PRODUCT BROCHURE. Elastimold recloser Smart. Light. Flexible.

Similar documents
Molded Vacuum Reclosers The recloser you want, all in one package. Single- and Three-Phase Molded Vacuum Reclosers, 15 38kV

Solid Dielectric, Triple Option Reclosers Catalog O-vlt14

Solid Dielectric, Single Phase Recloser

Solid Dielectric, Triple Option Reclosers Catalog O-vlt14

16kA Solid Dielectric, Triple Option Reclosers Catalog VLT12

Solid Dielectric, Single Phase Reclosers

REPORT OF TEST ON Elastimold Molded Vacuum Reclosers (MVRs)

Solid Dielectric, Three Phase Reclosers CATALOG VS11

Cobra-S. Catalog Cobra-S

FEBRUARY 14, 2017 Elastimold Solid dielectric switchgear customer presentation

Solid Dielectric, Independent Pole Operated Reclosers Catalog O-vst16

solutions RUS accepted

Solid Dielectric, Triple Option Reclosers Catalog O-vst14

PRODUCT SELECTION GUIDE

Solid Dielectric, Three Phase Reclosers Catalog O-vs18

RUS accepted Catalog O-vst18

CATALOG. Joslyn Hi-Voltage Overhead reclosers & switches

Joslyn Hi-Voltage. Overhead Reclosers & Switches. In this section...

Molded Current-Limiting Fuse

Product Group Brochure. PS Range Capacitor Vacuum Switches

CATALOG. Elastimold Reclosers, switches and switchgear

Descriptive Bulletin. R-MAG TM magnetically actuated dead tank outdoor vacuum circuit breaker 15.5 kv - 38 kv

Descriptive Bulletin. R-MAG magnetically actuated dead tank outdoor vacuum circuit breaker 15.5 kv - 38 kv

your Green Power WIND POWER SOLUTIONS only Greener

Padmount Solid Dielectric Switchgear Catalog

ELASTIMOLD MOLDED VACUUM SWITCHGEAR

Wind Power Solutions. Make Energy Renewable and Reliable!

R-MAG. Vacuum Circuit Breaker with Magnetic Actuator Mechanism

Technical Specification for Pole Mounted Capacitor Rack

Q pole Pole Mounted Capacitor System

M-Force three-phase switch

M-Force three-phase switch

Elastimold Molded Reclosers, Switches & Switchgear. In this section... Elastimold. Molded Reclosers,

R-MAG Vacuum Circuit Breaker with Magnetic Actuator Mechanism 15.5 kv - 27 kv; 1200 A A

Surge Arresters. UltraSIL Polymer-Housed Evolution (10 ka) Surge Arresters. General. Construction. features

Three-Phase Pole Mounted Recloser

Metal-Enclosed Switches. Medium Voltage. Medium Voltage Metal-Enclosed Switches Contents

FEBRUARY 14, 2017 Joslyn Hi-Voltage Capacitor switches customer presentation

Eaton s Cooper Power Systems catalog Medium-voltage vacuum circuit breakers

OVR Three Phase Recloser 15 kv - 38 kv. Descriptive Bulletin

Edison single-phase capacitor switch

NOVA three-phase, microprocessorcontrolled

Outdoor live tank vacuum circuit breaker Type OVB-VBF for 24/36/40.5 kv applications

Single-phase step voltage regulators

Longest Life Product for Electric Furnace Applications! 100,000 Operations No Routine Maintenance Required!

COOPER POWER CA280012EN

Guide Specification. Three-Phase Solid Dielectric Trident-SR with SafeVu Integral Visible Break

TRIMOD TM 300R SERIES VACUUM RECLOSER

CATALOG. Joslyn Hi-Voltage Capacitor switches

GROUP D. Switch & Protective device.

Single-Phase Step Voltage Regulators

TRINETICS CSD SERIES OIL SWITCH INSTALLATION INSTRUCTIONS

Medium Voltage Metal-Enclosed Switches

3 Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8 Series

Surge Arresters. UltraSIL Polymer-Housed VariSTAR Surge Arresters: Normal-Duty (5 ka), Heavy-Duty (10 ka), and Heavy-Duty Riser Pole (10 ka)

Figure 1. Two and Three-phase MagneX.

Elastimold. Cable Accessories. Underground Distribution Switchgear. Molded Vacuum Switches and Fault Interrupters

SafeGear Motor Control Center Arc Resistant Metal-Clad Construction Descriptive Bulletin

Transmission Switching

A. Three-phase, oil filled self-cooled, padmounted transformers are installed outdoors on pads in the EWEB distribution system.

Edison modular fuse, vault application products

DIVISION 26 ELECTRICAL SECTION CIRCUIT BREAKERS

Descriptive bulletin. ReliaGear ND ANSI narrow frame metal-clad switchgear

DO-III Fuse Holder TPL , May 2000, Page 1 of 4. General Information on the DO-III Draw Out Load Break Expulsion Fuse Holder. ABB Inc.

JOSLYN HI-VOLTAGE CAPACITOR SWITCHES

Types VSA12, VSA12B, VSA16, VSA20, and VSA20A; three-phase; air-insulated; electronically controlled recloser

H U B B ELL L ABOR ATORIES CAPABILITY GUIDE

TECHNICAL DESCRIPTION

Advance 27 ANSI 27 kv switchgear

Type L Cutouts. UltraSIL Polymer-Insulated and Porcelain Type L Open Distribution Cutout. Description

D-73P disconnect and bypass switches

SafeGear TM Motor Control Center Arc resistant metal-clad construction Motor Control Center Descriptive bulletin

Surge Arresters. UltraSIL Housed VariSTAR Station Class Surge Arresters GENERAL CONSTRUCTION

SF 6 Gas Insulated Load Break Switch

Medium Voltage Metal-Enclosed Switches

Solar Power Switchgear & Energy Storage Renewable Energy Systems

PRODUCT BROCHURE. Elastimold ComboT integral separable connectors

Elastimold & Hi-Tech Fuse Products

COOPER POWER SERIES. Type VSA12, VSA12B, VSA16, VSA20, and VSA20A operation and installation instructions. Reclosers MN280063EN

Medium voltage switchgear SafeGear HD 63 ka arc resistant metal-clad switchgear. ABB Group February 25, 2015 Slide 1

Power/Vac Vacuum Replacement Breakers for GE Magne-Blast Type AM & AMH Breakers

SUBSTATION VACUUM CIRCUIT BREAKER (38KV)

SUBSTATION VACUUM CIRCUIT BREAKER (25.8 / 27KV)

THP145 HYBRID GAS INSULATED SWITCHGEAR (HGIS) Energy, Fast! tgood.com

SUBSTATION VACUUM CIRCUIT BREAKER (15.5KV)

25 kv Apparatus Bushings

Dead Tank Circuit Breaker 145PM40-C Compact design with enhanced reliability

Single-phase pad-mounted step voltage regulator

Loadbreak Apparatus Connectors

Solid Dielectric Load Break Switch SPECIFICATION. 25kV, 630A, 4 WAYS, 4 WAYS SWITCHED PADMOUNTED VACUUM LOAD INTERRUPTER

DSE201 Compact design with enhanced protection

Medium Voltage Outdoor Apparatus Portfolio 2009

CATALOG. Hi-Tech Fuse Products

NEW Solutions for Underground System Growth

600 A 15 kv class Cleer loadbreak connector system

600 A 28 kv class Cleer loadbreak connector system

C1000 Series Automatic Cap Bank

S&C TripSaver II. Cutout-Mounted Recloser. For enhanced lateral circuit protection at 15 kv and 25 kv

US Brochure. Tmax XT Molded case circuit breakers Simply XTraordinary

GENERAL. CONSTRUCTION External

Transcription:

PRODUT BROHURE Elastimold recloser Smart. Light. Flexible.

2 ELASTIMOLD RELOSER The new standard in reclosers The recloser you want, all in one package The need for automated reclosers has never been greater. Unfortunately, many of today s reclosers come with negatives. They weigh too much, and that makes them difficult to install. They aren t easy to upgrade, so you have to guess about what features to include in case you need them several years from now. What s more, if the recloser you stock doesn t come with superior technical support, service and built-in quality, you may find it worse than having no recloser at all. The Elastimold recloser addresses all of these issues, and more. Weighing no more than 58 lbs. as a single-phase unit and 211 lbs. as a three-phase unit, the Elastimold recloser s light weight makes it easier and less costly to install. Modular design means smart grid sensors can be added quickly and simply. Our recloser is compatible with both Schweitzer Engineering Laboratories (SEL ) and Beckwith Electric controls. The ABB Elastimold experts' customer support, technical expertise and collaborative working relationships with customers mean that you will have the information you need, exactly when you need it.

