Danfoss Light Commercial Refrigeration Compressors GLT80TDC

Similar documents
Maneurop reciprocating compressors MT - MTZ - NTZ

USER MANUAL GLT80TDC. User manual for 24-42V Direct Current Compressor GLT80TDC

Danfoss scroll compressors SH series

Danfoss scroll compressors SH series

Maneurop reciprocating compressors MT - MTZ - NTZ

Danfoss scroll compressors SM SY SZ

Danfoss scroll compressors SM SY SZ

00% Light commercial reciprocating compressors for beverage coolers. Text in bar.

Optyma light commercial condensing units Reliable operation and easy installation

00% Light commercial reciprocating compressors for refrigeration. Text in bar.

Optyma TM Condensing Units Lightweight and compact solution

Optyma Slim Pack Cost Effective & Quiet Solution

Optyma TM Slim Pack Just mount, braze and plug

00% Text in bar Equipis atet nit ulput pratum zzril delent lam, con ut in vercing ea adit. Optyma Plus TM New Generation Plug and play solution

00% Optyma Plus TM New Generation Plug and play solution. Catalogue. R404A/R507, R134a MAKING MODERN LIVING POSSIBLE.

R134a R134a R13. 4a R134a R134a R134

00% Optyma Plus TM New Generation Plug and play solution. Catalogue. R404A/R507, R134a MAKING MODERN LIVING POSSIBLE.

Optyma PlusTM New Generation Plug and play solution

30% energy savings with Danfoss inverter scrolls accelerate ROI.

Optyma Slim Pack Just mount, connect piping and plug

Optyma TM condensing unit Scroll and reciprocating compressors for R404A / R507, R134a, R407C and R22-60 Hz

Solenoid valves REFRIGERATION AND AIR CONDITIONING. Fitters notes

V 2.0 DC TO AC POWER INVERTER PWRINV500012W PWRINV500024W PWRINV500036W PWRINV500048W. Instruction Manual

Optyma PlusTM with scroll or reciprocating compressors

VTZ variable speed Reciprocating compressors

TD35 VS - TD50 VS Compressor for R134a 12/24V DC Technical specifications

OptymaTM condensing unit Scroll and reciprocating compressors for R404A / R507, R134a, R407C and R22-60 Hz

MAKING MODERN LIVING POSSIBLE. Quick Setup VLT FCM 300 Series. Phone: Fax: Web: -

Advanced efficiency, precision cooling Design an HVAC system like no other

PART 1 GENERAL. Pfannenberg Inc.

GP-1000 Inverter. Go Power! Electric Inc. PO Box 6033 Victoria, BC V8P 5L4 Tel: Fax:

CHILLER START UP PROCEDURE FORM DOC. N (DOC.N BELOW TO BE RETURN TO AERMEC)

Advanced efficiency, precision cooling Design an HVAC system like no other

Advanced efficiency, precision cooling Design an HVAC system like no other

Variable speed application guidelines

Application example of a motor controlled by MCD100 and protected by a circuit breaker

TWA S/K/P. Incorporating. R410A Air cooled water chillers with axial fans and scroll compressors from 189 kw to 1007 kw

User manual. Standard Modular Chiller HP 1/8 compressors with CAREL driver Application program for pco 1, pco 2, pco 3, pco C and pco XS.

OWNER S MANUAL POWER INVERTER

SPECTRACOOL Slim Fit Air Conditioners (Surface-Mount Units Only) Quick Start Operation Guide

Inverter User Manual

AHN 064 to 304 EHN/CHN 064 to 304

Pressure-volume diagrams of scroll compressors at various operating points

PH120. Rooftop Packaged. R410a Refrigerant PERFORMANCE DATA OUTDOOR COIL ENTERING TEMPERATURE 0 C

TECH XP600/1100 INSTALLATION AND OPERATION MANUAL

CWP. Cooling Only Version (CO) Condenserless Version (RC) Heat Pump Version (HP) Models 02 to 35. Engineering Data Manual. Water Cooled Water Chillers

GUIDE SPECIFICATIONS. WW Series Water-to-Water Reverse Cycle Chillers & Low Temp Boilers. WW Reverse Cycle Chillers / Low Temperature Boilers

Go Power! Manual. GP-1750HD Inverter GP-2500 Inverter

LG Air conditioning CAC and Multi Split unit Fault code sheet Universal and Multi Split Units

19,1 261,0 kw COOLING 23,7 333,0 kw HEATING

TECH XP250 INSTALLATION AND OPERATION MANUAL. Manufacturer of UL Listed Products.

