TX800-Series FLOW SENSOR INSTRUCTIONS. TX81x TX82x 9 001:2008 ISO CERTIFIED COMPANY TX800-SERIES FLOW SENSOR INSTRUCTIONS

Similar documents
TX80-Series FLOW SENSOR INSTRUCTIONS TX81 TX :2008 ISO CERTIFIED COMPANY TX80-SERIES FLOW SENSOR INSTRUCTIONS

IP800-Series FLOW SENSOR INSTRUCTIONS IP810 IP :2008 ISO CERTIFIED COMPANY IP80-SERIES FLOW SENSOR INSTRUCTIONS

IP80-Series FLOW SENSOR INSTRUCTIONS IP81 IP :2008 ISO CERTIFIED COMPANY IP80-SERIES FLOW SENSOR INSTRUCTIONS

IP800-Series. Insertion Paddlewheel Flow Sensor Instructions PROUDLY MADE IN THE USA

IP800-Series. Insertion Paddlewheel Flow Sensor Instructions PROUDLY MADE IN THE USA

IP800-Series FLOW SENSOR INSTRUCTIONS IP810 IP :2008 ISO CERTIFIED COMPANY IP800-SERIES FLOW SENSOR INSTRUCTIONS

TX100/200-SERIES INSERTION TURBINE INSTRUCTIONS TX101/201 TX115/215 ISO 9001:2008 CERTIFIED COMPANY

EX80 Series EX81 EX82. E X 8 0 S E R I E S E l e c t r o m a g n e t i C F l o w s e n s o r i n s t r u c t i o n s. The Leader in Flow Meter Value.

EX80-Series ELECTROMAGNETIC FLOW SENSOR INSTRUCTIONS EX81 EX82 EX :2008 ISO CERTIFIED COMPANY

TX101/201 Insertion Turbine Instructions

ARCHIVED. EX80 Series. (Includes Dates 6/28/05 to 10/06) EX81 EX82

TX100/200-SERIES INSERTION TURBINE. T X / S E R I E S I N S E R T I O N T U R B I N E instru c tions TX101/201 TX115/215

SES. Stainless Single-Jet Meter Instructions PROUDLY MADE IN THE USA

TX101/201 Insertion Turbine Instructions

SERIES TBS INSERTION TURBINE TBS-0XX TBS-1XX

EX100/200-Series INSERTION MAGNETIC FLOW METER INSTRUCTIONS EX110 EX210 EX150 EX :2008 ISO CERTIFIED COMPANY

S-Series. Low Flow Meter Instructions SPX SPT. Precision Flow Measurement An ONICON Brand PROUDLY MADE IN THE USA

TX115/215 Hot-tap Insertion Turbine Instructions

EX100/200 Series. Insertion Magnetic Flow Meter Instructions. EX11x EX21x. EX15x EX25x PROUDLY MADE IN THE USA

TX 115/215 Hot-tap Insertion Turbine Instructions

WMX-series MUNICIPAL/INDUSTRIAL MAGMETER INSTRUCTIONS

EX800-Series. Electromagnetic Flow Sensor Instructions PROUDLY MADE IN THE USA

WMP-Series PLASTIC-BODIED MAGMETER INSTRUCTIONS 9001:2008 ISO CERTIFIED COMPANY WMP-SERIES PLASTIC-BODIED MAGMETER INSTRUCTIONS. 3 inch.

SERIES FLMG MUNICIPAL/INDUSTRIAL MAGMETER INSTRUCTIONS

EM101 LOW FLOW MAGNETIC FLOWMETER INSTRUCTIONS

SeaMetrics Flow Meters and Flow Computers

EM 101 EM EM EM GENERAL INFORMATION. SPECIFICATIONS MATERIALS Wetted Materials - FLOW RANGE

AG2000 IRRIGATION MAGMETER INSTRUCTIONS

PSF50 Paddle flow switch

PE202. Low Flow Magmeter Instructions. Precision Flow Measurement An ONICON Brand PROUDLY MADE IN THE USA

FIXED DEPTH INSERTION METER INSTRUCTIONS

Insertion turbine INSTRUCTION SHEET. TECHNICAL PRODUCT

FLS F6.60 MAGMETER FLOW SENSOR INSERTION FLOW SENSORS APPLICATIONS MAIN FEATURES

G2 Industrial Grade Meters

Flow Meter & Control Catalog

M SERIES Multi-Jet Cold Water Meter

TURBINE METERS - WP Series

LEVEL AND FLOW MEASUREMENT WS131 FLOW METER USER MANUAL.

