Chillers & Heat Pumps Water terminals Roof tops Close control Water source heat pumps Direct expansion SYSCOIL 2 Range of fan coil units from 0.5 to 9.1 kw from 0.8 to 12.6 kw
SYSCOIL 2 Innovation for an optimum comfort Easy to install, improvement of sound levels/performances and Aqu@Net electronic control are the key developments carried on our new fan coil units. The SysCoil 2 units range is issued from that development striving to meet customers wishes and advices. The design of the grille, associated with a refined casing allows a harmonious and smart integration of the fan coil units in every kind of interiors. They are the ideal solution to air-condition agreeably and efficiently, flats, hotels, hospitals, offices and other premises, all year long. VC Vertical console HC Ceiling exposed Air flow from 95 to1397 m 3 /h Capacity from 0.5 to 9.1 kw for cooling Capacity from 0.8 à 12.6 kw for heating Very low sound level VN Vertical concealed HN Available with EC motor Ceiling concealed A design adapted to your comfort A design dedicated to your needs Systemair Products aim to be tuned to the market and costumers wishes. Thus, each product is designed and conceived to answer to your needs. Dedicated design for vertical installation Dedicated design for horizontal installation Robust design, easy installation Systemair offers you a range with a robust design for an easy and safe installation. A design dedicated to energy savings Full range available with EC fans High efficiency EC motors with low electrical consumption for significant energy savings Fitted with ECospeed 3 interface card (supplied as standard) for a 3-speed optimized running Energy label up to A class Very large working range External drain pan included as a standard Monobloc painted drain pan for better robustness
Quick selection guide 4 models : VC, HC, VN, HN 8 sizes : from 10 to 80 (air flow from 95 to 1397 m 3 /h) 3 versions : 2 pipes, 2 pipes/2 wires or 4 pipes 2 types of fans : AC (Syscoil 2 STD) or EC (Syscoil 2 EC) Configurations : with or without cabinet / Vertical or Horizontal SysCoil 2 STD - 2 pipes Sizes Capacities at middle speed (kw) Acoustic (at middle speed) Air flow Pressure 10 0,9 1,3 NR 16 111-283 m³/h 0-30 Pa 20 1,1 1,4 NR 21 105-265 m³/h 0-30 Pa 30 1,9 2,4 NR 23 229-483m³/h 0-30 Pa 40 2,1 2,7 NR 23 172-493 m³/h 0-30 Pa 50 3,1 3,9 NR 23 253-716 m³/h 0-40 Pa 60 4,2 4,0 NR 29 350-933 m³/h 0-40 Pa 70 5,8 7,4 NR 34 480-1064 m³/h 0-40 Pa 80 6,6 9,2 NR 34 660-1397 m³/h 0-40 Pa Other models of water terminals KOG LN 9-18 (Cassette) 1.6-4.5 kw 1.7-5.7 kw EC Motor Ductys 0.4-6.4 kw 0.6-8.1 kw EC Motor KOG LN 30-45 (cassette) 4.1-9.7 kw 5.2-11.7 kw EC Motor VH 4.4-28.4 kw 5.2-33.9 kw Hawair 1.3-3.8 kw 1.8-4.7 kw
