GEI-90802E INSTRUCTIONS SYNCHRONISM CHECK RELAY TYPE 1J552D. GE Protection and Control 205 Great Valley Parkway Malvern, PA

Similar documents
INSTRUCTIONS SYNCHRONISM-CHECK RELAYS. GE Meter and Control. 205 Great Valley Parkway Malvern, PA Types IJS51A.

GEK41931B INSTRUCTIONS MULTI-CONTACT AUXILIARY RELAYS TYPE HFA73K. GE Protection and Control 205 Great Valley Parkway Malvern, PA

GEK 45484B INSTRUCTIONS MULTI-CONTACT AUXILIARY RELAY HFA151 TYPE. GE Protection and Control 205 Great Valley Parkway Malvern, PA

GENERALS ELECTRIC INSTRUCTIONS. GEK Insert Booklet- GEI SYNCHRONISM CHECK RELAY IJS52F INTRODUCTION

INSTRUCTIONS HAA 15A / 15B / 15C / 15D / 15E / 15F / 15G / 15H AUXILIARY CURRENT RELAYS

INSTRUCTIONS GEI-98305C UNDERVOLTAGE RELAY D-C. Type NGV18A GENERAL ELECTRIC

INSTRUCTIONS. GE Protection and Control. 205 Great Valley Parkway Malvern, PA UNDERVOL TAGE RELAYS TYPES: IAV54E IAV55C IAV54F IAV55F

INSTRUCTIONS. GEI-38974A Supersedes GEI INSTANTANEOUS CURRENT RELAY TYPE PJC2OA GENERALS ELECTRIC

INSTRUCT IONS GEH-1 793J INSTANTANEOUS AUXILIARY RELAY TYPES HGA11A, C, H, J, K, P, S, T, V, W, X GENERAL ELECTRIC AUILIARV P A GENERALS ELECTRIC

COM Overcurrent Relay

3.0 CHARACTERISTICS E Type CO-4 Step-Time Overcurrent Relay

INSTRUCTION S GEK 7354J AUXILIARY VOLTAGE RELAY TYPE HAA16B, HAA16C GENERAL ELECTRIC

2.0 CONSTRUCTION AND OPERATION 3.0 CHARACTERISTICS K. CO (HI-LO) Overcurrent Relay

B CW POWER RELAY

Type CRN-1 Reverse Power Relay 50 and 60 Hertz

P. Sub 4 184A404. Sub 3 876A220

TYPE KF UNDER-FREQUENCY RELAY A. Figure 1: Type KF Relay for 60 Hertz without Case. (Front & Rear View.) Front View Rear View

Figure 1. Type CWP-1 Ground Relay (Front View) Figure 2. Type CWP-1 Ground Relay (Rear View) E

C. Figure 1. CA-16 Front View Figure 2. CA-16 Rear View

A - Add New Information C - Change Existing Information D - Delete Information. Page 7. Delete the fourth paragraph beginning CAUTION

THERMAL OVER CURRENT RELAY

ABB. Type CRQ Directional Negative Sequence Relay for Ground Protection B 1.0 APPLICATION 2.0 CONSTRUCTION AND OPERATION CAUTION

GENERAL ELECTRIC INSTRUCTIONS GEK- 2M42. Insert Rooklet GEH 1793 INSTANTANEOUS AUXILIARY RELAY TYPE HGA MODEL 12HGAI1E(-)A I NTRODUCT ION

ABB ! CAUTION. Type KRV Directional Overcurrent Relay E 1.0 APPLICATION 2.0 CONSTRUCTION AND OPERATION. Instruction Leaflet

L. Photo. Figure 2: Types CA-16 Relay (rear view) Photo. Figure 1: Types CA-16 Relay (front view)

INSTRUCTIONS GEK G HIGH-SPEED DIFFERENTIAL RELAYS TYPES CFD22A AND CFD22B. GE Protection and Control

ABB Automation Inc. Substation Automation and Protection Division Coral Springs, FL 33065

INSTRUCTIONS HAA 15A/15B/15C/15D/15E/15F/15G/15H AUXILIARY CURRENT RELAYS. Iso9ooo. GE Power Management

INSTRUCTIONS. GE Protection and Control. 205 Great Valley Parkway Malvern, PA GEK-49826D INSTANTANEOUS OVERCURRENT RELAYS TYPES:

GENERAL ELECTRIC INSTRUCTIONS. GE I Supersedes GEI-28802E INSTANTANEOUS VOLTAGE RELAYS TYPES

INSTRUCTIONS GEI-10190L DC AUXILIARY RELAYS TYPE HGA17A TO F, H, M, R, S, T GENERAL ELECTRIC

Test Cabinet (Inspection Box) Instructions. for Testing Accessories on Manually and Electrically Operated EntelliGuard G Low Voltage Circuit Breakers

ABB Automation, Inc. Substation Automation & Protection Division Coral Springs, FL Allentown, PA

4.0 OPERATION Type ITH-T Relay

TABLE I 60 CYCLE BURDEN OF THE CVD RELAY AT CONTINUOUS RATING

HGA. Hinged Armature Auxiliary. Hinged armature auxiliary relay to perform auxiliary functions in AC and DC circuits.