WJ-Series. Turbine Meter Instructions ISO. 6 Meter. 3 Meter. Precision Flow Measurement. An ONICON Brand 9001:2008. if ie

FLOWX3 F3.20 High Pressure Paddlewheel Flow Sensor MAIN FEATURES APPLICATIONS OPERATING PRINCIPLE

FT430/440/450 RATE/TOTAL INDICATOR INSTRUCTIONS

imag 4700 SERIES FLANGED MAGMETER

Pipe fi ttings MUST be installed by a certifi ed welder only. Signet will not assume liability of any kind for improper fi tting installations.

MODEL 1100 TURBINE FLOW METER

BI-DIRECTIONAL INSERTION METER

MFM220 & MFM220DC Plastic-Bodied Magmeter

Instructions EM 101 Low Flow Electromagnetic Flow Meters

TR-QS Wafer-Style Turbine Flow Meters Installation, Operating & Maintenance Manual

ISTEC MAGNETIC METERS

WMX-SERIES Flanged Magmeter

BI-DIRECTIONAL INSERTION FLOW TRANSDUCER

Flow Meters & Instruments. Insertion Paddle Wheel & Magnetic Flow Meters Flow & Anaytical Instruments. Technical Catalogue

Liquid Turbine Flow Meter OwnerÊs Manual

WATER METERS OCTAVE ULTRASONIC WATER METER INSTALLATION & USER GUIDE

Pipe fittings MUST be installed by a certified welder only. +GF+ SIGNET will not assume liability of any kind for improper fitting installations.

Hydro-Flow Model 3100

Series TTMP PVC Electronic Totalizing Meter

Model 1100 Turbine Flow Meter

Paddle Wheel Turbine Flow Meters Installation, Operating & Maintenance Manual

INSERTION flow sensor for continuous flow measurement

AG2000 Irrigation Magmeter

RUN ACCUM. TOTAL STOP BAT LOW HIGH

Paddle Wheel Turbine Flow Meters Installation, Operating & Maintenance Manual

Ensuring Premium Performance with Foxboro I/A Series Pulsed dc Magnetic Flowmeters

A1 Commercial Grade Meters

INSERTION flowmeter with paddle wheel, ELEMENT design

FPD1001 thru FPD1003, FPD1102 and FPD1103, FPD1201 thru FPD1203 (includes -R Option) Positive Displacement Flowmeters

Hydro-Flow Model 2200 Fixed Insertion Vortex Flowmeter Installation and Operation Manual

Sanitary Turbine Flow Meter - TA3 Installation, Operating & Maintenance Manual

A1 Commercial Grade Meters

OVAL GEAR FLOWMETER ELECTRONIC MODEL 019 / ¾

Hydro-Flow 2200 Fixed Insertion Vortex Flow Meter

A1 SERIES COMMERCIAL GRADE METERS A1 SERIES COMMERCIAL GRADE METERS

Condensed Version of Operator s Manual For The VL600 Series Flowmeters

Hydro-Flow Model 2200 Installation and Operation Guide B

RPFS. ROTA PULSE FLOW SENSOR (Slip Insertion Paddlewheel) DATASHEET FEATURES

Industrial Meter Catalog

Hydro-Flow Model 3100 Retractable Insertion Vortex Flowmeter Installation and Operation Manual

Appendix. Clearance. Skewed profiles. Application Schematics

Electromagnetic flowmeters Series FLOMAT Insertion electromagnetic flowmeter for conductive liquids

Signet 2517 Brass Paddlewheel Flow Sensor * *

Installation & Operation Manual

F-4600 INLINE ULTRASONIC FLOW METER Installation and Operation Guide

TABLE OF CONTENTS GENERAL INFORMATION

Pipe fi ttings MUST be installed by a certifi ed welder only. Signet will not assume liability of any kind for improper fi tting installations.

Chapter Page. 1 Introduction Description 1

FLOWX3 F3.60M.S Insertion Magmeter

G2 SERIES INDUSTRIAL GRADE METERS

WMP-Series. Plastic-Bodied Magmeter Instructions ISO. 2 inch. Precision Flow Measurement. An ONICON Brand 9001:2008 PROUDLY MADE IN THE USA.

