Dynamic Adjustment Procedure for 700-series Digital Controls. Application Note (Revision A,8/1998) Original Instructions

Similar documents
Product Manual (Revision NEW) Original Instructions. Synchronous Motor Operated Potentiometer Operation Manual

Product Manual (Revision A) Original Instructions. Manifold Gauge Pressure Fuel Limiter for PG Governors. Operation Manual

Application Note (Revision NEW) Original Instructions. Governor Linkages for Butterfly Throttle Valves

Product Manual (Revision A) Original Instructions. Speed Droop Mechanism for PG Dial Governor. Operation Manual

Product Manual (Revision C) Original Instructions. Air/Fuel Ratio Control. Installation and Operation Manual

Product Manual (Revision A) Original Instructions. EG-3P Actuator Installation on Detroit Diesel V-149 Engine. Kit Installation Manual

Product Manual (Revision NEW) Original Instructions. PGA-EG, PGG-EG, PGM-EG 200/300/500 Governor/Actuator. Installation Manual

Product Manual (Revision NEW) Original Instructions. PGA-EG, PGG-EG, PGM-EG 12/29/58 Governor/Actuator. Installation Manual

Product Manual (Revision D) Original Instructions. PM Speed Adjusting Motor for UG-8 Governors. Operation Manual

UG-8 Speed Adjusting Devices. Product Manual (Revision NEW) Original Instructions. Pneumatic and Manifold Speed Setting for UG Type Governors

Product Manual (Revision H) Original Instructions. Solenoid Operated Shutdown Assembly for PGA and PGPL. Operation Manual

Product Manual (Revision G) Original Instructions. Auxiliary Devices for UG-40 Governors used in Marine Service.

Product Manual (Revision A, 8/2015) Original Instructions. ProAct II Digital Speed Control System. Technical Supplement

Product Manual (Revision D, 3/2000) Original Instructions. UG-5.7, UG-8, UG10 Governor. Installation Manual

Installation Manual Installation Kit. for EPG 1712/1724 Electric Actuator on the Caterpillar D3406 Engine. Manual 54086

Product Manual (Revision B) Original Instructions. PGA-58 and PGA-200/300 Vibration Resistant Governors. Operation Manual

Installation Manual Installation Kit. for EPG 1712/1724 Electric Actuator on the Caterpillar 3208 Engine. Manual (Revision A)

Application Note. Controllers for Stanadyne Pumps Using DC Integrated Actuators. Calibration Instructions. Manual 36579

Installation Kit. Product Manual (Revision NEW) Original Instructions

Product Manual (Revision NEW) Original Instructions. PGA Governor. Installation Manual

pplication Note (Revision A) Original Instructions Replacing the ST-125 Engine Control with an L-Series Speed Controller

Product Manual (Revision B) Original Instructions. PG-PL Governor Installation. Installation Manual

Installation Instructions. Bosch RSV Governor Shutdown Kit with 1751 & 1751ES Solenoids. Manual (Replaces SE-3042 Rev C)

EPG 1712/1724 or 512/524 Electric Actuator Installation. Product Manual (Revision NEW) Original Instructions

Application Note Original Instructions. Gas Fuel Control Valve (GFCV) O-ring Field Replacement Procedure

3055 Hydraulic Pump and Manifold Plate. Product Manual (Revision NEW) Original Instructions

Product Manual (Revision NEW) Original Instructions. EGB-10 Governor/Actuator. New Style Solenoid Speed Setting Mechanism.