INSTRUCTIONS. seconds. the tween the end of the bearing screw and the. top of the shaft. The moving contact is a small silver hemisphere

DIAC DIFC DSFC Digital Self Powered Overcurrent Protection

41-747G. Figure 1: Type DGF Relay without case (Photo)

CR193 Vacuum Limitamp* Contactors

Medium Voltage Standby non-paralleling Control GUIDE FORM SPECIFICATION

3. OPERATION 2.1. RESTRAINT CIRCUIT 2.6. INDICATING CIRCUIT 2.2. OPERATING CIRCUIT 2.7. SURGE PROTECTION CIRCUIT 2.3.

INSTRUCTIONS. GE Protection and Control 205 Great Valley Parkway Malvern, PA GLK 34117G

www. ElectricalPartManuals. com INSTRUCTIONS "INERTEEN AND OIL INSULATED FEEDER SWITCHES DESCRIPTION INSTALLATION MAINTENANCE

ichards MANUFACTURING COMPANY, SALES, INC. 517 LYONS AVENUE, IRVINGTON, NJ Phone Fax

www. ElectricalPartManuals. com INSTRUCTIONS TYPE CO CONTACT MAKING AMMETER INSTALLATION OPERATION MAINTENANCE I.. L APPLICATION

Data Bulletin. Ground-Censor Ground-Fault Protection System Type GC Class 931

GE K D IN ST RU CT ION S INSTANTANEOUS AUXILIARY RELAY TYPE HGA111 GENERAL ELECTRIC

2.0 CONSTRUCTION 3.0 OPERATION. SA-1 Generator Differential Relay - Class 1E 2.5 TRIP CIRCUIT

INSTRUCTIONS TIME OVERCURRENT RELAY TYPE IAC 12IAC77S(-)A INTRODUCTION

Type SOQ Negative Sequence Time Overcurrent Relay

GE Industrial Solutions. DEH Installation and Maintenance Manual AKD-20 AR / Entellisys AR Exhaust Plenum System

www. ElectricalPartManuals. com Instructions for Load Break Air Switch, Type LBF, for Power Centers

GE CONSUMER & INDUSTRIAL

UBC Technical Guidelines Section Edition Commissioning of Electrical Systems Page 1 of 5

Florham Park, NJ USA Call (ASCO) for sales or service

Installation Sheet January, 2016 Supersedes February, 2013

SL-6 & SL-6A. I UNION SWITCH & SIGNAL l[ml 645 Russell Street Batesburg, SC Service Manual Field and Shop Maintenance

TRINETICS CSD SERIES OIL SWITCH INSTALLATION INSTRUCTIONS

INSTRUCTIONS GEH-1789B GEH-1789A SUPERSEDES BALANCED-CURRENT RELAYS. Types. IJCSlB IJCSlC IJC53A. www. ElectricalPartManuals. com. GENERAL f) ELECTRIC

INSTRUCT ION S GEK A. Supersedes GEK TIME OVERCURRENT RELAY TYPE IAC66S GENERAL ELECTRIC

SERVICE MANUAL

ichards MANUFACTURING COMPANY, SALES, INC. 517 LYONS AVENUE, IRVINGTON, NJ Phone Fax

ABB Power T&D Company Inc. Relay Division Coral Springs, FL Allentown, PA. Non-Directional, Single Phase Adjustable Time Delay Device No.

SF-120, SF-170, SF-250, SF-400 Bearing Mounted, Flange Mounted, SFC-120, SFC-170, SFC-250, SFC-400 Bearing Mounted, Flange Mounted

600 D 220 E 230 J Hanover Road, Florham Park, New Jersey USA For sales or service call (ASCO)

Installation Sheet January, 2016 Supersedes June 2013

UNION SERVICE SPECIFICATION NUMBER SU A

Florham Park, NJ USA Call (ASCO) for sales or service

PT-150 PLUG-IN THERMAL RELAY WITH SNAP-ACTION BACK CONTACT *****************

Operator s Manual Series ACTS Automatic Closed Transition Transfer Switches 150 through 4000 amps A. Rating Label.

Instructions for De-Ion Air Circuit Breakers Types DM2R, DM2F

Horizontal Circuit Switchers

Horizontal Circuit Switchers

SecoVac * Ground & Test Device

Installation, Operation and Maintenance Instructions

Vacuum Circuit Breakers (Vehicle)

[ These instruction: do not purport to cover all details or variations eqiipment GENERAL ELECTR INSTRUCTIONS. Insert Book t Ci[ V.

