Loadbreak Apparatus Connectors. 200 A 15 kv Class Loadbreak Elbow Connector with Optional Integral Jacket Seal GENERAL

Similar documents
200 A 15 kv class loadbreak elbow connector with optional integral jacket seal

200 A 15 kv class loadbreak elbow connector with optional integral jacket seal-canadian Edition

Loadbreak Apparatus Connectors

200 A 25 kv and 28 kv class loadbreak elbow connector with optional integral jacket seal-canadian Edition

200 A 25 and 28 kv class POSI-BREAK loadbreak elbow connector with optional integral jacket seal-canadian Edition

25 kv class fused loadbreak elbow connector

Deadbreak Apparatus. connectors. 600 A 15/25 kv Class GENERAL

Tests are conducted in accordance with IEEE Standard 386. ac 60 Hz 1 Minute Withstand 50

1500 kva Padmount Transformer delta Primary Voltage 208Y/120 Secondary Voltage

INSTALLATION PRODUCTION TESTS

600 A 15 kv class T-OP II deadbreak connector

600 A 25 kv class BT-TAP deadbreak connector

600 A 35 kv class BT-TAP deadbreak connector

Loadbreak Elbows. 3 Loadbreak Elbows. 200 Amp 5-15 kv Industrial pg Loadbreak Elbows. 200 Amp 25 kv Industrial pg. 254.

copper stud. If a 900 A rating is desired, specify a C as the 8th digit when determining your part number (See Table 3, page 3.)

600 A 35 kv class separable splices

600 A 15 and 25 kv class deadbreak accessories, tools, and replacement parts

600 A 35 kv class deadbreak accessories, tools, and replacement parts

Specifier's Guide COOPER POWER. Line installation and protective equipment master catalog 5 kv - 35 kv electrical distribution systems SERIES

600 A 15 and 25 kv class Cleer grounding elbow

600 A 15 kv class Cleer loadbreak connector system

15 kv Class Fused Loadbreak Elbow Connector with Interchangeable Fuse Capability

600 A 28 kv class Cleer loadbreak connector system

Grounding equipment COOPER POWER SERIES. Temporary Connections CA325004EN. Contents

200 A and 600 A, 15, 25, and 35 kv junction bars for separable connectors

ELB ES. Product Installation Instructions

QS-III. 5513A, 5514A, 5515A and 5516A 15 kv Cold Shrink Inline Splice Kits. Data Sheet CAUTION. 1. Product Description. 2. Applications.

600A Deadbreak Elbow. K656LR Elbow Connector (with Test Point) Features:


Product Description: Objective and Certification: Test Samples and Test Cable:

3M Cold Shrink QS-III Inline Splice Kits 15 kv 5513A, 5514A, 5515A and 5516A

3M Cold Shrink 1/C Transition Splice Kit QS-III, 5510A-1T-PILC Series

Fusing Equipment. Sidewall-Mounted and Cover-Mounted Bay-O-Net Fuse Assembly GENERAL INSTALLATION

Quick Splice II. 35 kv Molded Rubber Inline Splicing Kit Data Sheet. 2. Applications. 1. Product Description

IEC Separable Connectors 17.5 kv/24 kv, 630A

Quick Splice II 5451R. 25/28 kv Molded Rubber Cable Repair Splicing Kit Data Sheet. 1. Product Description. 2. Applications

Jumpering and grounding equipment and assemblies

ELASTIMOLD UNDERGROUND CABLE ACCESSORIES

ELB ELB

Edison modular fuse, vault application products

A 1.2 kv class externally removable secondary bushing

Surge Arresters. UltraSIL Polymer-Housed VariSTAR Surge Arresters: Normal-Duty (5 ka), Heavy-Duty (10 ka), and Heavy-Duty Riser Pole (10 ka)

Installation Instructions

25kV 200A Loadbreak Bushing Insert and Elbow Design Test Report. Report Number:

COOPER POWER SERIES. 600 A 15 kv and 25 kv class BT-TAP connector system installation instructions. Deadbreak Apparatus Connectors MN650004EN