EPG Electrically Powered Governor. Installation and Troubleshooting Manual. Models 1712/1724 and 512/524 without Position Feedback

Installation Instructions. APECS 0250 Kit Isuzu 4BG1-TRV Engine. Installation Instructions. Right-Hand Version. Manual 36561

Installation Instructions. APECS Actuator Kit for Daihatsu Engines (DM 950D) Installation Instructions. Manual 36588

701 Digital Speed Control for Reciprocating Engines. Product Manual (Revision D) Original Instructions

2301A Load Sharing & Speed Control with Dual Dynamics. Product Manual (Revision NEW, 1990) Original Instructions

UG-5.7, UG-8, UG10 Governor

Product Manual (Revision B) Original Instructions. EPG Electrically Powered Governor Models 501 and Installation and Operation Manual

Product Manual (Revision D, 5/2015) Original Instructions. 2301A Speed Control. Installation and Operation Manual

UG-10 Governor 4 20 ma Speed Setting System. Product Manual (Revision NEW) Original Instructions. UG Governors P7

Product Manual (Revision E) Original Instructions. Min/Max Control Systems. Installation and Operation Manual

Product Manual (Revision C) Original Instructions. EPG (Electric Powered Governor) with Position Feedback. Installation and Operation Manual

723PLUS Digital Speed Control for Single Engine Marine Propulsion Applications. Product Manual (Revision C) Original Instructions

Product Manual (Revision K) Original Instructions. EG-3C and EG-R Actuators. Installation and Operation Manual

721 Digital Speed Control

Kubota Kit 3A Engine Shutdown System for 70mm & 82mm Series Engines with 1751 & 1751ES Solenoids. Service Manual

Product Manual (Revision C) Original Instructions. Real Power Sensor , , & Installation and Operation Manual

Product Manual (Revision C) Original Instructions. Load Sharing Module. Analog Output Installation and Operation Manual

EGB-Proportional Governor/Actuator with Hydraulic Amplifier Systems. Product Manual (Revision F, 5/2013) Original Instructions

Product Manual (Revision B) Original Instructions. PG Governor Absolute Manifold Pressure Bias Load Control and Fuel Limiter.

Operation and Maintenance Manual. PG Governor Dial Type Speed Setting. Manual (Revision D)

Product Manual (Revision A) Original Instructions. EGB-10PLS Hydraulic Actuator. Installation and Operation Manual

UG-8D MAS ma Speed Setting. Product Manual (Revision C, 12/2013) Original Instructions

Product Manual (Revision B) Original Instructions Governor. Air Pressure Fuel Limiter. Operation Manual

Pneumatic Load Balance System for PGA Governors. Product Manual (Revision NEW) Original Instructions

4024 EPG (Electrically Powered Governor) Product Manual (Revision B, 3/2008) Original Instructions

723PLUS Digital Speed Control for Reciprocating Engines Performance Control 598. Product Manual (Revision B, 7/2008) Original Instructions

Application Guidelines for TecJet with E3 Fuel Blending System. Application Note (Revision NEW, 4/2010) Original Instructions

Product Manual (Revision B) Original Instructions Governor. Torque Rise, Low Idle Offset, and Idle Detent.

Product Manual (Revision NEW) Original Instructions. Duplex Filter Assembly Installation and Operation Manual

DYNA 8000 DYNA 8200 DYNA

Installation and Operation Manual. ProAct Digital Speed Control System for Models I and II. Manual (Revision K)

Product Manual (Revision A) Original Instructions. Hydraulic Amplifier (Pressure Input) Installation and Operation Manual

Load Sharing Module. Analog Output Installation, Operation, and Calibration Manual. Manual 26011

Product Manual (Revision B, 3/2014) Original Instructions. UG-15 Dial Governor. Installation and Operation Manual

Installation and Operation Manual. Load Sharing Module Vdc Output Manual (Revision B)

Product Manual (Revision L, 12/2014) Original Instructions. UG-5.7, 8, and 10 Lever Governor. Installation and Operation Manual

Installation and Operation Manual. 701A Digital Speed Control for Reciprocating Engines , ,

Installation and Operation Manual. ProAct III / IV Electric Powered Actuator and Driver. Manual 04127B

EG-3P Actuator. Installation and Operation Manual. including EG-1P, EG-3P with compensation, EG-3P oil motor, and EG-3P oil pump

Product Manual (Revision G, 12/2014) Original Instructions. UG Dial Governor. UG-5.7/UG-8/UG-10 Dial. Installation and Operation Manual