1. Take the cover off the relay, taking care to not shake or jar the relay or other relays around it.

Operator s Manual Series ATB Automatic Transfer & Bypass Isolation Switches 150, 260, and 400 amp sizes A. Rating Label.

ProTrip Conversion Kits. For GE Types AK-15, AK-25, and AKU- 25 Low-Voltage Power Circuit Breakers INTRODUCTION. DEH Installation Instructions

GEK 65513D INSTRUCTIONS AUXILIARY LOCKOUT RELAY HAND RESET WITH TARGET. GE Meter and Control 205 Great Valley Parkway Malvern, PA

Vacuum Circuit Breaker (Vehicle)

GEK 65602B INSTRUCTIONS RECLOSING RELAYS TYPES HGA18M, HGA18N. GE Protection and Control. 205 Great Valley Parkway. Malvern, PA

Vacuum Circuit Breakers (Vehicle) Type HKR 7.5kV to 15kV. Instructions Installation Operation Maintenance SGIM-9928C

www. ElectricalPartManuals. com MAGNETIC TIME RELAYS GENERAL. ELECTRIC INSTRUCTIONS *IC *Also identified with prefix CR instead of IC.

GP/GPA GROUND FAULT PROTECTION

50 Hanover Road, Florham Park, New Jersey USA For sales or service call (ASCO)

BBC. Renewal Parts. I-T-E Low-Voltage Power Circuit Breakers

Installation, Operation and Maintenance Instructions

UNIT VIBRATOR MODELS 60U AND 70U

Page 2 DS LOW VOLTAGE POWER CIRCUIT BREAKERS Digitrip Trip Unit Inside Wiring Guide Outside Wiring Guide Shutter Drawout Unit Position Indicator Escut

Low Voltage WavePro TM and EntelliGuard TM Circuit Breakers Remote Racking Operator

Instruction Manual AVTM for. Strip Chart Recorder Catalog Nos and

February, Swissvale, Pa. INSTRUCTION PAMPHLET U-5623-A MASTER RELAY FOR AMPLIFIER FOR UNION CODED CAB SIGNAL EQUIPMENT

Vacuum Circuit Breakers (Vehicle)

Operation and Maintenance Manual

Instructions for Replacing

Installation Instructions For Motor Control Center (MCC) Units

Control Relays Overview

Transcription:

E INSTRUCTIONS SYNCHRONISM CHECK RELAY TYPE 1J552D GE Protection and Control 205 Great Valley Parkway Malvern, PA 19355-1337

CONTENTS INTRODUCTION 3 APPLICATION 3 RATINGS 4 CHARACTERISTICS 4 Operating Principles 4 BURDENS 5 CONSTRUCTION 6 RECEIVING, HANDLING AND STORAGE 6 ACCEPTANCE TESTS 6 Visual Inspection 6 Mechanical Inspection 7 Electrical Tests 7 INSTALLATION PROCEDURE 7 Electrical Tests 8 PERIODIC CHECKS AND ROUTINE MAINTENANCE 8 Contact Cleaning 8 Mechanical 9 Electrical 9 SERVICING 9 Mechanical Adjustments 9 Electrical Adjustments 9 RENEWAL PARTS 10 LIST OF FIGURES 11 PAGE Cover Photo (8038824) 2

SYNCHRONISM ChECK RELAY TYPE 13S52D INTRODUCTION The Type 1JS520 relays are of the induction-disk construction, and are intended for use as synchronism-check relays. The synchronism-check unit has two shaded-pole U-magnet driving elements acting on opposite sides of a single rotating disk (see Figure 2). One of these, the operating element, drives the disk in the contact closing direction, and the other, the restraining element, drives the disk in the opposite direction. The disk shaft is restrained by a spiral spring, the purpose being to hold the contacts open when the relay is de energized. The motion of the disk is retarded by permanent magnets (drag magnets) acting on the disk to give a time delay. The Type 1dS52D relay has two telephone-type undervoltage units. These are designated as B and L on Figure 7. The Type IJS52D relay does not have a seal in unit, since one is not required in its normal application. APPLI CATION The IJS relay is applicable as a synchronism-check relay to permit closure of a circuit breaker only when the two sources connected to it are correctly synchronized elsewhere. It determines that synchronism is being maintained by other incterconnections, and then permits closure of the circuit breaker. See Figure 9 for a typical elementary diagram. In such an application, the voltages may be slightly out of phase with each other because of different line and load characteristics. This condition may exist, for example, where one line is supplying a lagging load through a transformer bank, and the second is unloaded. The relay, however, can be calibrated to permit closure of the breaker under these conditions the voltage and the phase-angle differences are not excessive. if However, the IJS relay cannot discriminate between a very low slip frequency between systems, and systems in synchronism. Figures 13 and 14 illustrate that the slip frequency with which the IJS will permit closing increases with increasing closing angle settings, and decreases with increasing time dial settings. In general, the closing-angle setting is fixed by the maximum angular separation of the systems for which the IJS must operate, and the slip frequency for which the TJS will operate is reduced to an acceptable maximum by increasing the time dial setting. These instructions do not purport to cover all details or variations in equipment nor to provide for every possible citingency to be met in connection with installation, operation or maintenance. Should further infor,mtion be desired or should particular problezrz arise vhich are not covered sufficiently fot he purchasers purposes, the,nattej- shu1d be referred to the general 1ectriC Coe5ny. T the estent required the products described herein meet applicable ANSI, IrEt and?ftma standards, ic sic? assura,ce s sven with re.p.ct t i lcal codes and ordinances because they vary greatly.