Innovative components & control range High performance components Fans Available with AC and EC fan High quality 100% of the units are factory tested Coils 2 or 3 rows according to the mode Individually tested for leakage at 30 bars Valves 2 ways or 3 ways + bypass Innovative control range Aqu@net Electronic control Units provided with an ergonomic and discrete remote control that can be loose or integrated on the fan coil unit. All settings are made in the factory, so there is no needs to set anything on site. This innovating control offers, as a standard, a master/slave function up to 15 units from one single remote control. Other features like window contact, occupied/unoccupied, antifreeze modes are integrated without any additional cost. RCL remote control An elegant design to be integrated in every kind of environment The Syscoil 2 range is designed to be integrated in a harmonious and smart way into: Offices Hotels Administrations Industries Sysoft, the online selection tool by SYSTEMAIR AC Thanks to our online selection tool named Sysoft, select and dimension precisely and quickly, by yourself, THE water terminal you need. www.sysoftac.com
Technical data SysCoil 2 STD (AC fans) Sizes 10 20 30 40 50 60 70 80 Capacities - 2 Pipes S1 / S3 / S5 S1 / S3 / S5 S1 / S3 / S5 S1 / S3 / S5 S1 / S3 / S5 S1 / S3 / S5 S1 / S3 / S5 S1 / S3 / S5 Cooling (1) Total cooling capacity W 590/930/ 1290 Sensible capacity W 470/750/ 1050 Water flow l/h 102/161/ 222 Water pressure drop kpa 2.9/6.6/ 11.9 Heating (2) Heating capacity W 810/1300/ 1810 Capacities - 4 Pipes Total cooling capacity W 490/800/ 1110 Cooling (1) Heating (3) Sensible capacity W 390/640/ 900 Water flow l/h 85/137/ 192 Water pressure drop kpa 2.1/4.9/ 9.1 Heating capacity W 830/1240/ 1650 Water flow l/h 71/107/ 142 Water pressure drop kpa 1/1.9/ 3.3 700/1100/ 1490 520/830/ 1170 120/189/ 257 1.7/3.3/ 5.3 860/1390/ 1950 580/950/ 1310 430/720/ 1020 99/163/ 226 1.3/2.6/ 4.3 960/1380/ 1730 82/118/ 149 1.1/2.1/ 3.3 1210/1950/ 2400 1100/1710/ 2100 208/335/ 413 4.4/9.9/ 14.3 1350/2360/ 2970 1080/1760/ 2130 990/1550/ 1870 186/303/ 368 3.7/8.3/ 11.7 1560/2/ 2550 135/192/ 3.8/6.6/ 8.2 970/2140/ 2810 670/1620/ 2070 167/368/ 484 3.9/14/ 22.5 1370/2710/ 3670 860/1900/ 2520 590/1440/ 1880 148/327/ 435 3.3/11.5/ 18.7 1580/2660/ 3340 136/229/ 288 4.1/10.1/ 15.3 1620/3070/ 4090 1260/2160/ 3000 279/528/ 705 4.1/13/ 22.4 2050/3940/ 5400 1470/2790/ 3690 1150/1970/ 2690 254/480/ 635 3.5/10.9/ 18.4 2370/3760/ 4810 204/324/ 414 7.5/16.8/ 26.1 2630/4180/ 5460 1790/2960/ 4030 452/721/ 941 10.4/25.2/ 42.2 2360/3970/5 270 2410/3830/ 4980 1640/2700/ 3660 414/660/ 857 8.8/21.3/ 35.2 2340/3580/ 4530 201/308/ 391 9.1/18.5/ 27.9 3100/5840/ 6620 2170/4280/ 5030 533/1006/ 1140 4/13.9/ 17.9 4140/7370/ 8720 2840/5260/ 5980 1980/3840/ 4490 490/906/ 1030 3.4/11.3/ 14.6 4240/5900/ 7050 365/508/ 607 23.1/41.1/ 56.5 4710/6650/ 9140 3490/4930/ 6990 811/1146/ 1575 12.3/22.6/ 40.3 6520/9250/ 12580 4560/6490/ 9030 3360/4790/ 6880 785/1117/ 1555 11.6/21.7/ 