Surge Arresters. UltraSIL Polymer-Housed Evolution (10 ka) Surge Arresters. General. Construction. features

COOPER POWER SERIES. 600 A 35 kv class BT-TAP connector system installation instructions. Deadbreak Apparatus Connectors MN650003EN

CERTIFIED TEST REPORT. Cooper Power Systems. 25 kv Class 200 Amp 15.2/26.3 kv SEPARABLE CONNECTOR SYSTEM

High Voltage Joints and Terminations up to 72,5 kv 145 kv

COOPER POWER SERIES. 600 A 15/25 kv class BOL-T and separable splice connector assembly installation instructions

Type L Cutouts. UltraSIL Polymer-Insulated and Porcelain Type L Open Distribution Cutout. Description

COOPER POWER SERIES. Fused loadbreak elbow connector installation instructions. Loadbreak Apparatus Connectors MN650014EN

COOPER POWER SERIES. 600 A 15/25 kv class T-OP II connector assembly installation instructions. Deadbreak Apparatus Connectors MN650048EN

Elastimold & Hi-Tech Fuse Products

3M Cold Shrink 3-Conductor Inline Splice Kits QS-III 5786A- MT, 5787A-MT and 5788A-MT 25/28 kv for use with Armored and Non- Armored 3/C Cable

Branch Splice QS-2001B

25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

35-kV 200-kV BIL Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

Eaton s Cooper Power Systems

3M Cold Shrink QT-III Silicone Rubber 3/C Cabinet Mount Termination Kit

Fusing Equipment. Sidewall-Mounted and Cover-Mounted Bay-O-Net Fuse Assembly GENERAL INSTALLATION

IEC Separable Connectors 36 kv and 42 kv, 630A and 1250A Front T-Body / Coupling (Rear) T-Body Connector

35-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

15kV 200A Loadbreak Fuse Elbow Design Test Report. Report Number:

M-Force three-phase switch

3M Cold Shrink Splice Kits, QS T Series

Cold Shrink QS T Trifurcating Transition Splice Kit

3M Cold Shrink QT-III Silicone Rubber Three-Core Termination Kits

3 Cold Shrink Silicone Rubber Skirted Termination Kit QT-III 7672-S-8 Series

COOPER POWER SERIES. 200 A Fused Loadbreak Elbow Connector Replacement Fuse Installation Instructions. Fusing Equipment MN132021EN

Molded Current-Limiting Fuse

3M Cold Shrink Silicone Rubber Outdoor Termination Kit QT-III 7600-S-3W Series

25 kv Apparatus Bushings

Two-position sidewall (horizontal) and cover (vertical) mounted loadbreak switches

Effective March 2015 Supersedes S August 2012

COOPER POWER SERIES. 200 A loadbreak junction 15 and 25 kv class installation instructions. Loadbreak Connectors MN650015EN

Surge arresters. UltraSIl Polymer-Housed VariSTar Type UI Intermediate-Class Surge arresters. General. COnSTrUCTIOn

3M Cold Shrink QT-III Silicone Rubber Termination Kits 7640-T and 7650-T Series 5, 8, 15, 25/28 and 35 kv

100 A externally operated one-, twoand three-phase tap-changer switch

CATALOG. Hi-Tech Fuse Products

600 A Deadbreak Connectors

35-kV Thru-Bushings F Series (bolt-in) for Air-Insulated to Air-Insulated Service 200 Amp, 600 Amp, 900 Amp and 1250 Amp

11. CABLE SPECIFICATIONS 5kV, 15kV, AND 35kV RUBBER OR PLASTIC INSULATED CABLE

M-Force three-phase switch

High Voltage Copper, Smooth Aluminum Shield/Sheath

3M Cold Shrink QT-III Silicone Rubber Termination

UltraSIL polymer-insulated and porcelain loadbreak Type LB open distribution cutout

High Voltage Aluminum, Smooth Aluminum Shield/Sheath

15 kv and 25 kv Thru-Bushings

Effective November 2016 Supersedes February 2012 (S )

