Jet Fans. Instruction Manual READ AND SAVE THESE INSTRUCTIONS WARRANTY

Similar documents
INSTALLATION, OPERATION AND MAINTENANCE MANUAL WALL EXHAUST FANS BELT DRIVE XBL FANS

INSTALLATION, OPERATION AND MAINTENANCE MANUAL WALL EXHAUST FANS BELT & DIRECT DRIVE XB, HV, HVA, ADD, DDS, DDP

INSTALLATION, OPERATION & MAINTENANCE MANUAL AXIAL UPBLAST FANS RTA, RWTA, RHTA, RB, RD, RTA SH

INSTALLATION VARIABLE FREQUENCY DRIVE THREE PHASE ALX SERIES SPUN ALUMINUM EXHAUSTERS

READ AND SAVE THESE INSTRUCTIONS

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL RBK FRP FAN

DPL/DPL-AF SERIES PLENUM FANS OPERATION INSTRUCTIONS AND PARTS MANUAL MODELS: DPL/DPL-AF-12, 13, 15, 16, 18, 20, 22, 24, 27, 30, 33, 36 GENERAL SAFETY

MODEL VBO-HV & VBO UPBLAST PROPELLER ROOF FANS

Emergency Smoke Control Centrifugal Roof Exhaust Fans

Operation and Maintenance Manual. Series BI Centrifugal Blowers

Tubular Centrifugal Inline Fans TCN

Installation, Operation and Maintenance Manual

ECONOMIZER FAN. Receiving and Inspection

Models GED/GSD, DFE/DFS & DDE/DDS Installation, Operation, and Maintenance Manual

READ AND SAVE THESE INSTRUCTIONS. Centrifugal Downblast Exhaust Fan Belt Driven for Roof & Wall Mounting

Model CFD Installation, Operation, and Maintenance Manual

BCRFS Belt Driven Centrifugal Filtered Supply Fans

INSTALLATION, OPERATION, AND MAINTENANCE MANUAL CNW DHK PVK

MARLEY ENGINEERED PRODUCTS OPERATING INSTRUCTIONS AND PARTS LIST

READ AND SAVE THESE INSTRUCTIONS. High Velocity Restaurant-Duty Utility Set Belt Driven for Roof Mounting

REBEL/AQ/SEP/ETE/ETS IO&M

Models TXB,TXB-W, TXB-RHUL Installation, Operation, and Maintenance Manual

IM Centrifugal Power Roof & Wall Ventilators. Introduction. Shipment and Receiving. Handling. Storage. Issue Date: 4-97 Rev.

Axial Roof Ventilators & Tubeaxial Fans. General Installation, Operation and Maintenance Instructions For Aerovent Products

DUCT BLOWER Cabinet Fans INSTALLATION, OPERATION AND MAINTENANCE MANUAL

Model CFD Installation, Operation, and Maintenance Manual

Model CFD Installation, Operation, and Maintenance Manual

Model SDB Installation, Operation, and Maintenance Manual

Models STXB,STXBW, STXBRHUL, STXBHP Installation, Operation, and Maintenance Manual

Models BVS & CM - Level 1 Construction Installation, Operation, and Maintenance Manual

SQI Centrifugal Square Inline Fans INSTALLATION, OPERATION AND MAINTENANCE MANUAL

Models TXB & TXB-W Installation, Operation, and Maintenance Manual

OPERATOR MANUAL Combo Belt Conveyor

Ø5/16" HOLES FOR FASTENING TO CURB

Duct Blower Cabinet Fans

Models TXB,TXB-W, TXB-RHUL Installation, Operation, and Maintenance Manual

MODEL CLS Centrifugal Filtered Supply Fans

Models LC, L2 & L3 Installation, Operation, and Maintenance Manual

INSTALLATION, OPERATION & MAINTENANCE MANUAL Hooded Propeller & Tubeaxial Roof Fans. Models: LHB, LHD, LHBF, LHDF, THB, THD, THBF, THDF

Models eged/egsd. Installation, Operation, and Maintenance Manual. Direct Drive Sidewall Propeller Fans (Exhaust and Supply)