OVERVIEW 3 Now, as the industry implements smart grid technologies, our world-class designs, engineering and quality-rated production facilities, combined with exceptional after-sale support and training, have been applied to the nextgeneration recloser. Support and service best in the business The Elastimold brand is known for uncommon candor and fast, knowledgeable, user-oriented technical support. Lead times for the Elastimold recloser are short. From the first day you install it, no question is too small to receive our complete technical attention. If assistance is needed, our response will be swift, and often immediate. We offer unmatched customer service to go with world-class technical support, top warranties and training in all phases of installation and operation. Your crews will know exactly what we know about the Elastimold recloser. SEL controls are compatible with all configurations of the Elastimold recloser. Beckwith Electric controls are only compatible with three-phase and triple-single configurations.

4 ELASTIMOLD RELOSER Elastimold recloser MVR Smart, light and flexible The Elastimold recloser is world-class by design. It responds to every hardware requirement that utilities want, and then some. Smart Our recloser is smart grid ready with three integral load-side voltage sensors and provision to add source-side voltage sensors if desired. It is compatible with industry-leading controls from Schweitzer Engineering Laboratories and Beckwith Electric o. Light Weighing no more than 58 lbs. as a singlephase unit and 211 lbs. as a three-phase unit, the Elastimold recloser s light weight makes it easier and less costly to install. The simplicity of the mechanism design and the compactness of the encapsulated components contribute to making the Elastimold recloser easier to move and install. Flexible The Elastimold recloser is modular, so field upgrades and retrofits are easy and fast. The single-phase recloser has a pole rotation mounting bracket for easier installation. Made with your needs in mind We designed the Elastimold recloser only after extensive talks with electric utilities. Its characteristics, from easier-tosee open/close indicators to the many robust extra features that we consider standard are there because of you. Solid dielectric insulation urrent and voltage sensors Lifting rings Integrated pole mounting bracket Manual tripping lever Highly visible 360 indicators

OVERVIEW 5 Recloser operation The Elastimold molded vacuum recloser (MVR) operates electrically by energizing a magnetic actuator system with a completely sealed housing. Each pole contains a vacuum interrupter sealed in solid dielectric insulation for mechanical and high dielectric strength. The combination of the molded vacuum recloser with microprocessor controls accurately detects a wide range of line disturbances and provides reliable, high-speed isolation for adverse conditions. An open-closed position indicator provides a 360 view. An external manual trip assembly is located on the side; when in the down position, it maintains the recloser in a lockout position until it is manually restored. All electrical control connections are made through a sealed single-environment control cable connector on the side. Top silicone sheds urrent transformer Side silicone terminal Vacuum bottle Main body EPDM insulation Solid dielectric diaphragm Pull rod assembly/ load-side voltage sensor Bottom silicone sheds Upper cover Magnetic actuator Lower cover Position indicator

6 ELASTIMOLD RELOSER Elastimold recloser MVR Features and benefits Smart grid ready Integral current transformer (T) (1000:1/500:1 flexibility) and load-side voltage sensors; with provisions to add Elastimold source-side voltage sensors. urrent sensor ompatible with industry-leading controls: SEL controls SEL-351R SEL-351RS Kestrel SEL-351R Falcon SEL-651R-2 Pull rod assembly/ load-side voltage sensor Notes: Use with the SEL-351R and SEL-351R Falcon requires connection via MVR power module. The power module is connected to the recloser via a 6' 32-pin cable. Voltage sensors require SEL-651R-2 control with six 8 V A LEA inputs. SEL is a registered trademark of Schweitzer Engineering Laboratories, Inc. Smart SEL-351RS Kestrel 10/14-pin cable SEL-351R 14-pin cable SEL-351R Falcon 14-pin cable SEL-651R-2 32-pin cable Beckwith M-7679 R-PA 32-pin cable

FEATURES AND BENEFITS 7 ompatible with industry-leading controls: Beckwith recloser control M-7679 R-PA Embedded cyber security including: -- Role-based security -- omplex passwords -- Individual user accounts with activity log -- IPSec (VPN) tunnel -- ompatible with Radius password management systems -- IEEE 1686 compliant with additional features and functions to help customers with NER IP V5 ompatible with both three-phase and triple-single reclosers Recloser status monitoring tool displays real-time reclosing sequence and fault clearing time onnects with 32-pin cable Smart Typical control settings A range of controls is available for the Elastimold recloser. A typical control includes: Overcurrent protection fast and delay curves Sensitive earth fault omplete metering Recloser wear monitor Loop automation Fault locator Flexible control logic and integration Supervisory control and data acquisition (SADA) ready multiple communications protocols Load profile

8 ELASTIMOLD RELOSER Elastimold recloser MVR Features and benefits Lightweight Internal diaphragm and silicone rubber sheds reduce weight. Weight Singlephase Threephase Others Elastimold standard standard 15 kv 27 kv 38 kv Others Elastimold standard standard Others Elastimold standard standard 100 lb. 57 lb. 100 lb. 57 lb. 130 lb. 58 lb. 45 kg 25.8 kg 45 kg 25.8 kg 60 kg 26.3 kg 333 lb. 208 lb. 333 lb. 208 lb. 430 lb. 211 lb. 150 kg 94.3 kg 150 kg 94.3 kg 195 kg 95.7 kg Proven solid dielectric insulation Molded EPDM main body with overlapping silicone rubber sheds for improved dielectric weatherability and UV performance. Silicone rubber Silicone rubber Light EPDM rubber Silicone rubber Simplified mechanism Translates into a lightweight device.

FEATURES AND BENEFITS 9 Modular design Optimized modular design is lightweight and maintenance-free*. Design is modular and allows for individual pole or shed replacement if ever required. Top shed *Because it uses no oil or gas to potentially leak and require monitoring and maintenance, the Elastimold recloser is considered maintenance-free. Side terminal Bottom shed Flexible Pole rotation mount The single-phase recloser has a unique pole rotation mounting bracket for easier installation and 0 to 180 repositioning. 180 repositioning Mounting bracket Note: PPE should be worn.

10 ELASTIMOLD RELOSER Elastimold recloser MVR Features and benefits Easy-to-see position indicator 360 position indicator view with large color-coded reflective open/ closed indicators on bottom of recloser for easy visibility from ground level. losed indication Open indication Innovative Reliable long-life mechanism The state-of-the-art design of our magnetic actuator offers over 10,000 trip and close operations with no maintenance required.* *Because it uses no oil or gas to potentially leak and require monitoring and maintenance, the Elastimold recloser is considered maintenance-free. Magnetic actuator Single- and three-phase tripping capabilities The fast and highly reliable electrically ganged operation provides flexibility of simultaneous three-phase tripping or singlephase tripping with threephase lockout. The manual trip lever is mechanically linked to trip and lock out all three phases simultaneously. Trip handle normal, closed position lose phase position Open and locked-out position Trip phase position

FEATURES AND BENEFITS 11 Reduced inventory items Incorporating extra features and extended capabilities as standard can result in less stock on your floor. Innovative Rated max. voltage ontinuous current (A) Others standard 15 kv 27 kv 38 kv Elastimold standard Others standard Elastimold standard Others standard Elastimold standard 630 800 630 800 630 800 BIL (kv) 95 150 125 150 150 170 Pollution level Required creep in. (mm) Elastimold standard in. (mm) 15 kv 27 kv 38 kv Required creep in. (mm) Elastimold standard in. (mm) Required creep in. (mm) Elastimold standard in. (mm) I Light 9.8 (248) 17.0 (432) 23.9 (608) II Medium 12.2 (310) 21.3 (540) 30.0 (760) III Heavy 15.3 (388) 26.6 (675) 37.4 (950) IV Very heavy 18.9 (481) 41.5 (1054) 33.0 (837) 41.5 (1054) 46.4 (1178) 51.0 (1295)

12 ELASTIMOLD RELOSER Elastimold recloser MVR Installation Typical recloser installation detail Arresters are recommended to provide protection against overvoltage conditions. When arresters are installed, they should be mounted on the supplied arrester brackets or as close to the recloser as practical. Line Recloser PT LINE Line NEUTRAL neutral GROUND ground Arresters Pole ground System neutral POWER Power MODULE module Optional: 500:1 jumper cable dual ratio Ts will only be used if needing 500:1 T ratio Utility pole SEL-351R and SEL-351R Falcon only; cable plugs directly into recloser on SEL-351RS Kestrel, SEL-6516-2 and Beckwith M-7679 R-PA ontrol cable Recloser control Ground GROUND ontrol ONTROL Supply SUPPLY Protective shield around pole ground