Terminations. 3M Cold Shrink Terminations FAX TERMINATIONS. Glossary of Terminations Terms 263 Cable Types for Terminating 264 3M

PRODUCT BROCHURE. Elastimold ComboT integral separable connectors

25-kV Apparatus Bushings A Series (clamp-in) for Elbow to Air-Insulated Service 200 Amp and 600 Amp

MEDIUM VOLTAGE

Installation Instructions

Installation Instructions K656CY, K656CH and K656I Deadbreak Receptacles

3M Cold Shrink Silicone Rubber Termination QT-III 7600-S-3G Series Three-Core Outdoor Termination

PRODUCT BROCHURE. Elastimold advanced connection system (shear bolt)

Portable High-Voltage Cable Couplers 415, 515

Dry Well Cannister Type CLT, OIL Immersed PTAP-AFH926. Technical Guide Load-break, Dead-break

Transcription:

Loadbreak Apparatus Connectors 200 A 15 kv Class Loadbreak Elbow Connector with Optional Integral Jacket Seal Electrical Apparatus 500-10-7 GENERAL The Cooper Power Systems Loadbreak Elbow Connector is a fully-shielded and insulated plug-in termination for connecting underground cable to transformers, switching cabinets and junctions equipped with loadbreak bushings. The elbow connector and bushing insert comprise the essential components of all loadbreak connections. The Cooper Elbow Connector is a fully rated 200 A switching device, designed in accordance to IEEE Std 386 standard - latest revision. Cooper Loadbreak Elbows are molded using high quality peroxide-cured insulating and semi-conducting EPDM rubber. Standard features include a coppertop connector, tin-plated copper loadbreak probe with an ablative arc-follower tip and stainless steel reinforced pulling-eye. An optional capacitive test point, made of corrosion resistant plastic, is available for use with fault indicators (see Catalog Section 320-40 and 320-42). Cable ranges are designed to accept a wide range of cable conductor and insulation sizes with just three elbows and accommodate cable manufactured to either AEIC or ICEA standards. The coppertop compression connector is a standard item to transition from the cable to the loadbreak probe. An aluminum crimp barrel is inertia-welded to a copper lug. The aluminum barrel makes the connector easy to crimp and the copper lug ensures a reliable, tight, cool operating connection with the loadbreak probe. OPTIONAL INTEGRAL JACKET SEAL The optional integral jacket seal provides a quick and easy means to sealing the cable jacket to prevent moisture ingress. Our jacket seal is molded to the loadbreak elbow eliminating the need for separate cable sealing products. It s available with braided ground strap/ bleeder wire for terminating Tape shielded cable. (See Figure 5.) Figure 1 Figure 1A Figure 1. Loadbreak Elbow Connector with optional integral jacket seal and without test point shown. Figure 1A (right) Loadbreak Elbow without jacket seal and with test point. April 2008 New Issue 1

200 A 15 kv Class Loadbreak Elbow Connector with Optional Integral Jacket Seal SEMI-CONDUCTIVE INSERT High-quality peroxide-cured EPDM rubber creates a smooth surface around the current interchange to evenly distribute electrical stress within the insulation. PULLING EYE Stainless steel reinforced for positive shotgun stick switching operations. TEST POINT (OPTIONAL) Corrosion-resistant, conductive electrode provides consistent capacitive voltage for application of fault indicators and determining if the circuit is energized (cap not shown). LOADBREAK BAND UV resistant nylon band identifies the elbow as three-phase loadbreak rated and is field replaceable. INSULATION High-quality peroxide-cured EPDM rubber formulated, mixed, and milled in-house for consistent and reliable field performance. SEMI-CONDUCTIVE SHIELD High-quality peroxide-cured EPDM rubber provides protective deadfront shield that meets requirements of IEEE Std 592 standard. COPPERTOP COMPRESSION CONNECTOR Inertia-welded aluminum barrel and threaded copper lug makes crimping easy and ensures a tight, reliable electrical connection with loadbreak probe. GROUNDING TABS Molded into semi-conductive shield for the attachment of a ground wire to maintain deadfront safety. LOADBREAK PROBE Tin-plated copper probe with arc-ablative tip (arc follower) provides dependable loadbreak switching characteristics. CONDUCTIVE INSERT ENDS Encapsulated with insulating rubber. Reduces cable extrusion and distortion that can be caused by thermocycling. Mitigates the effects of the electrical stresses along the cable to elbow interface, greatly reducing the possibility of interface tracking. OPTIONAL INTEGRAL JACKET SEAL The optional integral jacket seal provides a quick and easy means to sealing the cable jacket to prevent moisture ingress. Also available with braided ground strap/bleeder wire for terminating Tape shielded cable. Figure 2. Cutaway drawing shows design detail. 2