TMX Mixed Flow Inline INSTALLATION, OPERATION AND MAINTENANCE MANUAL

BCFS Belt Driven Centrifugal Filtered Supply Fans

Upblast Propeller Roof Fans

Model CWD Installation, Operation, and Maintenance Manual

Installation, Operation and Maintenance Manual

SDBDe, STXDe, ered* Installation, Operation, and Maintenance Manual INSTALLATION AND WIRING INSTRUCTIONS READ AND SAVE THESE INSTRUCTIONS

READ AND SAVE THESE INSTRUCTIONS. Centrifugal Upblast Exhaust Fan (Standard & High Pressure Exhaust) Belt Driven for Roof & Wall Mounting

CCP Centrifugal Plug Fans

ASP/KSP Centrifugal Filtered Supply Fans INSTALLATION, OPERATION AND MAINTENANCE MANUAL

CPL Centrifugal Plenum Fans

HA/HAB Fiberglass Wall Mount Ventilators

INSTALLATION, OPERATION & MAINTENANCE MANUAL. Centrifugal Square Inline Fans

SDBDe, STXDe, STXDeRHUL

SRSH Tamper Proof Centrifugal Exhauster INSTALLATION, OPERATION AND MAINTENANCE MANUAL

8-12 INSTALLATION AND WIRING INSTRUCTIONS READ AND SAVE THESE INSTRUCTIONS

D-Series Blowers and Exhausters

Centrifugal Square Inline Fans. General Installation, Operation and Maintenance Instructions For Aerovent Products

Centrifugal Square Inline Fans

for Untempered - Make-Up Air Units

CFS Centrifugal Filtered Supply Fans

APCO CRF-100A RUBBER FLAPPER SWING CHECK VALVES

Installation. Centrifugal Roof and Wall Exhausters

LO-PRO. Receiving and Inspection. Handling Lift the fan by the base. NOTICE! Never lift by the shaft, motor or housing.

User s Manual D-Series Blowers and Exhausters

MODEL SCA Installation and Operation Manual Important:

ered Installation, Operation, and Maintenance Manual Direct Drive sizes 6-15 Nonoverloading B.I. Wheel

Backward Inclined Hinged Restaurant Exhaust Fan

WELDING FUME EXHAUSTERS & ARMS

FCE/FCRU Fiberglass Roof Exhausters INSTALLATION, OPERATION AND MAINTENANCE MANUAL

48" and 52" Hyflo Fans Installation and Operators Instruction Manual

Power Roof Ventilator Installation, Operation, and Maintenance Manual. Down-blast Centrifugal Fan Utility Set Axial Fan

IMH Industrial Material Handler INSTALLATION, OPERATION AND MAINTENANCE MANUAL

Air Curtain. Installation, Operating and Maintenance Instructions

TSL and QSL Inline Centrifugal and Mixed Flow Fans

CONTENTS. VIKING PUMP, INC. A Unit of IDEX Corporation Cedar Falls, IA USA SECTION TSM 710.1

IMPORTANT! READ BEFORE PROCEEDING! PHR Axial Flow Hooded Roof Ventilators

IMPORTANT! READ BEFORE PROCEEDING! PAF Axial Propeller Fans

582 Series. Instruction Manual. Two-Door Wafer Check Valve N-582 (R-08/2016)

INSTALLATION, OPERATION & MAINTENANCE MANUAL Propeller Wall Fans. Models: TCPE, WPB, WPD

NSGV Direct Drive Pressure Blower (AF) Aluminum Housing & Wheel

DUST COLLECTOR (BOTTOM REMOVAL BAG & CAGE) INSTALLATION AND OPERATING INSTRUCTIONS

AIR COMPRESSOR OPERATING INSTRUCTION AND PARTS LIST

36 HYPER MAX DIRECT DRIVE GALVANIZED BOX FAN

PHANTOM (PH10 and PH12) COMMERCIAL AND INDUSTRIAL SERIES

HOOD EXHAUST OR SUPPLY PROPELLER FAN

Propeller Wall Fans INSTALLATION, OPERATION & MAINTENANCE MANUAL

INDUSTRIES AMERICAN COOLAIR CORPORATION. Centrifugal Filtered Supply Roof Ventilators TYPE CFS - TYPE SIS

PO Box 645, Stockton, Missouri, FAX superiorgearbox.com W D0446-A 4/1/05 1

IM-210 INSTALLATION MAINTENANCE, OPERATING INSTRUCTIONS HOODED ROOF VENTILATORS UPBLAST ROOF VENTILATORS AIR PRESSURE AND SUCTION A WORD ABOUT SAFETY