LINE TO LINE = 150KV INSTALLATION AND DIMENSIONS 13 Elastimold recloser MVR Dimensions single-phase reclosers LOSED - RED OPEN/LOSED INDIATOR 15 kv and 27 kv single-phase reclosers 24.08 [611,6] 3.36 [85,3] 19.72 [501] 36.15 [918,2] 8.63 [219,3] NOTES: 1) DIMENSIONS IN BRAKETS [XXX] ARE MILLIMETERS. 2) MAXIMUM ANTILEVERED TERMINAL PAD LOAD OF 60 LBS. [27 KG.] PER PAD ALLOWABLE. HORIZONTAL ABLE TENSIONS PER PHASE TO 1.75 BE OPPOSITE IN DIRETION. 3) WEIGHT= 58 LBS. [26.3 KG.] [44,5] 4) STANDARD POSITION AS SHOWN. TRIP POSITION SHOWN DOTTED. 5) ONNETION OF THE RELOSER TO THE DESIGNATED LINE AND LOAD SIDE TERMINALS IS ONLY REQUIRED IF THE RELOSER IS BEING USED WITH A ONTROL ONTAINING DIRETIONAL OVER URRENT APABILITY. 6) REEPAGE DISTANE: LINE TO GROUND = 51.00" [1295] LOAD TO LINE = 60.00" [1524] 7) INTERRUPTER RATING = 12.5 KA 8) BIL: LINE TO GND = 170KV LINE TO LINE = 170KV 35.05 [890,1] NAMEPLATE 19.60 [497,8] UAL TRIP HANDLE (SEE NOTE 4) N/LOSED INDIATOR (SEE VIEW) GHTS FRONT VIEW 3/8-16 BOLT FOR SEURING RELOSER TO FRAME10.07 [255,7] 38 kv single-phase recloser NOTES: 1) DIMENSIONS IN BRAKETS [XXX] ARE MILLIMETERS. 2) MAXIMUM ANTILEVERED TERMINAL PAD LOAD OF 60 LBS. [27 KG.] PER PAD ALLOWABLE. HORIZONTAL ABLE TENSIONS PER PHASE TO BE OPPOSITE IN DIRETION. 3) WEIGHT= 58 LBS. [26.3 KG.] 4) STANDARD 1.75 POSITION AS SHOWN. TRIP POSITION [44,5] SHOWN DOTTED. 5) ONNETION OF THE RELOSER TO THE DESIGNATED LINE AND LOAD SIDE TERMINALS IS ONLY REQUIRED IF THE RELOSER IS BEING USED WITH A ONTROL ONTAINING DIRETIONAL OVER URRENT APABILITY. 6) REEPAGE DISTANE: LINE TO GROUND = 51.00" [1295] LOAD TO LINE = 60.00" [1524] 7) INTERRUPTER RATING = 12.5 KA 8) BIL: LINE TO GND = 170KV LINE TO LINE = 170KV UNDERSTANDING AND AGREEMENT BY AEPTANE OF THIS DOUMENT YOU AGREE THAT ALL RIGHTS TO THE DRAWINGS AND INFORMATION ONTAINE HEREON, AS WELL AS TO THE SUBJET MATTER HEREOF AND ALL PROPRIETARY AND NOVEL FEATURES DISLOSED HEREIN, ARE RESERVED BY THOMAS AND BETTS AND THAT DEVIES EMBODYING SUH FEATURES ORINFORMATION DERIVED FROM THESE DRAWINGS WILL NOT BE MANUFATURED BY OR FOR YOU OR DISLOSED TO OTHERS WITHOUT THE PRIOR EXPRESS WR RMATION ONTAINED THEREIN ARE AND REMAIN THE PROPERTY OF THOMAS AND BETTS AND ARE NOT TO BE OPIED OR REPRODUED OR DISLOSED TO OTHERS WITHOUT THE PRIOR WRITTEN ONSENT OF THOMAS AND BETTS ALL DRAWINGS AND INFORMATION TO BE RETURNED TO THOMAS AND BETTS UPON DEMAND OR UPON OMPLETION OF PURPOSE FOR WHIH LENT. 24.08 [611,6] 3.36 [85,3] NAMEPLATE 19.72 [501] 37.92 [963,1] 19.60 [497,9] 8.63 [219,3] OPEN/LOSED INDIATOR 35.05 [890,1] LOSED - RED UAL TRIP HANDLE (SEE NOTE 4) EN/LOSED INDIATOR (SEE VIEW) 3/8-16 BOLT FOR SEURING RELOSER TO FRAME 10.07 [255,7] OPEN/LOSED INDIATOR LOSED FRONT VIEW Note: All dimensions are shown in in. (mm).