500-10-7 S Dim. 25 kv S4 S3 S6 S3 3.4 (86 mm) S4 4.2 (106 mm) S5 2.7 (68 mm) S6 1.2 (30 mm) S5 NOTE: Dimensions given are for reference only. Figure 3. Elbow profile and stacking dimensions as referenced in IEEE Std 386 standard. INSTALLATION Cable stripping and scoring tools, available from various tool manufacturers, are recommended for use when installing loadbreak elbows. After preparing the cable, the elbow housing is pushed onto the cable. The loadbreak probe is threaded into the coppertop connector using the supplied installation tool or an approved equivalent. Use a shotgun stick to perform loadmake and loadbreak operations. Refer to Installation Sheet S500-10-7 for details. PRODUCTION TESTS Tests conducted in accordance with IEEE Std 386 standard: AC 60 Hz 1 Minute Withstand 34 kv Minimum Corona Voltage Level 11 kv Test Point Voltage Test Tests conducted in accordance with Cooper Power Systems requirements: Physical Inspection Periodic Dissection Periodic X-ray Analysis TABLE 1 Voltage Ratings and Characteristics Description kv Standard Voltage Class 15 Maximum Rating Phase-to-Phase 14.4 Maximum Rating Phase-to-Ground 8.3 AC 60 Hz 1 Minute Withstand 34 DC 15 Minute Withstand 53 BIL and Full Wave Crest 95 Minimum Corona Voltage Level 11 Voltage ratings and characteristics are in accordance with IEEE Std 386 standard. TABLE 2 Current Ratings and Characteristics Description Continuous Switching Fault Closure Short Time Amperes 200 A rms 10 operations at 200 A rms at 14.4 kv 10,000 A rms symmetrical at 14.4 kv for 0.17 s after 10 switching operations 10,000 A rms symmetrical for 0.17 s 3,500 A rms symmetrical for 3.0 s Current ratings and characteristics are in accordance with IEEE Std 386 standard. 3

200 A 15 kv Class Loadbreak Elbow Connector with Optional Integral Jacket Seal ORDERING INFORMATION The Elbow kits are packaged in a heavy duty polyethylene bag. There are 20 bagged kits to a carton. Individual boxed kits are also available by special part number. To order a 15 kv Class Loadbreak Elbow Kit follow the easy steps below. Each kit contains: Standard Elbow Body or Elbow Body with Jacket Seal Coppertop Compression Connector Loadbreak Probe Probe Installation Tool Silicone Lubricant Mastic Strips (Jacket Seal Elbow Only) Installation Instruction Sheet STEP 1: Determine the cable s diameter over the electrical insulation as shown in Figure 4 (including tolerances) from cable manufacturer. Then identify a cable range from Table 3 that brackets the minimum and maximum insulation diameters. Select the CABLE RANGE from the far right column. STEP 2: Identify the conductor size and type in Table 4 and select the from the far right column. STEP 3: For an elbow kit with a capacitive test point order: LE215 For an integral jacket seal elbow kit with a capacitive test point order: LEJ215 CABLE RANGE CABLE RANGE T T Figure 4. Illustration showing typical construction of high voltage underground cable. For an elbow kit without a capacitive test point order: LE215 DIAMETER OVER OUTER JACKET CABLE RANGE METAL NEUTRAL OR SHIELD For an integral jacket seal elbow kit without a capacitive test point order: LEJ215 CABLE RANGE OUTER JACKET For an elbow kit without a compression connector, use 00 for the conductor code. For an elbow kit with a hold down bail assembly included, insert a B after the test point option code. STEP 4: For optional braided ground strap/bleeder wire for terminating tape shielded cable, insert GS after test point and/or bail option code. (Integral Jacket Seal Elbow Only) STEP 5: (Optional) For an elbow kit individually packaged in a corrugated cardboard box, insert an X as the last character in the part number. INSULATION SHIELD INSULATION DIAMETER OVER INSULATION SHIELD Table 3 Cable Range for Loadbreak Elbow Inches Millimeters Cable Range Code 0.495-0.585 12.6-14.9 CCA* 0.575-0.685 14.6-17.4 CCB* 0.610-0.970 15.5-24.6 AB 0.750-1.080 19.1-27.4 CC 0.920-1.310 23.3-33.2 DD * Uses 5 kv cable adapter. (For use with CC range elbow only.) 4