701A Digital Speed Control for Reciprocating Engines. Product Manual (Revision A) Original Instructions , ,

Product Manual (Revision B) Original Instructions. ProAct III / IV Electric Powered Actuator and Driver. Installation and Operation Manual

ST-125 Control System for Stanadyne DB-4 Series Pumps. Product Manual (Revision NEW) Original Instructions

Product Manual (Revision B) Original Instructions. PG-500 Case, Accumulator, and Power Cylinder. Installation and Operation Manual

Illustrated Parts Catalogue Woodward Diesel Systems. Illustrated Parts Catalogue. Perkins Engines (formerly Rolls-Royce) Pumps & Injectors

Application Note Original Instructions Development of Gas Fuel Control Systems for Dry Low NOx (DLN) Aero-Derivative Gas Turbines

ENGINE GOVERNING SYSTEMS

TG-13 and TG-17 Governors TG and TG Governors. Product Manual (Revision L, 2/2013) Original Instructions

Installation and Operation Manual. PG-PL Governor. Manual (Revision P)

723PLUS Standard Generator Control LON Load Sharing. Product Manual (Revision NEW) Original Instructions

Product Manual (Revision E, 5/2015) Original Instructions. UG-25 + Governor (P3 version) Installation and Operation Manual

Product Manual (Revision J, 7/2016) Original Instructions. PG-EG Integral EG Actuator for PG Governors. Installation and Operation Manual

EG1069X. Generator Electronic Governor Controller Operation Manual

Illustrated Parts Catalogue Woodward Diesel Systems. Illustrated Parts Catalogue. Perkins Engines (formerly Perkins Dorman) Pumps & Injectors

VariStroke II Electro hydraulic Actuator

Illustrated Parts Catalogue. Illustrated Parts Catalogue Woodward Diesel Systems. GE Transportation Systems Pumps & Injectors.

CAMBELT TENSION GAUGE

Product Manual (Revision 0) Original Instructions. APECS 2000 Electronic Controller. Installation and Operation Manual (replaces I-SAL-036)

ProAct II Electric Powered Actuator and Driver

Product Manual (Revision F) Original Instructions. PG Governor with Differential Servomotor Basic Elements. Installation and Operation Manual

New Method for Improving On-Line Loading Rates on Mechanical Governors By Gerald G. Runyan

Installation and Operation Manual. UG-5.7, 8, and 10 Lever Governor. Manual (Revision J)

C1 Controller & Driver. User s Guide

PRODUCT SERIES: DPG-2100

with discrete output (Overspeed) with auxiliary input (Synchronizer and Load Sharing)

IMPORTANT SAFETY INSTRUCTIONS

Tuning the System. I. Introduction to Tuning II. Understanding System Response III. Control Scheme Theory IV. BCU Settings and Parameter Ranges

Appendix A: Motion Control Theory

Owner s Manual & Safety Instructions

Product Manual (Revision NEW) Original Instructions Series Pumps. Installation and Operation Manual

3161 Governor. Product Manual (Revision C) Original Instructions. Installation and Operation Manual

Product Manual (Revision P, 7/2013) Original Instructions. Liquid Shutoff Valve 25 (LSOV25) Installation and Operation Manual

p.t.o. Slip clutch Read this material before using this product. Failure to do so can result in serious injury. Save this manual.

Transcription:

Application Note 01304 (Revision A,8/1998) Original Instructions Dynamic Adjustment Procedure for 700-series Digital Controls (700, 701, 701A, 702, 705, 721, 723, 723PLUS, 828)