E L A S T I M O L D R E LO S E R 14 LOSED - RED Elastimold recloser MVR Dimensions three-phase reclosers LOSED - RED NOTES: 1) DIMENSIONS IN BRAKETS [XXX] ARE MILLIMETERS. 2) MAXIMUM ANTILEVERED TERMINAL PAD LOAD OF 60 LBS. [27 KG.] PER PAD ALLOWABLE. HORIZONTAL ABLE TENSIONS PER PHASE TO BE OPPOSITE IN DIRETION. 3) WEIGHT= 208 LBS. [94.4 KG.] 4) STANDARD POSITION AS SHOWN. TRIP POSITION SHOWN DOTTED. 5) ONNETION OF THE RELOSER TO THE DESIGNATED LINE AND LOAD SIDE TERMINALS IS ONLY REQUIRED OPEN/LOSED INDIATOR 15 kv and 27 kv three-phase reclosers 3D FRONT VIEW OPEN/LOSED INDIATOR 15.50 [393,7] 15.50 [393,7] 1.75 [44,5] 1.75 [44,5] 24.20 [614,8] 12.95 [328,9] 42.56 [1081] 35.08 [891,1] 8.81 [223,7] 6) REEPAGE DISTANE: LINE TO GROUND = 41.50" [1054] LOAD TO GROUND = 43.60" [1107] LINE TO LOAD = 52.17" [1320] 7) INTERRUPTER RATING = 12.5 KA 19.60 [497,9] 1 6.40 [416,6] NOTES: NOTES: 1) DIMENSIONS IN BRAKETS [XXX] ARE MILLIMETERS. 1) DIMENSIONS 2) MAXIMUM ANTILEVERED TERMINAL PAD LOAD OF 60 LBS. IN BRAKETS [XXX] ARE MILLIMETERS. MAXIMUM ANTILEVERED TERMINAL PAD LOAD OF 60 LBS. [27 KG.] PER PAD ALLOWABLE. HORIZONTAL2) ABLE TENSIONS PER PHASE TO BE OPPOSITE IN DIRETION. [27 KG.] PER PAD ALLOWABLE. HORIZONTAL ABLE 3) WEIGHT= 208 LBS. [94.4 KG.] REEPAGE DISTANE: TENSIONS PER PHASE TO6)BE OPPOSITE IN DIRETION. 4) STANDARD POSITION AS SHOWN. 3) WEIGHT= 208 LBS. [94.4 KG.]LINE TO GROUND = 41.50" [1054] TRIP POSITION SHOWN DOTTED. LOAD TO GROUND = 43.60" [1107] 4) STANDARD POSITION AS SHOWN. 5) ONNETION OF THE RELOSER TO THE DESIGNATED LINE TO LOAD = 52.17" [1320] TRIP POSITION SHOWN DOTTED. LINE AND LOAD SIDE TERMINALS IS ONLY REQUIRED 7) INTERRUPTER RATING = 12.5 KA 5) ONNETION OF THE RELOSER IF THE RELOSER IS BEING USED WITH A ONTROL 8) BIL: LINETO TOTHE GNDDESIGNATED = 150KV ONTAINING DIRETIONAL OVER URRENT APABILITY. LINE AND LOAD SIDE TERMINALS LINEIS TOONLY LINE =REQUIRED 150KV X ENGLISH 6) REEPAGE DISTANE: LINE -TO GROUND = 41.50" [1054] LOSED RED LOAD TO GROUND = 43.60" [1107] LINE TO LOAD = 52.17" [1320] 7) INTERRUPTER RATING = 12.5 KA 8) BIL: LINE TO GND = 150KV LINE TO LINE = 150KV MATERIAL DRAWN R.ARTELLI HEKED IS INFORMATION IS TRANSMITTED SUBJET TO THE FOLLOWING UNDERSTANDING AND AGREEMENT BY AEPTANE OF THIS DOUMENT YOU AGREE THAT ALL RIGHTS TO THE DRAWINGS AND INFORMATION ONTAINE HEREON, AS WELL AS TO THE SUBJET MATTER HEREOF AND ALL PROPRIETARY AND NOVEL FEATURES DISLOSED HEREIN, ARE RESERVED BY THOMAS AND BETTS AND THAT DEVIES EMBODYING SUH FEATURES ORINFORMATION DERIVED FROM THESE DRAWINGS WILL NOT BE MANUFATURED BY OR FOR YOU OR DISLOSED TO OTHERS WITHOUT THE PRIOR EXPRESS WRITTEN ONSENT OF THOMAS AND BETTS. THESE DRAWINGS AND THE INFORMATION ONTAINED THEREIN ARE AND REMAIN THE PROPERTY OF THOMAS AND BETTS AND ARE NOT TO BE OPIED OR REPRODUED OR DISLOSED TO OTHERS WITHOUT THE PRIOR WRITTEN ONSENT OF THOMAS AND BETTS ALL DRAWINGS AND INFORMATION TO BE RETURNED TO THOMAS AND BETTS UPON DEMAND OR UPON OMPLETION OF PURPOSE FOR WHIH LENT. 38 kv three-phase recloser THOMAS & BETTS, PROPRIETARY RIGHTS INH METRI TORQUE BOLTS & NUTS TO EMS-26 UNLESS OTHERWISE SPEIFIED. LOSED - RED HOMAS & BETTS, PROPRIETARY RIGHTS ENGINEERING SPE. ALL DIMENSIONS ON THIS DWG AR OPEN/LOSED INDIATOR IF THE RELOSER IS BEING USED WITH A ONTROL ONTAINING DIRETIONAL OVER URRENT APABILITY. REAR VIEW LOSED - RED 33.72 [856,6] - ADD VOLTAGE/URR TAGS R JP 02/06/15 B - UPDATED PER FIRST REVIEW R - 10/23/14 A - REATED FROM 31880112 R JP 09/05/14 REV EN- DESRIPTION BY DATE 09/05/14 DATE APPROVED DATE DRAWI TITLE NEXT ASS'Y SAL 0.06 HK. DATE THIS INFORMATION IS TRANSMITTED SUBJET TO THE FOLLOWING UNDERSTANDING AND AGREEMENT BY AEPTANE OF THIS DOUMENT YOU AGREE THAT ALL RIGHTS TO THE DRAWINGS AND INFORMATION ONTAINE HEREON, AS WELL AS TO THE SUBJET MATTER HEREOF AND ALL PROPRIETARY AND NOVEL FEATURES DISLOSED HEREIN, ARE RESERVED BY THOMAS AND BETTS AND THAT DEVIES EMBODYING SUH FEATURES ORINFORMATION DERIVED FROM THESE DRAWINGS WILL NOT BE MANUFATURED BY OR FOR YOU OR DISLOSED TO OTHERS WITHOUT THE PRIOR EXPRESS WRITTEN ONSENT OF THOMAS AND BETTS. THESE DRAWINGS AND THE INFORMATION ONTAINED THEREIN ARE AND REMAIN THE PROPERTY OF THOMAS AND BETTS AND ARE NOT TO BE OPIED OR REPRODUED OR DISLOSED TO OTHERS WITHOUT THE PRIOR WRITTEN ONSENT OF THOMAS AND BETTS ALL DRAWINGS AND INFORMATION TO BE RETURNED TO THOMAS AND BETTS UPON DEMAND OR UPON OMPLETION OF PURPOSE FOR WHIH LENT. 24.20 [614,8] NOTES: 1) DIMENSIONS IN BRAKETS [XXX] ARE MILLIMETERS. 2) MAXIMUM ANTILEVERED TERMINAL PAD LOAD OF 60 LBS. [27 KG.] PER PAD ALLOWABLE. HORIZONTAL ABLE TENSIONS PER PHASE TO BE OPPOSITE IN DIRETION. 3) WEIGHT= 211 LBS. [95.7 KG.] 4) STANDARD POSITION AS SHOWN. TRIP POSITION SHOWN DOTTED. 5) ONNETION OF THE RELOSER TO THE DESIGNATED LINE AND LOAD SIDE TERMINALS IS ONLY REQUIRED 15.50 [393,7] OPEN/LOSED INDIATOR 3D FRONT VIEW OPEN/LOSED INDIATOR 15.50 [393,7] 12.95 [328,9] 42.56 [1081] 19.60 [497,9] REAR VIEW ENGINEERING SPE. REAR VIEW 35.55 [903] ENGINEERING SPE. X ENGLISH INH METRI TORQUE BOLTS & NUTS TO EMS-26 UNLESS OTHERWISE SPEIFIED. MATERIAL DRAWN R.ARTELLI HEKED REV 6) REEPAGE DISTANE: LINE TO GROUND = 51.00" [1295] LOAD TO GROUND = 52.00" [1320] LINE TO LOAD = 60.56" [1538] 7) INTERRUPTER RATING = 12.5 KA 8) BIL: LINE TO GND = 170KV LOSED - RED IF THE RELOSER IS BEING USED WITH A ONTROL OP GROUND TERMIN QUALITY STD. Thomas & Be LEARANE SLOTS USER SUPPLIED 3/4 [19] DIA. LAG OR THRU BOLTS ALL DIMENSIONS ON THIS DWG AR 6) REEPAGE DISTANE: THI ALL DIMENSIONS ON THIS DWG ARE IN UNITS AS HEKED BELOW INH LINE TO GROUND = 51.00" [1295]X ENGLISH INH METRI mm DUAL mm LOAD TO GROUND = 52.00" [1320] TORQUE BOLTS & NUTS TO EMS-26 LINE TO LOAD = 60.56" [1538] UNLESS OTHERWISE SPEIFIED. MATERIAL A MEMBER OF THE ABB GR 7) INTERRUPTER RATING = 12.5 KA 8155 TB BOULEVAR 3D FRONT VIEW 35.08 [891,1] 8.81 [223,7] 18.23 [463,1] NOTES: NOTES: 1) DIMENSIONS IN BRAKETS [XXX] ARE MILLIMETERS. 1) DIMENSIONS IN BRAKETS [XXX] ARE MILLIMETERS. 2) MAXIMUM ANTILEVERED TERMINAL PAD LOAD OF 60 LBS. 2) MAXIMUM ANTILEVERED TERMINAL PAD LOAD OF 60 LBS. [27 KG.] PER PAD ALLOWABLE. HORIZONTAL ABLE TENSIONS PER PHASE TO BE OPPOSITE IN DIRETION. [27 KG.] PER PAD ALLOWABLE. HORIZONTAL ABLE Note: All dimensions are shown in in. (mm). 3) WEIGHT= 211 LBS. [95.7 KG.] 6) REEPAGE DISTANE: TENSIONS PER PHASE TO BE OPPOSITE IN DIRETION. 4) STANDARD POSITION AS SHOWN. LINE TO GROUND = 51.00" [1295] 3) WEIGHT= 211 LBS. [95.7 KG.] TRIP POSITION SHOWN DOTTED. LOAD TO GROUND = 52.00" [1320] 4) STANDARD POSITION AS SHOWN. 5) ONNETION OF THE RELOSER TO THE DESIGNATED LINE TO LOAD = 60.56" [1538] TRIP POSITION SHOWN DOTTED. LINE AND LOAD SIDE TERMINALS IS ONLY REQUIRED 7) INTERRUPTER RATING = 12.5 KA 5) ONNETION OF THE RELOSER TOGND THE=DESIGNATED IF THE RELOSER IS BEING USED WITH A ONTROL 8) BIL: LINE TO 170KV ONTAINING DIRETIONAL OVER URRENT APABILITY. LINE AND LOAD SIDE TERMINALS ISLINE ONLY REQUIRED LINE TO = 170KV HOMAS & BETTS, PROPRIETARY RIGHTS 1.75 [44,5] 1.75 [44,5] - ADD VOLTAGE/URR TAGS R JP 02/06/15 B - UPDATE PER FIRST REVIEW R - 10/23/14 A - REATED FROM 31880113 R JP 09/05/14 DATE 09/05/14 DATE APPROVED DATE NEXT ASS'Y DRAWI TITLE SAL