On systems where lines may or may not be tied together elsewhere, the IJS relay is used in parallel with the Type GES relay to permit closure of a breaker with zero frequency difference. Depending on the external connections used (see Figure 9), the telephone relays B and L, mentioned above, serve to reclose the breaker under conditions of (1) dead bus or line, (2) live bus, dead line, (3) dead bus, live line, (4) dead bus, live line, or live bus, dead line (5) dead line, bus live or dead (6) dead bus, line live or dead. RATI NGS The operating and restraining coils of the synchronism-check unit are continuously rated. The contact of this unit will make and carry momentarily 30 amperes, but it has no interrupting rating. The telephone-type voltage relay contacts will make and carry 30 amperes momentarily for normaly duty, but the circuit must be opened by a breaker auxiliary unit or other suitable means. The telephone type relays have operation coils rated at either 67 or 115 volts. CHARACTERISTICS 1 OPERATING PRINCIPLES The operating coils, mounted on the left hand side, produce a torque tending to close the synchronism-check contact. This torque is proportional to the vector sum of the voltages whose phase positions are being compared. The torque produced by the restraint coils is proportional to the vector difference of the voltages. The operating torque is maximum when they are in phase; the reverse is true of the restraining torque. The closing angle of the relay is defined as the maximum phase displacement of the two voltages at which the relay will close its synchronism check contact when the voltaqes are at rated value. The 200 closing angle is considered standard; however, other settings may be made, as indicated by the voltage-phase angle characteristics shown in Figure 1. The time-delay characteristics of the Type IJS relay are obtained primarily by the time-dial setting. The time dial controls the distance the contacts must travel before closure, and hence controls the time delay. At No. 10 time-dial setting, the travel is maximum, whereas at No. 0 the contacts are just closed. A certain amount of adjustment may be made by changing the position of the drag magnet on its shelf. Moving it toward the disk shaft decreases the time delay, while moving it away from the disk shaft increases the time delay. Typical time vs. phase-angle curves are shown in Figures 4 and 5 for 60 cycle relays. The Model 121JS52D1 relay has a standard closing angle setting of 200, and has its drag magnet adjusted to provide 20 seconds time delay from the No. 10 time dial setting for voltages in phase. The closing angle on this relay can be adjusted to angles greater than 200, but with a corresponding decrease in time delay, as 4

GEl- 90802 shown in Figure 4. The approximate time with both 40 seconds. The approximate time with one energized from 3 seconds on the 200 to 6 seconds on the 60 No. 10 varies time-dial setting. reset reset setting coil coils de-energized at rated voltage setting is about with the The 121JS52D3 which is designed for use where a angle than 200 is provides 20 seconds delay the 40 as shown in Figure 5. may be to angles between 20 and 60 with corresponding changes in time as shown in Figure 5. The approximate time with both de-energized is about 130 seconds the No. 10 time dial The approximate time with one energized voltage from 13 seconds on the 20 to 20 seconds on the 60 the No. 10 reset odel setting. required, time-dial setting. relay, It coils reset adjusted setting delay, Figure 6 gives the time in seconds for zero phase displacement and with Curves for 50 are The to pick up 50% or of of calibrated rated voltage. cycles operating at similar. at other closing coil rated voltage at less The burdens for the synchronism check with the phase displacement of the two 180. at closing greater closing-angle setting, at at rated setting at various time-dial settings 60 cycles on both telephone-type undervoltage units rated voltage BURDENS unit and are given in Table with a minimum voltages, to drop out I. at circuits. at with varies are 15% or more The burden 00 to a maximum varies T L Circuit TABLE Volts Cycles Phase Watts Volt Mips Power Factor 5 6 00 1.00 3.86 0.258 67* 5-6 180 1.25 4.00 0.312 60 7-8 1.10 3.63 0.300 7 8 180 1.36 3.77 0.360 5-6 1.45 4.73 0.306 67* 5-6 180 1.75 4.87 0.359 50 7-8 00 1.58 4.45 0.357 7-8 180 1.87 4.63 0.403 5-6 0 3.00 11.6 0.258 5-6 180 3.76 12.0 0.313 115 60 7-8 3.30 10.9 0.300 7-8 180 4.07 11.3 0.360 5-6 0 4.35 14.2 0.306 5 6 180 5.25 14.6 0.359 115 50 7-8 0 4.75 13.3 0.357 7-8 180 5.60 13.9 0.403 I Difference 0 0 0! * The burden of telephone relay 67 60 115 60 rated at volts, volts, cycles. cycles, units is 10 volt-amperes and 6 watts for each and 13 volt-amperes and 8 watts for each unit unit rated at 5