General Precautions Read this entire manual and all other publications pertaining to the work to be performed before installing, operating, or servicing this equipment. Practice all plant and safety instructions and precautions. Failure to follow instructions can cause personal injury and/or property damage. Revisions This publication may have been revised or updated since this copy was produced. To verify that you have the latest revision, check manual 26311, Revision Status & Distribution Restrictions of Woodward Technical Publications, on the publications page of the Woodward website: www.woodward.com/publications The latest version of most publications is available on the publications page. If your publication is not there, please contact your customer service representative to get the latest copy. Proper Use Any unauthorized modifications to or use of this equipment outside its specified mechanical, electrical, or other operating limits may cause personal injury and/or property damage, including damage to the equipment. Any such unauthorized modifications: (i) constitute "misuse" and/or "negligence" within the meaning of the product warranty thereby excluding warranty coverage for any resulting damage, and (ii) invalidate product certifications or listings. Translated Publications If the cover of this publication states "Translation of the Original Instructions" please note: The original source of this publication may have been updated since this translation was made. Be sure to check manual 26311, Revision Status & Distribution Restrictions of Woodward Technical Publications, to verify whether this translation is up to date. Out-of-date translations are marked with compare with the original for technical specifications and for proper and safe installation and operation procedures.. Always Woodward reserves the right to update any portion of this publication at any time. Information provided by Woodward is believed to be correct and reliable. However, no responsibility is assumed by Woodward unless otherwise expressly undertaken. Copyright Woodward 1993 1998 All Rights Reserved

Application Note 01304 700-series Dynamic Adjustment Procedure Contents WARNINGS AND NOTICES... 2 ELECTROSTATIC DISCHARGE AWARENESS... 3 DYNAMIC ADJUSTMENT PROCEDURE FOR 700-SERIES DIGITAL CONTROLS.. 4 Introduction... 4 Notes on Dual Dynamics... 4 Pre-Start Settings... 4 Dynamic Adjustments... 8 Generator Set... 9 Mechanical Drive... 10 Illustrations Figure 1. Control Gain as a Function of Speed Error... 7 Figure 2. Control Gain as a Function of Control Output... 7 Woodward 1

700-series Dynamic Adjustment Procedure Application Note 01304 Warnings and Notices Important Definitions This is the safety alert symbol. It is used to alert you to potential personal injury hazards. Obey all safety messages that follow this symbol to avoid possible injury or death. DANGER Indicates a hazardous situation which, if not avoided, will result in death or serious injury. WARNING Indicates a hazardous situation which, if not avoided, could result in death or serious injury. CAUTION Indicates a hazardous situation which, if not avoided, could result in minor or moderate injury. NOTICE Indicates a hazard that could result in property damage only (including damage to the control). IMPORTANT Designates an operating tip or maintenance suggestion. Overspeed / Overtemperature / Overpressure The engine, turbine, or other type of prime mover should be equipped with an overspeed shutdown device to protect against runaway or damage to the prime mover with possible personal injury, loss of life, or property damage. The overspeed shutdown device must be totally independent of the prime mover control system. An overtemperature or overpressure shutdown device may also be needed for safety, as appropriate. Personal Protective Equipment The products described in this publication may present risks that could lead to personal injury, loss of life, or property damage. Always wear the appropriate personal protective equipment (PPE) for the job at hand. Equipment that should be considered includes but is not limited to: Eye Protection Hearing Protection Hard Hat Gloves Safety Boots Respirator Always read the proper Material Safety Data Sheet (MSDS) for any working fluid(s) and comply with recommended safety equipment. Start-up Be prepared to make an emergency shutdown when starting the engine, turbine, or other type of prime mover, to protect against runaway or overspeed with possible personal injury, loss of life, or property damage. Automotive Applications On- and off-highway Mobile Applications: Unless Woodward's control functions as the supervisory control, customer should install a system totally independent of the prime mover control system that monitors for supervisory control of engine (and takes appropriate action if supervisory control is lost) to protect against loss of engine control with possible personal injury, loss of life, or property damage. 2 Woodward