DIMENSIONS 15 Typical pole installations Dimensions triple-single cluster-mounting frame 15 kv, 27 kv and 38 kv triple-single cluster-mounting frame 74.94 [1903,6] 24.58 [624,3] 30.13 [765,2] REV 48.06 [1220,8] 48.06 [1220,8] 37.47 [951,8] 37.47 [951,8] LINE SIDE (SEE NOTE 5) 23.99 [609,3] TORQUE TERMINAL LUGS TO 25 FT/LBS LOAD SIDE (SEE NOTE 5) 19.60 [497,9] 1.75 [44,5] NOTES: 1) ALL DIMENSIONS ARE FOR 15/27KV UNITS UNLESS NOTED OTHER DIMENSIONS IN BRAKETS [XXX] ARE MILLIMETERS. 2) MAXIMUM ANTILEVERED TERMINAL PAD LOAD OF 60 LBS. [27 KG.] PER PAD ALLOWABLE. HORIZONTAL ABLE TENSIONS PER PHASE TO BE OPPOSITE IN DIRETION. 3) WEIGHT: RELOSER: 15-27KV = 57 LBS. [25.8 KG.] 38KV = 58 LBS. [26.3 KG] FRAME: 62 LBS. [28.1 KG] 4) STANDARD POSITION AS SHOWN. TRIP POSITION SHOWN DOTTED. 5) ONNETION OF THE RELOSER TO THE DESIGNATED LINE AND LOAD SIDELINE TERMINALS IS ONLY REQUIRED SIDE NOTE 5) IF THE RELOSER(SEE IS BEING USED WITH A ONTROL ONTAINING DIRETIONAL OVER URRENT APABILITY. 1.75 [44,5] 6) REEPAGETORQUE DISTANE 15-27KV: TERMINAL TO 25=FT/LBS LINE TOLUGS GROUND 41.50" [1054] LOAD TO GROUND = 43.60" [1107] LOAD SIDE LINE TO LOAD = 52.17" [1320] (SEE NOTE 5) REEPAGE DISTANE 38KV: LINE TO GROUND = 51.00" [1295] LOAD TO GROUND8.63 = 52.00" [1320] LINE TO LOAD = 60.56" [219,3][1538] 7) INTERRUPTER 19.60RATING 15-27KV AND 38KV = 12.5 KA [497,9] 8) BIL 15-27KV: LINE TO GND = 150KV LINE TO LINE = 150KV BIL 38KV: LINE TO GND = 170KV 15/27KV=36.15 LINE TO LINE = 170KV LINE SIDE [918,1] (SEE NOTE 5) TORQUE TERMINAL LUGS TO 25 FT/LBS LOAD SIDE (SEE NOTE 5) 1.75 [44,5] RELOSER 58.94 [1497] 19.60 [497,9] 38KV=37.92 [963,1] RIGHTLEARANE SIDE VIEW SLOTS F USER SUPPLIED 5/8 [16] DIA. LAG OR THRU BOLTS 1.50 [38,1] 35.04 [890,1] 8.63 [219,3] 15kV 25kV 35kV DETAIL A 8.63 SALE 0.250 [219,3] 15/27KV=36.15 [918,1] LOSED - R 38KV=37.92 [963,1] THOMAS & BETTS, PROPRIETARY RIGHTS THIS INFORMATION IS TRANSMITTED SUBJET TO THE FOLLOWING UNDERSTANDING AND AGREEMENT BY AEPTANE OF THIS DOUMENT YOU AGREE THAT ALL RIGHTS TO THE DRAWINGS AND INFORMATION ONTAINE HEREON, AS WELL AS TO THE SUBJET MATTER HEREOF AND ALL PROPRIETARY AND NOVEL FEATURES DISLOSED HEREIN, ARE RESERVED BY THOMAS AND BETTS AND THAT DEVIES EMBODYING SUH FEATURES ORINFORMATION DERIVED FROM THESE DRAWINGS WILL NOT BE MANUFATURED BY OR FOR YOU O ONSENT OF THOMAS AND BETTS. THESE DRAWINGS AND THE INFORMATION ONTAINED THEREIN ARE AND REMAIN THE PROPERTY OF THOMAS AND BETTS AND ARE NOT TO BE OPIED OR REPRODUED OR DISLOSED TO OTHERS WITHOUT THE PRIOR WRITTEN ONSENT OF THOMAS AND BETTS ALL DRAWINGS AND INFORMATION TO BE RETURNED TO THOMAS AND BETTS UPON DEMAND OR UPON OMPLETION OF PURPOSE FOR WHIH LENT. 15/27KV=36.15 [918,1] 38KV=37.92 Note: All dimensions are shown in in. (mm). [963,1] GROUND TERMINAL (TYP. FOR 4) RIGHT SIDE VIEW RIGHT SIDE36.50 VIEW [927,1] DETAIL A SALE 0.250