TECH XP600/1100 INSTALLATION AND OPERATION MANUAL. Manufacturer of UL Listed Products.

Owner s Guide. DC TO AC Power Inverter

Owner s Manual. PowerVerterDC-to-AC Inverter

24% higher part-load efficiency saves running costs.

Fault Finding. Standard/Fundamental Faults

VLH 504 to Air-to-Water Reverse Cycle Heat Pumps. 126 to 294 kw. 133 to 307 kw

AIR COOLED CHILLERS WATER COOLED CHILLERS

Micro-Air Corporation Route 526 Allentown, NJ 08501

ENR Incorporating

DC TO AC POWER INVERTER PWRIC150012W INSTRUCTION MANUAL

Lightweight size. Heavyweight performance. Benefit from the cost-effective packaged solution!

XP600/1100/2000 INSTALLATION AND OPERATION MANUAL

Whad 0.8, 1, 1.5 kva. Manuel d installation Installation manual. Part. LE05733AA-07/12-01 GF

Observe all necessary safety precautions when controlling the soft starter remotely. Alert personnel that machinery may start without warning.

Phoenix Inverter

50 AMP Smart Energy Management System Model 800 SERVICE MANUAL 50 AMP SMART EMS. 50 Amp EMS Display Panel P/N A I N A I N

G213V STEP MOTOR DRIVE REV 7: March 25, 2011

Inverter scroll compressors VZH single and manifold

Air Cooled Water Chillers. CLS 182 to to 150 kw. Technical Brochure TM CLS-W.3GB Date : October 2004 Supersedes : TM CLS-W.2GB/07.

DC TO AC POWER INVERTER PWRINV150W INSTRUCTION MANUAL

INSTALLATION INSTRUCTIONS DNLOWAMB015A00, DNLOWAMB016A00

Standard Hydraulic Power Units Power Packages

CI-tronic Soft starters for Danfoss commercial compressor applications Type MCI 15C, MCI 25C, MCI 50CM-3 I-O

I. Safety precautions

CI-Tronic Soft start motor controller MCI 3, MCI 15, MCI 25, MCI 30 I-O, MCI 40-3D and MCI 50-3 I-O

1. INTRODUCTION SYSTEM DESCRIPTION Front Panel CONNECTION AND OPERATION TROUBLESHOOTING...8

Semi-hermetic reciprocating compressors

Installation and Operation Guide. Tundra HD 2500 Power Inverter. for the. Webasto BlueCool Truck System

Types of Motor Starters There are several types of motor starters. However, the two most basic types of these electrical devices are:

USERS MANUAL MCD REMOTE OPERATOR

CWP-CO / CWP-RC / CWP-HP 02 to 35

PROJECT MANUAL GUIDE SPECIFICATIONS FOR: PFANNENBERG SERIES EB COMPACT PACKAGED CHILLERS PART 1 GENERAL

Phone: Fax: Web: -

Installation, Operation and Maintenance Manual. EVC Controller (from February 2007)

GEA Bock 6 and 8 Cylinder Compressors HG76e and HG88e

Application Engineering Europe

MT/MTZ 50 Hz R22 R407C R134a R404A / R507

Design Guide. VLT Soft Start Controller MCD 100

Lightweight size. Heavyweight performance. Benefit from the cost-effective packaged solution!

Smart 110 with built-in flashlight for 6 240Ah lead-acid batteries

UPS. MEGALINE UPS MODULAR SINGLE-PHASE from 1250 to VA THE GLOBAL SPECIALIST IN ELECTRAL AND DIGITAL BUILDING INFRASTRUCTURES

Low Frequency Inverter. User Manual

Enclosed switches. from 20 to 1600 A

Data sheet. CI-tronic Soft start motor controller Type MCI 3, MCI 15, MCI 25, MCI 30 I-O, MCI 50 I-O 520B1443

Tips & Technology For Bosch business partners

JARD by MARS JARD by MARS

FOR APPROVAL SPECIFICATION OF ROTARY COMPRESSOR MODEL : UX9CJ5034ZJ7

Compact Sine Inverter

Power Inverter. User s Manual. Diamond Series CPD1200EILCD

Transcription:

Installation guide Danfoss Light Commercial Refrigeration Compressors GLT80TDC Electronic driver connection manual, 12-42V, Direct Current - R134a lightcommercialrefrigeration.danfoss.com

Content Wiring and Connections... 4 Setting up the speed... 6 Operating voltage... 7 Battery protection system... 8 Protections and alarms... 9 FRCC.PI.044.A1.02 3

