limit switches. 2. Remove the cylinder tubing and vent the air inside the cylinder. 3. Disconnect the piston rod from the gate by removing the clevis bolts & nuts. 4. Apply air slightly to the bottom port of the actuator so that the piston rod is retracted from the gate. 5. Remove the actuator assembly from the valve by removing the fasteners connecting the yokes to the valve body. 6. Remove the secondary seal retainer bolts (6). 7. Remove the seal retainer (5), wiper (4), if applicable and old sec ondary seal (3) from the packing chamber, using a long thin tool to pry it out. 8. Insert the new secondary seal (3) into the packing chamber. 9. Re-attach the wiper (4), if applicable, and secondary seal retainer (5) onto the valve body. 10. Tighten the secondary seal retainer bolts (6). 11. Mount the actuator and superstructure on the valve. 12. Connect the gate (2) and stem by clevis bolts and nuts 13. Apply air slightly for cylinder operated valves to lower the piston rod and fasten the gate. Without Seal Retainer 14. Adjust and ensure the gate positions from top of the body according to the following tables as appropriate. 5

Stroke Length Tables Series 760 Valve Size A (mm) B (mm) 50 38 126 80 36 149 100 37 175 125 41 221 150 49 247 200 38 283 250 48 352 300 47 414 350 67 483 400 55 498 450 65 571 500 77 642 600 74 772 B A Series 762 Valve Size A (mm) B (mm) 80 43 165 100 74 204 150 55 258 200 60 310 250 62 362 300 57 412 350 89 489 400 71 516 450 81 575 500 70 605 600 83 763 Series 765 & 766 Valve Size A (mm) B (mm) 50 41 117 80 41 149 100 41 180 125 41 210 150 42 232 200 44 289 250 47 350 300 53 414 350 65 475 400 62 522 450 54 587 500 61 632 600 90 810 6

Series 767 Valve Size A (mm) B (mm) 80 54 134 100 54 209 150 63 263 200 75 315 250 64 369 300 75 445 350 73 473 400 97 547 450 82 587 500 80 620 600 109 774 Series 768 Valve Size A (mm) B (mm) 50 32 112 80 32 151 100 37 181 125 44 219 150 48 250 200 50 310 250 52 355 300 50 425 350 48 448 400 68 528 450 54 587 500 61 632 600 90 810 Seat Replacement (Series 760, 762, and 767) Relieve line pressure before attempting to remove the valve from the line to avoid personnel injury and/or equipment damage. If the valve has a pneumatic actuator, solenoid valve, limit switches, or other accessories, disconnect the electrical and pneumatic supply. 1. Relieve the line pressure and close the valve. Flush the line if necessary. 2. Remove the valve from the line by loosening the flange mounting bolts, studs, and nuts. 3. Clamp the valve in the vertical position to a fixture. Do not block the valve port when clamping the valve. An overhead hoist may be needed for larger size valves. 4. Retract the gate to full open condition. 5. Remove the seat retainer screw (10) and remove the seat retainer (9). 6. Remove the seats (8) from the valve. 7. Verify that the circular bore is clear of all debris, scale, and elastomer residue. 8. Lay the valve down in a horizontal position on a flat surface. 9. Lubricate the O.D. and sealing lip of the first seat. Use recommended lubricants. 10. Install the seat (8), being careful to center the flange end in the bore of the housing. 11. Place a seat retainer (9) on the top of the sleeve. Align the seat retainer screws (10) with matching holes in the flange. Align the I.D. of the seat and seat retainer. 12. Tighten the seat retainer screws using a criss-cross pattern until there is a 1.5-3 mm gap between the seal retainer and the housing for Series 760. Leave no gap for Series 762 and 767. 13. Lubricate the O.D. and sealing lip of the second seat. Use recommended lubricants. 7

14. Install the second seat. Using a straight edge, check the seat position in four places, 90 degrees apart in relation to the replaced seat bore I.D. Adjust as required to make the seat concentric with the other seat. 15. Repeat Step 12. 16. Install the seat retainer with retainer screws and tighten down the retainer and seat to the point that the retainer screws can be engaged by hand. For sizes 14 and above, it may be necessary to use two C-clamps on opposite sides to pull down the seal retainer. 17. Install the retainer screws and tighten sufficiently to allow installation of the next screw. Continue this until all screws are installed. 18. Remove C-clamps, if used. 19. The valve is now ready for installation. The gate must remain in the open position until the valve is installed and ready for operation. Relieve line pressure before attempting to remove the valve from the line to avoid personnel injury and/or equipment damage. If the valve has a pneumatic actuator, solenoid valve, limit switches, or other accessories, disconnect the electrical and pneumatic supply. Seat Replacement (No Retainer - Series 765, 766, and 768) 1. Relieve the line pressure and close the valve. Flush the line if necessary. 2. Remove the valve from the line by loosening the flange mounting bolts, studs, and nuts. 3. Clamp the valve in the vertical position up to 12 & in the horizontal position for the sizes above 12 to a fixture. Do not block the valve port when clamping the valve. An over head hoist may be needed for larger size valves. 4. Retract the gate to full open condition. 5. Remove the seats (8) from the valve. 6. Verify that the circular bore is clear of all debris, scale, and elastomer residue. 7. Lay the valve down in a horizontal position on a flat surface. 8. Lubricate the O.D. and sealing lip of the first seat. Use recommended lubricants 9. Install the seat (8), being careful to center the flange end in the bore of the housing. 10. Lubricate the O.D. and sealing lip of the second seat. Use recommended lubricants 11. Install the second seat. Using a straight edge, check the seat position in four places, 90 degrees apart in relation to the replaced seat bore. Adjust as required to make the seat concentric with the other seat. 12. The valve is now ready for installation. The gate must remain in the open position until the valve is installed and ready for operation. ACTUATOR MAINTENANCE Pneumatic Cylinder The Bray/VAAS pneumatic cylinder actuator is a low maintenance design and does not require routine maintenance. It has an FRP tube which is lubricated for life with a special coating on the inside wall. Filtered dry, instrument quality air (nonlubricated) should be used for its operation at the specified air supply pressure. 8

Recommended Spare Parts Following are parts recommended as spares, which may be stocked. Following are general recommended spares for valves. Provide the valve serial number and work order number from the nameplate for proper parts. Secondary Seal, Wiper Spare Seat Cylinder repair kit Troubleshooting Trouble Possible cause Solution Seat is worn out or torn Replace seat In fully closed position, valve leaks Gate is scratched Replace gate High torque during valve seating and unseating Misalignment between gate and stem 1. Remove the clevis fasteners 2. Loosen the superstructure fasteners 3. Adjust the alignment of the stem and gate 4. Connect the clevis fasteners 5. Retighten superstructure fasteners Superstructure fasteners loosen Tighten the super structure fasteners Valve jerks during open and close Insufficient air supply Solenoid valve dust accumulation Pneumatic operated valves: Increase supply pressure Remove and clean solenoid valve Piston rod seal damaged Replace seal 9

All statements, technical information, and recommendations in this bulletin are for general use only. Consult Bray/VAAS representatives or factory for the specific requirements and material selection for your intended application. The right to change or modify product design or product without prior notice is reserved. Patents issued and applied for worldwide. Bray is a registered trademark of Bray International, Inc. 2015 Bray International, Inc. All rights reserved. OM 12_20_2016 Bray/VAAS Division of Bray International, Inc. 13333 Westland East Blvd. Houston, Texas 77041 Tel: 281.894.5454 www.bray.com 10