E L A S T I M O L D R E LO S E R 3188D0404 16 A REV DRAWING NUMBER TES: IMENSIONS IN BRAKETS [XXX] ARE MILLIMETERS. AXIMUM ANTILEVERED TERMINAL PAD LOAD OF 60 LBS. 7 KG.] PER PAD ALLOWABLE. HORIZONTAL ABLE ENSIONS PER PHASE TO BE OPPOSITE IN DIRETION. WEIGHT: RELOSER: 15-27KV = 57 LBS. [25.8 KG.] 38KV = 58 LBS. [26.3 KG] RAME = 62 LBS. [28.1 KG] TANDARD POSITION AS SHOWN. RIP POSITION SHOWN DOTTED. ONNETION OF THE RELOSER TO THE DESIGNATED NE AND LOAD SIDE TERMINALS IS ONLY REQUIRED THE RELOSER IS BEING USED WITH A ONTROL ONTAINING DIRETIONAL OVER URRENT APABILITY. 15 kv,15-27kv: 27 kv and 38 kv REEPAGE DISTANE INE TO GROUND = 41.50" [1054] pole-mounting frame triple-single OAD TO GROUND = 43.60" [1107] INE TO LOAD = 52.17" [1320] 10.00 pole REEPAGE DISTANE 38KV: [254] INE TO GROUND = 51.00" [1295] OAD TO GROUND = 52.00" [1320] INE TO LOAD = 60.56" [1538] NTERRUPTER RATING 15-27KV AND 38KV = 12.5 KA IL 15-27KV: LINE TO GND = 150KV LINE TO LINE = 150KV L 38KV: LINE TO GND = 170KV LINE TO LINE = 170KV Typical pole installations Dimensions triple-single pole-mounting frame NOTES: A 3188D0404 REV 22.16 [526,8] DRAWING NUMBER OTES: DIMENSIONS IN BRAKETS [XXX] ARE MILLIMETERS. MAXIMUM ANTILEVERED TERMINAL PAD LOAD OF 60 LBS. 27 KG.] PER PAD ALLOWABLE. HORIZONTAL ABLE TENSIONS PER PHASE TO BE OPPOSITE IN DIRETION. WEIGHT: 48.43 RELOSER: 15-27KV = 57 LBS. [25.8 KG.] [1230,2] 38KV = 58 LBS. [26.3 KG] FRAME = 62 LBS. [28.1 KG] STANDARD POSITION AS SHOWN. TRIP POSITION SHOWN DOTTED. LOSED - RED ONNETION OF THE RELOSER TO THE DESIGNATED LINE AND LOAD SIDE TERMINALS IS ONLY REQUIRED OPEN/LOSED INDIATOR F THE RELOSER IS BEING USED WITH A ONTROL ONTAINING DIRETIONAL OVER URRENT APABILITY. REEPAGE DISTANE 15-27KV: LINE TO GROUND = 41.50" [1054] LOAD TO GROUND = 43.60" [1107] LINE TO LOAD = 52.17" [1320] 10.07 REEPAGE DISTANE 38KV: [255,7] LINE TO GROUND = 51.00" [1295] LOAD TO GROUND = 52.00" [1320] LINE TO LOAD = 60.56" [1538] INTERRUPTER RATING 15-27KV AND 38KV = 12.5 KA 18.00 18.00 BIL 15-27KV: LINE TO GND = 150KV LINE TO LINE = 150KV [457,2] [457,2] BIL 38KV: LINE TO GND = 170KV LINE TO LINE = 170KV NOTES: 3D REAR VIEW 1) DIMENSIONS IN BRAKETS [XXX] ARE MILLIMETERS. 2) MAXIMUM ANTILEVERED TERMINAL PAD LOAD OF 60 LBS. KG.] PER PAD HORIZONTAL ABLE 1) DIMENSIONS [27 IN BRAKETS [XXX]ALLOWABLE. ARE MILLIMETERS. TENSIONS PER PHASE PAD TO BE OPPOSITE IN DIRETION. 2) MAXIMUM ANTILEVERED TERMINAL LOAD OF 60 LBS. [27 KG.] PER3) PAD ALLOWABLE. HORIZONTAL ABLE WEIGHT: TENSIONS PERRELOSER: PHASE TO BE OPPOSITE DIRETION. 15-27KV = 57INLBS. [25.8 KG.] 3) WEIGHT: 38KV = 58 LBS. [26.3 KG] RELOSER: 15-27KV = 57 LBS. [25.8 KG.] FRAME = 62 LBS. [28.1 KG] 38KV 58 LBS. [26.3POSITION KG] 4)=STANDARD AS SHOWN. FRAME = 62 LBS. KG] TRIP[28.1 POSITION SHOWN DOTTED. NOTES: 4) STANDARD POSITION AS SHOWN. 5) ONNETION OF THE RELOSER TO THE DESIGNATED 1) DIMENSIONS IN BRAKETS [XXX] ARE MILLIMETERS. TRIP POSITION SHOWN DOTTED. LINE AND LOAD SIDE TERMINALS IS ONLY 2) MAXIMUM ANTILEVERED PAD LOAD REQUIRED OF 60 LBS. 5) ONNETION OF THE RELOSER TOTERMINAL THE DESIGNATED IF THE IS BEING USED WITH A ONTROL KG.] PERRELOSER PAD ALLOWABLE. LINE AND [27 LOAD SIDE TERMINALS IS ONLYHORIZONTAL REQUIRED ABLE ONTAINING DIRETIONAL OVER URRENT APABILITY. TENSIONS PHASE BE OPPOSITE IN DIRETION. IF THE RELOSER IS PER BEING USEDTO WITH A ONTROL 6)DIRETIONAL REEPAGE DISTANE 15-27KV: 3) WEIGHT: ONTAINING OVER URRENT APABILITY. LINE TO15-27KV GROUND = 41.50" [1054] = 57 LBS. [25.8 KG.] 6) REEPAGERELOSER: DISTANE 15-27KV: LOAD TO= GROUND = 43.60" 38KV 58[1054] LBS. [26.3 KG] [1107] LINE TO GROUND = 41.50" LINE TO LOAD = KG] 52.17" [1320] FRAME = =62 LBS. [28.1 LOAD TO GROUND 43.60" [1107] STANDARD POSITION AS SHOWN. REEPAGE DISTANE 38KV: LINE TO4)LOAD = 52.17" [1320] TRIP POSITION SHOWN DOTTED. LINE TO38KV: GROUND = 51.00" [1295] REEPAGE DISTANE ONNETION THE RELOSER TO THE DESIGNATED LINE TO5)GROUND = 51.00" [1295] LOAD TO OF GROUND = 52.00" [1320] AND SIDE TERMINALS IS ONLY REQUIRED LOAD TOLINE GROUND =TO 52.00" [1320] LINELOAD LOAD = 60.56" [1538] IF 7) THE RELOSER IS BEING USED WITH A ONTROL LINE TO LOAD = 60.56" [1538] INTERRUPTER RATING 15-27KV AND 38KV = 12.5 KA ONTAINING DIRETIONAL OVER==URRENT 7) INTERRUPTER RATING 15-27KV 38KV 12.5 KA APABILITY. 8) BIL 15-27KV: LINEAND TO GND 150KV 6) REEPAGE DISTANE 15-27KV: 8) BIL 15-27KV: LINE TO LINE GND =TO 150KV LINE = 150KV TO GROUND = 41.50" [1054] LINELINE TO LINE = 150KV BIL 38KV: LINE TO GND = 170KV LOAD GROUND = 43.60" [1107] BIL 38KV: LINE TOTO GND = 170KV LINE TO LINE = 170KV LINE TO LOAD = 52.17" [1320] LINE TO LINE = 170KV REEPAGE DISTANE 38KV: LINE TO GROUND = 51.00" [1295] LOAD TO GROUND = 52.00" [1320] 3D REAR VIEW LINE TO LOAD = 60.56" [1538] 7) INTERRUPTER RATING 15-27KV AND 38KV = 12.5 KA 8) BIL 15-27KV: LINE TO GND = 150KV LINE TO LINE = 150KV BIL 38KV: LINE TO GND = 170KV LINE TO LINE = 170KV 15/27KV = 16.40 [416,7] 38KV = 18.20 [562,2] LOSED - RED LOSED - RED OPEN/LOSED OPEN/LOSED INDIATOR INDIATOR LOSED - RED 1.75 OPEN/LOSED INDIATOR [44,5] 1.75 [44,5] 24.08 [611,6] 35.31 [897] 8.63 [219,3] 19.60 [497,9] LOSED - RED OPEN/LOSED INDIATOR 22.12 [561,9] QUALITY STD. ENGINEERING SPE. MATERIAL STD. ALL DIMENSIONS ON THIS DWG ARE IN UNITS AS HEKED BELOW X ENGLISH INH METRI APPROVED DATE DEVIES EMBODYING SUH FEATURES ORINFORMATION DERIVED FROM THESE DRAWINGS WILL NOT BE MANUFATURED BY OR FOR YOU OR DISLOSED TO OTHERS WITHOUT THE PRIOR EXPRESS WRITTEN ON OMPLETION OF PURPOSE FOR WHIH LENT. A - REATED R REV EN- DESRIPTION BY XX 02/03/15 NEXT ASS'Y HK. DATE - mm Thomas & Betts A MEMBER OF THE ABB GROUP MATERIAL - INH mm DUAL TORQUE BOLTS & NUTS TO EMS-26 UNLESS OTHERWISE SPEIFIED. DATE DRAWN R.ARTELLI 02/03/15 HEKED DATE THIRD ANGLE PROJETION 8155 TB BOULEVARD MEMPHIS, TN 38125 1.50 PHONE: (800) 888-0211, FAX: (800) 888-0690 DRAWING[38,1] OUTLINE THREE 1PH RELOSER STANDARD POLE MOUTING FRAME, 15,27 AND 38kV TITLE SALE 0.059 SHT. SIZE D SHT. No. 1 of 4 DRAWING NUMBER 3188D0404 24.69 [627,1] DING AND AGREEMENT BY AEPTANE OF THIS DOUMENT YOU AGREE THAT ALL RIGHTS TO THE DRAWINGS AND INFORMATION ONTAINE HEREON, AS WELL AS TO THE SUBJET MATTER HEREOF AND ALL PROPRIETARY AND NOVEL FEATURES DISLOSED HEREIN, ARE RESERVED BY THOMAS AND BETTS AND THAT DEVIES EMBODYING SUH FEATURES ORINFORMATION DERIVED FROM THESE DRAWINGS WILL NOT BE MANUFATURED BY OR FOR YOU OR DISLOSED TO OTHERS WITHOUT THE PRIOR EXPRESS WRITTEN ONTAINED THEREIN ARE AND REMAIN THE PROPERTY OF THOMAS AND BETTS AND ARE NOT TO BE OPIED OR REPRODUED OR DISLOSED TO OTHERS WITHOUT THE PRIOR WRITTEN ONSENT OF THOMAS AND BETTS ALL DRAWINGS AND INFORMATION TO BE RETURNED TO THOMAS AND BETTS UPON DEMAND OR UPON OMPLETION OF PURPOSE FOR WHIH LENT. A - REV EN- Y RIGHTS OWING UNDERSTANDING AND AGREEMENT BY AEPTANE OF THIS DOUMENT YOU AGREE THAT ALL RIGHTS TO THE DRAWINGS AND INFORMATION ONTAINE HEREON, AS WELL AS TO THE SUBJET MATTER HEREOF AND ALL PROPRIETARY AND NOVEL FEATURES DISLOSED HEREIN, ARE RESERVED BY THOMAS AND BETTS AND THAT DEVIES EMBODYING SUH FEATURES ORINFORMATION DERIVED FROM THESE DRAWINGS WILL NOT BE MANUFATURED BY OR FOR YOU OR DISLOSED TO OTHERS WITHOUT THE PRIOR EXPRESS WRITTEN HE INFORMATION ONTAINED THEREIN ARE AND REMAIN THE PROPERTY OF THOMAS AND BETTS AND ARE NOT TO BE OPIED OR REPRODUED OR DISLOSED TO OTHERS WITHOUT THE PRIOR WRITTEN ONSENT OF THOMAS AND BETTS ALL DRAWINGS AND INFORMATION TO BE RETURNED TO THOMAS AND BETTS UPON DEMAND OR UPON OMPLETION OF PURPOSE FOR WHIH LENT. ETARY RIGHTS Note: All dimensions are shown in in. (mm). 6.00 [152,4] HE FOLLOWING UNDERSTANDING AND AGREEMENT BY AEPTANE OF THIS DOUMENT YOU AGREE THAT ALL RIGHTS TO THE DRAWINGS AND INFORMATION ONTAINE HEREON, AS WELL AS TO THE SUBJET MATTER HEREOF AND ALL PROPRIETARY AND NOVEL FEATURES DISLOSED HEREIN, ARE RESERVED BY THOMAS AND BETTS AND THAT DEVIES EMBODYING SUH FEATURES ORINFORMATION DERIVED FROM THESE DRAWINGS WILL NOT BE MANUFATURED BY OR FOR YOU OR DISLOSED TO OTHERS WITHOUT THE PRIOR EXPRESS WRITTEN GS AND THE INFORMATION ONTAINED THEREIN ARE AND REMAIN THE PROPERTY OF THOMAS AND BETTS AND ARE NOT TO BE OPIED OR REPRODUED OR DISLOSED TO OTHERS WITHOUT THE PRIOR WRITTEN ONSENT OF THOMAS AND BETTS ALL DRAWINGS AND INFORMATION TO BE RETURNED TO THOMAS AND BETTS UPON DEMAND OR UPON OMPLETION OF PURPOSE FOR WHIH LENT. ENGINEERING SPE. QUALITY STD. MATERIAL STD. R