QMX Mixed Flow Inline INSTALLATION, OPERATION AND MAINTENANCE MANUAL

Maintenance and Repair

INSTRUCTION MANUAL & PARTS BOOK. Vibratory Screed

C T h e A d va n t a g e

AC/VCR Centrifugal Roof and Wall Exhausters INSTALLATION, OPERATION AND MAINTENANCE MANUAL

MAINTENANCE - LPX PORTABLE TREATER

DEBRIS BLOWER 2700 OPERATOR S MANUAL. Debris Blower

Sofa Slideout Assembly OWNER'S MANUAL. Rev: Page 1 Sofa Slideout Owners Manual

Auger Belt Tension Adjustment DB7659

60 Series End-Mount Brake Instructions Standard Housing

APCO CSV-1600 SURGE CHECK VALVE

Transcription:

Jet Fans Instruction Manual READ AND SAVE THESE INSTRUCTIONS WARRANTY All Leader Fan products are guaranteed to be free from defects of workmanship or material and to function satisfactorily when properly installed, operated and maintained in accordance with instructions, for a period of twelve (12) months from date of delivery unless stated otherwise. The guarantee does not apply if the product has been altered or tampered with in any way after leaving the factory. Canarm assumes no liability for resultant damages, labour and services charges of any kind arising from the use of its products. On equipment furnished by Canarm but manufactured by others, such as motors, the warranty will be honoured by the manufacturers thereof. CANARM LTD. CORPORATE HEAD OFFICE 2157 Parkedale Avenue,P.O.Box 367, Brockville, Ontario Canada K6V 5V6 Ph:(613) 342-5424 Fax: (613) 342-8437 Web Site: www.canarm.com

JET FANS - JFHVA INSTALLATION, OPERATION, AND MAINTENANCE MANUAL The purpose of this manual is to aid in the proper installation and operation of the fans. These instructions are intended to supplement good general practices and are not intended to cover detailed instruction procedures. It is the responsibility of the purchaser to assure that the installation and maintenance of this equipment is handled by qualified personnel. Inspect all shipments carefully for damage. THE RECEIVER MUST NOTE ANY DAMAGE ON THE CARRIERS BILL OF LADING AND FILE A CLAIM IMMEDIATELY WITH THE FREIGHT COMPANY. ASSEMBLY INSTRUCTIONS 1. Remove the panels and electrical box from inside the fan. 2. If equipped: adjust pre-assembled linkage/damper position to suit application. 3. Once the fan has been properly wired by a licensed electrician, assemble two panels to the side of the fan using the supplied self drilling screws. Page 2 of 11

INSTALLATION 1. The fans are shipped mostly assembled, however final adjustments are required to suit your specific application. The fabric duct and associated hardware are shipped separately. 2. Jet Fans should be installed as near the roof as is practical while still providing a straight, clear, unobstructed run for the fabric duct. 3. The run of fabric duct should be kept clear of any moisture sensitive equipment. 4. Construct a framed wall opening. 5. Align the fresh air control damper with the framed wall opening and install in the opening and lag to the wall. 6. Hang the discharge side of the Jet Fan using threaded rod (by others) to the ceiling. 7. Place the fabric duct over the venturi extension and secure in place using a duct clamp. 8. Attach one end of the cable to the wall then thread the cable through the eyelets on the fabric duct. Attach the cable to the ceiling using beam clamps. 9. When utilizing the temperature sensor to adjust the amount of fresh and recirculated air, the sensor should be located in the system discharge duct. The temperature control can be located anywhere. 10. Caution: The fan contains rotating parts and requires electrical service. Appropriate safety precautions should be taken during installation, operation and maintenance. 11. All electrical work must be done in accordance with all applicable electrical codes, by a qualified electrician. 12. Prior to wiring, ensure that the power supply is locked in the off position and that the motor nameplate voltage and the supply voltage match. 13. Ensure that the propeller rotates freely. Page 3 of 11