39.6 6660/9440/ 11790 573/813/ 1016 17/31.9/ 48.1 Sound Levels - 2 Pipes Sound power level db(a) 33/41/47 32/44/51 31/45/53 29/46/53 36/48/57 40/52/58 46/59/63 52/57/66 Sound pressure level (4) db(a) 17/25/31 16/28/35 15/29/37 13/30/37 20/32/41 24/36/42 30/43/47 36/41/50 NR (4) db(a) 11/16/22 6/21/26 9/23/31 6/23/27 11/23/31 16/29/34 22/34/36 27/34/45 Sound Levels - 4 Pipes Sound power level db(a) 33/41/47 32/44/51 31/45/53 29/46/53 36/48/57 40/52/58 46/59/63 52/57/66 Sound pressure level (4) db(a) 17/25/31 16/28/35 15/29/37 13/30/37 20/32/41 24/36/42 30/43/47 36/41/50 NR (4) db(a) 11/16/22 6/21/26 9/23/31 6/23/27 11/23/31 16/29/34 22/34/36 27/34/45 Fans Number 1 1 1 2 2 2 2 3 Airflow - 2 Pipes m³/h 111/190/283 105/179/265 229/388/483 172/356/493 253/486/716 350/640/933 Airflow - 4 Pipes m³/h 95/168/253 89/161/241 214/366/450 162/333/461 242/466/671 334/614/885 480/893/ 1064 470/859/ 1012 660/936/ 1397 634/905/ 1370 Electrical Data - 230V / 1~ / 50Hz - 230V / 1~ / 60Hz Fan consumption - 2 pipes W 14/24/36 14/23/35 24/50/81 18/39/59 33/57/80 39/76/111 60/114/161 90/112/188 Fan consumption - 4 pipes W 14/24/36 14/23/34 24/50/80 18/39/58 33/56/78 39/75/110 60/113/159 90/112/188 Fan consumption - 2 pipes (EC fans) W 8/14/41 8/15/41 6/19/46 2/12/43 2/24/46 2/30/54 12/45/77 23/42/108 Fan consumption - 4 pipes (EC fans) W 8/14/39 8/15/40 6/18/45 2/12/41 2/23/44 2/28/52 12/44/74 22/41/116 Electrical heater (max) W 500 500 500/1000 1250/2500 1250/2500 1250/2500 1000/2000 1500/3000 Water connections Type Gas female threaded Cooling coil inches 1/2 1/2 1/2 1/2 1/2 1/2 3/4 1/2 Heating coil inches 1/2 Dimensions (LxWxH) VN HN mm mm VC mm HC mm 677 x x 430 677 x 430 x 766 x 477 766 x 477 x 225 677 x x 430 677 x 430 x 766 x 477 766 x 477 x 225 862 x x 430 862 x 430 x 951 x 477 951 x 477 x 225 1047 x x 430 1047 x 430 x 1136 x 477 1136 x 477 1232 x x 430 1232 x 430 x 1321 x 477 1321 x 477 1417 x x 430 1417 x 430 x 1506 x 477 1506 x 477 1232 x x 530 1232 x 530 x 1321 x 577 1321 x 577 1425 x x 530 1463 x 530 x 1508 x 578 1508 x 578 Weight VC / HC - 2 pipes kg 18 18 21,5 27 30 35 35 50 VC / HC - 4 pipes kg 19 19 22,5 29 32 37 37 52 VN / HN - 2 pipes kg 12 12 14,5 20 22 26 27 41 VN / HN - 4 pipes kg 13 13 15,5 22 24 28 29 43 (1) According to Eurovent standard. Air: 27 C DB/19 C WB, Water in: 7 C/12 C. (2) According to Eurovent standard. Air: 20 C, Water in: 50 C, same water flow as in cooling. (3) According to Eurovent standard. Air: 20 C, Water in: 70 C/60 C. (4) Informative data, considering a sound attenuation of the room and installation of 16dBA.
Systemair AC SAS Route de Verneuil 27570 Tillières-sur-Avre France Tel +33 02 32 60 61 00 Fax +33 02 32 32 55 13 Systemair srl Via XXV Aprile, 29 20825 Barlassina (MB) Italy Tel +39 0362 680 1 Fax +39 0362 680 693 Systemair AC SAS LEAF SYSCOIL 2-6P-S-1GB(07.16) www.systemair.com www.systemair.com