To do this, the relay is first disconnected by removing the connection plug that case when the relay is in operation, but they can be easily removed when desired. The relay components are mounted in a cradle assembly that is latched into a drawout CONSTRUCTION 6 relay agree with the requelsition. Check the nameplate stamping to make sure that the Model Number and rating of the VISUAL INSPECTION readjustment is necessary, refer to the section on SERVICING. calibrations have not been disturbed. If the examination or tests indicate that made to make sure that no damage has heen sustained in shipment and that the relay Immediately upon receipt of the relay, an inspection and acceptance test should be ACCEPTANCE TESTS cover is removed, and cause trouble in the operation of the relay. Foreign matter collected on the outside of the case may find its way inside when the If the relays are not to be installed immediately, they should be stored in their original cartons in a place that is free from moisture, dust and metallic chips. parts are injured or the adjustments disturbed. Reasonable care should be exercised in unpacking the relay in order that none of the cartons designed to protect them against damage. Immediately upon receipt of a Office. transportation company and promptly notify the nearest General Electric Sales relay, examine it for any damage sustained in transit. If injury or damage resulting from rough handling is evident, file a damage claim at once with the These relays, when not included as part of a control panel, will be shipped in RECEIVING, HANDLING AND STORAGE Figure 9. or L can be used separately, as shown in the typcial external connections in connections to terminal 10 are arranged so that the normally-closed contact of B Internal connections for the IJS52D are shown in Figure 7. Note that the be included. For outline and drilling dimensions, see Figure 15. thickness must be indicated on the relay order to insure that proper hardware will up to 2 inches thick, and appropriate hardware is available. However, panel The relay case is suitable for either semi-flush or surface mounting, on all panels provide adequate overlap when the connecting plug is withdrawn or inserted. Every circuit in the drawout case has an auxiliary brush, as shown in Figure 12, to inserted. arm that prevents the cover from being replaced until the connection plugs have been The cover, which is attached to the front of the relay case, contains an interlock To test the relay in its case, this connection block can be replaced by a test plug. completes the electrical connections between the case blocks and the cradle block.

Remove the relay from its case and check that there are no broken or cracked molded parts or other signs of physical damage, and that all screws are tight. Check that the short fingers are in the correct location, as Indicated In Figure 7, and that the auxiliary brushes are properly adjusted (see Figure 12). MECHANICAL INSPECTION 1. Check that the rotating element moves without noticeable friction. 2. Remove the time-dial locking screws and check that the moving contact just touches the stationary contact when the time dial is set at zero (0). The contact wipe should be approximately 1/32. Put locking screws back in place. 3. Check that the control spring is not deformed and that the spring convolutions at the No. 5 time-dial setting are reasonably concentric. 4. Check that the armatures of the telephone relays move freely. Also, with the telephone relays in the de-energized position, all circuit closing contacts should have a gap of 0.015 and all circuit-opening contacts should have a wipe of 0.005. Gap may be checked by inserting a feeler gage, and wipe can be checked by observing the amount of deflection on the stationary contact before parting the contacts. The armature should then be operated by hand and the gap and wipe again checked as described above. ELECTRICAL TESTS Connect the relay as shown in Figure 10 and check the following: 1. Check that the relay picks up with approximately the time delay shown in Figure 6 when a single phase source of at least rated voltage is connected to both operating coils. 2. Check that the relay picks up at a 20 closing angle (or other closing angle if used) within ± 30 when connected to a source with rated voltages on both coils. Check zero displacement pickup, which should agree with the value in Figure 1 within 10%. 3. WIth both coils connected to a rated voltage source with zero displacement, check that pickup time agrees with the values given in Figures 4 or 5 + 10%. 4. With an adjustable 115 volt source of rated frequency, check that the telephone type units pick up at 50% or less of rated voltage and drop out at 15% or more of rated voltage. To check the L relay, connect the voltage source to studs 5 and 6. To check B relay, connect voltage to studs 8 and 9. INSTALLATION PROCEDURE If, after acceptance tests, the relay is held in storage before shipment to the job site, it is recommended that the visual and manual inspections described in the section on ACCEPTANCE TESTS be repeated before Installation. 7