Wiring Instructions A qualified electrician, in accordance with all local and national electrical codes, should do all wiring. Lock off all power sources before any wiring is to be performed. All wiring is to be done in the electrical box on the exterior of the jet fan. Excess wire must be restrained in order to prevent it from entanglement with moving parts. Disconnect switches are recommended and should be located near the fan in order to swiftly cut off power in case of an emergency and maintain complete control of the power source. Follow the wiring diagrams provided. Jet Fans Extend the proper gauge wire to the fan motor. Restrain excess wire from entanglement with moving parts. Typical Installations Refer to page 8 and 9. OPERATION Pre Start Inspection Lock out all power sources. Inspect all fasteners and set screws and tighten as required to the proper torque settings (see chart). Inspect belt alignment and tension. Confirm power source voltage and motor voltage are the same and that the motor is wired correctly. Rotate the fan blade to ensure that the fan blade does not come into contact with the housing. Inspect the fan to ensure it is free from debris. Check to ensure that all guards and accessories are securely mounted. Check to be sure the propeller rotation is correct Check to ensure that the fabric duct is securely fastened to the fan discharge and that the fabric duct is in the correct orientation. Start Up Turn the fan on and inspect for the following: Direction of rotation Improper motor amperage Excessive vibration Unusual noise Improper belt tension or alignment Page 4 of 11

If a problem is discovered, shut off the fan and refer to the section on troubleshooting to discover the cause of the problem. The fan should be inspected after 30 minutes, 8 hours and 24 hours of operation to ensure all fasteners are tight and belts are properly tensioned and aligned. MAINTENANCE! WARNING: Disconnect and secure to the OFF position all electrical power to the fan prior to inspection or servicing. Failure to comply with this safety precaution could result in serious injury or death. 1. Fans should be checked at least once a year. For critical or severe applications a routine check every two or three months is suggested. 2. When removing or installing a belt, do not force the belt over the sheave. Loosen the motor mount so that the belt can be easily slipped over the sheave. 3. The belt should be removed and carefully checked for cracks, ply separation or irregular wear. A small irregularity in the contact surface of the belt will result in noisy operation. If any of these defects are apparent, the belt should be replaced. At the same time, check the sheaves for chips, dents or rough surfaces that could damage the belt. 4. The correct belt tension is important. Too tight a belt will result in excess bearing pressure, which can cause premature bearing failure and may cause the motor to overload; too loose a belt will result in slippage, which will burn out belts. Proper belt deflection should be 1/64 (half way between sheave centers) for each inch of belt span when a force of approximately five lbs. is applied. 5. The belt alignment should be checked to be sure that the belt is running perpendicularly to the rotating shafts. Motor and drive shafts must be parallel. 6. A periodic inspection of all fasteners should be carried out to ensure they have not loosened due to vibration. Particular attention should be paid to fasteners attaching the propeller to the shaft and those attaching the shaft to the bearings. 7. The standard pillow blocks on belt driven fans are factory lubricated. These bearings should be lubricated on a semi annual basis (more frequently in severe applications). With the fan being rotated by hand add grease very slowly, using a manual grease gun, until a slight bead of grease forms at the seal. Be careful not to unseat the seal by over lubricating or by using excessive pressure. When the bearings are obstructed from view, use no more than three injections with a hand operated grease gun. 8. Dust and dirt on the exterior surface of the motor, fan panel, and the propeller should be removed, at intervals determined by the severity of the application, to ensure proper service life and safety. Page 5 of 11

Belt Tension Belt and Pulley Replacement In the course of regular maintenance, the belts and pulleys may have to be changed and or adjusted. The recommended procedure is as follows: Do not change the pulley pitch diameter in order to tension the belts. This will result in a change in the fan speed. Loosen the nuts on the motor plate or motor in order to reduce the belt tension such that the belts will easily slip over the pulleys. Never force the belts over the rim of the pulley. Loosen the setscrews on the pulleys and remove from either the motor or fan shaft using a two or three jaw puller. Remove any shaft imperfections, such as setscrew marks, using a file or emery cloth. Install the replacement pulleys tightening all setscrews and bolts to the recommended torque rating (see chart page 7) and ensuring that they are properly aligned. Pulley alignment is achieved by moving the pulleys on their respective shafts or moving the entire motor until the pulleys are correctly aligned (see Pulley Alignment on next page). Using a square with one edge parallel to the motor shaft adjust the pulleys until the other edge is parallel to the belts. Slip the belts over the pulleys, and then adjust the motor/ motor plate until the proper tension is reached (1/64 deflection, half way between pulley centers, per inch of belt span when pressed firmly). Tighten the motor plate/ motor adjusting nuts in place. Pulley Alignment Page 6 of 11