Application Note 01304 700-series Dynamic Adjustment Procedure Battery Charging Device To prevent damage to a control system that uses an alternator or battery-charging device, make sure the charging device is turned off before disconnecting the battery from the system. Electrostatic Discharge Awareness Electrostatic Precautions Electronic controls contain static-sensitive parts. Observe the following precautions to prevent damage to these parts: Discharge body static before handling the control (with power to the control turned off, contact a grounded surface and maintain contact while handling the control). Avoid all plastic, vinyl, and Styrofoam (except antistatic versions) around printed circuit boards. Do not touch the components or conductors on a printed circuit board with your hands or with conductive devices. To prevent damage to electronic components caused by improper handling, read and observe the precautions in Woodward manual 82715, Guide for Handling and Protection of Electronic Controls, Printed Circuit Boards, and Modules. Follow these precautions when working with or near the control. 1. Avoid the build-up of static electricity on your body by not wearing clothing made of synthetic materials. Wear cotton or cotton-blend materials as much as possible because these do not store static electric charges as much as synthetics. 2. Do not remove the printed circuit board (PCB) from the control cabinet unless absolutely necessary. If you must remove the PCB from the control cabinet, follow these precautions: Do not touch any part of the PCB except the edges. Do not touch the electrical conductors, the connectors, or the components with conductive devices or with your hands. When replacing a PCB, keep the new PCB in the plastic antistatic protective bag it comes in until you are ready to install it. Immediately after removing the old PCB from the control cabinet, place it in the antistatic protective bag. Woodward 3

700-series Dynamic Adjustment Procedure Application Note 01304 Dynamic Adjustment Procedure for 700-series Digital Controls Introduction The following procedures are a guide to adjusting the dynamics of Woodward 700-series Digital Speed Controls (700, 701, 701A, 702, 705, 721, 723, 723PLUS, 828). Refer to the specific control manual for instructions on the use of your Hand Held Programmer and set point adjustment (menu) procedures. Notes on Dual Dynamics If the unit will be operated in dual mode applications, it is desirable to use the dual dynamics feature of the control. Dual mode applications include generator sets operated in both isolated bus and utility parallel applications, dual-fuel engines, and mechanical drive systems with clutches engaged or disengaged. Connect the discrete input which switches dynamics to a relay operated when the breaker closes, fuel changeover occurs, or the clutch is engaged. Set up the primary set of dynamics for operating in the first mode, and then repeat the setup procedure on the alternate set of dynamics in the second mode. For gas fueled engines, or other engines that are difficult to control at no-load, the dual dynamics feature allows one set of dynamics for control at no-load, and the second to be used when load is applied. Examples include a setup with high stability to control very low frequency hunting at no-load, or a generator set that requires one dynamic setting to synchronize efficiently and another setting for proper operation under load. Pre-Start Settings This section describes the dynamic set points and provides a preliminary value for each set point prior to starting the engine. If a first set of dynamics in a control has already been tuned, or a control on an identical engine has been previously set up, those values may be used for pre-start settings if desired. 1. GAIN is the proportional gain term in a PID (Proportional, Integral, Derivative) controller. GAIN determines how fast the control responds to an error in speed when the speed reference is changed or a load disturbance occurs. A value too high (over 100%) will result in sustained oscillations in speed. A value too small (less than 50%) will result in poor control performance. Preliminary Value: Diesel 0.10 (700, 701, 701A, 702, 705, 721) Gas 0.01 Preliminary Value: Diesel 10 (723, 723PLUS, 828) Gas 1 4 Woodward

Application Note 01304 700-series Dynamic Adjustment Procedure 2. RESET is the integral gain term in the PID controller. RESET compensates for lags in the engine control loop. It prevents slow hunting at steady state and controls damping when speed error returns to zero after a speed disturbance. A value too high (over 100%) will result in large, low frequency oscillations in engine speed. The actuator will tend to bang from stop-tostop. A value slightly too high (above 50%) is indicated by an over-damped condition, or the speed error returning too slowly to zero. A value slightly too low is indicated by an under-damped condition, or the speed overshooting the reference and returning, possibly with several damped oscillations. A value too low will result in slow, low amplitude hunting of speed about the speed reference. Preliminary Value: Set according to the initial value line in the following chart. For diesel engines, the final RESET value will typically be near or below (left of) the initial value. For gas engines, the final RESET value will typically be near or above (right of) the initial value. A final RESET value less than 0.25 seconds is not recommended. 3. ACTUATOR COMPENSATION is the derivative term in the PID controller. It adjusts the rate of change in actuator output when a load disturbance occurs. A value too low will result in a slow and under-damped control. A value too high will result in excessive high frequency actuator movement. Preliminary Value: 25% of RESET value (0.25 x RESET) 4. GAIN RATIO works in conjunction with WINDOW WIDTH to provide higher control gain for load transients outside the window, and lower control gain inside the window at steady state. The base GAIN set point defines the control gain inside the window. GAIN is multiplied by the GAIN RATIO set point value when outside the window. GAIN RATIO should be turned off by setting its value to 1.0 during initial dynamic adjustment. Preliminary Value: 1.0 Woodward 5