DIMENSIONS 17 B 3188D0396 REV DRAWING NUMBER Typical pole installations Dimensions single and three-phase reclosers 15 kv, 27 kv and 38 kv single-phase recloser 27.50 [698,4] 13.75 [349,2] 2.87 [73] LOAD SIDE ARRESTER QUALITY STD. ENGINEERING SPE. ALL DIMENSIONS ON THIS DWG ARE IN UNITS AS HEKED BELOW QUALITY STD. ENGINEERING SPE. ALL DIMENSIONS ON THIS DWG ARE IN UNITS AS HEKED BELOW R.ARTELLI REV A MEMBER OF THE ABB GROUP 15 kv, 27 kv and 38 kv 5/8-11 BOLT/NUT three-phase recloser FOR MOUNTING FRAME HEKED mm Thomas & Betts MATERIAL DRAWN THIRD ANGLE PROJETION INH mm DUAL DATE 09/05/14 DATE APPROVED DATE 397 INH METRI 8155 TB BOULEVARD MEMPHIS, TN 38125 PHONE: (800) 888-0211, FAX: (800) 888-0690 APPROVED DATE DRAWING TITLE OUTLINE, RELOSER 1-PH, 15-27KV MOUNTING FRAME FOR LINE ARRESTERS AND TRANSFORMERS SEE SHEET 1 OF 2 EN- DESRIPTION BY HK. DATE 1/8 D 2 of 2 3188D0396 REV EN- DESRIPTION NEXT ASS'Y BY HK. DATE mm Thomas & Bett A MEMBER OF THE ABB GROU MATERIAL DATE R.ARTELLI 09/05/14 HEKED DATE THIRD INH mm DUAL 8155 TB BOULEVARD MEMPHIS, TN 38125 PHONE: (800) 888-0211, FAX: (800) DRAWN ELL AS TO THE SUBJET MATTER HEREOF AND ALL PROPRIETARY AND NOVEL FEATURES DISLOSED HEREIN, ARE RESERVED BY THOMAS AND BETTS AND THAT DEVIES EMBODYING SUH FEATURES ORINFORMATION DERIVED FROM THESE DRAWINGS WILL NOT BE MANUFATURED BY OR FOR YOU OR DISLOSED TO OTHERS WITHOUT THE PRIOR EXPRESS WRITTEN SEE SHEET 1 OF 2 DRAWING NUMBER SHT. No. NEXT ASS'Y SALE SHT. SIZE THOUT THE PRIOR WRITTEN ONSENT OF THOMAS AND BETTS ALL DRAWINGS AND INFORMATION TO BE RETURNED TO THOMAS AND BETTS UPON DEMAND OR UPON OMPLETION OF PURPOSE FOR WHIH LENT. REV INH METRI TORQUE BOLTS & NUTS TO EMS-26 UNLESS OTHERWISE SPEIFIED. G NUMBER X ENGLISH TORQUE BOLTS & NUTS TO EMS-26 UNLESS OTHERWISE SPEIFIED. 3188D0 EW X ENGLISH 6.08 [154,5] MATERIAL STD. DRAWIN 20.48 [520,1] DRAWING TITLE OUTLINE, RELOSER 1-PH, 15-27 SALE 1/8 SHT. SIZE D SHT. No. 2 of 2 DRAWING 3188 LOAD SIDE ARRESTER 5/8-11 BOLT/NUT FRONT VIEW 9.75 [247,7] 24.48 [621,7] 38.74 [984] 3/8-16 BOLT/WASHER FOR MOUNTING FRAME 19.37 [492] 20.48 [520,1] LEFT SIDE VIEW AS & BETTS, PROPRIETARY RIGHTS SEE SHEET ATION IS TRANSMITTED SUBJET TO THE FOLLOWING UNDERSTANDING AND AGREEMENT BY AEPTANE OF THIS DOUMENT YOU AGREE THAT ALL RIGHTS TO THE DRAWINGS AND INFORMATION ONTAINE HEREON, AS WELL AS TO THE SUBJET MATTER HEREOF AND ALL PROPRIETARY AND NOVEL FEATURES DISLOSED HEREIN, ARE RESERVED BY THOMAS AND BETTS AND THAT DEVIES EMBODYING SUH FEATURES ORINFORMATION DERIVED FROM THESE DRAWINGS WILL NOT BE MANUFATURED BY OR FOR YOU OR DISLOSED TO OTHERS WITHOUT THE PRIOR EXPRESS WRITTEN THOMAS AND BETTS. THESE DRAWINGS AND THE INFORMATION ONTAINED THEREIN ARE AND REMAIN THE PROPERTY OF THOMAS AND BETTS AND ARE NOT TO BE OPIED OR REPRODUED OR DISLOSED TO OTHERS WITHOUT THE PRIOR WRITTEN ONSENT OF THOMAS AND BETTS ALL DRAWINGS AND INFORMATION TO BE RETURNED TO THOMAS AND BETTS UPON DEMAND OR UPON OMPLETION OF PURPOSE FOR WHIH LENT. 18.93 [480,9] REV EN- DESRIP 8.93 [226,9] HOMAS & BETTS, PROPRIETARY RIGHTS INFORMATION IS TRANSMITTED SUBJET TO THE FOLLOWING UNDERSTANDING AND AGREEMENT BY AEPTANE OF THIS DOUMENT YOU AGREE THAT ALL RIGHTS TO THE DRAWINGS AND INFORMATION ONTAINE HEREON, AS WELL AS TO THE SUBJET MATTER HEREOF AND ALL PROPRIETARY AND NOVEL FEATURES DISLOSED HEREIN, ARE RESERVED BY THOMAS AND BETTS AND THAT DEVIES EMBODYING SUH FEATURES ORINFORMATION DERIVED FROM THESE DRAWINGS WILL NOT BE MANUFATURED BY OR FOR YOU OR DISLOSED TO OTHERS WITHOUT THE PRIOR EXPRESS WRITTEN SENT OF THOMAS AND BETTS. THESE DRAWINGS AND THE INFORMATION ONTAINED THEREIN ARE AND REMAIN THE PROPERTY OF THOMAS AND BETTS AND ARE NOT TO BE OPIED OR REPRODUED OR DISLOSED TO OTHERS WITHOUT THE PRIOR WRITTEN ONSENT OF THOMAS AND BETTS ALL DRAWINGS AND INFORMATION TO BE RETURNED TO THOMAS AND BETTS UPON DEMAND OR UPON OMPLETION OF PURPOSE FOR WHIH LENT. W REAR VIE 24.60 [624,7] Note: All dimensions are shown in in. (mm). L STD. QUALITY IN UNITS mm TION LE PROJE OW D BEL AS HEKE ARE THIS DWG BOLT/NUT 5/8-11 DUAL METRI FOR FRAME INHMOUNTING NGLISH NSIONS ON ALL DIME MATERIA STD.. RING SPE ENGINEE INH mm THIRD ANG & Betts MOUNTING FRAME FOR LINE ARRESTERS AND R

18 ELASTIMOLD RELOSER Typical pole installations Electrical characteristics Ratings and specifications 15 kv 27 kv 38 kv* Nominal system voltage (kv RMS) 14.4 25 35 Rated maximum voltage (kv RMS) 17.1 29.3 38 Nominal frequency (Hz) 50 or 60 50 or 60 50 or 60 Phase spacing on 3-phase units (inches) 15.5 15.5 15.5 BIL (kv) 150 150 170 Power frequency withstand dry (kv) 50 60 70 Power frequency withstand wet (kv) 45 50 60 ontinuous current (A RMS) 800 800 800 Eight-hour overload current (A RMS) 960 960 960 T ratio 1000/500:1 1000/500:1 1000/500:1 Interrupting current (ka RMS symmetrical) 12.5 12.5 12.5 Making current (ka asymmetrical peak) 32.5 32.5 32.5 reepage distances inches (line to ground) 41.5 41.5 51 Arc-extinction medium Vacuum Vacuum Vacuum Insulation medium EPDM/silicone rubber EPDM/silicone rubber EPDM/silicone rubber Mechanical operations 10,000 10,000 10,000 Normal operating temperatures -10 to 45-10 to 45-10 to 45 Normal operating conditions voltage sensor accuracy (load/line) ±3%/1% ±3%/1% ±3%/1% Extreme operating temperatures -40 to 65-40 to 65-40 to 65 Extreme operating conditions voltage sensor accuracy (load/line) 5%/1% 5%/1% 5%/1% T accuracy lass 1 lass 1 lass 1 Weight (single-phase/three-phase) 57/208 lbs. 57/208 lbs. 58/211 lbs. * Single-phase 38 kv units are rated for use on grounded systems only. Three-phase 38 kv units can be used for single-phase tripping on grounded systems only. For ungrounded systems, three-phase tripping is required.