500-10-7 TABLE 4 Conductor Size and Type Class B Stranded or Compressed Compact or Solid AWG mm 2 AWG mm 2 No Connector 00 #6 16 #4 01 #4 #3 25 02 #3 25 #2 35 03 #2 35 #1 04 #1 1/0 50 05 1/0 50 2/0 70 06 2/0 70 3/0 07 3/0 4/0 95 08 4/0 95 250 120 09 250* 120 300 10 *Compressed stranding only. EXAMPLE: Select an integral jacket seal elbow kit with a capacitive test point for use on a #1 compact cable with a minimum insulation diameter of 0.770 and a maximum diameter of 0.830. STEP 1: From Table 3, identify the cable range 0.610 0.970 and select the AB CABLE RANGE. STEP 2: The conductor size is a #1 and the type is compact. From Table 4, under the column Compact or Solid identify #1 and select the 04 conductor code. STEP 3: Order catalog number. LEJ215AB04T 5

200 A 15 kv Class Loadbreak Elbow Connector with Optional Integral Jacket Seal TABLE 5 Replacement 2.88 Long Coppertop Connectors Conductor Size Concentric or Compressed Compact or Solid Catalog AWG mm 2 AWG mm 2 Number #6 16 #4 CC2C01T #4 #3 25 CC2C02T #3 25 #2 35 CC2C03T #2 35 #1 CC2C04T #1 1/0 50 CC2C05T 1/0 50 2/0 70 CC2C06T 2/0 70 3/0 CC2C07T 3/0 4/0 95 CC2C08T 4/0 96 250 120 CC2C09T 250* 120 300 CC2C10T * Compressed stranding only. Note: Coppertop compression connector may be used on both aluminum and copper cable conductors. ACCESSORIES TABLE 6 Replacement Parts Description Hold Down Bail Assembly 5 kv Cable Adapter (for use with C Elbow size only),.495.585.575.685 Loadbreak Band (package of 25) Probe Kit (includes Probe, Installation Tool, Silicone Lubricant, Installation Instruction Sheet) Loadbreak Probe Installation Tool Loadbreak Probe Only Silicone Grease 0.175 oz tube (5 grams) 5.3 oz tube (150 grams) Includes Ground Braid, Constant Force Spring and Mastic Catalog Number 2638351C01B CA225A CA225B 2639139B01B PK215 2602733A01 2637552C03 2603393A03 2605670A02M GRDBRAIDKIT Figure 5. Braided Ground Strap Accessories (see Table 6). Figure 6. 5 kv Cable Adapter (see Table 6). Figure 7. Optional Bail Assembly (see Table 6). 6

500-10-7 7

200 A 15 kv Class Loadbreak Elbow Connector with Optional Integral Jacket Seal 2008 Cooper Power Systems, Inc., or its affiliates IEEE Std 386 standard and IEEE Std 592 standard are trademarks of the Institute of Electrical and Electronics Engineers, Inc. IEEE is a registered trademark of the Institute of Electrical and Electronics Engineers, Inc., (IEEE). This publication/product is not endorsed or approved by the IEEE. 2300 Badger Drive Waukesha, WI 53188 USA www.cooperpower.com