FPD1001B thru FPD1003B, FPD1102B and FPD1103B, FPD1201B thru FPD1203B SERIES LOW FLOW Positive Displacement Flowmeters

Installation and Maintenance Instructions. World Leader in Modular Torque Limiters. PTM-4 Load Monitor

ROTA PULSE FLOW SENSOR Slip Insertion Paddlewheel (with inductive coil pulse output & built in op-amp circuit)

MODEL 106F TEFLON LIQUID FLOW SENSOR

Product Data Sheet. Flow Sensors. Insert Style Flow Sensors SDI Series DESCRIPTION HOT TAP SENSORS (OPTIONAL) APPLICATIONS FUNCTIONALITY

OVAL GEAR FLOWMETER ELECTRONIC MODEL 006/009 (¼ )

Low Profile Insertion Vortex

NIAGARA. Series WPX. Installation, Operation & Maintenance Manual. Models 210 and 222. Series WPX

Axial Turbine Flow Sensor Series Turbotron VTH 25 / VTI 25 / VTM 25

TABLE OF CONTENTS Service Information 2 Quick Start Instructions 4-5 Introduction 6 Specifications 6 Controls and Terminology

Paddle-wheel flow controller for On/Off control

Transcription:

TX800-SERIES FLOW SENSOR INSTRUCTIONS TX800-Series FLOW SENSOR INSTRUCTIONS TX81x TX82x 9 001:2008 ISO CERTIFIED COMPANY

TABLE OF CONTENTS General Information Generial Information, Features...Page 3 Specifications...Page 4 Installation Fitting Installation, Distorted Flows, Meter Installation, Orienting the Meter...Page 5 Straight Pipe Recommendations...Page 6 Full Pipe Recommendations...Page 7 Connections FT430, FT440...Page 8 FT450, Connecting to PLC's...Page 9 Operation and Maintenance Modularity, Output, Fittings, Minimum Flow, Flow Rate Tables, Calibration ( K-Factor )...Page 10 Rotor Replacement, Signal Troubleshooting, Sensor Replacement...Page 11 Parts List...Page 12 Troubleshooting Problem, Probable Cause, Things to Try...Page 13 TABLES AND DIAGRAMS Features...Page 3 Specifications...Page 4 Distorted Flows, Orienting the Meter...Page 5 Straight Pipe Recommendations...Page 6 Full Pipe Recommendations...Page 7 Connection Diagrams...Page 8-9 Flow Rate Table...Page 10 Rotor Replacement...Page 11 Parts Explosion, Parts List...Page 12 Troubleshooting...Page 13 Page 2 Seametrics 253.872.0284 www.seametrics.com

GENERAL INFORMATION The TX800-Series are insertion turbine meters designed for use in 1-1/2" to 8" pipe. High-quality jewel bearings and precision shafts ensure long life and low friction. Available in 316 stainless steel, brass and PVC, sensor bodies are machined from solid rod for maximum low-flow performance. The TX800- Series use special fittings that ensure ease of installation and correct depth setting in the pipe. The rotation of the turbine is detected by a non-drag Hall-effect sensor. Output is a pulse-type square wave, which can be sent long distances (up to 2,000 feet) without a transmitter. This signal can be connected directly to Seametrics controls and displays, as well as PLC's, counters, and computer cards. Seametrics TX800 meters are ideal for chemical proportioning applications. If no display is required, a simple divider such as the PD10 provides adjustable pump pacing. For rate and total display, as well as pump pacing, the FT420 flow indicator can be mounted directly on the TX800-Series, or remotely on a wall or panel. The FT415 offers a battery-operated rate/totalizer where power is not available. Features Cable-Seal Strain Relief Caution: U-clip must be installed before use. U-Clip Insertion Point O-Ring Fitting Bearing Housing Rotor Seametrics 253.872.0284 www.seametrics.com Page 3