ELECTRICAL TESTS Refore the following electrical tests are made, the relay should he in its case, preferably mounted in its permanent location. The relay closing angle should he set as required for its permanent location, which would normally be 200. Connect the relay as shown in Figure 10, and check that the relay picks up at the proper phase angle 3. IF a phase angle meter or a phase shifter is not available, it is possible to adjust the relay to approximately the closing angle desired by means of the connections and curve shown in Figure ii. In this test, rated voltage is held on one circuit (studs 7-8) and a reduced voltage is applied to the other circuit (studs 5-6). The voltage connected to studs 5-6 is adjusted until the synchronizing check unit just closes its contact. The difference between the two voltages should agree approximately with the voltage given on the curve shown in Figure 11 for the phase angle used (e.g. 24 volts for 20 closing). When using the connections shown in either Figure 10 or Figure 11, check the operating time at 0 displacement with rated voltage on each coil, using the timedial setting of the permanent location. See Figure 6 for nominal time delay values. Pickup and dropout of the telephone-type undervoltage relays should be checked as described in the section on ACCEPTANCE TESTS. PERIODIC CHECKS AND ROUTINE MAINTENANCE In view of the vital role of protective relays in the operation of a power system, it is important that a periodic test program be followed. The interval between periodic checks will vary depending upon environment, type of relay and the user s experience with periodic testing. Until the user has accumulated enough experience to select the test interval best suited to his individual requirements, it is suggested that the following points be checked once a year. CONTACT CLEANING A flexible burnishing tool should be used for cleaning relay contacts. This is a flexible strip of metal with an etched-roughened surface, which in effect resembles a superfine file. The polishing action of this file is so delicate that no scratches are left on the contacts, yet it cleans off any corrosion thoroughly and rapidly. The flexibility of the tool insures the cleaning of the actual points of contact. Relay contacts should not be cleaned with knives, files, or abrasive paper or cloth. Knives or files may leave scratches, which increase arcing and deterioration of the contacts. Abrasive paper or cloth may leave minute particles of insulating dbrasive material in the contacts, and thus prevent closing. The burnishing tool described above can be obtained from the factory. S

GEl- 90802 MECHANICAL The mechanical checks repeated. described in the section on ACCEPTANCE TESTS should be ELECTRICAL Using the connections in Figure 8: 1. Check the maximum angle for pic:up of the synchronizing-check agrees approximately with the value shown on the curve in Figure 11. that closing unit 2. Check the both circuits. closing time with the to provide on The time should agree with the values given in Figure 6, 10%. potentiometer set rated voltage Check the pickup and dropout of the telephone-type undervoltage units (27B and 27L). SERVICING If recalibration making adjustments. of the relay is necessary, the following should be considered when MECHANICAL ADJUSTMENTS 1. The moving should touch the secondary when the time is the zero (0) readjustment is loosen the two clamping screws which the stop arm to the and change the of the stop arm to the moving the touch with the time 0. A adjustment can be obtained by moving the brush in or out by means of screw. However, in the the brush must be so is 1/64 to 1/32 wipe with the Be sure the screws are the adjustment made. set at contact stationary contact relative just position. If fasten dial set at final adjustment, securely tightened after fine contact shaft contact until contact fully closed. is contact necessary, its adjusting positioned contacts just that dial position that there 1/6L1 when the synchronism- 2. The stop-arm check is unit leaf spring de-energized. should deflect at least 3. The disk and assembly should have a end play of 1/16 to 1/32 and both bearing screws should be The disk should be approximately centered between the poles of the U-magnet and drag magnet. shaft tight. vertical 4. Telephone type gaps may be by bending the brush to 0.015 inch gap. When the adjustment is made, the wipe must he rechecked to make sure there is a minimum of 0.005 wipe. contact relay contact obtain adjusted stationary ELECTRICAL ADJJSTMENTS Closing Angle Adjustment relay closinc angle, Connect means for the a voltage control. as shown in Figure 10. To make an accurage adjustment of the phase and phase angle meter are along with a shifter required, 9

Simultaneous adjustments of the two resistors are necessary. The left hand adjusting resistor Is for obtaining the correct closing angle setting. lagging the other voltage. That is, the closing angle will be the same, whether one voltage Is leading or adjustable resistor at the top of the frame permits equalizing the closing angle. Two adjustments are necessary for obtaining a desired closing angle. The right-hand 10 TESTS, ON PAGE 7. Since the last edition, changes have been made in the final step of ELECTRICAL give the General Electric requisition number on which the relay was furnished. complete nameplate data, including the serial number, of the relay. If possible, Electric Company. Specify the name of the part wanted, quantity required, and When ordering renewal parts, address the nearest Sales Office of the General replacement of any that are worn, broken or damaged. Sufficient quantities of renewal parts should be kept in stock for the prompt necessary, the drag magnet until the correct operating time is obtained. on the relay, using connections shown in Figure 10, arid adjust the time dial and, If If it is necessary to adjust the time characteristics, impose the chosen conditions Operating Time stop. After this adjustment is made, the contact wipe and gap must be rechecked. gap between the armature and the pole face by bending the contact operating arm The pickup and dropout of the telephone-type relay may be changed by adjusting the Pickup and Dropout this procedure until the relay contacts just close for Vi leading or lagging V2 by resistor until the contacts just close. Now, with rated voltage on both circuits, angle is desired, set V2 at rated voltage, leading Vi by 200. Adjust the left hand determine the angle at which the contact closes with V2 lagging Vi. If the two angles are unequal, equalize them at 200 by adjusting the right hand resistor. Then Using the connections shown in Figure 10, set Vi at rated voltage. If a 200 closing check the closing angle with V2 leading Vi, and readjust if necessary. Continue 200. Use the same procedure for other closing angle settings. GE 1-90802 RENEWAL PARTS