Wiring and Connections General rules Voltage drop in the power leads GLT80TDC must always be powered through the dedicated electronic driver FDC3, which is supplied with the compressor as a separate device. NEVER CONNECT THE COMPRESSOR S HERMETIC PINS (FUSITE) TO THE TERMINALS OF A BATTERY OR ANY OTHER DC OR AC SOURCE DIRECTLY. DO NOT TRY TO FIT AN ELECTRONIC DRIVER OTHER THAN THE FDC3. THE COMPRESSOR WILL NOT OPERATE AND IRREVERSIBLE DAMAGE MAY OCCUR. The FDC3 driver is directly connected to the battery poles as well as to the compressor pins. It checks battery voltage and adjusts itself to the voltage value for proper compressor operation, or switches itself off if the battery voltage is not adequate. The driver also controls the compressor speed. ALWAYS RESPECT THE POLARITY OF THE BATTERY WITH THE POWER INPUT TERMINALS OF THE ELECTRONIC DRIVER. To avoid excessive voltage drop in the leads, their length and cross section must be related to the voltage supply, as indicated in Table 1. The unit is protected against damage caused by wrong polarity of the supply. The compressor will not run correctly if it s wrongly connected. THE POWER INPUT TERMINAL - OF THE ELECTRONIC DRIVER SHOULD BE REFERRED TO THE CHASSIS OF THE VEHICLE AS WELL AS THE APPLIANCE FRAME* A FUSE MUST BE PLACED BETWEEN THE + POLE OF THE BATTERY OR DC POWER SUPPLY, AND THE + POWER INPUT TERMINAL OF THE ELECTRONIC DRIVER 12V SYSTEMS: 30A FUSE 24V SYSTEMS: 30A FUSE 42V SYSTEMS: 20A FUSE In some special vehicles, the chassis is connected to + terminal of the battery instead of - terminal (positive reference systems). In such cases, + should be understood as - and vice-versa. In systems powered by a variable DC source, the fuse should be selected following the rules above mentioned, considering the maximum voltage at the variable DC Source. Table 1: Maximum length of leads (m) Rated Operating Range Cross section mm 2 12-14 V 24-28 V 36-42 V 4 2.5 2.5 3 6 4 4 6 10 6 6 9 If any kind of connector or switch is placed between the battery poles and the power terminals of the electronic driver, its resistance should be less than 10mΩ. If the resistance is higher than 5mΩ, the maximum length of the wires indicated in Table 1 should be halved or the cross section should be doubled. In case of using a long cable to connect battery and electronic driver, it is recommended using a cable with low inductance. 4 FRCC.PI.044.A1.02

Wiring and Connections Wiring Diagram The FDC3 electronic driver features a terminal board where all connections are made. The terminal layout is described in Fig. 1: Fig 1. FDC3 wiring scheme 24 42V FUSE FDC3 ELECTRONICAL DRIVER PC BATTERY FAN 12V ELECTRONIC INTEGRAL MANAGER SPI THERMOSTAT ELECTROMECHANICAL OR ELECTRONIC ALARM SWITCHER CONTROL PANEL NO RESISTOR IS NEEDED TO BE INSTALLED IN FDC3 ELECTRONIC DRIVER When connecting the electronic driver to the compressor, any position of the connector is possible under an electrical point of view. However, in practice, the vertical position is not possible because the electronic box cannot be assembled. The connector should be connected as shown below: Fig 2. Connection of the FDC3 electronic driver to the compressor FRCC.PI.044.A1.02 5

Setting up the speed The electronic control unit FDC3 is supplied with the exclusive Serial Port Interface (SPI), featuring a RJ45 telephone type connector. This port is configured to set up the compressor speed through physical connections between their terminals. To facilitate this procedure, three connector cables are supplied together with the electronic driver. The compressor will run at a certain speed depending on the used connector, as shown in Table 2: Table 2. Compressor speed for each connector Connector Speed NONE 2000 BLACK 2500 BLUE 3000 RED 3500 Replacing a GLT80TDC compressor or FDC3 electronic driver Replacing a different brand DC compressor Furthermore, if a FDC programming kit is available, the new FDC3 electronic driver can be set up by programming it using the kit and a computer. 1. If a FDC programming kit is available, use it to check the setting of the old FDC3 electronic driver and set up the new one by programming the same parameters. 2. Otherwise, check the old FDC3 electronic driver for the presence of a connector at the SPI to set 1. Check for compressor displacement D 0 and Speed S 0. Then calculate the required velocity of GLT80TDC as follows: S = D 0 S 0 / 3 (D 0 in cm3) NEVER USE FDC3 ELECTRONIC DRIVER IN OTHER DC COMPRESSOR DIFFERENT THAN GLT80TDC. If the compressor or the FDC3 electronic driver should be replaced for servicing a refrigerator or a freezer, one of the next procedures should be followed. up the speed. If so, take it away and connect it again at the new FDC3 electronic driver. 3. Otherwise check the appliance for some information about compressor speed set up. If so, select the proper connector which gives the nearest speed set up from table 2. and set up GLT80TDC speed by programming (if FDC programming kit is available) or by selecting a proper connector according to Table 2. 6 FRCC.PI.044.A1.02