700-series Dynamic Adjustment Procedure Application Note 01304 5. WINDOW WIDTH works in conjunction with GAIN RATIO as described above. WINDOW WIDTH is not absolute, but an anticipated value. When the control senses a change in speed that it predicts will cause a speed error exceeding the WINDOW WIDTH, the control gain is set to the value determined by multiplying GAIN by GAIN RATIO. This allows the control to act quickly on a transient. When speed error is returning to zero after a disturbance, the control also predicts the error entering the window and automatically reduces control gain to the value determined by GAIN. The amount of anticipation is a function of RESET, higher values of RESET resulting in faster anticipation. WINDOW WIDTH should be disabled during preliminary dynamic adjustments by setting GAIN RATIO to 1.0. Preliminary Value: 3% of rated speed reference 6. GAIN SLOPE works in conjunction with GAIN BREAKPOINT to increase or decrease the control gain as a function of engine load. GAIN SLOPE can help compensate for non-linear fuel systems on some gas fueled engines. GAIN SLOPE can also improve stability and response during load rejections by providing higher gain at higher engine loads. GAIN SLOPE modifies the control GAIN value only when the actuator output is greater than the GAIN BREAKPOINT set point by the equation: Control Gain = GAIN x [1.0 + (actuator output GAIN BREAKPOINT) x GAIN SLOPE] The gain slope function is effective only when the actuator output of the control is a function of engine load. It is desirable to set up the fuel system to provide at least a 50% change in actuator output from noload to full-load (e.g., 25% to 75%). Smaller changes and the effects of turbochargers on gas and diesel engines, and boost-related pressure regulators on gas engines, may reduce or defeat the effectiveness of the gain slope function. For preliminary dynamic adjustments, the gain slope function should be disabled by setting the GAIN SLOPE to 0.0. Preliminary Value: 0.0 7. GAIN BREAKPOINT works in conjunction with GAIN SLOPE as described above to define the point at which the GAIN SLOPE affects the actuator output. GAIN SLOPE is typically a positive value resulting in an increase in gain as fuel is increased. GAIN BREAKPOINT is normally set to match the actuator output obtained at no-load. This prevents the control gain from dropping too low during load rejections when the actuator output may go to 0%. For preliminary dynamic adjustments, the gain slope function should be disabled by setting GAIN SLOPE to 0.0. Preliminary Value: 25%, or equal to no-load actuator output if known 8. Repeat the procedure above for the second set of dynamics (if available). 6 Woodward

Application Note 01304 700-series Dynamic Adjustment Procedure Figure 1. Control Gain as a Function of Speed Error Figure 2. Control Gain as a Function of Control Output Woodward 7