Recommended Torque for Set screws/bolts (inch/lbs) SIZE SET SCREWS RECOMMENDED HOLD DOWN BOLTS TORQUE INCH-LBS HEX KEY TORQUE MIN MAX SIZE INCH-LBS NO. 10 3/32 28 33 3.8 16 240 1/4 1/8 66 80 1/2-13 600 5/16 5/32 126 156 5/8 11 1200 3/8 3/16 228 275 3/4 10 2100 7/16 7/32 348 384 7/8 9 2040 1/2 1/4 504 600 1 8 3000 5/8 5/16 1104 1200 1 1/8 7 4200 3/4 3/8 1440 1800 1 1/4-7 6000 Bearings Replacement Canarm/LFI uses pillow block bearings. Before removing the bearings, mark the positions of the fan blade, bearings and pulley on the shaft. Note the clearance between the fan blade and the venturi. Remove the pulley and fan blade from the shaft using a puller. Unbolt the bearings and remove the shaft and pillow blocks as one unit. Clean the shaft and remove any marks using a file or emery cloth then remove the bearings using a bearing puller. Inspect the shaft and replace if necessary. Mount the new bearings on the shaft by tapping the bearings inner ring face using a soft mallet. Align the setscrews on the bearings and then tighten one setscrew on each bearing. Loosely install the bearings on the bearing mount. Rotate the shaft to find the center of free movement. Install the propeller adjusting the bearing location to center the propeller in the venturi. Tighten the bearing bolts to the proper torque rating (see chart page 7). Turn the propeller by hand; the propeller should rotate freely with the same resistance as before the bearing bolts were tightened. Tighten all setscrews to the proper torque rating (see chart page 7). Install the pulley and adjust the belt tension. Follow the start up steps as outlined above. Page 7 of 11

Typical Installations Dimensions SIZE A B C D F 24 32 32 36 25 18 7/8 30 38 38 42 31 18 7/8 36 44 44 48 37 26 3/4 42 50 50 54 42 7/8 24 1/4 48 56 56 60 48 7/8 27 1/4 Wall Mounted Page 8 of 11

Roof Mounted REPLACEMENTN PARTS LIST MODEL: JFHVA ITEM DESCRIPTION QUANTITY 10 MOTOR 1 11 MOTOR SHEAVE 1 12 MOTOR SHEAVE BUSHING 1 13 DRIVEN SHEAVE BUSHING 1 14 DRIVEN SHEAVE 1 15 V BELTS 2 16 PILLOW BLOCK BEARINGS 2 17 FAN SHAFT 1 18 PROPELLER 1 19 PROPELLER BUSHING 1 20 WELDED FAN ASSEMBLY 1 Page 9 of 11

FAN TROUBLESHOOTING GUIDE PROBLEM VIBRATION POSSIBLE CAUSES Propeller or sheaves loose Belts not tensioned properly Damaged shaft Out of balance propeller Loose fasteners Improper fan installation Loose or worn bearings Drive misalignment Mismatched belts Out of balance sheaves MOTOR OVERLOADING Static pressure higher than design Propeller rotating in wrong direction Improper fan speed Defective motor Fan speed higher than design NOT ENOUGH AIR Propeller rotating in the wrong direction Static pressure higher than design Clogged filters Fan speed lower than design Restricted inlet, outlet or duct TOO MUCH AIR Filters missing Static pressure lower than design Fan speed higher than design FAN DOES NOT OPERATE Lack of electricity to the fan Fan wired improperly Broken or missing belt Missing or blown fuses Overload protection has broken circuit Defective motor Page 10 of 11

FAN TROUBLESHOOTING GUIDE PROBLEM EXCESSIVE NOISE POSSIBLE CAUSES Propeller or sheaves loose Belts not properly tensioned Sheaves not properly aligned Propeller out of balance Sheaves out of balance Damaged shaft Bearings defective or require lubrication Worn belts Vibration or lack of isolation High velocity air Loose fasteners CANARM LTD. CORPORATE HEAD OFFICE 2157 Parkedale Avenue, Brockville, Ontario K6V 5V6 Canada Phone: (613) 342-5424 Fax: (613) 342-8437 Web Site: www.canarm.com Page 11 of 11