Operating voltage GLT80TDC is designed to operate in a wide range of DC voltages, supplied either by a battery or by any other kind of filtered DC power supply. DC VOLTAGE SUPPLY ALLOWED is 10V to 42.4V If the battery voltage is below 17V, the controller will assume that are working in a system of 12-14V; if the voltage is greater than 17V and less than 33V, assume that are working in a system of 24-28V and if the voltage is greater than 33V assume that are working in a system of 36-42V. The output power is 450W (Nominal) 500W (Maximum). 12-14V systems the output power is limited to 250W. In any case, the minimum operating voltage is 9V and maximum of 46.2 V, admitting, once initiated the launch, a minimum voltage of 8V during the first minute. From the value of the applied voltage, the electronic driver automatically decides the rated voltage range of the supply. Three possible ranges are considered: 12 to 14V: voltage is below 17V 24 to 28V: voltage is within 17 and 33V 36 to 42V: voltage is within 33 and 42.4V FRCC.PI.044.A1.02 7

Battery protection system There is a protection system for the battery that prevents the compressor from operating if the available voltage becomes too low. Battery protection level is set up for working under normal circumstances in most appliances. Cutout and cut-in values are: 12V system: cut-out = 10.0V; cut-in = 11.5 V 24V system: cut-out = 22.0V; cut-in = 24.5V 42V system: cut-out = 36.0V; cut-in = 38.5 V Other values can be set up if a FDC programming kit is available. 8 FRCC.PI.044.A1.02

Protections and alarms GLT80TDC is electronically protected against a number of possible dysfunctions and failures: Battery discharge. Fan over current: protects the compressor and the electronic driver against fan over current due to start or running overload, or short-circuit. Starting failure: if the running speed is not achieved during the starting sequence, the unit stops and retries the start up after one minute. Compressor overload: it operates when the compressor speed drops below the set up speed, or when the current drawn in is excessive, and thus preventing the appliance from operating under overload conditions that may cause otherwise refrigeration overload or compressor failure. Electronic driver overheat: if the temperature of the electronic components of the control becomes too high, an internal sensor will stop the unit. In case of overheating, one automatic attempt to restart the compressor is allowed. In case of battery protection, there is no limit of automatic attempts to restart. In case of any other protection occurring, there will be two automatic attempts to re-start the compressor. Once the sequence of automatic attempts to restart the compressor is finished, the unit will remain permanently unable to operate until switched off and on again from the power supply. The intervention of the thermostat during the sequence of automatic restart attempts interrupts and resets the sequence. FRCC.PI.044.A1.02 9

Danfoss Commercial Compressors is a worldwide manufacturer of compressors and condensing units for refrigeration and HVAC applications. With a wide range of high quality and innovative products we help your company to find the best possible energy efficient solution that respects the environment and reduces total life cycle costs. We have 40 years of experience within the development of hermetic compressors which has brought us amongst the global leaders in our business, and positioned us as distinct variable speed technology specialists. Today we operate from engineering and manufacturing facilities spanning across three continents. Danfoss Turbocor Compressors Danfoss Inverter Scrolls Danfoss Scrolls Danfoss Optyma Condensing Units Danfoss Maneurop Reciprocating Compressors Danfoss Light Commercial Refrigeration Compressors Our products can be found in a variety of applications such as rooftops, chillers, residential air conditioners, heatpumps, coldrooms, supermarkets, milk tank cooling and industrial cooling processes. http://cc.danfoss.com Danfoss Commercial Compressors, BP 331, 01603 Trévoux Cedex, France +334 74 00 28 29 FRCC.PI.044.A1.02 - Danfoss Light Commercial Refrigeration Compressors made by Huayi Danfoss DCS (CC) 2016.03