GEl- 90802 (8032224) Figure 1 (316547535 0) Figure 2 Figure 3 Lgure 4 ligure Figure 2 Figure 9 Fgure 10 Figure 11 Figure 12 Figure 13 Figure 14 Figure 15 (2038825) (8038823) (K-6400151-3) Hgurc 5 (337640964-1) Fgure S (K 6400150-2) (016546040-4) (016547532 i) (026430496-1) (016547533-0) (016547534-0) (8025039) (020842314-0) (0208A2315-O) (K-62O9271-5) 135 Relay in its Case, Front View Cover Typical Voltage/Phase-Angle Characteristic of 50/60 Cycle Relay for Various Closing-Angle Adjust merits with Rated Voltage Maintained on One Circuit. 12 Type IJS5?D Relay Unit in Cradle (Front View) 12 Type 135520 Relay Unit in Cradle (Rear View) 12 Typical Time/Phase-Angle Curve of Relay Type 13S52D1 with Rated Voltage 13 Typical Time/Phase Angle Characteristic of 50/60 Cycle Relay 13S52D3 with Rated Voltage on Both Circuits 13 Operating Time of Type IJS Relay with 20 Closing Angle at 00 Phase Displacement, Rated Voltage, 50/60 Cycles on Both Circuits Internal Connection Diagram for 13S52D Relay Pickup Test Connections (Front View) for 1JS520 Relay Elementary Diagram of External Connections of Type IJS Relays Time Test Connections for Relay Type 13S52D Connections and Curve to Make Approximate Closing-Angle Adjustment without Phase Shifter on 50/60 Cycle Type IJS52D Relay at Rated Voltage Cross Section of Drawout Case Showing Position of Auxiliary Brush IJS52D3A Cutoff Slip vs. Time Dial Settings for Closing-Angle Settings of 20, 40 and 600 IJS52D1A Cutoff Slip vs. Time-Dial Settings for Closing-Angle Settings of 20, 400 and 60 Outline and Panel Drilling Dimensions for Type IJS Relay 13 13 14 14 14 15 15 16 17 18 11

20 10 0 a - AD 4 C. 200 300-0 I0 0 0 12 in Cradle (Front View) in Cradle (Rear View) Hgure 2 (8038825) Type IJS52D Relay Unit Figure 3 (8038823) Type IJS52D Relay Unit for Various Closing-Angle Adjustments with Rated Voltage Maintained on One Circuit Figure 1 (0165A7535-0) Typical Voltage/Phase-Angle Characteristic of 50/60 Cycle Relay / CL0SEITHRATEV0LTA \ o 0 60 /50 500 40 60 ANGLE T WHICH NTACTS I I IT R LrSTARLE RSIS4OR TO QUALIZF CLOSING ANGLES _ø.,-- CRADLE AUXILIARY IjNT B I---- AUXILIARY LRT I RE STRAINING COIL OPERATING COIL 1

,. I T4 cl so LLLLt i4 I L4_LL I444C *44C41 L_ 4LiLliLLL. L_11_ 1 I INC L_LL_liLLLi PUASI *144,41 541,444 SI orr*rrl r 441 i s 04444,4 144441 414 14444 I 044*4 II 1444 :41 Figure 4 (K 6400151-3) Typical Time/Phase Angle Curve of Relay Type IJS52D1 with Rated Voltage Figure 5 (0316A0964 1) Typical Time/Phase Angle Characteristic of 50/60 Cycle Relay 1JS52D3 with Rated Voltage on Both Circuits C J6 4 I - 40 0 J V a. o C 44 44 44. Figure 6 (K-6400150-2) Operating Time of Type his Relay with 200 Closing Angle at 00 Phase Displacement, Rated Voltage. 50/60 Cycles on Both Circuits Figure 7 (0165A6040 4) Internal Connection Diagram for 1JS52D elay 13