RATINGS, SPEIFIATIONS AND TESTING 19 Test data summary Elastimold MVRs are tested under the requirements of ANSI 37.60 2003. This table highlights the testing covered in Elastimold Test Report # 372 17 12010. 37.60-2003 Standard clause and description 15 kv MVR compliance 27 kv MVR compliance 38 kv MVR compliance 6.2 Insulation (dielectric) tests 6.3 Switching tests 6.4 Making current capability 6.5 Operating duty tests 6.6 Minimum tripping current tests 6.7 Partial discharge (corona) tests 6.10 Temperature rise tests 6.11 Time-current tests 6.12 Mechanical duty tests 6.13 Surge withstand capability (SW) tests Other testing UV/weathering tests Other testing IE 62217 salt fog spray test (1,000 hr)

20 ELASTIMOLD RELOSER Ordering information Molded vacuum recloser catalog numbering system The following diagram shows how to construct a catalog number for a molded vacuum recloser: Indicates field that must be filled in to complete the full catalog number. Indicates optional field Product type Recloser R Phases Single phase 1 Three phase (single tank) 3 Triple single (3 - single) 4 Voltage class 15 kv 1 27 kv 2 38 kv 3 Frame Pole mounting frame for MVR1 1 Pole mounting frame for MVR3 3 Adjustable height substation frame for 3-phase (single-tank) Standard cluster mounting for triple single Horizontal mounting frame for triple-single Pole mounting for triple single Vertical mounting for triple single ustom frame Number of control power transformers None (customersupplied) Notes: Single-phase reclosers function with the SEL-351RS Kestrel control. Three-phase reclosers function with SEL-651R-2, SEL-351R or SEL-351R Falcon controls. The MVR power module must be specified when using a SEL-351R or SEL-351R Falcon control. Load-side voltage sensors are standard on all units and function with any SEL control having at least three 8 V A, 1M LEA inputs (LEA voltage inputs are not used with a SEL-351R or SEL-351R Falcon control). All units are upgradeable to source-side voltage sensing but require a SEL-651RX2XG control with six 8 V A, 1M LEA inputs. S H P V F X Single oil-filled PT 1 Dual oil-filled PT (applicable to 3-phase or triple-single) 2 Single dry-type PT 3 Dual dry-type PT (applicable to 3-phase or triple-single) 4 ontrol power transformer (PT) None (customersupplied) XX 15 kv class 1 7200: 120 V, 1 kva, 1PRI/1SE (single bushing) 7620: 120 V, 1 kva, 1PRI/1SE (single bushing) 7960: 120 V, 1 kva, 1PRI/1SE (single bushing) 13200: 120 V, 1 kva, 2PRI/2SE (two bushing) 1A 1B 1 1D 27 kv lass 2 13200: 120 V, 1 kva, 1PRI/1SE (single bushing) 14400: 120 V, 1 kva, 1PRI/1SE (single bushing) 13200: 120 V, 1 kva, 2PRI/2SE (two bushing) 14400: 120 V, 1 kva, 2PRI/2SE (two bushing) 2A 2B 2 2D 38 kv class 3 19920:120 V, 1 kva, 1PRI/1SE (single bushing) 3A 4 kv class 4 2300:120 V, 1 kva, 1PRI/1SE (single bushing) 2400:120 V, 1 kva, 1PRI/1SE (single bushing) Dual primary 4A 4B 14,400 V/7200 V: 120 V (dual primary), 1 kva DA ustomer-specified PT S ontrol model Ships without control (customer-supplied) 651R standard 651R premium 651R A transfer (applicable with dual PTs) 651R customer selected 651R customer special 351R standard 351R premium 351R customer selected 351RS Kestrel standard 351RS Kestrel premium 351RS Kestrel customer selected 351R Falcon standard 351R Falcon premium 351R Falcon customer selected Beckwith M-7679 R-PA standard Beckwith M-7679 R-PA premium Beckwith M-7679 R-PA customer special X A B D E F G H I J K L M N O P Q ontrol cable length and type Unit ships without cable 6', standard (for single-phase only) 20', standard 25', standard 30', standard 35', standard 40', standard 45', standard 50', standard 60', standard 75', standard 100', standard 20', 1st 10' armored 25', 1st 10' armored 30', 1st 10' armored 35', 1st 10' armored 40', 1st 10' armored 45', 1st 10' armored 50', 1st 10' armored 60', 1st 10' armored 75', 1st 10' armored 100', 1st 10' armored 20', full length armored 25', full length armored 30', full length armored X A B D E F G H I J K L M N O P Q R T U V W Y 35', full length armored 0 40', full length armored 1 45', full length armored 2 50', full length armored 3 60', full length armored 4 75', 1st 10' armored 5 100', full length armored 6 Special cable Z S

ORDERING INFORMATION 21 Source side voltage sensing None X 1 (One) voltage sensor 1 3 (Three) voltage sensors 3 Terminal lugs No terminal lugs X NEMA 2-hole lug 2 NEMA 4-hole lug 4 Aerial lug Special lug Line and load side arrester brackets No arrester brackets Both line and load side arrester brackets Load side arrester brackets only Line side arrester brackets only A S X B D E Surge arresters None 3 kv, 2.55 kv MOV 6 kv, 5.1 kv MOV 9 kv, 7.65 kv MOV 10 kv, 8.4 kv MOV 12 kv, 10.2 kv MOV 15 kv, 12.7 kv MOV 18 kv, 15.3 kv MOV 21 kv, 17 kv MOV 24 kv, 19.5 kv MOV 27 kv, 22 kv MOV 30 kv, 24.4 kv MOV 36 kv, 29 kv MOV ustomer specified (manufacturer, ratings) X A B D E F G H I J K L S Wildlife protectors (1 per Ø) No wildlife protectors Both side and top bushing of MVR (vented style) Both side and top bushing of MVR (non-vented style) Both side and top bushing of MVR (vented style) + protectors for PT(s) and/or arresters Both side and top bushing of MVR, (non-vented style) + protectors for pt(s) and/or arresters Side bushing of MVR (vented style) Side bushing of MVR (non-vented style) Top bushing of MVR (vented style) Top bushing of MVR (non-vented style) X B D E S R T U Position indicator Standard (green open, red closed) Alternative (green closed, red open) Factory pre-assembled Ships as subassemblies Ships completely assembled and site ready Frame pre-assembled, single-phase reclosers shipped upright ustomer-specific assembly and pre-wiring S A N Y F S ustomer special X X X X ontrol type 1-Phase 3-Phase Triple-single SEL-351RS Kestrel 10/14-pin cable X X SEL-351R X 14-pin cable X SEL-351R Falcon X 14-pin cable X SEL-651R-2 X 32-pin cable 32-pin cable Beckwith M-7679 R-PA X 32-pin cable 32-pin cable Notes: 1. Use with the SEL-351R or SEL-351R Falcon control requires connection via MVR power module. The power module is connected to the recloser via a 6 ft. 32-pin cable. 2. Voltage sensors require 8 V A, 1M LEA inputs. SEL is a registered trademark of Schweitzer Engineering Laboratories, Inc.

22 ELASTIMOLD RELOSER Ordering information Accessories Accessories Three-phase line-side arrester frame Three-phase load-side arrester frame Single-phase line-side arrester frame Single-phase load-side arrester frame Single-phase line and load-side arrester frame Horizontal mounting frame luster mounting frame Wildlife protector top bushing (one per phase) Wildlife protector side bushing (one per phase) Source-side voltage sensors (one per phase) Substation mounting frame NEMA 2-hole terminal lug kit NEMA 4-hole pad Aerial lug * Source-side voltage sensors for triple-single applications require different cable lengths. ontact your ABB representative for part number. Part number 3188D0120G1 3188D0121G2 31880122G1 31880123G1 31880474G1 3188D0293G1 3188D0204G1 3070A1191P1 3070A1190P1 31880075G1* 3188D0119G1 3188B0126G1 3180A0661P1 3070B1302P1

ORDERING INFORMATION 23 Ask us about the Elastimold recloser today. The Elastimold recloser team is eager to further demonstrate the benefits of this premier product. For additional technical information and details, contact us today.

ABB Installation Products Inc. Electrification Products Division 860 Ridge Lake Blvd. Memphis, TN 38120 solutions.abb/cable-accessories-apparatus 2019 ABB Installation Products Inc. All rights reserved. Specifications subject to change without notice. 7TKK000149 3.2019