GENERAL INFORMATION Specifications* Pipe Sizes EX11x/15x: 3 to 10 EX21x/25x: 10 to 48 (up to 72 optional) Materials Shaft/Fitting 316 SS or Brass Electrodes Electrode Cap Housing Valve Assembly (15x/25x only) O-Ring (15x/25x only) Hastelloy PVDF Cast powder-coated aluminum Bronze (stainless optional) with bronze ball valve EPDM Power Full Power 12-25 Vdc, 250 ma Low Power 12-25 Vdc, 40 ma average with 250 ma peaks Flow Range 0.28 to 20 ft/sec (0.08-6.09 m/sec) Fitting Size Required EX11x/21x EX15x/25x 1-1/2 FNPT 2 FNPT Temperature Ambient 0 to 160 F (-17 to 72 C) Fluid 32 to 200 F (0 to 93 C) Pressure Minimum Conductivity Calibration Accuracy Output Empty Pipe Detection 200 psi (14 bar) 20 microsiemens/cm /- 1% of full scale Square wave pulse, opto isolated, 550 Hz@20ft/sec 6mA max, 30 Vdc forward flow standard; reverse flow optional Software, defaults to zero flow Regulatory *Specifications subject to change. Please consult our website for the most current data (www.seametrics.com). Page 4 Seametrics 253.872.0284 www.seametrics.com

INSTALLATION Fitting Installation TX800-Series meters require special fittings. The meter fitting must first be installed in the pipeline. Straight pipe of at least ten times the diameter upstream of the meter and five diameters downstream is strongly recommended in order to achieve proper accuracy. These are minimum values. As the diagrams on the the next page will show, you may need more straight run under specific adverse circumstances. If you can t provide enough run to smooth out the turbulence caused by valves, fittings, and changes in direction, some decrease in accuracy may result. This does not mean that the flow meter s reading is meaningless, however. In some applications (for instance, where the flow meter is part of a control system, operating a valve or controlling chemical addition), a repeatable reading may be more important than a highly accurate one. TX800-Series PVC meter tees are supplied with some upstream straight pipe. The length provided may be less than ten diameters upstream and five downstream. It is not advisable to connect directly to the end of these fittings with a flow-disturbing device such as a valve or elbow. If possible, straight pipe should be added to the upstream end of these fittings. Meter Installation After the meter fitting is installed in the pipeline, the meter can be installed in the fitting. After noting the direction of the flow arrow, press the meter into the fitting as far as it will go. Retain the meter in place by inserting the U-clip. The pin can be installed from either side. It may be necessary to rotate the probe back and forth slightly to start the pin into the slots on the probe. Slide the pin in as far as it will go. Horizontal (3 o clock or 9 o clock position) is the preferred installation orientation, since it improves low-flow performance and avoids problems with trapped air and sediment. (See Orienting the Meter diagram below.) Bottom (6 o clock), top (12 o clock), and vertical pipe installations are all acceptable if required by the piping layout. Fair Unacceptable if pipe contains air Distorted flow profile Faster flow causes meter to read high Best Position FLOW 10X Diameter Minimum 5X Diameter Minimum Fair Unacceptable if pipe contains sediment Distorted Flows A PVC fitting is usually installed by solvent welding. The stainless steel and brass meter fittings have female pipe threads, requiring the appropriate male threaded fittings. Saddle fittings (size 3 and above) require a hole to be cut in the pipe. The recommended hole size is 1-3/4. Orienting the Meter Caution: Never remove the u-clip retainer when the pipe is under pressure. Always remove pressure from the pipe before you attempt to remove the meter. Removal under pressure may result in damage or serious injury. Seametrics 253.872.0284 www.seametrics.com Page 5

INSTALLATION Straight Pipe Recommendations (X = diameter) 10X 5X Reduced Pipe Two Elbows In Plane 10X 5X Two Elbows, Out Of Plane 20X 5X Expanded Pipe 20X 5X 30X Spiral Flow Propeller Meter 20X Swirling Flow Partially Open Butterfly Valve Page 6 Seametrics 253.872.0284 www.seametrics.com

INSTALLATION Full Pipe Recommendations Possible Problem Better Installation Allows air pockets to form at sensor Ensures full pipe Possible Problem Better Installation Post-valve cavitation can create air pocket Keeps pipe full at sensor Possible Problem Better Installation Air can be trapped Allows air to bleed off Caution: These flow sensors are not recommended for installation downstream of a boiler feedwater pump where installation fault may expose the flow sensor to boiler pressure and temperature. Maximum recommended temperature is 130 F (Plastic), 200 F (Metal). Seametrics 253.872.0284 www.seametrics.com Page 7