GEl- 90802 115 VOLT LEGEWO SlWII ET41 NIT 2L-LIM 4R VOLTM[ NIT 2JS tiloer V0tThf T9T C0 FCTICWS Figure 8 (0165A7532-1) Pickup Test Connections (Front View) for 13S520 Relay i 71 sf Fr :IZ.25 25 SIiLC CLOSE TL : M?rV rip Figure 10 (0165A7533-0) Time Test Connections for Relay Type IJS52D.7 1.+) CONT V)L TOO C C I CFLflO-.O T) L!%! ANTiMP tj SEAL IN :- T I.C7NNftTION 104 77444174 CLCSINC offo rt rjs IR rroc. Fr Fi, TO 1 134 OTIIR CINNE(TI N IMVI( EblETI0N NJ4R - 75 ThChRClII M (H7K 547.777 77110 SHEER-VOl TACI LVIII TIN 130 147 L NLII7710I.lHOf UNIT P7H54 CIUCIIII 17N144[17 52 0.5 0077TROL LW ILl (CYPT OW SOT AIJVIIJARY 7717 477 13452 Figure 9 (026430496-1) Elementary Diagram of External Connections of Type IJS Relays 14

GEl- 90802 Figure 11 (0165A7534 0) Connections and Curve to Make Approximate Closing Angle Adjustment without Phase Shifter on 50/60 Cycle Type IJS52D Relay at Rated Voltage CONNECTING PLUG MAIN BRUSH CONNECT!NG BLOCK a- AUXILIARY URJSH TERMINAL BLOCK NOTE AFTER ENGAGING AUX:LARY BRUSH, CONRECTIN( PLUG TRAVE3 1/4 INCH BEFORE ENGAGING THE MAIN BRUSH ON THE TERMINAL BLOCK Figure 12 (2025039) Cross Section of Drawout Case Showing Position of Auxiliary Brush 15

.1 - a - i a--i- 1 IrliltE 1-H IE -f *1 ih+f+hf± H±f -1-f4+H---- r r -- -I..: EJIiTP-. -;. i F1ff T1TVF 4 11- E, IU[ f4+ L1 I 15 -tr -r : rr :-. + h r - - ±-4+4 irr1 :r:ri r, -i r- - - Li_i : 44 1t 1JS51A3 CUTOFF SLIP VS TIME DIAL SE?rING FOR 200, 400 & 60 DLOS INC 4 SETTINGS,- - 1 I Fffl- LUJL. J1_._ --i+4 ± iiii -.----.- - -- -. 11H4i:;- r H I I: -frh- I -ihle - - - tr-f +, LIti ± ]- - -i - - 4 - --ti- H- - ;:Ei. - 1 -tui i+ H i_. L..i.. LLL. i_lu._li_l. i_li i_j_.._. --.i IL H.L..ti.,.L LJ.. Z.i. :t.- Figure 13 (0208A2314 0) IJS52D3A Cutoff Slip vs. Time Dial Settings for Closing Angle Settings of 200, 400 and 600 16

it.zir: Nt f: rlfff E ---; I.I ---- - -- - -4-.--_, i. 4-4 -- - 4-_.j...L -. l -.-_-+ L 3.. _1.,. J. 4 1.1.. --.fl.l Tht. _i.. -:l+ - 1 -. - Iu IJS5IA1 CUTOFF SLIP VS TINE DIAL SETTING FOR 200, 40, & 60 CLOSING 4.. SEINGS 4 t.- m: - Hi, :z -- I I -t I - r j 41, j E:: 1 -H 5*J.11-4-- E 4_44 r rr -ta z: r -j-4-4 -- i± -1-1-.- -....-- -. ---- - J - -L._- -. -. - -. zr ±+T_ i r L.. :Lrl -=.. ir -I L 1:1 k- - - LErt ;:ilzt ll -a. 4. Figure 14 (0208A2315-0) IJS52D1A Cutoff Slip vs. Time-Dial Settings for Closing-Angle Settings of 200, 400 and 600 17

PANEL LOCATION SEMI-FLUSH 5/16 18 STUDS SURFACE MTG. S, 375 212MM 9. 125 232MM 1/4 DRILL 4 HOLES GLASS 1. 125 29MM.CREWS 1 0-32 STUDS STUD NUMBERING 97531 00000 00000 10 8 6 2 BACK VIEW 5/8 DRILL 2 HOLES CUTOUT MAY REPLACE DRILLED HOLES -;--- 4 375 CUTUUT 1. 156 29MM 218 5MM 843 72MM 5. 687 144MM PANEL DRILLING FOR SEMI FLUSH MOUNTING FRONT VIEW 5.25 133MM 3/4 DRILL 10 HOLES 19MM I.500 12MM (TYPICAL) PANEL DRILLING FOR SURFACE MOUNTING FRONT VIEW TYPICAL DIM. INCHES MM C A SE 5/16-18 STUD 3.0 76MM VIEW SHOWING ASSEMBLY OF HARDWARE FOR SURFACE MIG. FIN STEEL PANELS Figure 15 (K-6209271 [81) Outline and Panel Drilling Dimensions IJS Relay for Type 18

GE Power Management 215 Anderson Avenue Markham, Ontario Canada L6E 1B3 Tel: (905) 294-6222 Fax: (905) 201-2098 www.ge.comlindsyslpm