700-series Dynamic Adjustment Procedure Application Note 01304 Dynamic Adjustments This section describes the dynamic adjustment procedures. Make preliminary adjustments with the engine at no load. 1. Select the GAIN set point on the dynamics menu. Be prepared to reduce the set point if instability should occur on the initial start-up. 2. Start the engine. If the engine is unstable, reduce the GAIN set point by 50%. If the instability decreases, reduce the GAIN set point in 50% steps until stability is achieved. If stability decreases as indicated by a slow hunt when reducing the GAIN, reduce the RESET and COMPENSATION set points each by 50% and double the gain. Repeat this procedure to obtain stable control. 3. Increase the GAIN value until the engine begins to hunt. Count the frequency of the hunt. (Count the number of oscillations per second.) Then reduce the GAIN value to 50% of the GAIN value where the engine started to hunt. The engine should be stable. 4. Set RESET to the inverse of the engine hunt frequency, that is: RESET = 1/(number of oscillations per second) Example: If the engine oscillated at 2 oscillations per second, then RESET = 1/2 = 0.5 5. Set COMPENSATION to 25% of RESET. 6. Increase the GAIN setting until the engine begins to hunt, then reduce to 50% of the value where the hunt began. This procedure will usually provide satisfactory control performance. Some engines, however, may be difficult to control at no load. If a slow, low-amplitude hunt occurs, first reduce GAIN by 50%, and then increase RESET by 100%. If this fails to reduce the low amplitude hunt, check for sticking linkages, pressure regulators, etc. Dynamic Adjustments may now be made with the engine under load. If the dual dynamics feature is used for no-load and loaded applications, the following adjustments apply to the second set of dynamics. Otherwise, they will provide a trimming procedure to the dynamics set above. Adjustments for generator sets are given first, followed by a procedure for mechanical drive units. If step mechanical loads can be applied to the unit, follow the generator set procedure with load steps. 8 Woodward

Application Note 01304 Generator Set 700-series Dynamic Adjustment Procedure The preferred adjustment procedure uses an artificial load bank. Use a utility or other sufficient capacity bus for a load only if a load bank is not available. 1. Apply a 25% to 50% step load to the generator, but avoid load-on steps that require significant time for the turbocharger to come up. This is best done with an artificial load bank, but plant loads such as compressor or fan motors may be started. If step loads cannot be obtained, use the procedure for mechanical drive units. Observe the off speed and recovery time performance when load is applied and dropped. 2. If excessive rapid but damped oscillations occur on load-off, reduce the GAIN set point slightly (25%). 3. If slow but damped oscillations occur on load-off, increase the RESET slightly. Increase the GAIN until the engine just begins to hunt and then reduce to 50% of that value. If speed slowly recovers on load-off, decrease the RESET slightly. Increase the GAIN until the engine just begins to hunt and then reduce to 50% of that value. 4. Set COMPENSATION to 25% of the RESET value and repeat steps 2 and 3 if desired. 5. Reduce COMPENSATION to 20% of RESET. Repeat the load steps and adjust GAIN as in steps 2 and 3 above. If control performance improves, leave COMPENSATION at 20% of RESET. If control performance degrades, increase COMPENSATION to 30% of RESET and readjust GAIN as in steps 2 and 3 above. If control performance improves, use the 30% value. If performance degrades or actuator movement is excessive, reduce COMPENSATION to 20 25% of RESET. The final value of COMPENSATION should normally be 20 30% of RESET. Satisfactory performance may be obtained with other values in certain systems. Values lower than 20% may require an increase in RESET and a decrease in GAIN from values obtained at 25%. A value of COMPENSATION greater than 30% will require a reduction in RESET. 6. Operate the generator set throughout its operating range and conditions. If excessive high speed but damped oscillations occur on load dumps, it may be desirable to reduce the GAIN setting. 7. If the above dynamic settings were performed on a isolated unit and the generator will be paralleled with a utility bus, duplicate the dynamic settings in the second set with the exception of setting GAIN to 50% of the value determined in steps 2 through 5 above. Parallel the generator to the utility and operate the generator set throughout its load range to verify correct performance. Woodward 9