CONNECTIONS FT430 FT430 Pulse Pass-thru 7-45Vdc Supply BLACK WHITE RED SENSOR POWER ENGD S S PULSE OUT 2 PULSE OUT 1 Pulse Responsive Metering Pump Flow Sensor FT440 FT440 4-20mA Device 9-30 Vdc Loop Power Supply BLACK WHITE RED SENSOR POWER ENGD S S PULSE OUT 2 PULSE OUT 1 Electronic Metering Pumps Flow Sensor Page 8 Seametrics 253.872.0284 www.seametrics.com

CONNECTIONS FT450 FT450 Pulse Pass-thru BLACK WHITE RED POWER ENGD SENSOR S S Lithium C, 3Vdc Replaceable Battery PULSE OUT 2 PULSE OUT 1 Pulse Responsive Metering Pump Micropower Flow Sensor Current Sinking Polarity-Sensitive Connecting to PLC's and other non-seametric Controls Input Designed for Current Sinking (NPN) Devices Input Designed for Current Sourcing (PNP) Devices Red DC Voltage 2.2k Ohm Pull-up Resistor Red DC Voltage White Signal White Signal Black Ground Black Ground NPN Device Figure 1 NPN Device Figure 2 Seametrics 253.872.0284 www.seametrics.com Page 9

OPERATION AND MAINTENANCE Modularity Any of the TX800-Series flow sensors can have electronic modules mounted directly to them, either at the time of order or by adding an adaptor kit in the field (part number 102632). Alternatively, the flow sensor and indicator or transmitter can be installed remote from each other. The FT420 is an indicating transmitter (rate, total, 4-20 ma output), and the AO55 is a blind 4-20 ma transmitter. For data logging, add the DL76. The FT520, which provides batching and other functions, is suitable for remote installation. Calibration ( K-factor ) The K-factor represents the actual number of pulses per gallon the meter produces during a flow test. This number can be entered into your electronic control to make it read properly. If the TX800-Series meter is ordered with a tee fitting, it is factory-calibrated in the fitting and the K-factor is indicated on the side of the fitting. For saddle and weldolet K-factors, see the K-factor calculator located at the bottom of the www. seametrics.com home page. Output The output is a current-sinking pulse (square wave) compatible with many controls in addition to the Seametrics indicators and transmitters. The most common of these are water treatment controllers and programmable logic controllers (PLC s). For these units, it is sometimes necessary to provide a pull-up resistor if the controller does not provide for a current-sinking output. (See the section on Connecting to PLC s and other controllers before connecting to a non-seametrics control.) Fittings Since the TX800-Series sensors are not adjustable, they must be purchased with fittings appropriate to the application. The TX81x is sized for fittings of 1 1/2 to 3. The TX82x is for fittings of 4 and 8. Each fitting insures that the flow sensor is installed at the correct point. Every flow sensor and every tee fitting is wet calibrated. Saddle fittings are normally not wet calibrated, because they are field-installed on a pipe. In PVC however it is possible to order a saddle pre-installed on a standard length of pipe, in which case the entire assembly is wet-calibrated. For all other saddles, the K-factor (pulses per gallon) is established through testing with various standard schedules of pipe and provided with the saddle. K: 53.6 MF81T-P200 10031295 Find Your K-Factory Here Minimum Flow As with any other flow sensor, there is a rate below which the TX800-Series sensor cannot read. Check the flow rate table below for the minimum flow rate detectable by the sensor for a given pipe size. Flow Rate (Gallons per Minute) Flow Rate (Liters per Minute) 1½ 2 3 4 6 8 Min 2.8 5 11.5 19.8 45 78 Max 190 314 691 1190 2700 4680 1½ 2 3 4 6 8 Min 10.60 18.93 43.53 74.95 170.34 295.26 Max 719.23 1189 2616 4505 10221 17716 Page 10 Seametrics 253.872.0284 www.seametrics.com