700-series Dynamic Adjustment Procedure Application Note 01304 Mechanical Drive 1. Vary engine speed or load through the operating range of the engine and observe the performance. 2. During speed or load changes, if engine speed lags excessively behind the speed reference when it is changed, or off speeds are excessive when changing load, increase the GAIN set point. If fast hunting occurs, decrease the GAIN set point to 50% less than the value where hunting begins and increase RESET by 50%. During speed or load changes, if engine speed is observed to slowly oscillate in speed, decrease GAIN by 50% and increase the RESET by 50%. 3. Set COMPENSATION to 25% of RESET. If actuator movement is excessive, COMPENSATION may be reduced to lower values. For gas fueled engines, GAIN RATIO and WINDOW WIDTH adjustments may reduce actuator movement to acceptable levels without reducing COMPENSATION below the 25% of RESET level. In some cases, particularly if some slow process is being controlled, it may be necessary to reduce the ACTUATOR COMPENSATION value to zero. This could result in a under-damped system where some engine instability may occur, but may be required for satisfactory control of the process. 4. Repeat steps 1 through 3 until you are satisfied with engine performance. 5. Continue with the additional adjustments below. Additional Adjustments After completing the above procedures, you can get improved control performance by adjusting GAIN BREAKPOINT, GAIN SLOPE, GAIN RATIO, and WINDOW WIDTH. Gain Slope 1. Set GAIN BREAKPOINT equal to the control output an no-load. Alternately, an optimum value of GAIN at 0%, 20%, 40%, 60%, 80%, and 100% loads may be determined. Apply load for each step and increase GAIN until the engine begins to hunt, then reduce GAIN to 50% of the value where hunting begin. Record the value of GAIN and ACTUATOR OUTPUT for each point. Plot the values of GAIN vs ACTUATOR OUTPUT. If GAIN remains relatively constant up to a particular ACTUATOR OUTPUT value and then starts increasing, set GAIN BREAKPOINT equal to that value. If GAIN increases somewhat linearly with load, set GAIN BREAKPOINT at the no-load level. 2. Restore GAIN to the optimum no-load setting. Increase load to near 80%. Slowly increase GAIN SLOPE until the engine begins to hunt. Reduce GAIN SLOPE until the engine is again stable. 3. Operate the unit through its full load range. If instability occurs at some intermediate load, reduce GAIN SLOPE to obtain stable control. 10 Woodward

Application Note 01304 700-series Dynamic Adjustment Procedure Gain Ratio In general, GAIN RATIO provides the greatest control improvement on gas fueled engines. A useful final GAIN RATIO of 10.0 or more can often be obtained on gas engines. Diesel engines can seldom take advantage of values over 2.0. The following procedure is for gas and diesel fueled engines, but directed specifically to gas engines. 1. Verify WINDOW WIDTH is set to 3% of RATED SPEED. Smaller values will typically result in the control remaining outside the window due to the anticipatory nature of the window. 2. Reduce GAIN to 50% of its current value and double the GAIN RATIO. 3. Perform speed or load changes to the unit. If instability occurs, reduce GAIN RATIO until stability is obtained and continue with step 4. If control remained stable, increase GAIN by 50%. If control continues to remain stable, repeat steps 2 and 3. If control becomes unstable, reduce gain by 50% and repeat steps 2 and 3. 4. Watch actuator movement while the engine is at steady state. Actuator movement should be minimal. If the actuator only occasionally jumps due to erratic cylinder combustion (indicating the control is operating at the higher gain outside the window), WINDOW WIDTH is at the optimum value. If excessive fast actuator movement occurs, slowly increase WINDOW WIDTH until only occasional jumps are observed. If WINDOW WIDTH is changed, repeat steps 2 and 3 above. Be sure to save any changed set points before removing power from the control. To prevent possible damage to the engine resulting from improper control settings, make sure you save the set points before removing power from the control. Failure to save the set points before removing power from the control causes them to revert to the previously saved settings. Woodward 11

We appreciate your comments about the content of our publications. Send comments to: icinfo@woodward.com Please reference publication 01304A. PO Box 1519, Fort Collins CO 80522-1519, USA 1000 East Drake Road, Fort Collins CO 80525, USA Phone +1 (970) 482-5811 Fax +1 (970) 498-3058 Email and Website www.woodward.com Woodward has company-owned plants, subsidiaries, and branches, as well as authorized distributors and other authorized service and sales facilities throughout the world. Complete address / phone / fax / email information for all locations is available on our website.