OPERATION AND MAINTENANCE Caution: Never remove the u-clip retainer when the pipe is under pressure. Always remove pressure from the pipe before attempting to remove the meter. Removal under pressure may result in damage or serious injury. Rotor Replacement It is unusual for a rotor to require replacement due to damage sustained in normal service. More commonly, the meter is dropped while it is out of the pipe. Another reason for rotor replacement is shaft wear after long service. Rotors are easily field-replaced. To install a rotor, follow these steps: 1. Unscrew the threaded bearing housings to expose the shaft ends. If bearings are being replaced, back them completely out. 2. Remove the rotor. Put the new rotor in its place. 3. Thread in one bearing housing part way, then the other. Take care to start the end of the shaft into the bearing hole before tightening further. 4. Screw in bearing housings until they bottom Note: Do not use excessive force. 5. Check for free spin. Blowing lightly on the rotor should result in it spinning rapidly and coasting to a smooth stop. Turbine Rotor Signal Troubleshooting The flow sensor has only one moving part, the rotor. If this is turning properly and there is no signal, the magnetic sensor is not operating properly. To check the signal, apply 12 Vdc regulated* power to the red () and black (-) leads. Set a multimeter to voltage reading. Put the positive multimeter lead on the red wire and the negative lead on the white wire. Slowly turn the rotor. Voltage reading should swing between 12 Volts and 0 Volts as the rotor turns. If it does not, the solid-state magnetic sensor is not working properly. Checking for continuity is not a useful test of these sensors. *NOTE: An unregulated power supply can exceed max voltage of micro powered sensor (gray cable) and damage sensor. Sensor Replacement It is very unusual for a sensor to require replacement in normal use. The primary cause of sensor failure is overvoltage (inadvertent connection of line voltage, for example) or incorrect polarity on hookup. The sensor is replaced by removing the strain relief, then threading out the sensor retainer plug. Remove the entire sensor capsule by pulling on the cable. The new sensor capsule can then be installed, orientation is not critical. Replace the retainer plug, and then replace and tighten the strain relief. Bearing Housing Rotor Replacement Shaft Seametrics 253.872.0284 www.seametrics.com Page 11

OPERATION AND MAINTENANCE TX800 Series Parts List TX800 Series Parts 1a 2a 4a 1 Upper housing/ electronics White Housing 1a thru 7a Contact service representative for your specific model Blue Housing 1b thru 7b 2 Housing Gasket/Seal 102025 100411 Contact service representative for your specific model 3a 6a 3 Lower housing Not field replaceable 4 Housing screw/washer kit (4 each) Not field replaceable 100414 100414 9 8 11 12 13 10 7a 5a 5 Plug, steel (battery units) 100360 100360 6 Strain relief kit, small (includes 2) 7 Strain relief kit, large (includes 1) (externally powered units) 100364 100364 101850 101850 8 Sensor pickup 100508 (Micropower, green cable, FT450) 100419 (Standard, blue cable, FT430/440) 15 9 Sensor retaining screw 100298 14 10 U-clip, retainer 100154 11 O-ring 100264 (EPDM) 100219 (Viton ) 12 Body See distributor 4b 1b 2b Blue Housing 5b 6b 7b 13 Bearings (includes 2) 103315 14 Rotor assembly 101862 (Kynar /tungsten carbide) 15 Rotor repair kit (#13 & #14 above) 101912 (Kynar /tungsten carbide) 3b Page 12 Seametrics 253.872.0284 www.seametrics.com

TROUBLESHOOTING Problem Probable Cause Try... No signal after installation Insufficient flow Reduce pipe size if possible, use different type of sensor Bad connections to control electronics Reconnect if necessary Incompatible control Use different power supply Add pull-up resistor (see page 9) Damaged or missing rotor Obtain new rotor and replace (see page 11) Failed magnetic sensor Replace magnetic sensor Inaccurate metering Not enough straight pipe between meter and severe flow disturbance Wrong K-Factor entered Magnetic sensor failing to pick up each blade Move meter away from flow Check K-Factor (see page 10), enter correct K-Factor in your control Replace magnetic sensor and rotor Seametrics 253.872.0284 www.seametrics.com Page 13

Page 14 Seametrics 253.872.0284 www.seametrics.com

Seametrics 253.872.0284 www.seametrics.com Page 15

Seametrics 19026 72nd Avenue South Kent, Washington 98032 USA (P) 253.872.0284 (F) 253.872.0285 1.800.975.8153 www.seametrics.com LT-65200048r1.1-20161018 10/18/16